Original_AAB_Plans_Pages_37-48.pdf
PDF 7 MB Posted
- Solicitation number
- 9TSC0108
- Issued by
- Fresno County, Inyo County, Kings County, Madera County, Merced County, Mono County, San Bernardino County, Tulare County, Fremont City, Fresno City, Kingsburg City, Inyokern CDP, Madera City, Madera Acres CDP, Madera Ranchos CDP, Corte Madera Town, Merced City, University of California-Merced CDP, Mono City CDP, Kings Beach CDP, San Bernardino City, East Tulare Villa CDP, Tulare City, Mono Vista CDP, California
About this file
This document is an approved architectural and engineering plan set for the Fresno Air Attack Base C130 Barracks project located at 2311 N Clovis Avenue, Fresno, California, prepared under the jurisdiction of the Department of General Services (DGS), Division of the State Architect (DSA), and reviewed by the Office of the State Fire Marshal (OSFM). The plans detail comprehensive structural, mechanical, and HVAC systems for a barracks facility. The structural drawings specify foundation details, standard framing requirements, wall connections, and sill plate anchorage using concrete slabs with reinforced steel bars, while the mechanical plans outline HVAC equipment including split system condensers, fan coils, thermostats, ductwork systems, and ventilation components. The project includes multiple bedrooms, common areas, kitchen facilities, and support spaces, with mechanical systems incorporating variable-refrigerant-flow HVAC equipment, energy recovery ventilators, ceiling fans, and exhaust systems. Plans were dated June 28, 2023, with DSA approval granted on April 15, 2024, with fire and panic approval only status.
The specifications require all materials and equipment to be new and equivalent in quality to those noted on drawings, with installation performed in accordance with the 2022 California Mechanical Code, California Plumbing Code, California Building Code, and California Energy Efficiency Standards. Ductwork must achieve 6% leakage compliance relative to nominal airflow per nonresidential standards, with all systems undergoing testing and balancing to SMACNA, TABB, AABC, and NEBA procedures. The mechanical systems include heat pump water heaters, fire dampers with duct smoke detectors, and comprehensive firestopping details for fire-rated assembly penetrations using UL-listed systems. All equipment and components must be seismically restrained per 2022 CBC requirements, with permanent engraved plastic nameplates required for all installed equipment. The project incorporates multiple HVAC zones, condensate drain systems with high-water level detection, and integrated controls complying with California Title 24 Energy Code standards.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1'-4"
1' -2
AT SW HOLD DOWNS TYPICAL
1' -6
1 1/2"
SLAB REINFORCEMENT
AT MID DEPTH
#4 W/ 90° BEND, INTO SLAB
AT 24" OC STD LAP SPLICE
#4 CONT OFFSET TO AVOID SILL
ANCHORS, CLR 3" TOP, 2" SIDE
CONCRETE SLAB/FLAT
WORK AS OCCURS
HD PER PLANS
SB PER PLANS
EXCEPT AT OPENINGS
#4 VERT BAR INTO CURB W/ STD
HOOK AT BOTTOM AT 24" OC
(2) #4 CONT T&B
3" CLR,
TYP 3"
C
LR
, T
YP
6"
6"
OPTIONAL JOINT
1' -0
6"
(3) #4 EA WAY
(2) #4 W/ 90° BEND
INTO SLAB, 1 EA WAY
STANDARD LAP SPLICE
PER PLANS
CPTZ BASE PER PLANS
3" CLR, TYP
2'-0" SQ
6"
(2) PAB PER PLANS
SLAB REINFORCEMENT
@ MID DEPTH
1'-0" SQ
ABU BASE PER PLANS
W/ 5/8"Ø x 10" TITAN HD
#4
PER PLANS
3" CLR, TYP
8" x 2'-0"
(3) #4
PORCH SLAB
1' -2
SLAB REINFORCEMENT
@ MID DEPTH
WALL FOOTING OUTLINE
AND REINFORCEMENT
1'-4"
ISOLATION JOINT
(2) #4 3" CLR, TYP (3) #4
6" TYP ON 3 SIDES
PORCH POST
BUILDING WALL
PORCH SLAB
(2) PAB PER PLANS
CPTZ BASE PER PLANS
1'-2" x 2'-0"
1' -2
SLAB REINFORCEMENT
@ MID DEPTH
WALL FOOTING OUTLINE
AND REINFORCEMENT
1'-4"
STRIP FOOTING EDGE
STRIP FOOTING EDGE
INTERIOR WSP
EXTERIOR WSP
STUD , TYP
SILL PLATE
S502
FOUNDATION DETAILS
A. ECCLESTON
A. ECCLESTON
K. LAM
C U s e rs
\A E c c le s t\ A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
S S
S .d w g
A u g
:2 P M
V2
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
TE
CHN
ICAL SERVICES
Capital
Outlay
Rea l Estate Surveying
Architecture&Enginee ring
Co ns tr uc ti on
M an ag em en t
To we rs Va ul ts
1131 S STREET, SACRAMENTO, CA 95811-2460
A
E� E
CCLESTO
N
C 90�16
CIVIL
R E
G
IS
T E
R E
D P
ROFESSIONA
L
E N
G
IN
E E
R
S
T
ATE OF CALIFORN
IA
S C A L E :
11" = 1'-0"
PERIMETER FOOTING
S C A L E :
41" = 1'-0"
24 INCH SQUARE ISOLATED FOOTING
S C A L E :
21" = 1'-0"
PORCH POST FOOTING AT EXTERIOR WALL
S C A L E :
31" = 1'-0"
OFFSET PORCH POST FOOTING AT EXTERIOR WALL
S C A L E :
51" = 1'-0"
EXTERIOR TO INTERIOR WALL INTERSECTION V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
A . E
. E CC LES T O
N
C 90716
C IV I L
R E G
IS
T E R E D
PROFES S IO NA L
E N G
IN
E E R
S
T A T E OF CA L IFORNI
A
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
1' -0
M
IN
HD AND AB PER PLAN SET
FLUSH ON SILL PLATE
SHEAR WALL EDGE NAILING
ALONG FULL HEIGHT OF POST
HD POST SIZE PER PLAN
(2) 1-1/2"Ø MAX BORED HOLES
ALLOWED IN HATCH AREA.
ANCHOR BOLTS PER PLAN
3" M
IN
1' -0
TOP OF CURB
32" MAX
TOP OF SLAB
7" M
IN
EM
B
ED
M
EN
T, T
YP
℄ OF
CURB
BPS5/8-6 BEARING
PLATE
ANCHOR BOLT PER PLANS
1/2" MAX
CURB OR SLAB
WHERE OCCURS
SECTION "A"
PROVIDE SILL
PLATE W/ FULL
LEVEL BEARING ON
CONCRETE OR
MORTAR BED
8" MIN, 12" MAX FROM
END OF SILL PLATE OR
HOLE GREATER THAN
1/3 PLATE WIDTH
A
1-3/4" MIN
NOTE: USE POSTS AT CORNERS AND INTERSECTIONS WHERE SHOWN ON FOUNDATION PLAN.
INTERSECTION CORNER
STUD, TYP
WSP WHERE OCCURS, TYP
TRUSS BC
SDPW19600 AT 4'-0" OC,
MIN 2 PER WALL
1/ 2"
C
LR
NON-BEARING WALL
BLOCK AT 4'-0" OC,
MIN 2 PER WALL
SDPW19600
1/ 2"
C
LR
NON-BEARING WALL
0" O
FF
S
ET
TRUSS BC
(2) 16d EA END
PERPENDICULAR PARALLEL
0" O
FF
S
ET
4'-0" MIN LAP, TYP
3"
1/
4"
3" 1 1/2"
(20) 10d COMMON NAILS
PER SPLICE SIDE
DOUBLE TOP PLATE
SPLICE OVER CENTERLINE
OF STUD, TYP
SPLICE AT INTERSECTING
WALL
(0.4*D)Ø MAX HOLE
DOUBLE TOP PLATE
(0.6*D)Ø MAX HOLE OR MAX
NOTCH:
PROVIDE CTS218 EA PLATE W/
(24) 10d PER STRAP1'-0" MIN
D
NOTES:
1. DO NOT LOCATE HOLES WITHIN 4'-0" EA SIDE OF TOP PLATE SPLICES.
2. DO NOT LOCATE HOLES WITHIN 12" OF END OF STUD.
3. ALTERATION OF OTHER STRUCTURAL MEMBERS IS NOT PERMITTED UNLESS OTHERWISE DETAILED.
4. PORTION OF STUD REMAINING AROUND HOLES SHALL BE SOUND WOOD WITHOUT EXCESSIVE STRENGTH
REDUCING PROPERTIES SUCH AS KNOTS, BREAKS, SPLITS, EXCESSIVE SLOPE GRAIN, ETC.
STUDS
5/8" MIN
EDGE
DISTANCE
SINGLE STUD: (0.4D)Ø MAX HOLE
DOUBLE STUD OR (0.6D)Ø MAX HOLE
NONBEARING:
BEARING/EXTERIOR: (0.25D) MAX NOTCH DEPTH
NON BEARING: (0.4D) MAX NOTCH DEPTH
D M
IN
D
3/ 4"
M
IN
ED
G E
D
IS
TA
N C E
4" MAX
0.
6D
M A X
B
LO
C K
ED
U N B
LO
C K
ED
MEMBER
BELOW
EDGE NAILING
FIELD NAILING
BLK WHERE
NOTED
W/4 TYP
STUD, TRUSS OR BLK PLACED
SO JOINT IS CENTERED
NAIL SIZE &
SPACING PER PLAN
W (1 1/2" MIN)
1/8" GAP
3"
22° 1/2" MIN
1/2" MIN
DTP
SPLICE
3"
22.0°
1/
2"
TRUSS TO DTP OR BEAM
WIDE FACE STUD TO SILL
NARROW FACE TO DTP OR BEAM
1/2" MIN
7/8" MAX
3/4" MIN
1" MAX
22°
DTP TO TRUSS/BEAM (SINGLE)
1/2" MIN
1-3/4" MAX
1/2" MIN
MEMBER
BELOW
EDGE NAILING
FIELD NAILING
NOTE: OPENING IN SHEAR WALL PANELS TO BE SPACED NOT CLOSER THAN 4'-0" OC HORIZ AND
8'-0" OC VERT
NO BLK REQD
FOR OPENINGS
SMALLER THAN
8"x8"
S Q M
A X
FLAT BLK @ EDGES OF OPENING
W/ NAILING TO MATCH EDGE
CMSTC16 W/ (20)
10d EA SIDE
CORNER STUDS
DTP
2x TIE PLATE OR DTP
WHERE OCCURS
S C A L E :
2 1" = 1'-0" HOLDOWN POST
S C A L E :
33/4" = 1'-0" LOAD-BEARING WALL SILL PLATE ANCHORAGE
S C A L E :
4 1-1/2" = 1'-0" LOAD-BEARING WALL CORNER
S C A L E :
11" = 1'-0" NON-LOAD-BEARING WALL FASTENING
S C A L E :
11 1" = 1'-0" LOAD-BEARING DOUBLE TOP PLATE SPLICE
S C A L E :
7 1" = 1'-0"NOTCHES AND BORED HOLES IN STRUCTURAL MEMBERS
S C A L E :
6 1/2" = 1'-0" STRUCTURAL SHEATHING LAYOUT
S C A L E :
8 6" = 1'-0" STRUCTURAL SHEATHING NAILING
S511
STANDARD FRAMING DETAILS
A. ECCLESTON
A. ECCLESTON
K. LAM
C U s e rs
\A E c c le s t\ A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
S S .d g
:2
S C A L E :
5 1" = 1'-0" SDWC CONNECTIONS
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
TE
CHN
ICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs Va ul ts
1131 S STREET, SACRAMENTO, CA 95811-2460
A . E
. E CC LESTO
N
C 90716
C IV I L
R E
G I S
T E R E D
PROFES S IO NA L
E N G
IN
E E R
S
TA TE OF CA L IFORNI
A
S C A L E :
9 1/2" = 1'-0" OPENING IN SHEAR PANELS
S C A L E :
10 NTS STRAP AT CORNERS OF TOP PLATE
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
A . E
. E CC LES T O
N
C 90716
C IV I L
R E G
IS
T E R E D
PROFES S IO NA L
E N G
IN
E E R
S
T A T E OF CA L IFORNI
A
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d
BN
WSP
BN
2x SHAPED BLK W/ VENT HOLES, SEE ARCH DETAILS
BN
2x FASCIA W/ (2)10d
NAILS TO TRUSS
SDWC15600 NARROW FACE
OF STUD TO DTP, SEE 5/S511
(2) SDWC15450 WIDE FACE
OF STUD TO SILL PLATE,
SEE 5/S511
(2) SDWC15600 TRUSS TO
DTP, SEE 5/S511
A35 EA BLK TO DTP
RAKE WALL STUD, TYP
2x6 SHAPED BLK, TYP
A35 BLK TO DTP, TYP
CMSTC16 W/ (20)
10d NAILS EA SIDE
2x BLK, TYP
SEE ARCHITECTURAL DRAWINGS
FOR FASTENING OF METAL
ROOFING TO BLK
TRUSS TC, TYP
VENTED RIDGE, SEE ARCHITECTURAL
DETAILS
2x SHAPED BLK W/ VENT
HOLES, SEE ARCH DETAILS
BN
2x FASCIA W/ (2)10d
NAILS TO TRUSS
BEAM PER PLANS
(2) SDWC15600 TRUSS
TO BEAM, SEE 5/S511
A35 BLK TO BEAM
STUDS PER PLANS
HEADER PER PLAN
(2) 2x6 OR HOLDOWN
POST
SILL ANCHORAGE PER PLAN
SW HD,
WHERE
OCCURS
A35, TYP
ALTERNATE FRAMING,
(4) 16d STUD TO HDRHH6 STUD TO
HEADER
A35 HEADER TO
JACK STUD T&B
EN
STAGGERED
AT DOUBLE
STUDS
FIRE BLOCKING, SEE
ARCHITECTURAL
JACK STUD
(2) SDWC15450 WIDE
FACE OF STUD TO SILL
PLATE, SEE 5/S511
SDWC15600 NARROW FACE
OF STUD TO DTP, SEE 5/S511
16d AT 12" OC
STAGGERED
STUDS PER PLANS
HEADER PER PLAN
(2) 2x6 OR HOLDOWN
POST
SILL ANCHORAGE
PER PLAN
HH6 STUD
TO HEADER
A35, TYP
ALTERNATE FRAMING,
(4) 16d STUD TO HDR
FIRE BLOCKING, SEE
ARCHITECTURAL
A35 HEADER TO JACK
STUD T&B
JACK STUD
EN
STAGGERED
AT DOUBLE
STUDS
SDWC15600 NARROW FACE OF STUD TO DTP, SEE 5/S511
(2) SDWC15450 WIDE
FACE OF STUD TO SILL
PLATE, SEE 5/S511
16d AT
12" OC
STAGGERED
2x FASCIA W/ (2)10d
NAILS TO OLKR
BN
BN
STUD WALL
DTP
A35 OLKR TO TRUSS
OLKR
TRUSS
WSP
WSP
2x BLK BN
SILL PLATE
(2) SDWC15600 OLKR
TO DTP, SEE 5/S511
SDWC15600 NARROW FACE
OF STUD TO DTP, SEE 5/S511
(2) SDWC15450 WIDE FACE
OF STUD TO SILL PLATE,
SEE 5/S511
(4) 10d AT 6" OC WSP TO OLKR
A35 EA BLOCK TO DTP
2x BLK, TYP
BN
DRAG TRUSS ALIGN
W/ 2x BLK LINE
(SCISSOR TRUSS
WHERE OCCURS)
CMSTC16 W/ (20)
10d NAILS EA SIDE
2x SCAB W/ (10) 10d
NAILS TO TRUSS BC
STRAP NAILS TO
CLR TRUSS PL
BN
(6) 8D NAILS/BLK,
TYP
LS30 TRUSS BC TO BLK EA END
2x FLAT BLK AT EA
END, MITER TO FIT
BN
TRUSS TC
TRUSS BC
SDWS22600DB
AT 16" OC, TO DTP
SDWS22600DB
AT 16" OC, TO
STUD OR BLK
SHAPED 2x10 LEDGER
W/ (3) SDWS22600DB
AT 16" OC TO STUD
OR BLK
HTU210 TRUSS
TO LEDGER
SHORTENED
HEEL TRUSS
VTCR VALLEY TRUSS BC TO
EA COMMON TRUSS TC AT
INTERSECTION, TYP
SHAPED 2x BLK
BTWN TRUSSES W/
(4) 10d TO LEDGER
10d STAGGERED AT 6"
OC WPS TO LEDGER
BN (4) 10d AT 6" OC WSP
TO BLK
2x BLK AT 24" OC
DTP
STUD, TYPSHEARWALL
DOUBLE 2x6 BLK, TYP
LEDGER
TRUSS DTP
EXTEND CMSTC16 TO
ACHIEVE MIN (20) 10d
NAILS TO DTP
EXTEND CMSTC16 LENGTH OF SHEARWALL,
10d NAILS TO BLK EVERY OTHER HOLE
S512
FRAMING DETAILS
A. ECCLESTON
A. ECCLESTON
K. LAM
C U s e rs
\A E c c le s t\ A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
S S
S .d g
:2
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
TE
CHN
ICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs Va ul ts
1131 S STREET, SACRAMENTO, CA 95811-2460
A � E
� E
CCLESTO
N
C 90716
CIVIL
R E
G
IS
T E
R
ED
P
ROFESSIONA
L
E N
G
IN
E E
R
S
T
ATE OF CALIFORN
IA
S C A L E :
41" = 1'-0"
TYPICAL EAVE WALL
S C A L E :
31" = 1'-0"
TYPICAL EAVE TO BEAM CONNECTION
S C A L E :
61" = 1'-0"
RIDGE OUTLOOKER
S C A L E :
91" = 1'-0"
TYPICAL VENTED RIDGE
S C A L E :
11/2" = 1'-0"
TYPICAL EAVE WALL
S C A L E :
21/2" = 1'-0"
TYPICAL RAKE WALL
S C A L E :
51" = 1'-0"
TYPICAL RAKE WALL
S C A L E :
71" = 1'-0"
DRAG TRUSS
S C A L E :
81" = 1'-0"
HEEL TRUSS CONNECTION AND TYPICAL VALLEY SET
S C A L E :
101" = 1'-0"
DOUBLE TOP PLATE TO BALLOON-FRAMED WALL
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
A . E
. E CC LES T O
N
C 90716
C IV I L
R E G
IS
T E R E D
PROFES S IO NA L
E N G
IN
E E R
S
T A T E OF CA L IFORNI
A
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d
POST
6-16d STUD TO BEAM EA SIDE
16d AT 12" OC, STUD TO POST
FULL HEIGHT STUD EA SIDE
BEAM, PER PLANS
LTP4 BLK
TO TRUSS
BN
2x BLK
WSP
BN
A35 OLKR TO TRUSS BN
2x FASCIA W/ (2)10d
NAILS TO OLKR
SDWC15600
TRUSS TO OLKR
LATERAL BRACING
AS REQUIRED BY
TRUSS CALCS
3"
(4) 10d AT 6" OC
WSP TO OLKR
3"
5' -0
ST9 BEAM TO DTP
ALIGN W/ PORCH
BEAM BLK
CBT4Z BEAM
TO BRACE
CBT4Z BEAM TO POST
CBT4Z BRACE TO POST
6x6 BRACE
PORCH POST
PORCH BEAM
WSP
BUILDING WALL
RAKE WALL
BN
TRUSS TC
TRUSS BC
WSP
2x6 BLOCKING W/
2-16d EN TO STUD
EA SIDE
SDS25312 AT 16" OC,
TO STUD OR BLK
DRAG TRUSS ALIGN
W/ 2x BLK LINE
CMSTC16 W/ (10)
10d EA SIDE
2x BLK, TYP
BEAM
NOTCH BEAM FOR DTP
POST
BN
STRAP NAILS TO
CLR TRUSS PL
(4) 16d EA BLK TO
TRUSS
2x SCAB W/ (5) 10d
NAILS TO TRUSS BC
BEAM TO WALL, SEE DETAIL 2
POST
6-16d STUD TO BEAM EA SIDE
16d AT 12" OC, STUD TO POST
FULL HEIGHT STUD EA SIDE
BEAM, PER PLANS
DTP
DRAG TRUSS
THA29 TRUSS TO
PERP TRUSS
BN
WSP
BN
(2) SDWC15600 TRUSS TO
DTP, SEE 5/S511
SDWC15600 NARROW
FACE OF STUD TO DTP,
SEE 5/S511
(2) SDWC15450 WIDE FACE
OF STUD TO SILL PLATE,
SEE 5/S511
(4) 16d EA BLK
TO TRUSS
TRUSS
DRAG TRUSS BEYOND
CMSTC16 W/ (10)
10d NAILS EA SIDE
EVERY OTHER HOLE
TO BLOCK AND DTP
2x BLK, TYP
DTPTRUSS, TYP
CMSTC16 W/ (10)
10d EA SIDE
BEAM
NOTCH BEAM FOR DTP
POST
DTP
6-16d STUD TO BEAM
16d AT 12" OC, STUD TO POST
S513
FRAMING DETAILS
A. ECCLESTON
A. ECCLESTON
K. LAM
C U s e rs
\A E c c le s t\ A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
S S
S .d g
:3
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
TE
CHN
ICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs Va ul ts
1131 S STREET, SACRAMENTO, CA 95811-2460
A
E� E
CCLEST
O
N
C 90716
CIVIL
R E
G
IS
T E
R E
D P
ROFESSIONA
L
E N
G
IN
E E
R
S
T A
TE OF CALIFORN
IA
S C A L E :
31" = 1'-0"
BEAM PERPENDICULAR TO WALL
S C A L E :
41" = 1'-0"
TYPICAL PORCH RAKE WALL
S C A L E :
71" = 1'-0"
ENTRY ANGLE-BRACED PORCH
S C A L E :
51" = 1'-0"
PORCH TO RAKE WALL
S C A L E :
11" = 1'-0"
PORCH CONNECTION TO DRAG TRUSS
S C A L E :
21" = 1'-0"
BEAM PERPENDICULAR TO WALL
S C A L E :
61" = 1'-0"
ENTRY TRUSS
S C A L E :
81" = 1'-0"
ENTRY DRAG TRUSS
S C A L E :
91" = 1'-0"
BEAM AT CORNER V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
A . E
. E CC LES T O
N
C 90716
C IV I L
R E G
IS
T E R E D
PROFES S IO NA L
E N G
IN
E E R
S
T A T E OF CA L IFORNI
A
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 10d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 10d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d AutoCAD SHX Text: 16d
GENERAL REQUIREMENTS
1. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND SHALL BE EQUAL IN QUALITY, TYPE, CAPACITY, EFFICIENCY AND ACCESSORIES TO THE EQUIPMENT NOTED ON THE DRAWINGS. ADJUSTMENTS TO
CONSTRUCTION AND ACCESSORIES ON SUBSTITUTED EQUIPMENT MAY BE REQUIRED TO ACHIEVE THIS
EQUALITY, AND ALL SUCH ADJUSTMENTS SHALL BE PERFORMED TO ACHIEVE FULLY OPERATIONAL
SYSTEMS. INSTALLER SHALL MAKE ANY CHANGES IN DUCTWORK, PIPING, FRAMING, ETC., AS REQUIRED TO
ACCOMMODATE SUBSTITUTED EQUIPMENT.
2. INSTALL ALL EQUIPMENT AND MATERIALS AND PERFORM ALL WORK IN ACCORDANCE WITH ALL
APPLICABLE CODES. APPLICABLE CODES SHALL INCLUDE, BUT NOT BE LIMITED TO THE 2022 EDITIONS OF
THE CALIFORNIA MECHANICAL CODE, CALIFORNIA PLUMBING CODE & CALIFORNIA BUILDING CODE, THE
CALIFORNIA CODE OF REGULATIONS (CCR), CALIFORNIA FIRE REGULATIONS, AND CALIFORNIA ENERGY
EFFICIENCY STANDARDS. WHERE HEAVIER GAGES OF MATERIAL, LARGER SIZES, THICKER INSULATION OR
MORE STRINGENT REQUIREMENTS THAN THE CODES ARE REQUIRED BY THE CONSTRUCTION DOCUMENTS, SUCH INCREASED REQUIREMENTS SHALL APPLY. WHERE THERE MAY BE DISCREPANCIES OR DIFFERENCES
BETWEEN THE CODE REQUIREMENTS AND THE CONSTRUCTION DOCUMENTS, THE MORE STRINGENT
REQUIREMENTS SHALL GOVERN.
3. CONTROLS SHALL COMPLY WITH THE 2022 EDITION OF THE CALIFORNIA ENERGY CODE, SUBCHAPTER 3, SECTION 122. ALL CONTROL SYSTEM COMPONENTS AND CONTROL WIRING REQUIRED AND NECESSARY
FOR A COMPLETE AND WORKABLE SYSTEM SHALL BE FURNISHED AND INSTALLED WHETHER OR NOT
SHOWN ON THE CONSTRUCTION DOCUMENTS.
4. ALL AIR AND WATER SYSTEMS SHALL UNDERGO TESTING AND BALANCING BY QUALIFIED TESTING AND
BALANCING PERSONNEL, USING SMACNA, TABB, AABC AND/OR NEBB PROCEDURES, AND THE PROJECT
SPECIFICATIONS. FLOW QUANTITIES SHALL BE BALANCED TO NOT MORE THAN 10% ABOVE OR 0% BELOW
THE QUANTITIES SHOWN ON THE DRAWINGS. SUBMIT A COMPLETE TEST AND BALANCE REPORT
INDICATING, AS A MINIMUM, THE FLOW DELIVERY FOR EACH AIR OUTLET LOCATION, THE FINAL OPERATING
DATA FOR THE SYSTEMS AND THE AIR CONDITIONING UNITS.
5. SUBMIT FOR APPROVAL, COMPLETE SUBMITTAL DATA ON SPECIFIED AND PROPOSED EQUIPMENT AND
MATERIALS. SUBMITTALS SHALL INCLUDE EQUIPMENT SIZES, CAPACITY, MOTOR LOCATIONS,
PERFORMANCE CURVES AND OTHER PERTINENT DATA. EACH SUBMITTAL SHALL INCLUDE IDENTIFICATION
TAGS OR SYMBOLS TO MATCH THE CONSTRUCTION DOCUMENTS. PARTIAL SUBMITTALS OR SUBMITTALS
WHICH ARE NOT MARKED WITH EQUIPMENT TAGS OR PERFORMANCE DATA WILL BE REJECTED. REFER TO
PROJECT SPECIFICATIONS FOR ADDITIONAL SUBMITTAL REQUIREMENTS.
6. PROVIDE PERMANENT ENGRAVED PLASTIC NAME PLATES FOR ALL EQUIPMENT INSTALLED, INDICATING THE
PLAN DESIGNATION OF THE UNIT (GRVR-1, LV-1, IDU-1, ETC.) AND ALSO THE BUILDING AREA SERVED
(BEDROOMS, CONFERENCE ROOM, ETC.). STAMPED METAL TAPES APPLIED WITH SELF-CONTAINED
ADHESIVE WILL NOT BE ACCEPTABLE.
7. INSTALLER SHALL VERIFY ALL WORK CONDITIONS PRIOR TO COMMENCING WORK, INCLUDING, BUT NOT
LIMITED TO: DIMENSIONS, EQUIPMENT, STRUCTURAL ELEMENTS, ELECTRICAL REQUIRMENTS, MATERIALS
INDICATED AS EXISTING, AS WELL AS THE COORDINATED INSTALLATION OF ALL NEW WORK, MATERIALS, EQUIPMENT, ETC. COORDINATE THE LOCATIONS OF ALL EQUIPMENT WITH STRUCTURAL, AND ALL OTHER
AFFECTED TRADES.
8. INSTALLER SHALL FIELD COORDINATE AND INSTALL PACKAGED HVAC EQUIPMENT TO MAINTAIN A MINIMUM
OF 10'-0" CLEARANCE FROM OUTSIDE AIR INTAKE TO ALL EXHAUST OUTLETS, PLUMBING VENT-THRU-ROOFS
(VTR'S), FLUE VENT DISCHARGES, TYPICAL.
9. MECHANICAL SYSTEMS DESIGN REFLECT EQUIPMENT SPECIFIED. WHEN EQUIPMENT SUBSTITUTIONS
OCCUR AND DUCT CONNECTIONS, CONFIGURATIONS & SIZES, GAS INPUT AND ELECTRICAL SERVICE VARIES
FROM THAT SPECIFIED, THEN IT SHALL BE THE RESPONSIBILITY OF THE INSTALLER TO PREFORM ALL
REQUIRED OR NECESSARY ADJUSTMENTS OR MODIFICATIONS WHEN THE SUBSTITUTED EQUIPMENT
REFLECT OR REQUIRE REVISIONS OR CHANGES FROM THAT SHOWN ON THE CONSTRUCTION DOCUMENTS.
HVAC DUCTWORK
10. EXCEPT AS OTHERWISE ALLOWED OR PERMITTED, HVAC DUCTWORK SHALL BE CONSTRUCTED OF SMACNA
GAGE (MINIMUM 26 GA THICKNESS) RIGID GALVANIZED STEEL MATERIAL IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS. PROVIDE FLAT SEAM CONSTRUCTION FOR ANY DUCTS EXPOSED IN OCCUPIED
SPACE. DUCTWORK SHALL CLEAR OBSTRUCTIONS, PRESERVE HEADROOM AND KEEP OPENINGS,
ACCESSWAYS AND PASSAGEWAYS CLEAR, WHETHER OR NOT SHOWN ON THE DRAWINGS. ALL DUCT SIZES
SHOWN REFER TO THE NET INSIDE DIMENSION OF THE DUCT.
11. CONSTRUCT, FABRICATE AND INSTALL ALL DUCTWORK IN ACCORDANCE WITH THE LATEST EDITION OF
SMACNA DUCT CONSTRUCTION STANDARDS AND GUIDELINES, THE CALIFORNIA MECHANICAL CODE AND
MANUFACTURER RECOMMENDATIONS. ALL DUCT JOINTS INCLUDING MECHANICAL FLANGED JOINTS SHALL
BE SEALED WITH SILVER TAPE, OR ARABOL AND CANVAS. SEAL THE JOINTS OF ALL DUCTS EXPOSED TO
THE WEATHER WITH ARABOL AND CANVAS.
12. ROUND DUCTWORK SHOWN ON THE DRAWINGS SHALL BE PREFABRICATED TYPE. NOTE: ALUMINUM
FLEXIBLE DUCT IS NOT ACCEPTABLE IN LIEU OF ROUND RIGID DUCTWORK. IF RECTANGULAR DUCTWORK IS
USED IN LIEU OF ROUND DUCT, THE RECTANGULAR DUCT AREA SHALL BE EQUIVALENT TO THE NET AREA OF
THE ROUND DUCT. THE ASPECT RATIO OF THE RECTANGULAR DUCTWORK FROM THE LONG SIDE TO THE
SHORT SIDE SHALL NOT EXCEED 2:1. TRANSITION DUCT SLOPE RATIO SHALL BE 1:5.
13. PROVIDE ALL BRANCH DUCTS WITH VOLUME DAMPERS WITH LOCKING QUADRANTS LOCATED AT LEAST FIVE
FEET (5'-0") FROM THE GRILLE OR DIFFUSER SERVED.
14. WHERE APPLICABLE, ALL DUCTWORK RUNS CONNECTED TO A DIFFUSER BOX SHALL BE CONNECTED VIA A
RIGID SHEETMETAL ELBOW.
DUCT INSULATION
15. PROVIDE ALL SUPPLY AND RETURN DUCTS WITH EXTERIOR INSULATION, FIBERGLASS MATERIAL DUCT
WRAP, WITH FACTORY APPLIED FLAME RETARDANT FOIL REINFORCED KRAFT FACING. INSULATION SHALL
HAVE MINIMUM R-8 VALUE. ALL INSTALLATIONS SHALL BE ACCORDING TO MANUFACTURER INSTRUCTIONS
AND PROJECT SPECIFICATIONS. LAP ALL JOINTS 4" MINIMUM, AND SECURE WITH GALVANIZED STEEL WIRE.
ACOUSTICAL DUCT LINER
16. IN ADDITION TO THE EXTERIOR INSULATION, PROVIDE ALL MAIN DUCT PLENUMS, AND MAIN DUCT RUNS (AS
INDICATED WITH "L" DESIGNATION AFTER THE DUCT SIZE) WITH INTERIOR ACOUSTICAL DUCT LINER. DUCT
LINER SHALL BE 1-1/2" THICK. ALL INSTALLATION SHALL BE ACCORDING TO MANUFACTURER
INSTRUCTIONS AND PROJECT SPECIFICATIONS. INSTALL WITH 100% COVERAGE ADHESIVE, AND FURTHER
APPLY MECHANICAL PIN FASTENERS WHERE DUCT SIDE EXCEEDS 24". SEAL BUTT ENDS OF EXPOSED
INSULATION IN THE DUCTS WITH MANUFACTURERS RECOMMENDED SEALANT OR ADHESIVE.
RIGID FIBER GLASS DUCTBOARD
17. WHERE APPLICABLE OR REQUIRED/NOTED/ALLOWED, PROVIDE RIGID FIBERGLASS DUCT BOARD WITH
THICKNESS OF 1-1/2" MINIMUM. INSTALL ACCORDING TO MANUFACTURER INSTRUCTIONS.
FLEXIBLE DUCT
18. FLEXIBLE DUCT MAY BE USED AT BRANCH DUCT SECTIONS FOR CONNECTIONS BETWEEN RIGID SHEET
METAL DUCTS PRIOR TO DIFFUSERS, GRILLES, ETC. FLEXIBLE DUCTS SHALL BE NO GREATER THAN 6 FEET
IN LENGTH AND SHALL NOT BE ALLOWED IN ANY EXPOSED DUCT LOCATIONS. COMPLY WITH
REQUIREMENTS OF THE PROJECT SPECIFICATIONS.
19. FLEXIBLE DUCT FOR SUPPLY & RETURN AIR APPLICATIONS SHALL BE INSULATED TYPE CPE LINER DUCT
PERMANENTLY BONDED TO A COATED ALUMINUM CORRIGATED, PROVIDED WITH FIBERGLASS INSULATION
EQUIVALENT TO AN R-8 VALUE, AND LOW PERMEABILITY FIBERGLASS REINFORCED METALLIZED OUTER FILM
VAPOR BARRIER. UNINSULATED FLEXIBLE ALUMINUM DUCT SHALL BE ALLOWED FOR EXHAUST
APPLICATIONS.
20. FLEXIBLE DUCT FOR TRANSFER AIR APPLICATIONS SHALL BE INSULATED TYPE CPE LINER DUCT
PERMANENTLY BONDED TO A COATED SPRING STEEL WIRE HELIX, PROVIDED WITH FIBERGLASS INSULATION
EQUIVALENT TO AN R-8 VALUE, AND LOW PERMEABILITY FIBERGLASS REINFORCED METALLIZED OUTER FILM
VAPOR BARRIER. UNINSULATED FLEXIBLE ALUMINUM DUCT SHALL BE ALLOWED FOR EXHAUST
APPLICATIONS (EXCEPT AT THE APPARATUS BAYS).
21. FLEXIBLE DUCT SHALL BE INSTALLED AS PER THE LATEST EDITION OF SMACNA DUCT CONSTRUCTION
STANDARDS AND GUIDELINES, AND MANUFACTURER RECOMMENDATIONS. THE FINISHED DUCT SYSTEM
SHALL MEET THE REQUIREMENTS OF CMC, AND COMPLYING WITH THE REQUIREMENTS OF U.L. STANDARD
FOR SAFETY U.L. 181 FOR CLASS 1 AIR DUCT. SECURE FLEXIBLE DUCTWORK WITH TWO MECHANICALLY
APPLIED PLASTIC STRAPS OR ONE WORM DRIVE CLAMP. SUPPORT FLEXIBLE DUCTS WITH 2" WIDE HANGER
STRAPS.
DUCT TAPES & ADHESIVES
22. APPROVED TAPES (PRESSURE-SENSITIVE AND HEAT SCALABLE) SHALL MEET THE REQUIREMENTS OF U.L.
181A, CLOSURE SYSTEMS FOR USE WITH RIGID AIR DUCTS AND AIR CONNECTORS. GLASS FABRIC AND
MASTIC SHALL BE APPROVED BY THE SPECIFIC DUCT BOARD MANUFACTURER.
23. ALL FABRICATION, APPLICATION, AND INSTALLATION STEPS SHALL BE IN COMPLIANCE WITH THE
MANUFACTURER'S RECOMMENDATION AND NAIMA STANDARDS, UNLESS CLEARLY STATED ON APPROVED
WAIVERS.
DIFFUSERS, GRILLES & REGISTERS
24. ALL DIFFUSERS, GRILLES AND REGISTERS SHALL BE OF COMMERICAL QUALITY AND DESIGN AND GIVE THE
AIR PATTERN AS SHOWN ON THE HVAC PLAN DRAWINGS. FOR MODULAR CORE CEILING DIFFUSERS, INSTALLER SHALL FIELD ADJUST AIR PATTERN AS REQUIRED AT EACH INDIVIDUAL DIFFUSER INSTALLATION
LOCATION.
25. ALL DIFFUSER/REGISTER BOXES SHALL BE SUPPORTED ON ALL FOUR SIDES: WITH T-BARS IN A T-BAR
CEILING SYSTEM, OR WITH 2 X 4 BLOCKING IN A TRUSS SUPPORTED CEILING SYSTEM.
DUCTWORK AND PIPING SUPPORTS
26. SUPPORTS FOR ALL PIPING AND DUCTWORK SHALL BE IN ACCORDANCE WITH CALIFORNIA MECHANICAL
CODE, CALIFORNIA PLUMBING CODE AND SMACNA "GUIDELINES FOR SEISMIC RESTRAINT OF MECHANICAL
SYSTEMS". INSTALLER SHALL PROVIDE CALCULATIONS FOR ISOLATORS AND MOUNTING ACCEPTABLE TO
THE REVIEWING AUTHORITY WHEN REQUIRED BY SAME.
FIRE DAMPERS
27. FIRE DAMPERS SHALL BE ACTIVATED BY A SMOKE SENSOR LOCATED BETWEEN HALLWAY 2 & 3 PER CBC
717.5. FIRE DAMPER DETAIL(S) SHOWN ON THE DRAWINGS ARE FOR REFERENCE ONLY. FIRE DAMPERS
SHALL BE STATE FIRE MARSHAL APPROVED AND INSTALLED STRICTLY PER MANUFACTURER'S PRINTED
INSTRUCTIONS. MANUFACTURER'S INSTALLATION INSTRUCTIONS SHALL BE MADE AVAILABLE TO THE
STATE FIRE MARSHAL FOR VERIFICATION.
AUTOMATIC AIRFLOW SHUTOFFS
28. AUTOMATIC SHUTOFF SHALL BE PROVIDED FOR ALL AIR-MOVING SYSTEMS SUPPLYING AIR IN EXCESS OF
2,000 CFM (940 L/S) TO ENCLOSED SPACES WITHIN BUILDINGS. FURTHERMORE, AUTOMATIC SHUTOFF
SHALL BE PROVIDED FOR ALL AIR-MOVING SYSTEMS REGARDLESS OF CAPACITY IF SO INDICATED ON THE
DRAWINGS. AUTOMATIC SHUTOFF SHALL BE ACCOMPLISHED BY INTERRUPTING THE POWER SOURCE OF
THE AIR-MOVING EQUIPMENT UPON DETECTION OF SMOKE IN THE MAIN SUPPLY-AIR DUCT SERVED BY
SUCH EQUIPMENT. SMOKE DETECTORS SHALL BE LABELED BY AN APPROVED AGENCY AND LISTED BY THE
CALIFORNIA STATE FIRE MARSHAL FOR AIR DUCT INSTALLATION. INSTALL IN ACCORDANCE WITH THE
MANUFACTURER'S APPROVED INSTALLATION INSTRUCTIONS. SUCH DEVICES SHALL BE COMPATIBLE WITH
THE OPERATING VELOCITIES, PRESSURES, TEMPERATURES AND HUMIDITIES OF THE SYSTEM. WHERE FIRE
DETECTION OR ALARM SYSTEMS ARE PROVIDED FOR THE BUILDING, THE SMOKE DETECTORS REQUIRED BY
THIS SECTION SHALL BE SUPERVISED BY SUCH SYSTEMS AND INSTALLED IN ACCORDANCE WITH NFPA 72
AND THE CALIFORNIA BUILDING AND FIRE CODES. THE REQUIREMENTS FOR AUTOMATIC SHUTOFFS ARE
SUBJECT TO EXCEPTIONS AS INDICATED IN SECTION 608.0 OF THE CALIFORNIA MECHANICAL CODE.
VENTILATION AIR
29. PER CBC 1202.1, BUILDINGS SHALL BE EITHER PROVIDED WITH NATURAL VENTILATION IN ACCORDANCE
WITH CBC SECTION 1202.5, OR PROVIDED WITH MECHANICAL VENTILATION IN ACCORDANCE WITH THE
CALIFORNIA MECHANICAL CODE, CHAPTER 4.
FLUE VENTS
30. VENTS SHALL EXTEND ABOVE THE ROOF SURFACE, THROUGH A FLASHING, AND TERMINATE IN A LISTED
VENT CAP INSTALLED IN ACCORDANCE WITH ITS LISTING AND THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
MISCELLANEOUS GENERAL MECHANICAL NOTES
31. COORDINATE ALL WORK AMONG VARIOUS AFFECTED TRADES AS REQUIRED AND AS NECESSARY TO ENSURE
THE INSTALLATION OF ALL WORK SHALL FIT IN THE AVAILABLE SPACE. MODIFY/EXTEND/ ADJUST WORK AS
NECESSARY TO ENSURE THAT ALL REQUIRED INSTALLATIONS AND CONNECTIONS ARE PROPERLY
COMPLETED.
32. ROUTE DUCTWORK INSIDE CEILING OR ATTIC SPACE TIGHT TO UNDERSIDE OF OVERHEAD ROOF FRAMING
MEMBERS AS MUCH AS POSSIBLE. FIELD COORDINATE ALL DUCT ROUTING AND SIZES WITH ACTUAL
CONDITIONS, STRUCTURAL MEMBERS, PIPING, OTHER DUCTS, SUPPORTS, LIGHT FIXTURES, ALL OTHER
AFFECTED TRADES, ETC., AND ADJUST ROUTING AS REQUIRED, TYPICAL.
33. PROVIDE ALL RECTANGULAR DUCT ELBOWS WITH DOUBLE THICKNESS TURNING VANES.
34. FURNISH AND INSTALL MANUAL VOLUME DAMPERS IN ALL INDIVIDUAL BRANCH DUCTS, WHETHER OR NOT
SHOWN ON THE DRAWINGS. BALANCE TO AIR VOLUME SHOWN, TYPICAL.
35. PROVIDE SUPPORTS AND BRACING AS APPLICABLE FOR ALL EQUIPMENT AND DUCTWORK AS REQUIRED BY
SMACNA STANDARDS, AND APPLICABLE CODE REQUIREMENTS.
36. ROUTE AND INSTALL ALL MECHANICAL SYSTEMS AND DUCTS IN A MANNER THAT WILL NOT BLOCK OR
OBSTRUCT PERSONNEL ACCESS AND USE OF THE CEILING ACCESS PANELS AND CATWALKS IN THE
BUILDING CEILING/ATTIC AREA SPACES. COORDINATE LOCATION OF ALL ACCESS PANELS AND ATTIC
WALKWAYS WITH ARCHITECTURAL AND STRUCTURAL.
37. DESCRIPTION OF WORK MAY INCLUDE BUT IS NOT LIMITED TO FURNISHING AND INSTALLING NEW SPLIT
SYSTEM CONDENSER, FAN COIL, AND OTHER EQUIPMENT SHOWN ON PLANS INCLUDING THERMOSTATS, AND ASSOCIATED EQUIPMENT AND COMPONENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY
TRANSITION, OFFSET, ETC. NECESSARY TO MAKE A COMPLETE AND FUNCTIONING SYSTEM CONSISTENT
WITH DESIGN INTENT. COMMISSION AND PERFORM OPERATIONAL TEST PER MANUFACTURER'S
INSTRUCTIONS.
38. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO REQUIREMENTS SET FORTH IN THE CURRENT
CALIFORNIA TITLE 24 MECHANICAL, PLUMBING AND ENERGY CODES, APPLICABLE INDUSTRY STANDARDS
AND THE MANUFACTURER'S INSTRUCTION. NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT
WORK NOT CONFORMING TO THESE CODES AND THE DESIGN SPECIFIED HEREIN. WHEN CONFLICT BETWEEN
CODES AND STANDARDS ARISE, THE MOST STRINGENT SHALL APPLY.
39. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S
RECOMMENDATIONS AND NOTE-2. PROVIDE ALL FITTINGS. LINESETS, DRAINS, AND OTHER DEVICES
REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.
40. FURNISH AND INSTALL CONDENSING UNIT ON MANUFACTURER'S PAD WHERE APPLICABLE AT LOCATION
SHOWN ON DRAWINGS. PAD HEIGHT SHALL BE 3 INCHES MINIMUM. MAINTAIN THE MANUFACTURER'S
CLEARANCES AROUND UNITS. DO NOT MOUNT UNIT TO EXTERIOR WALL.
41. MAINTENANCE LABELS SHALL BE AFFIXED TO ALL MECHANICAL EQUIPMENT IN THE DIRECTION OF FLOW.
42. ALL EQUIPMENT, PIPING, AND DEVICES AND MATERIALS INSTALLED OUTSIDE OF THE BUILDING OR
OTHERWISE EXPOSED TO THE WEATHER SHALL BE COMPLETELY WEATHERPROOF AND LEAK PROOF.
PROTECT WATER LINES FROM FREEZING AND CONDENSATION. INSULATION SHALL BE COVERED WITH
VAPOR BARRIER. PROTECT ALL DISSIMILAR METALS EXPOSED TO GALVANIC ACTION TO PREVENT
CORROSION.
43. ALL EQUIPMENT AND COMPONENTS FURNISHED AND INSTALLED SHALL BE NEW AND LISTED WITH AN
APPROVED TESTING AGENCY FOR THIS APPLICATION. UL LISTED. ETC.
44. FIELD COORDINATE ALL DUCT ROUTING AND SIZES WITH ACTUAL CONDITIONS, STRUCTURAL MEMBERS, PIPING, OTHER DUCTS, SUPPORTS, LIGHT FIXTURES, ALL OTHER AFFECTED TRADES, ETC., AND ADJUST
ROUTING AS REQUIRED, TYPICAL.
45. THE CONTRACTOR SHALL BE FAMILIAR WITH THE MECHANICAL AND PLUMBING SYSTEMS LAYOUT AND
DIAGRAMS BEFORE COMMENCING WORK. THE ENTIRE WORK SHALL BE COORDINATED, VISIT THE SITE, REFER TO CONSTRUCTION DRAWINGS, EQUIPMENT AND MACHINERY MANUFACTURER'S DATA SHEETS, CONNECTION DRAWINGS, AND PLUMBING EQUIPMENT LIST.
46. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY TRANSITION, OFFSET, ETC. NECESSARY TO MAKE A
COMPLETE AND FUNCTIONING SYSTEM CONSISTENT WITH DESIGN INTENT. WHEREVER PIPE REDUCERS OR
ENLARGERS ARE USED, THEY SHALL BE ECCENTRIC WITH FLAT SURFACE UPWARD TO AVOID AIR
ENTRAPMENT.
47. ALL THERMOSTATS SHALL BE CALIFORNIA ENERGY COMMISSION APPROVED, ENCASED WITH APPROVED
LOCKABLE COVERS LOCATED 4 FEET MAXIMUM ABOVE FINISHED FLOOR AT LOCATIONS SHOWN ON
DRAWING. VENTILATION SHALL BE PROVIDED DURING OCCUPANCY.
48. FAN COILS AND FURNACES LOCATED IN CEILING OR ATTIC SPACES SHALL HAVE PRIMARY AND SECONDARY
DRAINS, DEEP TRAPS AND PLUMBED TO PREVENT WATER DAMAGE TO CEILINGS.
49. SUSPEND DUCTS PER 2022 CBC RESTRAINT OF MECHANICAL SYSTEMS. ALL DUCTWORK SHALL BE
CONCEALED AND INSTALLED TO MAINTAIN THE MANUFACTURER'S CLEARANCES AND T-24 MANDATORY
MEASURES. PROVIDE VAPOR BARRIER WITH INSULATION.
50. ROUTE AND INSTALL ALL MECHANICAL SYSTEMS AND DUCTS IN A MANNER THAT WILL NOT BLOCK OR
OBSTRUCT PERSONNEL ACCESS AND USE OF THE CEILING ACCESS PANELS AND CATWALKS IN THE
BUILDING CEILING/ATTIC AREA SPACES. COORDINATE LOCATION OF ALL ACCESS PANELS AND CATWALKS
WITH ARCHITECTURAL AND STRUCTURAL.
51. INSTALL FIRE PROTECTION PER STATE FIRE MARSHALL AND NFPA 13. PROVIDE ACCESS TO ALL FIRE/SMOKE
DAMPERS.
52. ALL DUCT SMOKE DETECTORS AND FIRE DAMPERS SHALL BE STATE FIRE MARSHALL APPROVED AND
INSTALLED STRICTLY PER THE MANUFACTURER'S INSTRUCTIONS. FURNISH AND INSTALL WHERE DUCT
PENETRATE FIRE-RATED WALLS AND FLOORS. TYPICAL FOR ALL BUILDINGS. INSTALL ACCESS PANELS TO
ALL DAMPERS.
53. FLASH AND SEAL ALL PENETRATIONS THROUGH ROOF AND MAKE WATERTIGHT. INSULATE TO PREVENT
CONDENSATION. PIPE, VENT, AND DUCT ROOF PENETRATIONS SHALL BE COORDINATED WITH OTHER
TRADES AND STATE REPRESENTATIVE TO ENSURE ROOFING WARRANTY AND SOLAR-READY ZONES ARE
MAINTAINED.
54. COMPLETE ALL PIPING AND PLUMBING INSTALLATIONS AND JOINTS PER THE MANUFACTURER'S
INSTRUCTIONS, 2022 CMC, AND CPC CODES, STANDARDS AND BEST INDUSTRY PRACTICES.
55. THE CONTRACTOR SHALL VERIFY SIZE, LOCATION AND POINTS OF CONNECTIONS REQUIREMENTS OF
PROPOSED UTILITIES BEFORE COMMENCING WORK.
56. ALL EQUIPMENT AND PIPING SHALL BE SUPPORTED AND SEISMICALLY RESTRAINED PER 2022 CBC FOR
RESTRAINT OF MECHANICAL SYSTEMS.
57. THE CONTRACTOR SHALL ROUTE PIPING AND DUCTWORK TO AVOID INTERFERENCE WITH BUILDING
STRUCTURE, ELECTRICAL CONDUITS, LIGHT FIXTURES AND ELEVATOR PIPING AND TO PROVIDE ACCESS TO
MAINTENANCE. COORDINATE THE LOCATION OF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES WITH THE
ARCHITECTURAL REFLECTIVE CEILING PLAN, AND ELECTRICAL LIGHTING LAYOUT.
58. DESCRIPTION OF WORK MAY INCLUDE BUT IS NOT LIMITED TO FURNISHING AND INSTALLING NEW HVAC, GAS FURNACES, FAN COILS, HEATERS, EXHAUST FANS, AIR COMPRESSORS SYSTEM, GAS HEAT/ELECTRIC
PACKAGE, AND OTHER EQUIPMENT SHOWN ON PLANS INCLUDING DUCTS, GAS WATER HEATER,
THERMOSTATS, AND ASSOCIATED EQUIPMENT AND COMPONENTS. PROVIDE AND INSTALL THERMOSTATS, DUCTWORK, AND PIPING AS SHOWN ON DRAWINGS. COMMISSION AND PERFORM OPERATIONAL TEST PER
MANUFACTURER'S INSTRUCTIONS.
59. FURNISH AND INSTALL UNITS ON MANUFACTURER'S CURB WHERE APPLICABLE AT LOCATION SHOWN ON
DRAWINGS. PACKAGE UNIT PLATFORM HEIGHT SHALL BE 12 INCHES MINIMUM. MAINTAIN THE
MANUFACTURER'S CLEARANCES AROUND UNITS. ENSURE NO PLUMBING VENT IS WITHIN 10 FEET OF
OUTSIDE AIR INTAKE.
60. ALL MOUNTING HEIGHT ELEVATIONS INDICATED FOR LOUVERS AND EQUIPMENT ARE DIMENSIONED TO
BOTTOM OF LOUVER OR EQUIPMENT FINISH FLOOR. REFER TO ARCHITECTURAL FOR ADDITIONAL
INFORMATION.
61. INSULATE ALL PIPES IN CEILINGS, ATTICS AND WALLS TO PREVENT CONDENSATION DAMAGE TO ADJACENT
BUILDING COMPONENTS.
62. FURNISH AND INSTALL FIRE SUPPRESSION SYSTEMS FOR FIRE PROTECTION PER 2022 CFC CHAPTER 80:
2022 NFPA 13 AND 2022 NFPA 24.
GENERAL MECHANICAL (HVAC) NOTES
MECHANICAL GENERAL NOTES
M001
R. GALLAGHER
R. GALLAGHER
M. MADISON
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs V au lts
1131 S STREET, SACRAMENTO, CA 95811-2460
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \M
E C
H A N
IC
A L \2
M
.d
J n
:3
V2V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
MECHANICAL LEGENDMEP EQUIPMENT ANCHORAGE
CEILING SUPPLY AIR DIFFUSER/REGISTER
CEILING RETURN AIR GRILLE/REGISTER
FLEXIBLE AIR DUCTWORK
AIR FLOW DIRECTION
THERMOSTAT, 48" AFF MAX TO TOP OF BOX
HVAC
EA EXHAUST AIR
RR
FR
FLOOR RETURN AIR REGISTER
MANUAL VOLUME BALANCE DAMPER
ZONE DAMPER
CC COOLING COILS
CD CEILING DIFFUSER, CONDENSATE DRAIN
COND CONDENSING UNIT
FSD FIRE & SMOKE DAMPER
RR RETURN AIR REGISTER
RH RANGE HOOD
WD WALL DIFFUSER
ZD ZONE DAMPER
HP HEAT PUMP
RETURN AIRRA
VENTILATION AIR DAMPER
SENSOR
RETURN AIR DAMPER
EXHAUST AIR DAMPER
BY-PASS DAMPER
BACK DRAFT DAMPER
TO BE RELOCATED
VL VENTILATION LOUVER
BAROMETRIC RELIEF DAMPER
RIGID DUCTWORK
WV WALL VENT
MVD
MD
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
TG TRANSFER GRILLE
AF AIR FILTER
FURN, FU FURNACE UNIT
TO BE DEMOLISHED/REMOVED
EXISTING TO BE FIELD VERIFIED
ABOVE CEILINGABC
REF
TYP.
AFG
AFF
FB, TB
FA, TA
/FT
FF
FROM BELOW, TO BELOW
ABOVE FINISHED FLOOR
FROM ABOVE, TO ABOVE
ABOVE FINISHED GRADE
TYPICAL
(E), EXISTING
(N)
AE
N.T.S.
O.B.D.
FC
CLG.
CFM,
CD
AP
SMOKE DETECTOR
NEW
FLEXIBLE CONNECTION
AIR EXTRACTOR
CONDENSATE DRAIN
ACCESS PANEL
CEILING
ACOUSTICALLY LINED DUCT
POINT OF CONNECTION
DUCT TRANSITION
DUCT DROP
OUTSIDE AIR
DUCT RISE
DIAMETER OR PHASE
SUPPLY AIR
RETURN AIR
POC
12x10L
12x10
RA
SA
OA
R
D
UCD UNDER CUT DOOR
R
EXHAUST AIR GRILLE/REGISTER
MOTORIZED DAMPER
SD
FINISHED FLOOR
PER FOOT
NOT TO SCALE
OPPOSED BLADE DAMPER
REFRIGERANT
DUCT - DIMENSION SHOWN X WIDTH OR
HEIGHT NOT SHOWN
BD BYPASS DAMPER
BRD BAROMETRIC RELIEF DAMPER
Ø
OR
OR12x10L 12Ø
DL DOOR LOUVER
OH OVERHEAD
HEATING, VENTILATING AND AIR CONDITIONING
CUBIC FEET OF AIRFLOW PER MINUTE
AC AIR CONDITIONER
1. WHETHER OR NOT SHOWN ON THE DRAWINGS, PROVIDE UL LISTED PENETRATION ASSEMBLIES FOR ALL PENETRATIONS THRU FIRE RATED AND SMOKE ASSEMBLIES. ALL FIRESTOPPING SYSTEMS PROPOSED FOR THE PROJECT
SHALL BE SUBMITTED FOR REVIEW BY THE STATE FIRE MARSHAL AND THE STATE REPRESENTATIVE PRIOR TO INSTALLATION.
2. ALL FIRESTOPPING WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE 2022 CALIFORNIA BUILDING CODE (CBC) SECTION 714.
2.1. FOR PENETRATIONS THRU FIRE RATED WALLS, COMPLY WITH PARAGRAPH 714.4 INCLUDING APPLICABLE SUB-PARAGRAPHS. THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED WALL SHALL COMPLY WITH PARAGRAPHS
714.4.1 INCLUDING APPLICABLE SUB-PARAGRAPHS. PENETRATIONS SHALL BE PROTECTED BY APPROVED FIRESTOP SYSTEMS PER THE PARAGRAPH 714.4.1.2.
2.2. FOR MEMBRANE PENETRATIONS (OPENINGS) IN A FIRE RATED WALL, COMPLY WITH THE PARAGRAPH 714.4.2 AND ALL APPLICABLE SUB-PARAGRAPHS.
2.3. FOR THROUGH PENETRATIONS AND MEMBRANE PENETRATIONS THRU RATED HORIZONTAL ASSEMBLIES (FLOOR, FLOOR/CEILING, ROOF/CEILING, ETC.), COMPLY WITH PARAGRAPH 714.4 INCLUDING APPLICABLE
SUB-PARAGRAPHS. PENETRATION OF HORIZONTAL FIRE BARRIERS SHALL BE DEMONSTRATED TO HAVE THE EQUIVALENT T AND F FIRE RATINGS AS THE HORIZONTAL ASSEMBLIES.
3. DUCTS AND AIR TRANSFER OPENINGS SHALL COMPLY WITH THE REQUIREMENTS OF CBC SECTION 717.
4. ALSO REFER TO FIRESTOPPING THRU PENETRATION DETAILS AND NOTES ON SHEET M511 FOR ADDITIONAL REQUIREMENTS.
ALL MECHANICAL PLUMBING AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. THE FOLLOWING COMPONENT SHALL BE ANCHORED OR
BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2022 CBC, SECTIONS 1617.11.15 THROUGH 1617.11.18 AND ASCE 7 CHAPTER 13.
1. ALL PERMANENT EQUIPMENT AND COMPONENTS.
2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH ELECTRICITY, GAS OR WATER. "PERMANENTLY ATTACHED" SHALL INCLUDE ALL ELECTRICAL CONNECTIONS EXCEPT PLUGS FOR 110/120 VOLT RECEPTACLES HAVING A FLEXIBLE CABLE.
3. TEMPORARY, MOVEABLE OR MOBILE EQUIPMENT WHICH IS HEAVIER THAN 400 POUNDS OR HAS A CENTER OF MASS LOCATED 4 FEET OR MORE ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORTS THE
COMPONENT IS REQUIRED TO BE RESTRAINED IN A MANNER APPROVED BY DSA.
THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT DEMONSTRATE DESIGN COMPLIANCE WITH THE REFERENCED NOTED ABOVE. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING AND CONDUIT, FLEXIBLE CONNECTIONS MUST ALLOW MOVEMENT IN BOTH TRANSVERSE AND
LONGITUDINAL DIRECTIONS:
A. COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT.
B. COMPONENTS WEIGHING LESS THAT 20 POUNDS, OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR HUNG FROM A WALL.
THE ANCHORAGE OF ALL MECHANICAL, ELECTRICAL AND PLUMBING COMPONENTS SHALL BE SUBJECT TO THE APPROVAL OF THE DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE OR STRUCTURAL ENGINEER DELEGATED RESPONSIBILITY AND ACCEPTANCE BY DSA. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENTS HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS.
PIPING, DUCTWORK AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-16 SECTION 13.3 AS DEFINED IN ASCE 7-16 SECTION 13.6.5, 13.6.6, 13.6.7,
13.6.8 AND 2022 CBC, SECTIONS 1617.11.19 AND ASCE 7 CHAPTER 13.
THE METHOD OF SHOWING BRACING AND ATTACHMENTS TO THE STRUCTURE FOR THE IDENTIFIED DISTRIBUTION SYSTEMS ARE AS NOTED BELOW. WHEN BRACING AND ATTACHMENTS ARE BASED ON PREAPPROVED INSTALLATION
GUIDE (E.G. OSHPD OPM FOR 2022 CBC OR LATER), COPIES OF THE BRACING SYSTEM INSTALLATION GUIDE OR MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF AND DURING THE HANGING AND BRACING OF THE
DISTRIBUTION SYSTEMS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.
MECHANICAL PIPING…
This is the start of the file's text. The full file is on GovTribe.