Original_AAB_Plans_Pages_61-72.pdf
PDF 5 MB Posted
- Solicitation number
- 9TSC0108
- Issued by
- Fresno County, Inyo County, Kings County, Madera County, Merced County, Mono County, San Bernardino County, Tulare County, Fremont City, Fresno City, Kingsburg City, Inyokern CDP, Madera City, Madera Acres CDP, Madera Ranchos CDP, Corte Madera Town, Merced City, University of California-Merced CDP, Mono City CDP, Kings Beach CDP, San Bernardino City, East Tulare Villa CDP, Tulare City, Mono Vista CDP, California
About this file
This document comprises approved architectural and engineering plans for the 2421 Fresno Air Attack Base C130 Barracks project located at 2311 N. Clovis Avenue, Fresno, California, prepared under the Department of General Services' Division of the State Architect (DSA) with approval from the Office of the State Fire Marshal (OSFM). The plans specify comprehensive mechanical, plumbing, electrical, fire suppression, and communications systems for a multi-building barracks complex. Key specifications include plumbing fixtures from manufacturers such as Elkay, American Standard, Moen, and Toto; a heat pump water heater system with storage capacity of 83 gallons and recovery rate of 20 GPH; domestic water re-circulation pump with 4 GPM capacity; automatic wet-pipe fire sprinkler systems designed per NFPA 13; a 75 kVA transformer providing 480V/277V distribution; electrical service with main switchboard and multiple panelboards; emergency lighting systems with 90-minute backup power; voice/data communications infrastructure with CAT6 cabling and network equipment racks; and a public address system with interior and exterior speakers. The project includes six bedrooms, three bathrooms, kitchen, dining room, day room, library, laundry facilities, and associated support spaces, with all work requiring compliance with 2022 California Building Code and fire-rated wall penetration requirements.
The plans were approved on December 23, 2023, with final review and approval contingent upon field inspection. All electrical work shall route through Panel B per circuit schedules, with equipment sizing and installation per manufacturer recommendations and applicable versions of the California Electrical Code. Lighting control utilizes digital occupancy sensors and dimming capabilities with emergency inverter backup for designated fixtures. Fire sprinkler and fire alarm systems are identified as deferred-approval items requiring submission to the State Fire Marshal by a California-licensed engineer with comprehensive hydraulic calculations, product cut sheets, and firestopping details for penetrations through fire-rated assemblies. The project accommodates phased installation approaches, with contractors responsible for determining additional scope required for phasing. As-built documentation must include all mechanical, electrical, and plumbing modifications made to accommodate fire protection and alarm systems. No contract pricing, award information, or specific bidding details are contained within these technical construction documents.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLUMBING SCHEDULE
MARK NAME DESCRIPTION
NAMED PRODUCT (MANUFACTURER AND MODEL
NO.) (NOTE 1)
CONNECTIONS
WASTE VENT
COLD
WATER
HOT
WATER
BF-1 BOTTLE FILLER
IN-WALL BOTTLE FILLING STATION, FILTERED, NON-REFRIGERATED STAINLESS. ANTI-BACTERIAL,FILTERED, CUMULATIVE COUNTER (FILL COUNT), HANDS FREE, LAMINAR FLOW, REAL DRAIN, VISUAL FILTER MONITOR. ELECTRONIC BOTTLE FILLER SENSOR ACTIVATION. PRODUCT SHALL BE
IN-WALL MOUNT (FRAME & PLATE), FOR INDOOR APPLICATIONS, SERVING 1 STATION. UNIT SHALL BE CERTIFIED TO UL 399 AND CSA C22.2 NO. 120. UNIT SHALL BE LEAD-FREE DESIGN WHICH IS CERTIFIED TO NSF/ANSI 61 &372.
"ELKAY" MODEL LZWSDK 1-1/4" 1-1/4" 1/2"
KS-1/
KS-2
KITCHEN SINK(S), STAINLESS
STEEL COUNTERTOP
DOUBLE COMPARTMENT SINK(S) SHALL BE A PART OF, AND INTEGRAL WITH THE STAINLESS STEEL COUNTERTOP SYSTEM, AND SHALL COMPLY WITH THE REQUIREMENTS OF THE APPROPRIATE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS. FURNISH WITH DISPOSER AS NOTED ON
PLANS OR FURNISH WITH TYPE 316 STAINLESS STEEL DRAIN FITTING AS APPLICABLE.
"JUST" J-35-316 DRAIN FITTING 1-1/2" 1-1/4" - -
LAV-1 LAVATORY SINK
WHITE VITREOUS CHINA, OVAL SINGLE BOWL UNDERCOUNTER MOUNT, 19-1/4" x 16-1/4" UNIT DIMENSIONS, 17" x 14" BY 5-1/2" DEEP BOWL, BUILT-IN OVERFLOW. BRASS METAL POLISH CHROME FINISH GRID DRAIN ASSEMBLY. FURNISH WITH INSULATION/PROTECTION ON WATER AND
WASTE PIPING LOCATED UNDER COUNTER, AND UNDERCOUNTER MOUNTING KIT AND TEMPLATE. UNIT SHALL COMPLY WITH ADA & TITLE 24 REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.
"AMERICAN STANDARD" OVALYN 0496.221 WITH 2411.015 GRID
DRAIN
1-1/4" 1-1/4" - -
LS-1 LAUNDRY SERVICE SINK
18 GAUGE TYPE 304 (18-8) STAINLESS STEEL SEAMLESS DIE-DRAWN CONSTRUCTION, HAND-BLENDED POLISHED FINISH WITH HIGHLIGHTED BOWL RIM, SINGLE BOWL UNDERCOUNTER MOUNT. 24" x 18" UNIT DIMENSIONS, 22" x 16" BY 10-1/2" DEEP BOWL, CENTER DRAIN OPENING.
TYPE 316 STAINLESS STEEL DRAIN FITTING, SOUND AND CONDENSATE UNDERCOATING. FURNISH WITH UNDERCOUNTER MOUNTING KIT AND TEMPLATE.
"JUST" UNDERMOUNT GROUP USX-1824-A WITH "JUST" J-35-316
DRAIN FITTING
1-1/2" 1-1/4" - -
MS-1 MOP SERVICE SINK
FLOOR MOUNTED SINGLE BOWL TYPE 304 ALL STAINLESS STEEL CONSTRUCTION, 16 GAUGE BOWL AND 18 GAUGE APRON THICKNESS. 33" x 25" x 16" UNIT DIMENSIONS, 28" x 20" x 12" DEEP BOWL, TILE EDGE ON REAR OF UNIT. ALL TIG WELDED CONSTRUCTION, SATIN FINISH.
FURNISH COMPLETE WITH MOP SINK DRAIN ASSEMBLY.
"ADVANCE TABCO" 9-OP-48 2" 1-1/2" - -
S-1 SINK, A.D.A. COMPLIANT
18 GAUGE TYPE 304 (18-8) STAINLESS STEEL SEAMLESS DIE-DRAWN CONSTRUCTION, HAND-BLENDED POLISHED FINISH WITH HIGHLIGHTED BOWL RIM, SINGLE BOWL UNDERCOUNTER MOUNT. 24" x 18" UNIT DIIMENSIONS, 22" x 16" BY 5-1/2" DEEP BOWL, REAR-CENTER DRAIN
OPENING, TYPE 316 STAINLESS STEEL DRAIN FITTING, SOUND AND CONDENSATE UNDERCOATING. FURNISH WITH UNDERCOUNTER MOUNTING KIT AND TEMPLATE. FURNISH INSULATION/PROTECTION ON WATER AND WASTE PIPING LOCATED UNDER COUNTER. UNIT SHALL COMPLY
WITH ADA & TITLE 24 REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.
"JUST" UNDERMOUNT GROUP US-ADA-1824-A WITH "JUST"
J-35-316 DRAIN FITTING
1-1/2" 1-1/4" - -
WC-1
WATER CLOSET, A.D.A.
COMPLIANT
VITREOUS CHINA, FLOOR MOUNTED, 16-1/2" HIGH ELONGATED BOWL, SIPHON ACTION FLUSH, CLOSE COUPLED TANK. ULTRA HIGH EFFICIENCY 1.1 GPF MAX, BOLT CAPS, POLYPROPYLENE OPEN-FRONT EXTRA HEAVY DUTY SEAT LESS COVER WITH 304 SERIES STAINLESS STEEL HINGE
POSTS. CHROME TRIP LEVER LOCATED ON "OPEN" SIDE OF FIXTURE. ANTI-MICROBIAL FINISH ON BOTH FIXTURE AND SEAT. ALL COMPONENTS SHALL BE WHITE. UNIT SHALL COMPLY WITH ADA & TITLE 24 REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.
"AMERICAN STANDARD" H2OPTIMUM SIPHONIC RIGHT HEIGHT
228AA.114 OR 228AA.115 WITH "AMERICAN STANDARD" 5905.110
SEAT
3" 2" 1/2" -
F A U C E T S
D R A
IN
S
FAU-1
FAUCET, KITCHEN SINK, SINGLE
HANDLE, ADA/CBC COMPLIANT,
SINGLE HOLE, COUNTERTOP
MOUNT
METAL CONSTRUCTION, "DURALAST" CONTROL CARTRIDGE, INTEGRAL BACKFLOW PREVENTION SYSTEM. SINGLE LEVER HANDLE MOUNTED ON RIGHT SIDE OF SPOUT BASE. 360 DEGREE ROTATING HIGH ARC 7-17/32" SPOUT MOUNTED MINIMUM 9-1/2" ABOVE COUNTERTOP DECK, PULL-DOWN SPRAY SPOUT WITH RETRACTABLE 68" BRAIDED HOSE AND SPRAY TO STREAM TOUCH CONTROL. SPOT RESISTANT STAINLESS STEEL FINISH. FLOW RESTRICTOR WITH 1.5 GPM MAXIMUM FLOW RATE. FURNISH WITH DECK PLATE OR ESCUTCHEON FOR SINGLE-HOLE
MOUNTING ON STAINLESS STEEL COUNTERTOP.
NOTE: FURNISH ONE FAUCET AT EACH SINK BOWL. UNIT SHALL COMPLY WITH ADA/CBC REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.
"MOEN" ALIGN 7565 SRS - - 1/2" 1/2"
FAU-2
FAUCET, LAVATORY, SINGLE
HANDLE, ADA/CBC COMPLIANT
SINGLE HOLE, COUNTERTOP
MOUNT
METAL CONSTRUCTION, CERAMIC CONTROL COMPONENTS, SINGLE SWIVEL STYLE LEVER HANDLE WITH RED & BLUE HOT/COLD INDICATORS. ROUND POST BODY WITH DECK PLATE OR ESCUTCHEON FOR SINGLE-HOLE MOUNTING ON COUNTERTOP. 4" SPOUT MOUNTED MINIMUM 3-3/4"
ABOVE COUNTERTOP DECK. FLOW RESTRICTOR WITH 0.35 GPM MAXIMUM FLOW RATE, POLISHED CHROME FINISH. FURNISH WITH METAL GRID DRAIN ASSEMBLY. UNIT SHALL COMPLY WITH ADA/CBC REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.
"TOTO" OBERON-S TL363SDA03#CP - - 1/2" 1/2"
FAU-3
FAUCET, SINK, SINGLE HANDLE,
ADA/CBC COMPLIANT SINGLE
HOLE, COUNTERTOP MOUNT
METAL CONSTRUCTION, "DURALAST" CONTROL CARTRIDGE, SINGLE LEVER HANDLE MOUNTED ON RIGHT SIDE OF SPOUT BASE. 360 DEGREE ROTATING HIGH ARC 8" SPOUT MOUNTED MINIMUM 9-5/8" ABOVE COUNTERTOP DECK, FIXED SPOUT. SPOT RESISTANT STAINLESS STEEL
FINISH. FLOW RESTRICTOR WITH 1.5 GPM MAXIMUM FLOW RATE. FURNISH WITH DECK PLATE ESCUTCHEON FOR SINGLE-HOLE MOUNTING ON COUNTERTOP. UNIT SHALL COMPLY WITH ADA/CBC REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.
"MOEN" ALIGN 7365 SRS - - 1/2" 1/2"
FAU-4
FAUCET, SINK, GOOSENECK
SPOUT, ADA/CBC COMPLIANT
SINGLE-HOLE COUNTERTOP
MOUNT
METAL CONSTRUCTION, QUARTER TURN CERAMIC CONTROL COMPONENTS, 4-INCH VANDAL PROOF WRISTBLADE HANDLES. COUNTERTOP MOUNTED FAUCET SINGLE-HOLE FIXED CENTER-SET. 8" RIGID/SWING GOOSENECK SPOUT MOUNTED MINIMUM 9-1/4" ABOVE SINK DECK, CHROME STEEL FINISH. FLOW RESTRICTOR WITH 1.5 GPM MAXIMUM FLOW RATE WITH INTEGRAL AERATOR. 3/8" COMPRESSION FLEXIBLE STAINLESS STEEL SUPPLY H0SES. UNIT SHALL COMPLY WITH ADA/CBC REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.
"CHICAGO" MECHANICAL FAUCET 50-GN8AE35-317XKAB - - 1/2" 1/2"
FAU-5
FAUCET, MOP SINK, WALL
MOUNTED
CAST BRASS BODY, EXPOSED YOKE WALL MOUNT, 9-3/4" SPOUT WITH BUCKET HOOK, TOP BRACE AND THREADED HOSE END. 1/4-TURN CERAMIC DISC VALVE CARTRIDGES, VANDAL RESISTANT METAL LEVER HANDLES WITH HOT AND COLD INDICATORS. INTEGRAL SERVICE STOPS AND
VACUUM BREAKER. OFFSET SHANKS WITH INTEGRAL CHECK VALVES. /2" FEMALE INLETS WITH WALL FLANGES, ADJUSTABLE ROUGH-IN 6' TO 10". POLISHED CHROME FINISH. FURNISH WITH 1/2" BLACK HEAVY DUTY UTILITY HOSE 36" LONG, WITH 3/4" FEMALE HOSE FITTING ON ONE
END AND OPEN ON THE OTHER END, RATED AT 175# MAX WORKING PRESSURE, AND STAINLESS STEEL WALL MOUNT HOSE HANGER.
"AMERICAN STANDARD" UTILITY FAUCET 8354.112
WITH "ELKAY" LK402 UTILITY HOSE AND LK404 HOSE HANGER
- - 1/2" 1/2"
FR-1 FLOOR RECEPTOR, 3" CAST IRON BODY, ACID RESISTING ENAMELED INTERIOR. 12-1/2" SQUARE TOP, 10" DEEP SUMP, FLANGE WITH SEEPAGE OPENINGS, ALUMINUM DOME STRAINER, NICKEL BRONZE RIM AND GRATE, FURNISH WITH SECURED HALF GRATE, TRAP PRIMER CONNECTION, CAULK OUTLET "J.R. SMITH" SANI-CEPTOR 3160C-12 3" 2" - -
IMO-1 ICE MAKER WALL OUTLET BOX
20 GAUGE G90 HOT DIPPED GALVANIZED STEEL CONSTRUCTION, WITH FACTORY INSTALLED WATER SHUT-OFF VALVE. 1/2" NPT INLET x 1/4" COMPRESSION OUTLET. FURNISH COMPLETE WITH VALVES, LOCKNUTS AND O-RINGS AS REQUIRED, COORDINATE MOUNTING LOCATION WITH
ICE MAKER OR REFRIGERATOR BEING SERVED.
"IPS CORPORATION" GUY GRAY BIM 875 - - 1/2" 1/2"
SD-1 SHOWER DRAIN - LINEAR CAST IRON BODY, 5" DIAMETER ROUND NICKEL BRONZE TOP. REVERSIBLE FLASHING COLLAR & ADJUSTABLE STRAINER HEAD, FLANGE WITH SEEPAGE OPENINGS. SPEEDI-SET SERVICE WEIGHT OUTLET. "J.R. SMITH" 2005L-NB 2" 1-1/2" - -
SH-1
SHOWER SYSTEM, A.D.A.
COMPLIANT
SHOWER-HAND SHOWER SYSTEM WITH CYLINDER STYLE LEVER HANDLES. PRESSURE BALANCING MIXING VALVE WITH BRASS, BRONZE AND STAINLESS STEEL CONSTRUCTION, METAL ESCUTCHEON, SINGLE LEVER HANDLE, ADJUSTABLE STOP SCREW, INTEGRAL SERVICE STOPS.
SEPARATE DUAL-OUTLET DIVERTER VALVE. THREE-MODE SHOWER HEAD WITH ARM AND FLANGE, WALL/HAND SHOWER WITH FLEXIBLE 5-FOOT METAL HOSE, IN-LINE VACUUM BREAKER WALL CONNECTOR AND FLANGE, AND CRADLE FOR HAND SHOWER MOUNTING, 30" SLIDE BAR FOR
CRADLE MOUNTING, POLISHED CHROME FINISH. FLOW RESTRICTOR WITH 1.5 GPM MAXIMUM FLOW RATE. INSTALLATION SHALL INCLUDE GRAB BARS AND SEAT, AND ALL ASSOCIATED ACCESSORIES, CONNECTORS AND PIPING FOR A COMPLETE SYSTEM.. UNIT SHALL COMPLY WITH
ADA & TITLE 24 REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.
"SYMMONS" DIA 3505-H321-V-CYL-B-X-1.5-352SH-3 - - 1/2" 1/2"
WOB-1
WASHING MACHINE WALL OUTLET
BOX
20 GAUGE G90 HOT DIPPED GALVANIZED STEEL CONSTRUCTION. 1/2" MIP/SWEAT INLETS x 1/2" HOSE OUTLETS FOR WASHING MACHINE, 2" MALE THREADED DRAIN CONNECTION WITH 24" HIGH STANDPIPE. FURNISH COMPLETE WITH VALVES, LOCKNUTS AND O-RINGS, COORDINATE
MOUNTING LOCATION WITH WASHING MACHINE BEING SERVED. ALL INSTALLATION SHALL BE PER MANUFACTURER INSTRUCTIONS.
"IPS CORPORATION" GUY GRAY B200 2" 1-1/2" 1/2" 1/2"
HB-1 HOSE BIB
HOSE VALVES INCLUDE A HEAVY ROUGH BRASS BODY, FURNISHED WITH A LOCKSHIELD BONNET AND REMOVABLE LOOSE KEY WHEEL HANDLE. VALVES CLOSE WITH THE WATER PRESSURE AND FEATURE A REPLACEABLE CARTRIDGE WHICH CONTAINS ALL WEARING PARTS INCLUDING
THE SEAT. INLET IS 3/4” NPTI, OUTLET IS 3/4” NPSH. VACUUM BREAKERS ARE ATMOSPHERIC TYPE AND CONFORM TO THE REQUIREMENTS OF ASSE STANDARD 1011. HOSE VALVES MEETS THE LEAD FREE REQUIREMENTS WHERE THE WETTED SURFACE OF THIS PRODUCT CONTACTED BY
WATER CONTAINS LESS THAN 0.25% LEAD. CHECK LOCAL CODE AUTHORITY FOR VACUUM BREAKER REQUIREMENTS
"ACORN" 8121-LF - - 3/4" -
NOTES:
1. PROVIDE A NAMED PRODUCT OR A COMPARABLE PRODUCT OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea l Estate Surveying
Architecture&Enginee ring
Co ns tr uc ti on
M an ag em en t
To we rs V au lts
1131 S STREET, SACRAMENTO, CA 95811-2460
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
PLUMBING SCHEDULES
R. GALLAGHER
R. GALLAGHER
M. MADISON
P601
C U s e rs
\M m a d is o n \A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
P .d w g
J u n
:2 P M
V2V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
PLUMBING SCHEDULE
MARK NAME DESCRIPTION
NAMED PRODUCT (MANUFACTURER AND MODEL NO.)
(NOTE 1)
ASV-1 ANGLE STOP VALVE
1/4-TURN BALL STOP VALVE, MACHINED ONE-PIECE BRASS BODY, PRECISION-MACHINED BRASS BALL, CHROME PLATED FINISH. TWO HIGH PERFORMANCE O-RINGS, BLOW-OUT PROOF, PLATED, BRASS STEM. CHROME PLATED METAL HANDLE. 1/2" FIP THREADED INLET, COMPRESSION
OUTLET SIZES AS REQUIRED AT EACH FIXTURE BEING SERVED. 40-180 DEG F TEMPERATURE RATING, 125 PSI MAX PRESSURE RATING. COMPLIANT WITH CALIFORNIA HEALTH AND SAFETY CODE 116875 REQUIREMENTS.
"BRASSCRAFT" KT COMPLIANT SERIES
BV-1 BALL SHUT-OFF VALVE
TWO-PIECE FULL PORT, BRONZE BODY WITH CHROME PLATED SOLID MACHINED BALL. MSS SP-110, ANSI/NSF 61 "LEAD FREE" COMPLIANT. FEMALE NPT CONNECTIONS. 600 PSI CWP MAX PRESSURE, 500 DEG F MAX TEMPERATURE. PREMIUM MULTI-FILL MTFE SEATS AND SEALS, ADJUSTABLE PACKING, BLOW-OUT PROOF STEM DESIGN. SIZE TO MATCH PIPE BEING SERVED.
"APOLLO" 77CLF SERIES
CVB-1 CURBED VALVE BOX
HIGH DENSITY REINFORCED CONCRETE BOX, 11-3/4" x 22-1/4" INSIDE DIMENSIONS, ETCHED POLYPROPYLENE FACE ANCHORED IN CONCRETE, 12" HIGH, NON-SETTLING SHOULDERS, ULTRA-VIOLET INHIBITOR, EXCEEDS ASTM-D1693 STANDARDS FOR STRESS CRACKING RESISTANCE.
FURNISH WITH MATCHING CAST IRON LID.
"CHRISTY" B16 BOX WITH B16C LID
FCO CLEANOUT TO FLOOR CAST IRON BODY, ROUND ADJUSTABLE SCORIATED SECURED NICKEL BRONZE TOP, TWIST-TO-FLOOR ADJUSTMENT, FLASHING FLANGE & CLAMP, SPEEDI-SET OUTLET, GASKET SEAL WITH BRONZE PLUG. SIZE TO MATCH WASTE PIPE BEING SERVED. "J.R. SMITH" 4032L
FCV-1 FLOW CONTROL VALVE
BRONZE BODY, VITON PACKING MATERIAL CARBON/GLASS FILLED PTFE SEATS. TIGHT SHUT-OFF, BALL DESIGN, BI-DIRECTIONAL, BLOW-OUT RESISTANT, WITH POSITION INDICATOR, MEMORY DEVICE, CHECKED METERING PORTS WITH DRIP CAPS, INTEGRAL DRAIN PORTS OPPOSITE METERING
PORTS, 3/4" NPT SIZE. APPROVED FOR DOMESTIC WATER SERVICE.
"WATTS" CSM-61-M1-T
GCO CLEANOUT TO GROUND/GRADE CAST IRON BODY, GASKET SEAL WITH BRONZE PLUG, SPEEDI-SET OUTLET, SIZE TO MATCH WASTE PIPE BEING SERVED. MOUNTED WITH PRE-CAST CONCRETE CURBED VALVE BOX WITH CAST IRON LID.
"J.R. SMITH" 4292L CLEANOUT WITH
"CHRISTY" G08 VALVE BOX WITH G05C LID
GD-1 GARBAGE DISPOSAL
CONTINUOUS FEED, WALL SWITCH ON-OFF CONTROL, 1.0 HP, 120 V / 1 PHASE / 60 HZ, 10.2 AMP (AVERAGE LOAD), AUTOMATIC GRINDER REVERSING, INTERMITTENT TIME RATING, 13" TALL, ANTI-VIBRATION MOUNTS AND FLEXIBLE CONNECTIONS, SOUND INSULATION, STAINLESS STEEL
GRIND CHAMBER AND COMPONENTS, 40-OUNCE GRIND CHAMBER, MANUAL RESET MOTOR OVERLOAD PROTECTION, DISHWASHER DRAIN CONNECTION (NO NEED FOR AIR GAP ABOVE SINK). FURNISH WITH A POWER CORD. UL AND IAPMO LISTED, WARRANTY- 7-YEAR PARTS AND IN-HOME
SERVICE. STAINLESS STEEL STOPPER, STAINLESS STEEL SINK FLANGE WITH QUICK-LOCK MOUNT.
INSINKERATOR "EVOLUTION EXCEL"
TBV-1 TEMPERED WATER BLENDING VALVE (NEAR WATER HEATER TANK)
INTERNAL CHECK STOPS, LEAD-FREE BRASS/BRONZE BODY. 0.5 GPM MINIMUM FLOW RATE. 150 PSIG MAX OPERATING PRESSURE. 70-145 DEG F OUTLET TEMPERATURE. INLET AND OUTLET SIZES ACCORDING TO PLANS. ASSE LISTED 1017, NSF/ANSI 61, CALIFORNIA HEALTH AND
SAFETY CODE 116875. TEMPERATURE SET-POINT ACCORDING TO WATER HEATER SCHEDULE. PROTECT SET-POINT WITH CAP.
"HONEYWELL" AM-1-LF
TBV-2 TEMPERED WATER BLENDING VALVE (ANTI-SCALD POINT-OF-USE)
INTERNAL CHECK STOPS, LEAD-FREE BRASS/BRONZE BODY WITH NICKEL PLATING, POLYSUFONE PISTON, STAINLESS STEEL SPRINGS AND SCREEN. 0.35 GPM MINIMUM FLOW RATE, 8 PSIG MAXIMUM PRESSURE LOSS AT 5 GPM FLOW RATE. 145 PSIG MAX OPERATING PRESSURE, 195 DEG F
MAX INLET TEMPERATURE. INLET AND OUTLET SIZES ACCORDING TO PLANS. ASSE LISTED 1070, NSF/ANSI 61, CALIFORNIA HEALTH AND SAFETY CODE 116875. ANTI-SCALD TEMPERATURE SET-POINT = 105 DEG F. PROTECT SET-POINT WITH CAP.
"ZURN" ZW1070XL
TP-1 TRAP PRIMER VALVE
MACHINED BRASS BODY, 60 MESH STAINLESS STEEL SCREEN, VACUUM BREAKER PORTS. UNIT SHALL CONTAIN NO SPRINGS, DIAPHRAGMS OR PLASTIC PARTS. 20-80 PSIG PRESSURE OPERATING RANGE, PRIMING VALVE AUTOMATICALLY ACTUATED BY MINIMUM 10 PSI PRESSURE
FLUCTUATION. 1/2" MNPT INLET, 1/2" FNPT OUTLET. FURNISH COMPLETE WITH SERVICE SHUT-OFF VALVE AT INLET AND UNION CONNECTION AT DISCHARGE TO DRAIN TRAP. FURNISH WITH 12"x12" HINGED METAL ACCESS DOOR FOR CONCEALED UNIT
"PRECISION PLUMBING PRODUCTS" PRIME-RITE PR-500
WCO CLEANOUT TO WALL
CAST IRON BODY CLEANOUT TEE, COUNTERSUNK BRONZE CLOSURE PLUG, SUITABLE FOR INSTALLATION ON WASTE/VENT VERTICAL PIPE RISER IN CONCEALED LOCATIONS, SIZE TO MATCH PIPE RISER. REMOVABLE ROUND STAINLESS STEEL ACCESS COVER MOUNTED ON SURFACE OF FINISH
WALL DIRECTLY SECURED BY SCREW TO TAPPING PROVIDED IN CLEANOUT PLUG.
"J.R. SMITH" 4531S
WHA-1 WATER HAMMER ARRESTER PDI STANDARD WH-201. ALL STAINLESS STEEL CONSTRUCTION, PNEUMATIC AND HYDRAULIC PRESSURE CONTROL. FACTORY CHARGED AND SEALED PRESSURIZED COMPRESSION CHAMBER, EXPANSION BELLOWS. PDI-A RATING, 3/4" THREADED CONNECTION. "J.R. SMITH" HYDROTROL 5005
NOTES:
1. PROVIDE A NAMED PRODUCT OR A COMPARABLE PRODUCT OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
PL
O T D
AT
E:
PR
O
JE
C T
PA
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs V
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
PLUMBING DETAILS
R. GALLAGHER
R. GALLAGHER
M. MADISON
P602
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \P
L U M
B
IN
G \2
P .d l
:4
A
V2
DOMESTIC WATER PUMP SCHEDULE (SPECIFICATION SECTION 221123.21)
MARK NAME DESCRIPTION
NAMED PRODUCT
(MANUFACTURER AND MODEL
NO.) (NOTE 1)
ELECTRICAL CHARACTERISTICS CONNECTION SIZES
VOLTS / PHASE
/ HERTZ
POWER (HP)
HOT WATER
SUPPLY
HOT WATER
RETURN
DOMESTIC HOT WATER
RE-CIRCULATION PUMP
ETL LISTED, MAINTENANCE FREE IN-LINE CIRCULATING PUMP SPECIFICALLY DESIGNED FOR POTABLE DOMESTIC WATER APPLICATIONS. 4 GPM NOMINAL CAPACITY, 150 PSI MAX WORKING PRESSURE AND 230 DEG F MAX WORKING TEMPERATURE. SEAL-LESS CONSTRUCTION, LEAD-FREE BRASS PUMP BODY, EPDM OR VITON O-RING, CERAMIC BEARING, NYLON/PPO IMPELLER. ALL OTHER WETTED PARTS SHALL BE TYPE 316 STAINLESS STEEL. UNIT SHALL USE PERMANENT MAGNET ELECTRONICALLY COMMUTATED MOTOR (ECM) TECHNOLOGY WITH
SHAFT-LESS SPHERICAL MOTOR. SELF-REALIGNING BEARING AUTOMATICALLY COOLED BY SYSTEM FLUID. ROTOR MAGNETICALLY CENTERED ON THE BEARING. CONSTANT SPEED UNIT WITH INTEGRAL BUILT-IN ADJUSTABLE TEMPERATURE SENSOR, SET TO 105 DEG. UNIT SHALL
INCLUDE BUILT-IN UNION CONNECTIONS, AIR PURGER AND CHECK VALVE. MOTOR SHALL HAVE AUTOMATIC OVERLOAD PROTECTION AND LOW IN-RUSH CURRENT. FURNISH PRE-WIRED WITH 6-FT ELECTRICAL PLUG. FURNISH WITH PROGRAMMABLE TIMER. TIMER SHALL BE MOUNTED
ON MOTOR END CAP WITHOUT ANY ADDITIONAL WIRING REQUIRED. INCLUDE OCCUPANCY SENSOR FOR AUTOMATIC MOTION DETECTION START.
"TACO GENIE" 006-CT WITH MOTION SENSOR
STARTER KIT 554-4
115/1/60 1 / 40 1/2" MALE NPT 1/2" MALE NPT
NOTES:
1. PROVIDE A NAMED PRODUCT OR A COMPARABLE PRODUCT OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.
ELECTRIC, DOMESTIC WATER HEATER SCHEDULE (SPECIFICATION SECTION 223300)
MARK
NAMED PRODUCT
(MANUFACTURER AND MODEL
NO.) (NOTES 1 AND 2)
TYPE
CAPACITY -
GALLONS
RECOVERY -
GPH AT 90
DEG. F
TEMPERATURE
RISE
FLOW RATE
(MINIMUM)
HEAT PUMP
CAPACITY -
BTU/H
HEAT PUMP
REFRIGERANT TYPE
TEMPERATURE
RISE - DEGREE
F AT GPM
HOT-WATER
TEMPERATURE
SETTING -
DEGREES F
TEMPERATURE
BLENDING
VALVE
SETTING -
DEGREES F
UNIFORM
ENERGY
FACTOR
(MINIMUM)
BLOCK OUT
TIMES (HEAT
PUMP OFF)
SETTING
POWER
DEMAND
- KW
ELECTRICAL CHARACTERISTICS
WEIGHT - LBS. ACCESSORIES
VOLTS / PHASE / HERTZ
MINIMUM
CIRCUIT
AMPACITY
BREAKER
SIZE
SANCO2 GS4-45HPC-US OUTDOOR UNIT AND
SAN-83SSAQA INDOOR STAINLESS STEEL
STORAGE TANK
HEAT PUMP,
STORAGE
83 20 - 15400 R744 (CO2) _ 150 108 3.85
3 P.M. TO 9 P.M.
(NOTE 3)
- 208-230/1/60 7 15
110# OUTDOOR
UNIT
EXPANSION TANK
(ET-1) (223300)
NOTES:
1. PROVIDE A NAMED PRODUCT OR A COMPARABLE PRODUCT OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS. 2. MUST BE LISTED IN THE CURRENT CALIFORNIA ENERY COMMISSION'S APPLIANCE EFFICIENCY DATABASE. 3. ADJUST BLOCK OUT TIMES TO AVOID PG&E'S TIME-OF-USE "PEAK" HOURS. CHECK CURRENT TIME-OF-USE RATE PLAN.
TANK
TANK
HPWH
HWRP
HPWH
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
LIBRARY
DINING
ROOM
KITCHEN
PHYSICAL
TRAINING
STOR
HALL 1
H A L L
BATHRM
ENTRY
PANTRY
DAY ROOM
MECH
ELEC /
TELECOMM
BATHRM
STOR
BDRM 6BDRM 1
BDRM 4BDRM 3
BDRM 5 BDRM 2
BATHRM
LAUN
H A L L
F101
FIRE SPRINKLER PLAN
R. GALLAGHER
R. GALLAGHER
M. MADISON
C U s e rs
\M m a d is o n \A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
F .d l
:1
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N ICA L
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECHNICAL SERVICES
Capital Outlay
Rea
Architecture&Engineering tr uc ti on M an ag em en t
To we rs
V
1. AUTOMATIC FIRE SPRINKLER SYSTEM DESIGNED TO COVER AREAS DENOTED BY HATCH MARKS (/////), ABOVE
AND BELOW CEILING, INCLUDING OVERHANGS, PATIOS, PORCHES, AND ALL SPACES REQUIRED BY NFPA 13, THE STATE FIRE MARSHAL (SFM) AND PROJECT SPECIFICATIONS.
2. LICENSED PROFESSIONAL FIRE SPRINKLER ENGINEER OF THE FIRE PROTECTION SYSTEM SHALL COORDINATE
WITH THE ARCHITECTURAL REFLECTED CEILING PLAN, PLUMBING PLAN AND MECHANICAL PLAN FOR ANY
OBSTRUCTION ABOVE THE CEILING.
3. THE SPRINKLER SYSTEM DESIGN, INCLUDING SPRINKLER CONNECTIONS TO BUILDING SHALL BE IN
COMPLIANCE WITH SEISMIC REQUIREMENTS. REFER TO STRUCTURAL SHEET S001 FOR DESIGN NOTES. SEE
FIRE SPRINKLER NOTES AND DEFERRED SUBMITTAL NOTES ON THIS SHEET FOR MORE INFORMATION.
4. WITH THE EXCEPTION OF THE MAIN SPRINKLER RISER AREA, ALL OTHER PIPING INSTALLED IN THE BUILDING
SHALL BE CONCEALED. ALL POSSIBLE PIPING ROUTING SHALL BE EVALUATED IN ORDER TO AVOID EXPOSING
ANY PIPING. WHERE EXPOSED PIPING CAN NOT BE AVOIDED, CONTRACTOR SHALL NOTIFY STATE
REPRESENTATIVE OF PROPOSED LOCATIONS WHERE PIPING SHALL BE EXPOSED PRIOR TO PRELIMINARY
REVIEW. EXPOSED PIPING, IF NOT AVOIDABLE, SHALL BE KEPT TO A MINIMUM, AND MAY BE INSTALLED ONLY
AS ALLOWED IN WRITING BY THE STATE REPRESENTATIVE.
5. SEE CIVIL SHEETS FOR LOCATION OF FIRE DEPARTMENT CONNECTION.
099113 EXTERIOR PAINTING
211100 FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING
211313 WET-PIPE SPRINKLER SYSTEMS
1. WET-PIPE FIRE SPRINKLER DESIGN AREA. SEE FIRE SPRINKLER NOTES AND DEFERRED SUBMITTAL NOTES ON
THIS SHEET FOR MORE INFORMATION.
2. PROPOSED LOCATION OF FIRE RISER. SEE SHEET CU101 FOR FIRE WATER SUPPLY OUTSIDE THE BUILDING.
3. INSPECTORS TEST PORT AND AUXILIARY DRAIN LOCATION.
4. RATED FIRE WALL SEPARATION.
1. PROVIDE A HYDRAULICALLY DESIGNED SPRINKLER SYSTEM WITH A PERMANENTLY MARKED WEATHERPROOF
METAL SIGN. SECURE WITH CORROSION-RESISTANT WIRE, CHAIN OR OTHER APPROVED MEANS. PLACE SUCH
SIGNS AT THE ALARM VALVE, DRY PIPE VALVE, PREACTION VALVE, OR DELUGE VALVE SUPPLYING THE
CORRESPONDING HYDRAULICALLY DESIGNED AREA. INCLUDE THE FOLLOWING INFORMATION ON THE SIGN:
1.A. LOCATION OF THE DESIGN AREA OR AREAS.
1.B. DISCHARGE DENSITIES OVER THE DESIGN AREA OR AREAS.
1.C. REQUIRED FLOW AND RESIDUAL PRESSURE DEMAND AT THE BASE OF THE RISER.
1.D. HOSE STREAM DEMAND INCLUDED IN ADDITION TO THE SPRINKLER DEMAND.
2. THE AUTOMATIC FIRE SPRINKLER SYSTEM SHALL CONFORM TO THE REQUIREMENTS OF NFPA 13 AND STATE
FIRE MARSHAL. SPRINKLERS SHALL BE QUICK-RESPONSE.
3. DO NOT BEGIN INSTALLATION OF THE AUTOMATIC SPRINKLER SYSTEM UNTIL THE COMPLETE PLANS AND
SPECIFICATIONS (INCLUDING WATER SUPPLY INFORMATION AND TYPE OF SYSTEM, IF ANY) HAVE BEEN
APPROVED BY STATE FIRE MARSHAL.
4. DO NOT BURY FIRE WATER MAIN UNTIL INSPECTED AND APPROVED BY STATE FIRE MARSHAL.
5. TEST THE SYSTEM IN THE PRESENCE OF STATE FIRE MARSHAL, LOCAL AUTHORITY HAVING JURISDICTION AND
THE STATE REPRESENTATIVE AT VARIOUS STAGES OF CONSTRUCTION AND UPON COMPLETION.
6. PROVIDE FIRESTOPPING DESIGN AND DETAILS SHOWING THE REQUIRED CLEARANCES AND FLEXIBLE FIRE STOP
SYSTEM/SEALANT WHERE SPRINKLER PIPING PENETRATES RATED WALLS AND WHERE OPENINGS ARE
REQUIRED TO BE PROTECTED (2022 CBC, SECTION 714). SEE SHEET A101 FOR RATED WALL LOCATIONS AND
LEGEND.
7. PROVIDE A CABINET WITH STOCK OF SPARE SPRINKLERS, SPECIAL SPRINKLER WRENCH AND LIST OF
SPRINKLERS. LOCATE AND LABEL THE CABINET NEAR THE FIRE SPRINKLER RISER OR IN THE PUMP ROOM.
PROVIDE NUMBER, TYPE OF SPRINKLERS AND LIST CONFORMING TO 2022 NFPA 13, SECTION 6.2.9.
AUTOMATIC FIRE SPRINKLER SYSTEM AND FIRE ALARM ARE DEFFERED-APPROVAL ITEMS.
HIRE LICENSED PROFESSIONALS AS REQUIRED TO DESIGN AND CONSTRUCT THE SYSTEMS INCLUDING PROVIDING
SERVICES FOR PREPARING DRAWINGS AS NECESSARY FOR APPROVAL FROM THE STATE FIRE MARSHAL OFFICE
(SFM) HAVING JURISDICTION OVER THE PROJECT.
DO NOT INSTALL DEFERRED SUBMITTAL ITEMS UNTIL THE DESIGNATED SUBMITTAL DOCUMENTS HAVE BEEN
APPROVED BY THE SFM.
ALL COMPONENTS MUST BE LISTED PRODUCTS AND APPROVED BY SFM.
INCLUDE WITH THE SUBMITTAL:
1. COMPREHENSIVE ENGINEERING ANALYSIS BY CALIFORNIA LICENSED ENGINEERS USING PERFORMANCE
REQUIREMENTS AND DESIGN CRITERIA INDICATED ON THESE DRAWINGS AND RELATED SPECIFICATION
SECTIONS.
2. COMPLETE CALCULATIONS FOR HYDRAULIC, BATTERY, VOLTAGE DROP, SEISMIC BRACING AND SUPPORTS, ETC.
3. CUTSHEETS FOR MATERIALS AND PRODUCTS USED IN THE SYSTEM(S).
4. FIRESTOPPING LOCATIONS AND DETAILS FOR PENETRATIONS THROUGH FIRE-RATED WALLS, FLOOR AND
CEILING ASSEMBLIES.
5. PROPOSED FIRE WATER PIPING, VALVES AND APPURTENCES.
SUBMIT FIRE SPRINKLER AND FIRE ALARM SYSTEMS **AS-BUILT INCLUDING ANY MECHANICAL, ELECTRICAL AND
PLUMBING MODIFICATION TO ACCOMMODATE THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
GENERAL SHEET NOTES
REFERENCE KEYNOTES
SHEET KEYNOTES
FIRE SPRINKLER NOTES
DEFERRED SUBMITTAL NOTES
SCALE: 3/16" = 1'-0"
FIRE SPRINKLER PLAN
MAIN SPRINKLER RISER WITH
INDICATING VALVE AND CHECK
VALVE AT BASE OF RISE
MAIN FW LINE, FOR CONTINUATION
SEE CIVIL DRAWINGS
4FIRE WALL SEPARATION
P
LA
N N O R
TH
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
FA
C P
NO
PARK
ING
CLEAN A IR /
VANPOOL/EV
NO PARKING
CLEAN A IR /
VANPOOL/EV
ES101
ELECTRICAL SITE PLAN
E. GIFFORD
E. GIFFORD
S. THOMAS
C U s e rs
\E g iff o rd
\A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
E S .d n
:0
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
TE
CHN
ICAL SERVICES
tr uc ti on
M an ag em rs V au lts
1131 S STREET, SACRAMENTO, CA 95811-2460
NELECTRICAL SITE PLAN
0 20 4010 20
1" = 20'-0"
CPB2
UEPB1
PANEL P
SWB UTILITY PULL/METER SECTION
(E) COMMS 2436 PB
(E) COMMS 2436 PB
CPB1
(E) PG&E PAD MOUNTED
TRANSFORMER
FACP
COMMS
RACKS
75 kVA 1Ø 240X480-120/240V
TRANSFORMER
(E) COMMS 2436 PB
CPB3
CPB4
CPB5
(E) PG&E 480V VAULT
EPB2
EPB5
SWB MAIN BREAKER AND 480/277V
DISTRIBUTION SECTION
COMMS ROOM
(E) FACP
FAA
1. APPLICABLE REVISIONS OF REFERENCED CODES ARE SHOWN ON G001.
2. ALL EQUIPMENT SHOWN AS DARKER COLOR IS NEW UON.
3. VERIFY THE EXISTING LOCATIONS OF ALL UNDERGROUND UTILITIES PRIOR TO TRENCHING OR EXCAVATING.
CALL UNDERGROUND SERVICE ALERT, (USA) AT 1-800-642-2444, 48 HOURS BEFORE WORK IS TO BEGIN.
4. VERIFY EXISTING CONDITIONS PRIOR TO START OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO A CAL
FIRE TECHNICAL SERVICES REPRESENTATIVE PRIOR TO STARTING DEMOLITION AND/OR CONSTRUCTION.
5. ALL EXTERIOR CONDUIT ABOVE GRADE SHALL BE GALVANIZED RIGID STEEL (GRS). ALL CONDUITS ROUTED
UNDERGROUND SHALL BE PVC SCHEDULE 40 UON. REFER TO JOINT UTILITIES TRENCH DETAIL AND
UNDERGROUND CONDUIT SECTION DETAILS ON E501 FOR ALL REQUIREMENTS. WHERE MULTIPLE CONDUITS
ARE SHARING THE SAME TRENCH, ELECTRICAL CONDUIT MUST BE PLACED ABOVE THE WATER AND/OR GAS
PIPES. ALL CONDUITS SHALL BE SEALED WITH RTV DUCT SEAL AFTER WIRES AND PULL ROPE ARE INSTALLED.
6. REFER TO SINGLE LINE DIAGRAM ON E601 AND SITE CONDUIT AND CONDUCTOR SCHEDULE ON E603 FOR
CONDUIT AND CONDUCTOR SIZES AND QUANTITIES.
7. PROVIDE AND INSTALL PULL BOXES, AKA HANDHOLES, SIZED PER ARTICLE 314.30 IN APPLICABLE VERSION OF
CEC AND PER REQUIREMENTS OF SPECIFICATION SECTION 260543 UON. ALL ELECTRICAL SPLICES IN PULL
BOXES SHALL BE MADE VIA MULTI-TAP CONNECTORS, PRE-FILLED WITH DE-OX®, RATED FOR DIRECT BURIAL.
8. TOP OF PULL BOXES SHALL BE FLUSH WITH SURROUNDING GRADE OR TOP OF ADJACENT CURB, EXCEPT IN
UNPAVED AREAS WHERE PULL BOX IS NOT IMMEDIATELY ADJACENT TO AND PROTECTED BY A CONCRETE
FOUNDATION, POLE, OR OTHER PROTECTIVE CONSTRUCTION. IN THESE AREAS THE BOX SHALL BE PLACED
WITH ITS TOP 1" ABOVE SURROUNDING GRADE. WHERE PRACTICABLE, PULL BOXES SHOWN IN THE VICINITY
OF CURBS SHALL BE PLACED ADJACENT TO BACK OF CURB.
GENERAL SHEET NOTES SHEET KEYNOTES SHEET KEYNOTES
UTILITIES CONTACT INFO:
PACIFIC GAS AND ELECTRIC
J.B. ROTH
559-246-0169
E-MAIL: JBRc@pge.com
ECC
(E) FA J-BOX
COMMAND ROOM
COMMUNICATION ROOM
(SECOND FLOOR)
AIR OPS BUILDING
120V POWER PEDESTAL
& CONCRETE FOOTING
120V POWER PEDESTAL
& CONCRETE FOOTING
14' X 8' CONCRETE PAD WITH
UFER FOR SWB AND XFMR
EPB4
CS502
EPB1
PANEL B
PANEL K
PANEL LTB
CPB6
(E) NETWORK EQUIPMENT RACK 9
7 E 23257
E L E C T R I C A L
S P
E N
C ER P . THO
M
A S
EPB3
1. CONDUCTORS BY PACIFIC GAS AND ELECTRIC (PG&E). COORDINATE ELECTRICAL SERVICE REQUIREMENTS WITH
UTILITY REPRESENTATIVE PRIOR TO ANY WORK. CONTRACTOR SHALL CONTACT PG&E INSPECTOR PRIOR TO
START OF WORK TO VERIFY SEPARATION/OFFSETS BETWEEN ELECTRIC UTILITIES AND WET & GAS UTILITIES.
2. GROUNDING ELECTRODE SYSTEM FOR THE SERVICE SHALL BE A CONCRETE-ENCASED ELECTRODE (UFER)
INSTALLED WITHIN THE CONCRETE PAD FOR THE SWITCHBOARD. SEE DETAIL 1 ON E501 AND E601 FOR DETAILS.
3. VERIFY EXACT CONDUIT STUB-UP LOCATION PRIOR TO ROUGH-IN. PANELS B, K, LIGHTING CONTROL PANEL LTB, AND FACP SHALL BE RECESS MOUNTED. PANEL P SHALL BE SURFACE MOUNTED. 75kVA TRANSFORMER SHALL
BE ANCHORED TO CONCRETE PAD.
4. SEE DETAIL 6 ON E502 FOR THE NETWORK EQUIPMENT (COMMS) RACK BELOW GRADE CONDUIT DETAIL.
5. PULL BOX SHALL SUPPORT EV CAPABLE PARKING SPACES. SEE E603 FOR DETAILS ON CONDUITS SERVING BOX.
6. PULL BOXES CPB1 AND CPB2 SHALL BE POLYMER CONCRETE, SIZED 30"X48" WITH TWO-PIECE LIDS, OLDCASTLE
POLYMER 3048 OR APPROVED EQUAL. BOXES AND LIDS SHALL HAVE ANSI/SCTE 77 TIER 15 STRUCTURAL LOAD
RATING, MINIMUM. (E) 24"X36" PULL BOX CPB3 SHALL BE REPLACED WITH THE SAME 30"X48" BOX AND
TWO-PIECE LID AS SPECIFIED FOR CPB1 AND CPB2.
7. CPB6 SHALL BE SAME TYPE/RATING AS CPB1 AND CPB2 BUT SIZED 11"X18"X12" WITH ONE-PIECE LID.
8. CONTRACTOR SHALL FURNISH AND INSTALL A 36"H TYPE 304 STAINLESS STEEL 120V POWER PEDESTAL IN A
BLACK POWDER COATED FINISH, PEDOC 1P36-C-HT-B OR APPROVED EQUAL. PEDESTAL SHALL HAVE A
SINGLE GANG OUTLET BOX AND LOCKABLE WHILE-IN-USE HINGED COVER THAT MEETS THE REQUIREMENTS
OF ARTICLE 406.9(B) IN THE APPLICABLE VERSION OF THE CEC AND IS LISTED TO UL 1773 AS A
WEATHERPROOF NEMA-3R ENCLOSURE. PEDESTAL SHALL HAVE INTEGRAL BASE AND BE ATTACHED TO AN 18"
SQUARE BY 12" DEEP CONCRETE FOOTING WITH MANUFACTURER APPROVED ANCHORS. SEE DETAIL 7 ON
CS502 FOR FOOTING REQUIREMENTS. A 3/4" PVC SCH40 CONDUIT SHALL STUB UP 2" INTO THE PEDESTAL IN
THE MANUFACTURER APPROVED STUB-UP AREA. SEE E602 AND E603 FOR MORE DETAILS ON SOURCE POWER
FOR PEDESTALS AND CONDUIT ROUTING.
9. FOC AND PA SYSTEM WIRE SHALL BE INSTALLED FROM RACK1 IN ELEC/TELECOMM ROOM OF THE BARRACKS
TO THE AIR OPS BUILDING COMMUNICATION ROOM. SEE E111 FOR FOR COMPLETE DETAILS ON FOC AND PA
SYSTEM WIRE AND E603 FOR DETAILS ON THEIR ROUTING. ONCE INSIDE ROOM FOC SHALL BE ROUTED UP
WALL AND ACROSS (E) CABLE TRAY, UTILIZING THE PATH SHOWN, AND TERMINATE IN A (N) RACKMOUNT FDU
IN (E) NETWORK EQUIPMENT RACK. ONCE PA SYSTEM WIRE EXITS CONDUIT INSIDE COMMUNICATION ROOM, IT SHALL BE COILED IN A 40' LOOP FOR FUTURE TERMINATION BY CAL FIRE.
10. A FIRE ALARM ANNUNCIATOR (FAA) FOR THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN THE COMMAND
ROOM IN THE ECC. BELOW GRADE RATED CABLE FOR FAA SHALL BE ROUTED THROUGH (N) AND (E) CONDUIT
TO AN (E) FA J-BOX ON THE NORTH WALL OF THE COMMS ROOM IN THE ECC. SEE E603 AND E701 FOR MORE
DETAILS.
(TYP)
CS502
(TYPICAL OF TWO)
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
AutoCAD SHX Text: J AutoCAD SHX Text: F AutoCAD SHX Text: F AutoCAD SHX Text: F AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: C AutoCAD SHX Text: C AutoCAD SHX Text: M AutoCAD SHX Text: E AutoCAD SHX Text: E AutoCAD SHX Text: E AutoCAD SHX Text: E AutoCAD SHX Text: E AutoCAD SHX Text: C
N O
PA
R K
IN
G
CLEAN AIR/
VANPOOL/EV
NO PARKING
CLEAN AIR/
VANPOOL/EV
0 10 205 10
1" = 10'-0"
ES102
SOLAR READY AREA PLAN
E. GIFFORD
E. GIFFORD
S. THOMAS
C U s e rs
\E g iff o rd
\A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
E S .d n
:0
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
ICAL SERVICES
tr uc ti on
M an ag em en t
To we rs V au lts
1131 S STREET, SACRAMENTO, CA 95811-2460
NSOLAR READY AREA PLAN
GENERAL SHEET NOTES
SHEET KEYNOTES
E 23257
E L E C T R I CA L
S P E N
CER P . THO
M
A S
SOLAR READY AREA
1. ALL WORK ON THIS SHEET IS PURELY PROVISIONAL TO MEET TITLE 24 SOLAR READY CODE REQUIREMENTS.
NO SOLAR ARRAYS HAVE BEEN DESIGNED OR SPECIFIED FOR THIS PROJECT. IF A PV SYSTEM WERE TO BE
ADDED, IT WOULD REQUIRE A SEPARATE DSA APPLICATION.
1. SOLAR ARRAY READY AREAS SHOW WHERE SOLAR PANELS AND OTHER EQUIPMENT COULD BE
INSTALLED AT A FUTURE DATE. SIZE SHOWN DOES NOT NECESSARILY REFLECT THE ACTUAL SIZE OF THE
SOLAR ARRAY IF A PHOTOVOLTAIC SYSTEM IS DESIGNED, FURNISHED, AND INSTALLED IN THE FUTURE.
1 1
FUTURE PV EQUIPMENT (NIC)EPB2
CONDUIT STUB-UP PROVIDING ACCESS
TO FUTURE PV ROOF CABLING
BARRACKS
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: X AutoCAD SHX Text: M AutoCAD SHX Text: E
DISTRIBUTION & EQUIPMENT
DESCRIPTIONSYMBOL
DIAGRAMS
DESCRIPTIONSYMBOL
LIGHTING
DESCRIPTIONSYMBOL
R
C
M
F
M
FLANGED LED LUMINAIRE (SIZE/SHAPE VARIES) - RECESSED
(FLUSH) MTD.
WRAPAROUND LED LUMINAIRE - SURFACE MTD.
SHADING OF ANY LUMINAIRE INDICATES CONNECTION TO
BACKUP POWER SOURCE (EM INVERTER, UPS, ETC.) PER
METHOD AND CIRCUITING INDICATED
ILLUMINATED EXIT SIGN, SHADED QUADRANT INDICATES FACES/
DIRECTIONS, ARROWS AS SHOWN - WALL, CEILING MTD.
LUMINAIRE MARKING CONVENTION LEGEND:
XX = LUMINAIRE TYPE. SEE LIGHTING FIXTURE SCHEDULE.
3c = CIRCUIT NUMBER VIA LOCAL SWITCH OR DIGITAL DEVICE
(LOWERCASE LETTER) THAT CONTROLS LUMINAIRE.
BRANCH CIRCUIT PANELBOARDS, SURFACE AND RECESS
MOUNTED, DASHED LINES INDICATE REQUIRED CLEARANCE
TRANSFORMER WITH REQUIRED CLEARANCES SHOWN
SERVICE AND/OR DISTRIBUTION EQUIPMENT WITH METER
CONNECTION TO MOTOR PROVIDED BY ELECTRICAL
DISCONNECT SWITCH, SIZE AS NOTED. WHEN NOT SHOWN,
SIZE FOR CONNECTED MOTOR(S), PER ARTICLE 430 OF CEC.
FUSED DISCONNECT SWITCH, FRAME SIZE AS NOTED.
SIZE FUSE PER EQUIPMENT MANUFACTURER'S
RECOMMENDATIONS.
INDUSTRIAL STRIP LED LUMINAIRE - SURFACE MTD
LINEAR LED FLOOD LIGHT - WALL (SURFACE) MTD. AT ENDS
OR VIA SINGLE CENTER MOUNT
BEDSIDE LED LUMINAIRE - WALL MTD.
LED MINI WALL PACK RUSTPROOF AND VANDAL RESISTANT
LUMINAIRE - SURFACE/WALL MTD.
LED DOWNLIGHT LIGHT - RECESSED MTD.
LED DOWNLIGHT LIGHT, WET LOCATION - RECESSED MTD.
LED WALL PACK LUMINAIRE - WALL MTD.
LED AREA LIGHT LUMINAIRE - POLE MTD.
ACCENT LED LUMINAIRE - WALL MTD.
XX
3c
C
CIRCUIT BREAKER, SIZE AS NOTED. SIZE PER EQUIPMENT
MANUFACTURER'S RECOMMENDATIONS.
SWITCH
OVERLOADS
NORMALLY CLOSED CONTACTOR OR RELAY CONTACTS
NORMALLY OPEN CONTACTOR OR RELAY CONTACTS
BUS BAR
CONTACTOR COIL
RELAY COIL
UTILITY CO. APPROVED SOCKET WITH METER INSTALLED.
SQUARE = REMOTE MOUNTED
DELTA CONNECTION
GROUNDED WYE CONNECTION
CONNECTION TO GROUND
CIRCUIT BREAKER, WITH TRIP POINT, FRAME AMPERE
RATING, AND NUMBER OR POLES
100AT
225AF
3P
COMBINATION EMERGENCY LIGHT-EXIT SIGN. SHADED QUADRANT
INDICATES FACES/DIRECTIONS - WALL, CEILING MTD.
ABBREVIATIONS
A AMPERE
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
ATS AUTOMATIC TRANSFER SWITCH
BBS BATTERY BACKUP SYSTEM
BC BARE COPPER CONDUCTOR
C CONDUIT
CATX CATEGORY X ETHERNET CABLE
CB CIRCUIT BREAKER
CO CONDUIT ONLY
COMM COMMUNICATION
CP CONTROL PANEL
CT CURRENT TRANSFORMER
CU COPPER CONDUCTOR
D DRYER
DOS DIGITAL OCCUPANCY SENSOR
DPC DIGITAL PLUG CONTROLLER (POWER)
DRC DIGITAL ROOM CONTROLLER (LIGHTING)
DDS DIGITAL DIMMER SWITCH
DW DISHWASHER
E EXISTING
EC ELECTRICAL CONTRACTOR
EGC EQUIPMENT GROUNDING CONDUCTOR
EM UNSWITCHED CIRCUIT (EM/EXIT LTG)
EMT ELECTRIC METALLIC TUBING
ENT ELECTRIC NONMETALLIC TUBING
ER EXISTING RELOCATED
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FD FLOOD LIGHT
FDU FIBER DISTRIBUTION UNIT
FG FINISHED GRADE
FOC FIBER OPTIC CABLE
FR ONE-HOUR FIRE RATED ENCLOSURE
FRZ FREEZER
GD GARBAGE DISPOSAL
GEC GROUNDING ELECTRODE CONDUCTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL
H HOOD
HD HEAT DETECTOR
HDPE HIGH DENSITY POLY ETHYLENE
IG ISOLATED GROUND
JB JUNCTION BOX
KO KNOCKOUT
KVA KILO VOLT AMPERE
KW KILOWATT
LC LIGHTING CONTACTOR
LED LIGHT EMITTING DIODE
LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT
LTG LIGHTING
MAX MAXIMUM
MCP MOTOR CONTROL PANEL
MDP MAIN DISTRIBUTION PANEL
MIN MINIMUM
MTD MOUNTED
MTTB MAIN TELECOMMUNICATION TERMINAL BOARD
NC NORMALLY CLOSED
NO NORMALLY OPEN
OG ORIGINAL GROUND
OH OVERHEAD
PA PUBLIC ADDRESS SYSTEM
PB PULL BOX
PBS PHOTOCELL BYPASS SWITCH
PCP PUMP CONTROL PANEL
PEC PHOTOELECTRIC CONTROL
PEU PHOTOELECTRIC UNIT
PH PHASE
PNL ELECTRICAL PANEL
PUG PRIMARY UNDERGROUND UTILITIES
R REMOVE (TO BE DEMOLISHED)
REF REFRIGERATOR
RL TO BE RELOCATED
RTP RADIO TERMINATION PANEL
SD SMOKE DETECTOR
SP SERVICE POINT
SPD SURGE PROTECTIVE DEVICE
SUG SECONDARY UNDERGROUND UTILITIES
SWB SWITCHBOARD
TCX TELEPHONE CABLE (X-PAIR)
TTB TELECOMMUNICATION TERMINAL BOARD
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
V VOLT
W WASHER
WH WATER HEATER
WP WEATHERPROOF
GENERAL PROJECT NOTES
A. REFER TO DETAIL DRAWINGS FOR ADDITIONAL INFORMATION. ALL DETAILS APPLY FOR ALL APPLICABLE SITUATIONS WHETHER REFERENCED OR NOT, UON.
B. REFER TO ARCHITECTURAL FLOOR PLANS, INTERIOR ELEVATIONS, AND DETAIL DRAWINGS PRIOR TO ROUGH-IN FOR EXACT LOCATION OF RECEPTACLES, FLOOR BOXES, AND OUTLETS. NOTIFY
STATE REPRESENTATIVE OF ANY CONFLICTS.
C. THESE DOCUMENTS REFLECT THE FINAL ANTICIPATED LAYOUT OF SYSTEMS AND APPURTENANCES FOR THIS PROJECT. IT IS NOT THE INTENT OF THESE DOCUMENTS TO INDICATE SPECIFIC SCOPE OF WORK REQUIRED ON A PHASE BY PHASE BASIS. THE FINAL DESIGN INDICATED DOES ALLOW FOR THE WORK TO BE INSTALLED IN A PHASED APPROACH. CONTRACTOR SHALL DETERMINE ADDITIONAL SCOPE OF WORK REQUIRED TO ACCOMMODATE ALL PHASING ASPECTS OF THE PROJECT AND INCLUDE THAT SCOPE IN THEIR BID.
D. THE CIRCUITING SHOWN IS DIAGRAMMATIC. THE DRAFTING METHOD WHICH MOST SIMPLY CONVEYS THE CIRCUITING INTENT IS EMPLOYED. WHERE DEVICES OR EQUIPMENT ARE SHOWN UNCONNECTED, CONNECT (IN A MANNER CONSISTENT WITH THE MATERIALS AND METHODS INDICATED IN THE PLANS AND SPECIFICATIONS) FROM THE WIRING EXTENSION POINT SHOWN TO EACH DEVICE USING 1) MC CABLE IN HARD AND ACCESSIBLE CEILING AREAS -OR- 2) CONDUIT & WIRE ONLY IN EXPOSED AREAS. EMT CONDUIT AND WIRE SHALL BE USED FROM A PANEL TO A J-BOX IN AN ACCESSIBLE PORTION OF THE CEILING. MC CABLE MAY BE USED ONLY FROM THE J-BOX TO THE DEVICE OR IN BETWEEN DEVICES. AS-BUILT DRAWINGS SHALL INCLUDE THE
LOCATION OF THESE JUNCTION BOXES AND WHICH RECEPTACLES OR DEVICES THEY FEED.
E. CONTRACTOR IS RESPONSIBLE FOR REVIEWING ARCHITECTURAL DRAWINGS TO CONFIRM CEILING TYPES IN ALL ROOMS (ACCESSIBLE, EXPOSED, OR "HARD") AND TO EMPLOY APPROPRIATE WIRING METHODS FOR EACH TYPE. ENSURE ALL J-BOXES ARE ACCESSIBLE AFTER WORK BY ALL OTHER TRADES IS COMPLETED. DO NOT INSTALL J-BOXES ON "HARD" CEILINGS. ALL WIRING MUST BE ACCESSIBLE THROUGH DEVICE VIA "DAISY-CHAIN" METHOD OR VIA DEDICATED HOME-RUNS FROM PANEL TO EACH DEVICE. J-BOXES MAY BE LOCATED ABOVE ACCESS DOORS INSTALLED BY OTHER TRADES, PROVIDED THE J-BOX INSTALLATION DOES NOT INTERFERE WITH ACCESS THROUGH DOOR.
F. THE COMPLETED INSTALLATION SHALL CONFORM TO THE LATEST ADOPTED EDITIONS OF ALL APPLICABLE STATE, COUNTY AND CITY CODES, ORDINANCES, AND REGULATIONS INCLUDING
NECESSARY PERMITS AND INSPECTIONS REQUIRED BY THE GOVERNING AUTHORITIES.
G. INSTALL ALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS.
H. ALL ELECTRICAL COMPONENTS SHALL BE BRACED OR ANCHORED PER THE DETAILS ON THE APPROVED CONSTRUCTION DOCUMENTS. WHERE DETAILS ARE NOT SHOWN THE FIELD INSTALLATION SHALL MEET THE REQUIREMENTS OF THE APPLICABLE VERSION OF ASCE 7 AND BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER.
I. REFER TO MECHANICAL DRAWINGS FOR MOUNTING AND EQUIPMENT DETAILS. SINCE WALL MOUNTED CONTROLS FROM ELECTRICAL AND MECHANICAL PLANS ARE OFTEN CO-LOCATED, CONTRACTOR SHALL REVIEW BOTH PLANS PRIOR TO ROUGH-IN TO ENSURE EQUIPMENT IS PROPERLY LOCATED AND ADEQUATE SPACE IS PROVIDED. UON EQUIPMENT ADJACENT TO DOORWAYS SHALL BE PLACED AS FOLLOWS (CLOSEST TO DOOR FIRST): LIGHT CONTROL/SENSOR, PA VOLUME, THERMOSTAT/FAN CONTROL.
J. IN COMMON PARTY WALLS AND CEILINGS PROVIDE PUDDY PADS AROUND JUNCTION BOXES, RECEPTACLES, AND TELECOM OUTLETS. RECEPTACLES AND TELECOM OUTLETS SHALL BE INSTALLED SUCH THAT THERE IS A MINIMUM SPACING OF 24 INCHES, FROM BACK OF ONE OUTLET TO THE OTHER.
K. ALL NEW RACEWAYS AND CONDUCTORS SHALL BE INSTALLED CONCEALED WITHIN WALLS, INCLUDING FURRED SECTIONS WHERE APPLICABLE. CONDUITS SHALL BE INSTALLED AT A 90° ANGLE
TO BUILDING LINES.
L. DEDICATED HOT(S) AND NEUTRAL SHALL BE RUN WITH EVERY BRANCH CIRCUIT. WHILE 240V CIRCUITS SHALL HAVE A DEDICATED EGC, ONLY ONE EGC IS REQUIRED PER CONDUIT FOR 120V CIRCUITS, I.E. WHEN MULTIPLE 120V CIRCUITS ARE RUN IN A SINGLE CONDUIT, ONLY ONE EGC IS REQUIRED. METAL CONDUIT MAY NOT BE USED AS AN EGC.
M. UP SIZE WIRE FOR VOLTAGE DROP, AS REQUIRED, BASED ON FINAL ROUTING OF WIRES. PROVIDE SPECIAL RECEPTACLES THAT MATCH CORD AND CAP PROVIDED WITH EQUIPMENT, UON. USE
ADJACENT NEMA CONFIGURATION NUMBER, IF ONE IS SHOWN.
N. PER ARTICLE 110.26 IN THE APPLICABLE VERSION OF CEC, PROVIDE CODE REQUIRED WORKING AND DEDICATED EQUIPMENT SPACE FOR ALL ELECTRICAL EQUIPMENT. CONTRACTOR TO VERIFY ADEQUATE SPACING PRIOR TO ROUGH-IN AND INSTALLATION. NOTIFY STATE REPRESENTATIVE OF ANY CONFLICTS.
O. ALL EXTERIOR MOUNTED EQUIPMENT AND CONDUIT SHALL BE WEATHERPROOF WITH A MINIMUM RATING OF NEMA 3R.
P. A PULL ROPE SHALL BE INSTALLED IN ALL NEW RACEWAYS AND IN EXISTING RACEWAYS WHENEVER NEW CABLE IS PULLED AND/OR EXISTING CABLE IS REMOVED.
Q. DO NOT ROUTE CONDUIT ON ROOF. RUN ALL HORIZONTAL CONDUIT BELOW ROOF.
R. ROUTE ALL CONDUITS UP THROUGH EQUIPMENT CURBS. COORDINATE LOCATION TO AVOID CONFLICTS AND ALLOW FOR CODE CLEARANCES AND MAINTENANCE ACCESS.
S. LUMINAIRES WITH "EM" ADJACENT TO IT INDICATES A REQUIRED CONNECTION TO AN UNSWITCHED HOT CONDUCTOR UON.
T. EXTERIOR MOUNTED RECEPTACLES SHALL BE WEATHERPROOF, GFI PROTECTED, AND EMPLOY A WEATHERPROOF "WHILE IN USE" COVER PER APPLICABLE VERSION OF CEC.
SYMBOL DESCRIPTION
SWITCHING CONTROLS
SINGLE POLE SWITCH (LETTER DENOTES SIMILARLY MARKED
LUMINAIRE CONTROLLED TOGETHER), +48" AFF UON
THREE WAY SWITCH, +48" AFF UON
FOUR WAY SWITCH, +48" AFF UON
DIMMER SWITCH, +48" AFF UON
FAN SWITCH, +48" AFF UON
GARBAGE DISPOSAL SWITCH
TIMER SWITCH, 30' MAX DELAY, +48" AFF UON
THERMAL OVERLOAD SWITCH FOR FAN
OCCUPANCY SENSOR - WALL, CEILING MTD.
ATTIC SWITCH/OUTLET COMBINATION
T T
THERMOSTAT - WALL, CEILING. PROVIDED BY MECHANICAL,
INSTALLED AND WIRED BY ELECTRICAL; +48" AFF UON
WEATHERPROOF SWITCH, +48" AFF UON
EMERGENCY POWER OFF PUSH BUTTON (EPO), +48" AFF UON
SWITCH WITH PILOT LIGHT, +48" AFF UON
DIGITAL OCCUPANCY SENSOR, CORNER/WALL & CEILING MOUNT
DIGITAL LIGHTING ROOM CONTROLLER (LETTER DENOTES
SIMILAR…