Original_AAB_Plans_Pages_49-60.pdf
PDF 9 MB Posted
- Solicitation number
- 9TSC0108
- Issued by
- Fresno County, Inyo County, Kings County, Madera County, Merced County, Mono County, San Bernardino County, Tulare County, Fremont City, Fresno City, Kingsburg City, Inyokern CDP, Madera City, Madera Acres CDP, Madera Ranchos CDP, Corte Madera Town, Merced City, University of California-Merced CDP, Mono City CDP, Kings Beach CDP, San Bernardino City, East Tulare Villa CDP, Tulare City, Mono Vista CDP, California
About this file
This is a mechanical and plumbing design document for a C-130 Barracks construction project at Fresno Air Attack Base in Fresno, California, prepared by the California Department of General Services, Division of the State Architect (DSA). The project specifications detail comprehensive HVAC, mechanical, and plumbing systems for a new barracks facility. The mechanical systems include variable-refrigerant-flow (VRF) HVAC equipment with multiple indoor units (Daikin FXAQ and FXTQ series), two outdoor units (Daikin REYQ series), energy recovery ventilators, heat wheels, and gravity ventilators specified by Greenheck. The plumbing systems encompass domestic water piping, sanitary waste and vent piping, commercial fixtures including water closets, lavatories, showers, and kitchen sinks, along with two heat pump water heaters (HPWH-1 and HPWH-2) and associated hot water recirculation systems. The facility includes six bedrooms, multiple bathrooms, kitchen, dining facilities, laundry, library, day room, and support spaces requiring climate control and domestic water systems across two HVAC zones.
The design specifications establish detailed performance requirements including cooling capacity ratings of 7,500 to 54,000 BTU/h for indoor units, heating capacity ratings of 8,500 to 60,000 BTU/h, and R-410A refrigerant systems operating at 208-230V single phase or 460V three-phase power. Domestic water calculations indicate a minimum 3-inch water supply pipe and 4-inch waste pipe with 32 GPM equivalent cold water flow rate demand across 59 total fixture units. The document mandates compliance with California Mechanical Code, California Plumbing Code, California Building Code, 2022 California Fire Code, and California Title 24 Energy Efficiency Standards. All piping penetrations through fire-rated assemblies require approved firestopping systems per UL standards with submission and approval by the State Fire Marshal prior to installation. Equipment seismic bracing, pipe support details, and detailed installation specifications are provided throughout the design documents, with the project receiving DSA approval dated April 15, 2024.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M602
MECHANICAL SCHEDULES
R. GALLAGHER
R. GALLAGHER
M. MADISON
C U s e rs
\M m a d is o n \A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
M
.d w g
J u n
:4 P M
V2
HVAC GRAVITY VENTILATORS (SPECIFICATION SECTION 233723)
MARK NO. AREA SERVED NAMED PRODUCT (NOTE 1) FUNCTION AIRFLOW - CFM MINIMUM THROAT DIAMETER, INCHES MINIMUM THROAT AREA, SF WEIGHT, POUNDS ACCESSORIES
ENERGY RECOVERY VENTILATOR
(ERV-1)
GREENHECK, MODEL GRSI-12 EXHAUST 400 AT MAXIMUM 0.04 IN WC TOTAL PRESSURE DROP 12 0.82 SF WITH 500 MAX THROAT VELOCITY 10 DUCTED CONNECTION, INTEGRAL BIRDSCREEN
BARRACKS KITCHEN MAKE-UP
AIR
GREENHECK, MODEL GRSI-15 INTAKE 550 AT MAXIMUM 0.04 IN WC TOTAL PRESSURE DROP 15 1.12 SF WITH 500 MAX THROAT VELOCITY 13 DUCTED CONNECTION, INTEGRAL BIRDSCREEN
BARRACKS KITCHEN- RANGE
HOOD
GREENHECK, MODEL GRSR-15 EXHAUST 660 AT MAXIMUM 0.08 IN WC TOTAL PRESSURE DROP 15 1.12 SF WITH 500 MAX THROAT VELOCITY 13 DUCTED CONNECTION, INTEGRAL BIRDSCREEN
ERV-1 GREENHECK, MODEL FDS-602 INTAKE 6000 AT MAXIMUM 0.08 IN WC TOTAL PRESSURE DROP 12 X 16 8.15 SF WITH 750 MAX THROAT VELOCITY 24 DUCTED CONNECTION, INTEGRAL BIRDSCREEN
NOTES:
1. PROVIDE NAMED PRODUCT OR A COMPARABLE OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.
GRVR
GRVI
GRVR
LV
HEAT WHEEL AIR-TO-AIR ENERGY RECOVERY UNIT (SPECIFICATION SECTION 237213)
MARK NO.
NAMED PRODUCT (NOTE 1) DAIKIN, MODEL VAM300-GVJU WITH DOUBLE-WALLED CABINET AND NON-HINGED DOORS
TYPE- FIXED-PLATE, SENSIBLE OR TOTAL WHEEL
EXHAUST AIR
AIRFLOW - CFM 300
EXHAUST EXTERNAL STATIC PRESSURE (IN. WG.) 0.64
AIR PRESSURE DROP - INCHES WG 0.45 MAXIMUM
FAN MOTOR HORSEPOWER (0.09 KW *2), 0.12 * 2 BRAKE HP
SUPPLY AIR
AIRFLOW - CFM 300
EXHAUST EXTERNAL STATIC PRESSURE (IN. WG.) 0.64
AIR PRESSURE DROP - INCHES WG 0.45 MAXIMUM
FAN MOTOR HORSEPOWER (0.09 KW *2), 0.12 * 2 BRAKE HP
COMBINED ELECTRICAL CHARACTERISTICS VOLTS / PHASE / HERTZ / UNIT MCA 208-230 / 60 / 1 / 1.6
ASHRAE 90.1 ENTHALPY RECOVERY RATIO: SUMMER / WINTER 40/ 57
FILTERS TYPE, DIRTY FILTER SENSORS 2" PLEATED MERV 13 FILTERS AND DIRTY FILTER SENSORS FOR EACH OUTDOOR AIR AND SUPPLY AIR
CONTROLS POTENTIOMETER SPEED CONTROLLER, ON/OFF WITH OCCUPANCY SENSORS, REMOTE CONTROL PANEL WITH DIRTY FILTER LIGHT, HAND/OFF/AUTO SWITCH, ON/OFF LIGHT
ACCESSORIES BYPASS DAMPERS FOR ECONOMIZER OPERATION MODE, METAL BACKDRAFT DAMPERS, SMOKE DETECTORS, UNIT DISCONNECT, 2 YEAR WARRANTY
WEIGHT - POUNDS 71
SPARE PARTS ENERGY WHEEL BELT, SPARE BELTS, SPARE ENERGY WHEEL SEGMENTS, SPARE FILTER SET: 3 SUPPLY, 3 EXHAUST.
NOTES:
1. PROVIDE NAMED PRODUCT OR A COMPARABLE OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.
2. ERV OPERATES ONLY WHEN INDOOR UNITS 3 & 4 ARE ON. WHEN IDUS ARE BEING USED . THE ERV CAN BE OPERATED IN CIRCULATION OR VENTILATION MODE.
ERV
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea l Estate Surveying
Architecture&Enginee ring
Co ns tr uc ti on
M an ag em en t
To we rs V au lts
1131 S STREET, SACRAMENTO, CA 95811-2460
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
NOT TO SCALE
MECHANICAL SCHEDULES
FIRE DAMPER (SPECIFICATION SECTION 233300)
MARK NO. AREA SERVED NAMED PRODUCT (NOTE 1) FUNCTION RATINGS SIZE CONSTRUCTION
SLEEPING AREA - BEDROOMS GREENHECK, MODEL DFD-150
DYNAMIC FIRE DAMPER WITH
CURTAIN STYLE BLADES
U.L. 555 1,5 HOURS, 4000 FPM MAXIMUM VELOCITY ( VERTICAL MOUNT),
MAX. PRESSURE OF 4.0 in. WG, 165 f FUSIBLE LINK. {CALIFORNIA STATE FIRE
MARSHALL (LISTING # 3225-0981:0102)}
MATCH DUCT PER DUCTING PLAN SHEET. 1. VERTICAL MOUNT, DUCTED FACTORY SLEEVE CONNECTION. 2. GALVANIZED FRAME/BLADE FINISH. 3. FACTORY SUPPLIED RETAINING ANGLES. 4. 165F FUSIBLE LINK CLOSURE DEVICE.
NOTES:
1. PROVIDE NAMED PRODUCT OR A COMPARABLE OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.
FD
MISCELLANEOUS EQUIPMENT SCHEDULE (SPECIFICATION SECTION 230923)
MARK NO. NAME DESCRIPTION NAMED PRODUCT (NOTE 1) (MANUFACTURER AND MODEL NO.)
MD-1 MOTORIZED CONTROL DAMPER
MINIMUM 16 GA CHANNEL TYPE FRAME WITH REINFORCED CORNERS, MINIMUM 16 GA BLADES, ALL GALVANIZED STEEL CONSTRUCTION. TWO-POSITION BLADE ACTION. LOW LEAKAGE TYPE WITH BLADE AND JAMP SEALS. BLADE LINKAGE CONCEALED OUT OF AIR STREAM. PROVIDE 120V
EXTERNAL ACTUATOR, TWO-POSITION SPRING RETURN FAIL CLOSED POSITION WITH NEMA 1 ENCLOSURE WITH AUXILIARY SWITCH.
"GREENHECK" VCD-18 WITH "BELIMO" FSLF-120US ACTUATOR, OR APPROVED EQUAL
NOTES:
1. PROVIDE A NAMED PRODUCT OR A COMPARABLE PRODUCT OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
M603
MECHANICAL SCHEDULES
R. GALLAGHER
R. GALLAGHER
M. MADISON
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \M
E C
H A N
IC
A L \2
M
.d l
:4
VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS (SPECIFICATION SECTION 238129)
MARK NO.
INDOOR UNIT, MARK "IDU"
NAMED PRODUCT (NOTE 1) (MANUFACTURER AND MODEL NO.) DAIKIN FXAQ07PVJU DAIKIN FXAQ12PVJU DAIKIN FXTQ30TAVJUD DAIKIN FXTQ54TAVJUD
TYPE HIGH WALL HIGH WALL
CONCEALED FLOOR-MOUNTED DUCTED
(MULTI-POSITION)
CONCEALED FLOOR-MOUNT DUCTED
(MULTI-POSITION)
REFRIGERANT TYPE R-410A R-410A R-410A R-410A
COOLING CAPACITY
RATED - BTU/H (NOTE 2) 7,500 12,000 30,000 54,000
SENSIBLE COOLING CAPACITY - BTU/H (NOTE 2) 6,400 8,900 21,400 39,300
ENTERING - AIR
TEMPERATURE
DRY BULB - DEG F 79 79 79 79
WET BULB - DEG F 64 64 64 64
LEAVING - AIR
TEMPERATURE
DRY BULB - DEG F 54 54 54 54
WET BULB - DEG F 51 51 51 51
HEATING CAPACITY RATED - BTU/H (NOTE 3) 8,500 13,500 34,000 60,000
ELECTRICAL
VOLTS / PHASE / HERTZ 208-230 / 1 / 60 208-230 / 1 / 60 208-230 / 1 / 60 208-230 / 1 / 60
FAN MOTOR FLA 0.03 0.03 3.9 6.9
MCA 0.4 0.4 4.9 8.6
MOP 15 15 15 15
AIRFLOW
HIGH - CFM (WITH WET COILS DURING COOLING) 260 260 1000 1,800
LOW - CFM (WITH WET COILS WHILE COOLING) 160 180 700 1,260
EXTERNAL STATIC PRESSURE (HIGH / LOW) - INCHES OF
WATER COLUMN
- - 0.1/0.9 0.1/0.9
AIR-FILTER TYPE - (DISPOSABLE, WASHABLE, CHARGED
MEDIA, OR HEPA)
WASHABLE WASHABLE NOTE 7 NOTE 7
ACCESSORIES (NOTE 1) - - NOTE 10 &11 NOTE 10 & 11
MAXIMUM SOUND PRESSURE LEVEL -DBA 36 38 52 50
WEIGHT - LBS. 26 26 115 167
AIR-COOLED OUTDOOR
UNIT
NAMED PRODUCT (NOTE 1) (MANUFACTURER AND MODEL NO.) (ODU-1) DAIKIN REYQ96XAYDA (AHRI CERTIFICATIED REFERENCE NUMBER: 203334947) (ODU-2) DAIKIN REYQ72XAYDA (AHRI CERTIFICATIED REFERENCE NUMBER: 203334947)
TOTAL BTU/H (HEATING / COOLING)(NOTES 3 AND 2) 108,000 / 96,000 81,000 / 72,000
HEAT PUMP EFFICIENCY
EER (NOTE 2) 9.0 MINIMUM 9.0 MINIMUM
COEFFICIENT OF PERFORMANCE (NOTE 4) 2.0 MINIMUM 2.0 MINIMUM
ELECTRICAL
CHARACTERISTICS
VOLTS / PHASE / HERTZ 460 / 3 / 60 460 / 3 / 60
FAN MOTOR FLA 1.0*2 1.0*2
COMPRESSOR
FLA 10.5 9.4
MCA 21.1 18.9
MOP 25 25
MAXIMUM SOUND PRESSURE LEVEL - DBA 80 79
OPERATING WEIGHT - LBS. 727 727
ACCESSORIES NOTE 8 NOTE 8
THERMOSTAT NAMED PRODUCT (NOTE 1) (MANUFACTURER AND MODEL NO.) NOTE 6 NOTE 6 NOTE 6 NOTE 6 NOTE 6 NOTE 6
NOTES:
1. PROVIDE NAMED PRODUCT OR A COMPARABLE OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.
2. AHRI COOLING RATING CONDITIONS ARE 95 DEG F DRY-BULB OUTDOORS AND 80 DEG F DRY BULB, 67 DEG F WET-BULB INDOORS.
3. AHRI HEATING RATING CONDITIONS ARE 17 DEG F DRY-BULB OUTDOORS AND 70 DEG F DRY BULB, 60 DEG F WET-BULB INDOORS.
4. AHRI (AIR-CONDITIONING, HEATING & REFRIGERATION INSTITUTE) EFFICIENCY RATINGS AT 17 DEG. F
5. DECORATIVE PANEL COLOR: WHITE
6. WIRED REMOTE CONTROLLER: OCCUPANT CONTROLLED SMART THERMOSTAT (OCST) CERTIFIED WITH CALIFORNIA ENERGY COMMISSION. INSTALLED IN WALL PER PLANS.
7. DISPOSABLE, 2-INCH THICK, PLEATED, MERV-13 IN AIR-SEALED 4" FILTER FRAME WITH PRE-FILTERS. SIZED AS SHOWN ON PLANS. (SPECIFICATION SECTION 234100)
8. HVAC PIPE PENETRATION WALL SEAL (AIREX TITAN OUTLET)
9. THERMOSTAT CONTROLLER TO RUN SIMULTANEOUS WITH WEF-1 TO MAINTAIN NEGATIVE PRESSURE IN APPARATUS BAY. INTERLOCK TO SHUT-OFF WHENEVER APPARATUS BAY DOORS OPEN.
10. MULTI-POSITION AHU: NOT TO EXCEED 22".
11. DISCONNECT: EACH IDU SHALL HAVE A 15A, NON-FUSED DISCONNECT WHICH IS LOCKABLE, PER ARTICLE 110.25 OF CEC "LATEST EDITION". INSTALL DISCONNECT ADJACENT TO AND WITHIN SIGHT OF IDU.
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs V
IDU
IDU
IDU
IDU
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
HEAT RECOVERY CONTROL UNIT (BRANCH SELECTOR BOX) SCHEDULE, SPECIFICATION 238129
TAG DESCRIPTION # PORTS INDOOR UNIT CONNECTIONS OUTDOOR UNIT CONNECTIONS CAPACITY, MBH POWER VOLTAGE/PH MCA MOP
WEIGHT,
LBS
BASIS OF DESIGN NOTES, COMMENTS
LIQ: Ø, " GAS: Ø , " LIQ: Ø, " GAS: Ø, " HP/LP GAS: Ø " MBH WATTS VAC/PH AMPS AMPS LBS MANUFACTURER MODEL
MULTI-PORT BRANCH SELECTOR BOX FOR REFRIGERANT MIXING,
INDIVIDUAL INDOOR UNIT CONTROL AND INCREASED EFFICIENCY
10 1/4 & 3/8 1/2 & 5/8 1/2 1-1/8 3/4 96 86 208-230/1/60 1.00 15 101 DAIKIN BS10Q54TVJ
MULTI-PORT BRANCH SELECTOR BOX FOR REFRIGERANT MIXING
FOR INDIVIDUAL INDOOR UNIT CONTROL AND INCREASED
EFFICIENCY.
4 1/4 & 3/8 1/2 & 5/8 3/8 7/8 3/4 86 43 208-230/1/60 0.40 15 49 DAIKIN BS4Q54TVJ
HRCU
HRCU
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
M611
MECHANICAL CONTROLS
R. GALLAGHER
R. GALLAGHER
M. MADISON
C U s e rs
\M m a d is o n \A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
M
.d l
:0
HVAC SYSTEMS SET-POINTS
EQUIPMENT ZONE SETPOINT VALUE PARAMETER
THERMOSTATS 1 - 2 INSIDE AIR TEMPS. COOLING / HEATING 72 DEGREES F / 66 DEGREES F OCCUPIED 24 HOURS PER DAY, 7 DAYS PER WEEK.
THERMOSTAT 1 - 2
OUTSIDE AIR TEMPS: COOLING / FAN ONLY / HEATING 81-110+ DEGREES F / 60 - 80 DEGREES / 30-59 DEGREES F
OCCUPIED 24 HOURS PER DAY, 7 DAYS PER WEEK.
FREEZESTAT ODU-1 AND ODU-2 SET TO DEFROST AS INFREQUENTLY AS EQUIPMENT ALLOWS - -
ENERGY RECOVERY VENTILATOR (ERV) WITH BYPASS DAMPER
COOLING MODE - INDOOR TEMP. IS GREATER THAN OUTDOOR TEMP BYPASS
OCCUPIED 24 HOURS PER DAY, 7 DAYS PER WEEK.
COOLING MODE - OUTDOOR TEMP. IS GREATER THAN INDOOR TEMP. ERV
HEATING MODE - INDOOR TEMP. IS GREATER THAN OUTDOOR TEMP. ERV
HEATING MODE - OUTDOOR TEMP. IS GREATER THAN INDOOR TEMP. BYPASS
SEQUENCE OF OPERATIONS
EQUIPMENT ZONE OPERATION
ENERGY RECOVERY VENTILATOR (ERV-1) 1 - 2 ERV-1 IS CONTROLLED TWO IDU-3 &4. SENSORS: RUN FOR 8 HOURS AFTER OCCUPANCY IS DETECTED IN ANY OF THESE ZONES.
SMOKE DETECTOR 1 - 2 SYSTEM SHUT DOWN
IDU #'s 1 - 3 1 - 2 CONTROLLED BY INDIVIDUAL ROOM THERMOSTATS. RUN FOR 8-12 HOURS AFTER OCCUPANCY IS DETECTED IN ANY OF THESE ZONES.
IDU-1, IDU-4 1 - 2 CONTROLLED BY INDIVIDUAL ROOM THERMOSTATS.
HVAC ZONES
ZONE
1 2
LOCATION BEDROOM 1, BEDROOM 2, BEDROOM 3, BEDROOM 4, BEDROOM 5, BEDROOM 6, HALL 2, HALL 3, TELECOM/ELECT, STOR1, PHSC. TRNG., RESTROOMS 1-3, AND LAUNDRY. DINING ROOM, DAY ROOM, KITCHEN, PANTRY, ENTRY, LIBRARY AND HALL 1
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs V
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
NOT TO SCALE
MECHANICAL CONTROLS
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
OUTDOOR UNIT #1
ODU
1 HRCU
IDU
IDU
ZONE #1
IDU
FIRST FLOOR
EF
ERV
VF
OSA
EA
LAUNDRY
BDRM 1
OUTDOOR UNIT #2
ODU
2 HRCU
IDU
IDU
ZONE #2
IDU
IDU
IDU
IDU
IDU
IDU
IDU
IDU
IDU
IDU
BDRM 2 BDRM 3 BDRM 4 BDRM 5 BDRM 6 STORAGE 1 PT ROOM BATHRM 1 BATHRM 2 BATHRM 3 LAUNDRY HALL 1LIBRARY DAY RM DINING RM KITCHEN DINING (CD)HALL 2 HALL 3
BATHRM 1 BATHRM 2 BATHRM 3 KITCHEN
BEDROOM 1 BEDROOM 2 BEDROOM 3 BEDROOM 4 BEDROOM 5 BEDROOM 6
ELEC/TELECOM PHYSICAL TRAINING CENTRAL HVAC - ZONE 1
LIBRARY DAY ROOM DINING ROOM CENTRAL HVAC - ZONE 2
GENERAL SHEET NOTES
M612
MECHANICAL SCHEMATIC -
HVAC SYSTEM
R. GALLAGHER
R. GALLAGHER
M. MADISON
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \M
E C
H A N
IC
A L \2
M
.d l
:4
SCALE: NOT TO SCALE
VENTILATION SCHEMATIC
SCALE: NOT TO SCALE
REFRIGERANT SCHEMATIC - ZONE 2
SCALE: NOT TO SCALE
REFRIGERANT SCHEMATIC - ZONE 1
1. PIPING SCHEMATICS SHOWN AS REFERENCE ONLY, NOT TO SCALE.
2. BRANCH SELECTOR BOXES SHALL BE INSTALLED LEVEL, PLUMB AND TRUE.
3. REFRIGERANT PIPING CALCULATION FACTORS
3.1. MAXIMUM TOTAL LENGTH.
3.2. MAXIMUM LONGEST ACTUAL LENGTH
3.3. MAXIMUM LONGEST EQUIVALENT LENGTH
3.4. MAXIMUM MAIN PIPE LENGTH (SIZE UP OF MAIN PIPE REQUIRED IF LONGER)
3.5. MAXIMUM LENGTH FIRST BRANCH TO INDOOR UNIT(SIZE UP OF INTERMEDIATE PIPES REQUIRED IF
LONGER)
3.6. MAXIMUM LENGTH FIRST BRANCH TO INDOOR UNIT
3.7. MAXIMUM LENGTH OF INDOOR UNITS TO NEAREST BRANCH
3.8. MAXIMUM LENGTH DIFFERENCE BETWEEN LONGEST AND SHORTEST DISTANCE TO INDOOR UNITS
3.9. MAXIMUM HEIGHT DIFFERENCE, OUTDOOR UNIT BELOW INDOOR UNITS
3.10. MINIMUM CONNECTION RATIO, OUTDOOR UNIT BELOW INDOOR UNITS
3.11. MAXIMUM HEIGHT DIFFERENCE, OUTDOOR UNIT ABOVE INDOOR UNITS
3.12. MINIMUM CONNECTION RATIO, OUTDOOR UNIT ABOVE INDOOR UNITS
3.13. MAXIMUM HEIGHT DIFFERENCE IN TECHNICAL COOLING, OUTDOOR UNIT BELOW INDOOR UNITS
3.14. MAXIMUM HEIGHT DIFFERENCE IN TECHNICAL COOLING, OUTDOOR UNIT ABOVE INDOOR UNITS
3.15. MAXIMUM HEIGHT DIFFERENCE BETWEEN INDOOR UNITS
3.16. CONNECTION RATIO RANGE
3.17. REFRIGERANT PIPE DIAMETERS
3.18. MAXIMUM EQUIVALENT LENGTH FROM BP UNIT OR VRV INDOOR TO VRV REFNET (SIZE UP OF
INTERMEDIATE PIPES REQUIRED IF LONGER)
3.19. MAXIMUM EQUIVALENT LENGTH FROM BP UNIT OR VRV INDOOR TO VRV REFNET
3.20. MAXIMUM ACTUAL LENGTH BETWEEN CM AND HM
3.21. MAXIMUM HEIGHT DIFFERENCE BETWEEN CM AND HM .
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECHNICAL SERVICES
Capital Outlay
Rea
Architecture&Engineering tr uc ti on M an ag em en t
To we rs
V
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
M901
MECHANICAL ISOMETRIC VIEW
- DUCTING
R. GALLAGHER
R. GALLAGHER
M. MADISON
C U s e rs
\M m a d is o n \A p p D a ta
\L o c a l\ T e m p \A c P u b lis h \2
M
M
M
.d n
:3
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P L O T D
A T E
P R O J E C T P
A T H
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs V
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
SCALE: 1/4" = 1'0"
MECHANICAL SCHEMATIC - DUCTING (NORTHEAST ISOMETRIC VIEW)
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
GENERAL PLUMBING NOTES
1. ALL PRODUCTS USED SHALL BE NEW AND SHALL BE EQUAL IN QUALITY, TYPE, CAPACITY AND ACCESSORIES TO THE PRODUCTS NOTED ON THE DRAWINGS AND/OR SPECIFICATIONS. ADJUSTMENTS TO CONSTRUCTION AND
ACCESSORIES ON SUBSTITUTED EQUIPMENT MAY BE REQUIRED TO ACHIEVE THIS EQUALITY, AND SHALL BE INCLUDED AS PART OF THE ORIGINAL WORK. MAKE ANY CHANGES IN PIPING, FRAMING, ETC., AS REQUIRED TO
ACCOMMODATE SUBSTITUTED EQUIPMENT.
2. INSTALL ALL EQUIPMENT AND MATERIALS AND PERFORM ALL WORK IN ACCORDANCE WITH ALL APPLICABLE CODES. APPLICABLE CODES SHALL INCLUDE, BUT NOT BE LIMITED TO THE CURRENT EDITIONS OF THE CALIFORNIA
MECHANICAL CODE, CALIFORNIA PLUMBING CODE AND CALIFORNIA BUILDING CODE; THE CALIFORNIA CODE OF REGULATIONS (CCR); CALIFORNIA FIRE REGULATIONS; AND CALIFORNIA TITLE 24 ENERGY EFFICIENCY STANDARDS.
WHERE HEAVIER GAGES OF MATERIAL, LARGER SIZES OR MORE STRINGENT REQUIREMENTS THAN THE CODES ARE REQUIRED BY THE CONTRACT DOCUMENTS, SUCH INCREASED REQUIREMENTS SHALL APPLY.
3. ALL WORK SHALL ALSO BE IN COMPLIANCE WITH THE REQUIREMENTS OF APPLICABLE STATE AND LOCAL OFFICIALS, PUBLIC WORKS DEPARTMENT, FIRE MARSHAL AND/OR OTHER AUTHORITIES HAVING JURISDICTION.
4. CONTRACTOR SHALL VERIFY ALL WORK CONDITIONS, PRIOR TO COMMENCING WORK, INCLUDING, BUT NOT LIMITED TO: PIPING SIZES, INVERT ELEVATIONS, POINTS OF CONNECTION, FIXTURES AND EQUIPMENT, STRUCTURAL
ELEMENTS AND MATERIALS INDICATED AS EXISTING, AS WELL AS THE COORDINATED INSTALLATION OF ALL NEW WORK, MATERIALS, EQUIPMENT, ETC. VERIFY THE LOCATION AND REQUIRED PIPING CONNECTIONS OF ALL HVAC OR
OTHER MECHANICAL EQUIPMENT. NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO TRENCHING OR COMMENCING OTHER WORK.
5. ADA PLUMBING FIXTURES SHALL BE ADA COMPLIANT AND BE INSTALLED TO MEET THE ADA REQUIREMENTS.
6. AFTER INSTALLATION, CLEAN ALL FIXTURES, PIPING, EQUIPMENT, ETC. OF CONSTRUCTION DEBRIS. POLISH ALL CHROME AND STAINLESS STEEL..
DRAWINGS AND SPECIFICATIONS
7. IT IS THE INTENT OF THE PROJECT DRAWINGS AND SPECIFICATIONS TO COMPLEMENT EACH OTHER. SHOULD THERE BE ANY DISCREPANCY BETWEEN THE REQUIREMENTS LISTED OR DESCRIBED BETWEEN THE DRAWINGS AND
SPECIFICATIONS, THE MORE STRINGENT REQUIREMENT SHALL GOVERN.
8. THE STATE REPRESENTATIVE'S INTERPRETATION OF THESE DOCUMENTS, INCLUDING THE DESIGN INTENT OF THESE DOCUMENTS, SHALL BE FINAL.
9. IN CASE OF POSSIBLE OMISSIONS OR CONFLICTS BETWEEN VARIOUS ELEMENTS OF THE DRAWINGS, NOTES, DETAILS AND/OR SPECIFICATIONS, SUCH ISSUES SHALL BE BROUGHT TO THE ATTENTION OF THE STATE REPRESENTATIVE
FOR RESOLUTION BEFORE PROCEEDING THE WORK.
10. THE DRAWINGS AND SPECIFICATIONS ALSO INTEND TO REPRESENT FINISHED CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MEANS AND METHODS OF CONSTRUCTION INCLUDING BUT NOT LIMITED TO SHORING
AND TEMPORARY BRACING.
11. NO DEVIATION FROM THE APPROVED DRAWINGS AND SPECIFICATIONS IS PERMITTED WITHOUT THE PRIOR WRITTEN CONSENT OF THE ENGINEER. THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ANY FIELD CHANGES MADE
WITHOUT THE AUTHORIZATION FROM ENGINEER.
MISCELLANEOUS
12. COORDINATE ALL WORK AMONG VARIOUS TRADES AS NECESSARY OR REQUIRED TO ENSURE THE INSTALLATION OF ALL WORK IN THE AVAILABLE SPACE. FIELD COORDINATE ALL PIPE ROUTING AND INVERTS WITH SITE CONDITIONS, STRUCTURAL MEMBERS, DUCTWORK, OTHER PIPING, SUPPORTS, LIGHT FIXTURES, OTHER AFFECTED TRADES, ETC., AND ADJUST ROUTING AS REQUIRED, TYPICAL. AS NECESSARY, MODIFY, EXTEND OR ADJUST THE WORK AS NEEDED
TO ENSURE THAT ALL REQUIRED INSTALLATIONS AND CONNECTIONS ARE PROPERLY COMPLETED.
13. WHERE REQUIRED OR NECESSARY, OFFSET THE ROUTING OF THE PIPING, AND PIPING SERVICES TO FIXTURES AND EQUIPMENT SO AS TO AVOID CONFLICTS WITH WINDOWS, OTHER BUILDING COMPONENTS AND OTHER SIMILAR
OBSTRUCTIONS.
14. ROUTE ALL CONNECTING DUCTWORK AND PIPING TO FIXTURES AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS, RECOMMENDATIONS AND REQUIREMENTS, AND APPLICABLE REGULATIONS AND STANDARDS.
FIELD COORDINATE ALL ROUTING AND SIZES WITH ACTUAL SITE CONDITIONS, STRUCTURAL MEMBERS, OTHER DUCTWORK AND PIPING, SUPPORTS, LIGHT FIXTURES, AND ALL OTHER AFFECTED TRADES. MODIFY/ADJUST/EXTEND
ROUTING AS REQUIRED TO AVOID ALL CONFLICTS.
15. WORK NOT DETAILED, MARKED, OR SPECIFIED SHALL BE THE SAME AS SIMILAR WORK THAT IS DETAILED, MARKED OR SPECIFIED
16. DO NOT SCALE PLANS - USE DIMENSIONS SHOWN OR ASK STATE REPRESENTATIVE FOR CLARIFICATION.
17. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE STATE REPRESENTATIVE IF ANY DISCREPANCIES OCCUR BEFORE BEGINNING WORK.
18. FIRE SAFETY DURING CONSTRUCTION, ALTERATION OR DEMOLITION SHALL BE IN ACCORDANCE WITH CHAPTER 33 OF THE CFC AS AMENDED.
19. FOR CONTINUATION OF ALL UTILITIES, REFER TO CIVIL DRAWINGS. COORDINATE INVERT ELEVATIONS WITH CIVIL TRADE.
20. ALL WASTE PIPING SHALL HAVE A MINIMUM SLOPE OF 1/4" PER FOOT. VENT PIPING SHALL BE ROUTED ABOVE CEILING OR INSIDE ATTIC SPACE, TIGHT TO UNDERSIDE OF ROOF STRUCTURE, UNLESS OTHERWISE NOTED.
21. ALL COLD WATER AND HOT WATER PIPING SHALL BE ROUTED ABOVE CEILING OR INSIDE ATTIC SPACE, TIGHT TO UNDERSIDE OF ROOF STRUCTURE, UNLESS OTHERWISE NOTED.
22. ALL GAS PIPING SHALL BE ROUTED ABOVE CEILING TIGHT OR INSIDE ATTIC SPACE, TO UNDERSIDE OF ROOF STRUCTURE, UNLESS OTHERWISE NOTED.
23. ALL COMPRESSED AIR PIPING SHALL BE ROUTED ABOVE CEILING OR INSIDE ATTIC SPACE, TIGHT TO UNDERSIDE OF ROOF STRUCTURE, UNLESS OTHERWISE NOTED.
24. LOCATE VALVES FOR SERVICE ACCESSIBILITY. VALVES INSTALLED ABOVE CEILING SHALL BE WITHIN 18" OF CEILING.
25. AS NOTED ON THE DRAWINGS, IN THE APPARATUS BAY SPACES WHERE THERE IS A STORAGE LOFT ABOVE, CERTAIN DOMESTIC WATER (CW AND HW), AND VENT PIPING ARE TO BE ROUTED INSIDE THE CEILING SPACES UNDER THE
STORAGE LOFT FLOOR, AND MAY NEED TO PENETRATE THROUGH THE FLOOR JOISTS. COORDINATE ALL ROUTING AND INSTALLATION WITH STRUCTURAL.
26. PLUMBING VENT PIPING PENETRATIONS THRU ROOF SHALL BE PROVIDED WITH APPROPRIATE PIPE BOOT AND/OR FLASHING COMPATIBLE WITH THE BUILDING ROOFING SYSTEM, AND BE SEALED WATERPROOF. FOR TYPICAL VENT
THRU ROOF DETAIL, REFER TO ARCHITECTURAL DRAWINGS. COORDINATE ALL WORK WITH ARCHITECTURAL AND ROOFING TRADES. FOR VENT-THRU-ROOF'S SIZE 3" AND LARGER, PROVIDE 1/2" GALVANIZED WIRE MESH PEST SCREEN
AT PIPE TERMINATION.
27. CONTRACTOR SHALL PROVIDE MINIMUM 7 WORKING DAYS NOTIFICATION OF UNDERGROUND SERVICE ALERT PRIOR TO ANY SITE EXCAVATION.
1. WHETHER OR NOT SHOWN ON THE DRAWINGS, PROVIDE APPROPRIATE FIRESTOPPING AT ALL PIPING PENETRATIONS THRU FIRE RATED WALL AND/OR FLOOR/CEILING/ROOF ASSEMBLIES. ALL FIRESTOPPING SYSTEMS PROPOSED FOR
THE PROJECT SHALL BE SUBMITTED FOR REVIEW BY THE STATE FIRE MARSHAL AND THE STATE REPRESENTATIVE PRIOR TO INSTALLATION.
2. ALL FIRESTOPPING WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE 2022 CALIFORNIA BUILDING CODE (CBC) SECTION 714.
2.1. FOR PENETRATIONS THRU FIRE RATED WALLS, COMPLY WITH PARAGRAPH 714.4 INCLUDING APPLICABLE SUB-PARAGRAPHS. THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED WALL SHALL COMPLY WITH PARAGRAPHS
714.4.1 INCLUDING APPLICABLE SUB-PARAGRAPHS. PENETRATIONS SHALL BE PROTECTED BY APPROVED FIRESTOP SYSTEMS PER THE PARAGRAPH 714.3.1.2.
2.2. FOR MEMBRANE PENETRATIONS (OPENINGS) IN A FIRE RATED WALL, COMPLY WITH THE PARAGRAPH 714.4.2 AND ALL APPLICABLE SUB-PARAGRAPHS.
2.3. FOR THROUGH PENETRATIONS AND MEMBRANE PENETRATIONS THRU RATED HORIZONTAL ASSEMBLIES (FLOOR, FLOOR/CEILING, ROOF/CEILING, ETC.), COMPLY WITH PARAGRAPH 714.5 INCLUDING APPLICABLE SUB-PARAGRAPHS.
3. ALSO REFER TO FIRESTOPPING THRU PENETRATION DETAILS AND NOTES ON SHEET P504 FOR ADDITIONAL REQUIREMENTS.
1. LOCATE ALL ROOF PENETRATIONS WITHIN 18" OF RIDGE VENT.
PIPING PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES
ROOF PENETRATIONS
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECHNICAL SERVICES
tr uc ti on M an ag em rs
V
R. GALLAGHER
R. GALLAGHER
M. MADISON
GENERAL PLUMBING NOTES
P001
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \P
L U M
B
IN
G \2
P .d n
:2
V2V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
PLUMBING LEGEND
CLEAN OUT TO GRADE / GRADE CLEAN OUT
VERTICAL VENT PIPING / VENT RISER
VENT THRU ROOF
VENT LINE PIPING
CLEAN OUT THRU WALL / WALL CLEAN OUT
HORIZONTAL VENT PIPING
DRAIN LINE
CLEAN OUT TO FLOOR / FLOOR CLEAN OUT
SANITARY WASTE PIPING
CURBED VALVE BOX
HOSE BIBB
WATER HAMMER ARRESTER
GAS REGULATOR
SEISMIC VALVE
GAS COCK VALVE
GAS PIPING
AIR (PNEUMATIC) PIPING
AIRHOSE COUPLER
HOT WATER RECIRCULATION PIPING
BALL VALVE
GATE VALVE
PIPING TO BE RELOCATED
HOT WATER PIPING
COLD WATER PIPING
PIPING TO BE DEMOLISHED
CONDENSATE DRAIN LINE
FLOOR SINK / FLOOR RECEPTOR
FLOOR DRAIN
DB DISTRIBUTION BOX
COTF / FCO
COTG / GCO
COTW / WCO CLEANOUT TO WALL / WALL CLEAN OUT
GI GREASE INTERCEPTOR
HV HORIZONTAL VENT
VD VERTICAL DRAIN
VTR VENT THRU ROOF
VR VENT RISER
FR FLOOR RECEPTOR
FD FLOOR DRAIN
FREZ FREEZER
GR GAS RANGE
GV GATE VALVE or GAS VALVE
HB HOSE BIBB
KS KITCHEN SINK
LAV LAVATORY SINK
LS / LT LAUNDRY SINK / LAUNDRY TRAY
MO MICROWAVE OVEN
PH POST HYDRANT
REF REFRIGERATOR
REG REGULATOR
WC WATER CLOSET
GD GARBAGE DISPOSAL
HW HOT WATER PIPING
SV SEISMIC VALVE
FAU FAUCET
VALVE BOXVB
ICE MAKER OUTLET BOXIMB / IMO
WOB WALL OUTLET BOX
CW COLD WATER PIPING
WHA WATER HAMMER ARRESTER
WH WATER HEATER
SH SHOWER SYSTEM / SHOWER VALVE
PTR PRESSURE-TEMPERATURE RELIEF
CHECK VALVE
POC POINT OF CONNECTION
CLEANOUT TO GROUND (or GRADE) /
CLEANOUT TO FLOOR / FLOOR CLEAN OUT
GROUND (or GRADE) CLEAN OUT
OH OVERHEAD
VTR
VR
HV
HB
WHA
A
G
CD
V
CVB
AIRC
A
FS / FR
FD
COTW / WCO
COTG / GCO
COTF / FCO
G
G
G
S SINK
EWS EYE/FACE WASH STATION
MS MOP SERVICE SINK
SD SHOWER DRAIN
FCV FLOW CONTROL VALVE
TBV TEMPERED BLENDING VALVE
TRAP PRIMERTP
ET EXPANSION TANK
HWRP HOT WATER RETURN PUMP / PIPING
SS SERVICE SINK
IRON PIPE SIZEIPS
CO CLEANOUT
EXISTING(E)
(N) NEW
(R) TO BE RELOCATED
AIR GAP / BACKFLOW PREVENTERAG / BFP
BS BAR SINK
BV BALL VALVE
CVB CURBED VALVE BOX
AFF ABOVE FINISHED FLOOR
(D) DEMOLISH
ABC ABOVE CEILING
ASV ANGLE STOP VALVE
AIRC COMPRESSED AIR COUPLER
ACOMP AIR COMPRESSOR
SYMBOL / ABBREVIATION DESCRIPTION SYMBOL / ABBREVIATION DESCRIPTION
AIR RELIEF VALVE
AR
PIPING SEISMIC BRACE, 2-WAY
PIPING SEISMIC BRACE, 1-WAY
WATER AND WASTE SERVICE CALCULATIONS - FIRE STATION
FIXTURE TYPE NO.
WASTE COLD WATER HOT WATER TOTAL WATER
FU TOTAL FU TOTAL FU TOTAL FU
CLOTHES WASHER 1 3 3 3 3 3 3 4
DISHWASHER 1 2 2 0 0 1.5 1.5 1.5
FLOOR SINK RECEPTOR (3" TRAP) 2 3 6 0 0 0 0 0
LAVATORY (SINGLE) 4 1 4 0.75 3 0.75 3 4
SINK, KITCHEN (1-1/2 INCH TRAP) 1 2 2 1.125 1.125 1.125 1.125 1.5
SINK, LAUNDRY 1 2 2 1.125 1.125 1.125 1.125 1.5
SINK, SERVICE OR MOP BASIN (2 INCH
TRAP)
4 3 12 1.125 4.5 1.125 4.5 6
SHOWER 3 2 6 1.5 4.5 1.5 4.5 6
WATER CLOSET, 1.6 TANK 4 3 12 2.5 10 0 0 10
MISC. EQUIP. - ICEMAKER 3 0 0 1 3 0 0 3
OTHER / FUTURE 1 10 10 6 6 6 6 8
TOTAL FIXTURE UNITS 59 36.3 24.75 45.5
EQUIVALENT COLD WATER FLOW RATE (GPM): 32
ADDITIONAL DEMAND LOAD (GPM) 0
PRESSURE AVAILABLE AT MAIN (PSI): 43
MINIMUM REQUIRED FIXTURE PRESSURE (PSI): 30
ELEVATION RISE (FT): 6
METER LOSS (PSI): 3
BACKFLOW PREVENTER LOSS (PSI): 5
ADDITIONAL LOSSES (PSI): 0
EQUIVALENT PIPE LENGTH FROM METER TO MOST REMOTE FIXTURE (FT): 660
FRICTION LOSS PRESSURE AVAILABLE (PSI): 2.40
MAXIMUM ALLOWABLE FRICTION LOSS (PSI/100 FT): 0.36
WATER FLOW VELOCITY (FPS): 1.51
CALCULATED FRICTION HEAD LOSS (PSI/100 FT): 0.18
MINIMUM REQUIRED 'WATER' PIPE SIZE (INCHES): 3
MINIMUM REQUIRED 'WASTE' PIPE SIZE (INCHES): 4
*CALCULATIONS PER THE CPC
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs V
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
PLUMBING LEGEND AND
CALCULATIONS
R. GALLAGHER
R. GALLAGHER
M. MADISON
P002
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \P
L U M
B
IN
G \2
P .d n
:2
V2V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
AutoCAD SHX Text: A AutoCAD SHX Text: S AutoCAD SHX Text: R
REFERENCE KEYNOTES
SHEET KEYNOTES
221316 SANITARY WASTE AND VENT PIPING
221319 SANITARY WASTE PIPING SPECIALTIES
224200 COMMERCIAL PLUMBING FIXTURES
P101
PLUMBING PLAN - SANITARY
SEWER
R. GALLAGHER
R. GALLAGHER
M. MADISON
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \P
L U M
B
IN
G \2
P P .d l
:2 A
1. PIPE SLEEVES WHERE PIPES PASS THROUGH FOUNDATION PER FOUNDATION SHEET(S) DETAILS, TYPICAL.
2. WATER CLOSET: PROVIDE WASTE DROP, VENT BELOW SLAB TO WALL, AND COLD WATER PIPING IN FURRED
WALL SPACE. VENT RISER IN WALL TO ABOVE FINISHED CEILING.
3. LAVATORY: PROVIDE WASTE DROP WITH CLEANOUT, VENT RISER AND COLD WATER & HOT WATER PIPING IN
FURRED WALL SPACE.
4. SINK: PROVIDE WASTE DROP WITH CLEANOUT, VENT RISER AND COLD WATER & HOT WATER PIPING IN
FURRED WALL SPACE.
5. FLOOR MOP SINK: PROVIDE WASTE DROP, VENT BELOW SLAB TO WALL AND COLD WATER & HOT WATER
PIPING IN FURRED WALL SPACE. PROVIDE VENT RISER IN WALL TO ABOVE FINISHED CEILING.
6. SHOWER STALL: PROVIDE WASTE DROP FOR SHOWER DRAIN, VENT BELOW SLAB TO WALL. PROVIDE VENT
RISER IN WALL TO ABOVE FINISHED CEILING. PROVIDE COLD WATER & HOT WATER PIPING IN FURRED WALL
SPACE.
7. CLOTHES WASHER: PROVIDE WASTE DROP TO WASTE STANDPIPE, VENT RISER AND HOT WATER & COLD
WATER PIPING IN FURRED WALL SPACE. CONNECT TO WALL BOX AT LOCATION SHOWN.
8. FLOOR RECEPTOR: PROVIDE WASTE DROP, VENT BELOW SLAB TO WALL AND COLD WATER PIPING FROM
TRAP PRIMER. PROVIDE VENT RISER IN WALL TO ABOVE FINISHED CEILING.
BF-1
KS-1
GD-1
3"S
2"S
1-1/2"S
2"S
3"S
3"S
3"S
FR-1
2" VTR, OFFSET IN ATTIC SPACE, CATWALK
(MECH. EQPT PLATFORM) TO PENETRATE
ROOF 18" FROM RIDGE VENT
OFFSET/ROUTE VENT
PIPE UNDER WINDOW
3" VTR, OFFSET IN ATTIC SPACE TO
PENETRATE ROOF 18" FROM RIDGE
VENT.
WCO, FOR TYPICAL DETAIL SEE 3/P501
DISHWASHER
2" V RISER TO ATTIC SPACE
CONTINUE TO VTR.
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
SCALE: 3/16" = 1'-0"
PLUMBING PLAN - SANITARY SEWER
GCO (2-WAY)
INV = 2.8' BELOW FINISHED FLOOR
4" VTR, OFFSET IN ATTIC SPACE TO
PENETRATE ROOF 18" FROM RIDGE
VENT.
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs V
S-1
WC-1
SD-1
6 LAV-1
WC-1
2LS-1
WOB-1
MS-1
LAV-1
SD-1
WC-1
SD-1
LAV-1
3"S
DAY
ROOM
DINING
ROOM
KITCHEN
LAUNDRY BATHRM
BATHRM
BATHRM
STORAGE 1
PHYSICAL
TRAININGPANTRY
H A L L
ENTRY
HALL 1
STORAGE 2
MECH
ELEC /
TELECOMM
LIBRARY
BDRM 6BDRM 1
BDRM 5BDRM 2
BDRM 4BDRM 3
H A L L
1-1/2"V
1-1/4"V
2"V
3"V
2"V
GCO-1
INV = 2.8' BELOW FINISHED FLOOR
GCO-1
INV = 3' BELOW FINISHED FLOOR
P501
P501
P501
WCO, FOR TYPICAL DETAIL SEE 3/P501
FCO, SEE 5/P501
P
LA
N N O R
TH
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
P102
PLUMBING PLAN - DOMESTIC
WATER PIPING
R. GALLAGHER
R. GALLAGHER
M. MADISON
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \P
L U M
B
IN
G \2
P P .d l
:5
TANK
M 27273
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N ICA L
LAV-1,
FAU-2
ASV-1
LAV-1,
FAU-2
ASV-1
MS-1,
FAU-5
1/2"
3/4"
1/2"
1/2" HWR, 1" CW, 3/4" HW
1. PIPE SLEEVES WHERE PIPES PASS THROUGH FOUNDATION PER FOUNDATION SHEET(S) DETAILS, TYPICAL.
2. WATER CLOSET: PROVIDE WASTE DROP, VENT BELOW SLAB TO WALL, AND COLD WATER PIPING IN FURRED
WALL SPACE. VENT RISER IN WALL TO ABOVE FINISHED CEILING.
3. LAVATORY: PROVIDE WASTE DROP WITH CLEANOUT, VENT RISER AND COLD WATER & HOT WATER PIPING IN
FURRED WALL SPACE.
4. SINK: PROVIDE WASTE DROP WITH CLEANOUT, VENT RISER AND COLD WATER & HOT WATER PIPING IN
FURRED WALL SPACE.
5. FLOOR MOP SINK: PROVIDE WASTE DROP, VENT BELOW SLAB TO WALL AND COLD WATER & HOT WATER
PIPING IN FURRED WALL SPACE. PROVIDE VENT RISER IN WALL TO ABOVE FINISHED CEILING.
6. SHOWER STALL: PROVIDE WASTE DROP FOR SHOWER DRAIN, VENT BELOW SLAB TO WALL. PROVIDE VENT
RISER IN WALL TO ABOVE FINISHED CEILING. PROVIDE COLD WATER & HOT WATER PIPING IN FURRED WALL
SPACE.
7. CLOTHES WASHER: PROVIDE WASTE DROP TO WASTE STANDPIPE, VENT RISER AND HOT WATER & COLD
WATER PIPING IN FURRED WALL SPACE. CONNECT TO WALL BOX AT LOCATION SHOWN.
8. HEAT PUMP WATER HEATERS (HPWH) OUTDOOR UNITS, WEIGHT=110# EACH (223300):
8.1. INSTALL ONE HPWH ON A CONCRETE PAD PER 1/M501. ANCHOR TO PAD WITH FOUR STAINLESS STEEL
3/8"Ø x 2-5/8" EMBED SIMPSON "WEDGE-ALL" EXPANSION ANCHORS OR EQUAL.
8.2. WALL-MOUNT SECOND UNIT 18" ABOVE FIRST UNIT WITH STAINLESS STEEL STAND-OFF BRACKETS, REFER TO DETAIL 14/M501. PROVIDE 6" CLEARANCE BETWEEN HEAT PUMP AND WALL. PAINT
EXTERIOR EXPOSED SURFACES OF CHANNEL SYSTEM PER SPECIFICATION SECTION 099113 EXTERIOR
PAINTING. ANCHOR BRACKET TO WALL FRAMING STUDS WITH A TOTAL OF A MINIMUM SIX STAINLESS
STEEL 3/16" x 6" LAG SCREWS. ATTACH EACH OF 4 HEAT PUMP FEET TO BRACKET ARMS WITH 1"
STAINLESS STEEL BOLTS, WASHERS, NUTS AND RUBBER VIBRATION ISOLATION PADS.
8.3. EQUIPMENT LABEL: "HPWH-1" AND "HPWH-2" (210553)
9. LINE SETS: SIZES OF COLD WATER SUPPLY AND HOT WATER RETURN PIPING SHALL BE PER MANUFACTURER
RECOMMENDATIONS TO CONSIDER LENGTH OF PIPING. CONNECT ELECTRIC TRACE TAPE HEATING SYSTEM
TO 24 HOURS CONTINUOUS POWER SUPPLY. WRAP PIPING WITH TAPE THEN COVER WITH INSULATION.
ENERGIZE TAPE WITH PIPE TEMPERATURE SENSOR (NOT OUTSIDE AIR). INSULATE COLD AND HOT WATER
PIPING, FITTINGS AND CONNECTIONS WITH 4"-THICK FOAM INSULATION AND JACKET. ROUTE PIPING FROM
CONDENSING UNITS TO BUILDING EXTERIOR WALL STUD SPACE AND RISE UP TO CEILING/ATTIC SPACE.
ENTER BUILDING WITH APPROVED LINE SET PROTECTION PER DETAIL 1/M501. ROUTE PIPING ABOVE THE
CEILING, OFFSET AS REQUIRED, DROP DOWN INSIDE MECHANICAL ROOM AND CONNECT TO TANKS.
10. HEAT PUMP WATER HEATER TANK: SECURE TANK TO WALL FRAMING MEMBERS PER 1/P502. PROVIDE 3/4"
COLD WATER AND HOT WATER RISERS ALONG WALL, AND CONNECT TO TANK. ROUTE 3/4" PRESSURE RELIEF
VALVE PIPING AS SHOWN. ROUTE PRESSURE RELIEF PIPING TO DISCHARGE TO FLOOR RECEPTOR.
TERMINATE WITH DOWNTURNED ELLS AT MINIMUM 1" AIR GAP ABOVE FIXTURE FLOOD RIM LEVEL. ALL
INSTALLATION SHALL BE PER EQUIPMENT MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS. SEE
DETAILS ON SHEET P502.
11. HOT WATER RECIRCULATING PUMP-1 FOR TANK-2: ACTIVATE BY OCCUPANCY SENSORS. LOCATE ONE
OCCUPANCY SENSOR IN THE KITCHEN, IN BETWEEN FAUCETS OF SINKS KS-1 & KS-2. LOCATE AN
ADDITIONAL OCCUPANCY SENSOR IN THE LAUNDRY ROOM, NEAR FAUCET FAU-5. RETURN COLD WATER TO
BOTTOM OF TANK-2. SHUT-OFF HWRP-1 AFTER KITCHEN IS UNOCCUPIED FOR 30 MINUTES. (221123)
12. REFRIGERATOR ICE MAKER: PROVIDE 3/4" COLD WATER PIPING IN FURRED WALL SPACE TO WALL BOX, CONNECT SUPPLY LINE FROM WALL BOX TO UNIT.
13. DISHWASHER: PROVIDE HOT WATER PIPING IN FURRED WALL SPACE. CONNECT DISCHARGE PIPING TO
GARBAGE DISPOSER WITH AIR GAP DEVICE MOUNTED ON SINK DECK.
14. TRAP PRIMER: PROVIDE COLD WATER PIPING IN FURRED WALL SPACE. PROVIDE WALL ACCESS PANEL FOR
UNIT MOUNTING. ROUTE PRIMER PIPING TO BELOW SLAB AND CONNECT TO FLOOR DRAIN OR FLOOR SINK.
ALL INSTALLATION SHALL BE PER EQUIPMENT MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS.
15. PROPOSED FIRE RISER LOCATION. SEE SHEET F101.
16. WATER LINE RISERS, TYPICAL, PENETRATE CEILING AND ROUTED THROUGH ATTIC SPACE.
SHEET KEYNOTES
REFERENCE KEYNOTES
099113 EXTERIOR PAINTING
220517 SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
220518 ESCUTCHEONS FOR PLUMBING PIPING
220523.12 BALL VALVES FOR PLUMBING PIPING
220523.14 CHECK VALVES FOR PLUMBING PIPING
210529 HANGERS AND SUPPORTS FOR PIPING AND EQUIPMENT
210548 VIBRATION AND SEISMIC CONTROLS FOR PIPING AND EQUIPMENT
210553 IDENTIFICATION FOR PIPING AND EQUIPMENT
210719 PIPING INSULATION
221116 DOMESTIC WATER PIPING
221119 DOMESTIC WATER PIPING SPECIALTIES
221123 DOMESTIC WATER PUMPS
223300 ELECTRIC, DOMESTIC WATER HEATERS
224200 COMMERCIAL PLUMBING FIXTURES
WHA-1
BF-1,
ASV-1
SH-1
WC-1,
ASV-1
KS-1
FAU-1
ASV-1
13 ASV-1
S-1, FAU-3
ASV-1
IMO-1, TYP. OF 3
WOB-1
WHA-1 LS-1,
FAU-4
ASV-1 4
TBV, TYP OF 2
1/2"
1/2"
HWR
DISHWASHER
BV-1,
CVB-1
HB-1
HB-1
HB-1HB-1
SCALE: 3/16" = 1'-0"
PLUMBING PLAN - DOMESTIC WATER PIPING
LAV-1,
FAU-2
ASV-1
SH-1
WC-1,
ASV-1
WC-1,
ASV-1
SH-1
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECHNICAL SERVICES
tr uc ti on M an ag em rs
V
DAY
ROOM
DINING
ROOM
KITCHEN
LAUNDRY BATHRM
BATHRM
BATHRM
STORAGE 1
PHYSICAL
TRAININGPANTRY
H A L L
ENTRY
HALL 1 STORAGE 2
MECH
ELEC /
TELECOMM
LIBRARY
BDRM 6BDRM 1
BDRM 5 BDRM 2
BDRM 4BDRM 3
H A L L
1/2"
1/2"
1-1/2" CW,
FOR CONTINUATION,
SEE SHEET CU101
KS-2
FAU-1
ASV-1
P
LA
N N O R
TH
TP-1
TANK
HPWH
HPWH
1-1/4" CW RISER,
SEE DETAIL 8/P501
HWRP
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-121081
04/15/2024
AutoCAD SHX Text: A AutoCAD SHX Text: A AutoCAD SHX Text: A AutoCAD SHX Text: A
FINISHED GRADE
24"
MIN
SERVICE TO BUILDINGS
DOMESTIC WATER LINE
BALL SHUT-OFF VALVE
UNION CONNECTION (TYPICAL)
CONCRETE VALVE BOX
BALL SHUT-OFF VALVE
UNION CONNECTION (TYPICAL)
CONCRETE VALVE BOX, TOP
FLUSH WITH PAVING/CONCRETE
OR 1" ABOVE SURROUNDING
SURFACE
PLAN
SECTION
SERVICE TO BUILDINGS
REDUCER (AS REQUIRED)
GAS PIPING
UNION
LINE SIZE GAS SHUT-OFF VALVE
GAS LINE SUPPLY
DIRT LEG
(MIN. 6")
CAP
GAS APPLIANCE
FINISHED FLOOR
TO
S
U
IT
M
IN
. 1 2"
WASTE/VENT PIPE (WHERE OCCURS)
CAST IRON CLEANOUT TEE
WASTE/VENT PIPE RISER
WALL PLATE (TYPICAL)
WALL SIDING
PROVIDE PLUG WHERE THERE IS NO
PIPING ABOVE CLEANOUT TEE
STAINLESS STEEL ACCESS COVER
SECURED BY SCREW TO CLEANOUT PLUG
COUNTERSUNK BRONZE PLUG
WALL CAVITY
CONDITION
AT PAVING
CONDITION
AT GRADE
"CHRISTY" F22 CURB VALVE BOX
- F08 BOX WITH ADS ADAPTER
AND 18" ADS EXTENSION, AND
F08R CONCRETE LID
MIN. 4" DEEP CONCRETE PERIMETER
COLLAR, ROUND OR SQUARE. MOUNT 1"
ABOVE SURROUNDING GROUND
SURFACE
FILL WITH WASHED PEA GRAVEL TO
WITHIN 2" OF END OF CONDENSATE
DRAIN PIPE
MOUNT BOX FLUSH WITH
CONCRETE OR PAVEMENT
CONDENSATE DRAIN
PIPE FROM MECH. UNIT,
TYP.
FINISHED FLOOR OR CONCRETEFINISHED GRADE
2" M
A X.
6"
FINISHED FLOOR
V
ER
IF
Y
IN
VE
R T W
IT
H P
LA
N S
M
IN
. 1 8"
FLOOR CLEANOUT WITH TWIST-TO-FLOOR ADJUSTMENT,
SPEEDI-SET BODY AND SPEEDI-SEAL.
ADJUST TOP TO BE FLUSH WITH FINISH FLOOR
FLOOR SLAB
BEDDING/BACKFILL
SANITARY SEWER LINE
LONG RADIUS
FITTINGS (TYP)
FINISHED GRADE
8" ALL AROUND
V
ER
IF
Y
IN
V
ER
T W
IT
H P
LA
N S
M
IN
. 1 8"
NOTE:
ALL PIPE AND FITTINGS SHALL BE THE SAME SIZE AND MATERIAL AS THE
HORIZONTAL PIPE TO WHICH THEY CONNECT. JOINT SHALL BE AS SPECIFIED FOR THE
TYPE OF PIPE USED.
CURB VALVE BOX WITH CAST
IRON LID, TRAFFIC RATED
FINISHED PAVEMENT
OR SIDEWALK
GCO, WITH GASKET SEAL AND BRONZE
PLUG
CONCRETE COLLAR FLUSH WITH
PAVING/SIDEWALK OR 1" ABOVE
SURROUNDING GROUND SURFACE
SANITARY SEWER LINE
2-WAY CLEANOUT FITTING
FINISHED GRADE
CURB VALVE BOX WITH CAST
IRON LID, TRAFFIC RATED
FINISHED PAVEMENT
OR SIDEWALK
8" ALL AROUND
LONG RADIUS FITTINGS (TYP)
SANITARY SEWER LINE
V
ER
IF
Y
IN
V
ER
T W
IT
H P
LA
N S
M
IN
. 1 8"
NOTE:
ALL PIPE AND FITTINGS SHALL BE THE SAME SIZE AND MATERIAL AS THE
HORIZONTAL PIPE TO WHICH THEY CONNECT. JOINT SHALL BE AS SPECIFIED FOR THE
TYPE OF PIPE USED.
4" Ø PVC CLEANOUT, WITH GASKET
SEAL AND THREADED BRONZE PLUG
CONCRETE COLLAR FLUSH WITH
PAVING/SIDEWALK OR 1" ABOVE
SURROUNDING GROUND SURFACE
CW SINGLE-PIECE RISER. NO FITTINGS
ARE ALLOWED UNDER FOUNDATION OR
CONCRETE SLAB.
CONCRETE SLAB FLOOR
PIPE SLEEVE THROUGH CONCRETE SLAB
WITH STACK-SLEEVE FITTING (220517)
PENETRATION TO
THROUGH FOUNDATION
FOOTING PER DETAIL ON
S501
GROUND LINE
SERVICE STOP (220523.15)
DRAIN VALVE
WITH HOSE END
TO BUILDING SUPPLY
STUD
WALL
1-5/8" x 1-5/8" x 12 GA CHANNELS, LENGTHS AS REQUIRED. B-LINE B22
CHANNEL SYSTEM OR APPROVED EQUAL
B-LINE B2000 SERIES PIPE CLAMP ASSEMBLY
11 GA THICKNESS, SUITABLE FOR MOUNTING
ON CHANNEL SYSTEM, COMPLETE WITH
1/2" BOLT, NUT AND LOCK WASHER, TYP.
SIZE TO ACCOMODATE PIPE WITH INSULATION
WALL STUDS,
BEHIND (TYP)
SDS 14 X 3" WITH 11
2" MINIMUM EMBEDMENT AT
WALL STUDS, MIN TWO EACH PER BRACKET, TYP.
PIPE ALONG WALL, WITH INSULATION AS REQUIRED
4" LONG STAINLESS STEEL SHT METAL
INSULATION SHIELD AROUND INSULATED
PIPE AT POINT OF SUPPORT
NOTES:
1. MULTIPLE PIPES MAY BE SUPPORTED ON ONE CHANNEL AS REQUIRED. ADJUST
CHANNEL LENGTH TO SUIT AND ANCHOR AT EVERY STUD LOCATION.
2. LOCATE SUPPORTS AT MINIMUM 48 INCHES SPACING AND AT EVERY TURN.
ABOVEGROUND PIPE , WITH
INSULATION AS REQUIRED
8" LONG STAINLESS STEEL SHT METAL
INSULATION SHIELD AROUND INSULATED
PIPE AT POINT OF SUPPORT
2" WIDE STAINLESS STEEL U-TYPE
HOLD-DOWN PIPE CLAMP
6 x 6 BLOCKING, MIN 12"
LONG, SEE NOTE BELOW
SDS 14 X 3", MIN
TWO EACH PER
CLAMP, TYP.
FIN
GRADE
NOTES:
1. MULTIPLE PIPES MAY BE SUPPORTED ON ONE BLOCKING AS REQUIRED. ADJUST
BLOCKING LENGTH TO SUIT.
2. BLOCKING SHALL BE GROUND-CONTACT (AWPA UC4A) PRESSURE TREATED LUMBER.
3. LOCATE SUPPORTS AT MINIMUM 48 INCHES SPACING AND AT EVERY TURN.
12" x 3/8" DIA
GALVANIZED STEEL SPIKE
SDS 14 X 3", TWO EACH
PER ANGLE, TYP.
SDS 14 X 3", MIN
TWO EACH PER
CLAMP, TYP. 14 GAUGE STEEL 2-1/2" x 2-1/2"
BENT ANGLE BRACKET 4" MIN
FROM ENDS OF 6x6
ANGLE AND SPIKE
LOCATED BEHIND
BLOCKING
ANGLE BRACKET PLACEMENT
(PLAN VIEW)
BLOCKING
PIPE CL
ANGLE BRACKET/
SPIKE (TYP)
4"
2" X 2" X 2" X 1/4" THICK
BENT STEEL
(2) #12 SHEET METAL SCREWS
SIMPSON WEDGE-ALL BOLT,
3/8" DIA X 2 5/8" EMBED
EQUIPMENT
EQUIPMENT
1 /2"
1 /2"
3/4"
3/4"
SIDE VIEW
PLAN VIEW
ISOMODE PAD
S C A L E :
1NOT TO SCALE DOMESTIC WATER SERVICE VALVE BOX
S C A L E :
2NOT TO SCALE TYPICAL GAS SUPPLY CONNECTION
S C A L E :
3NOT TO SCALE WALL CLEANOUT
S C A L E :
4NOT TO SCALE DRYWELL
S C A L E :
5 NOT TO SCALE CLEANOUT TO FLOOR
S C A L E :
6 NOT TO SCALECLEANOUT TO GRADE (2-WAY)
S C A L E :
7 NOT TO SCALE CLEANOUT TO GRADE (1-WAY)
S C A L E :
8 NOT TO SCALE BUILDING WATER SUPPLY ENTRANCE
S C A L E :
9 NOT TO SCALE PIPE SUPPORT - VERTICAL
S C A L E :
10 NOT TO SCALE PIPE SUPPORT - HORIZONTAL
S C A L E :
11 NOT TO SCALE ADDITIONAL PIPE SUPPORT DETAILS
P501
PLUMBING DETAILS
R. GALLAGHER
R. GALLAGHER
M. MADISON
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \P
L U M
B
IN
G \2
P .d l
:1
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em rs V
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/23/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-1342
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
P502
PLUMBING DETAILS
R. GALLAGHER
R. GALLAGHER
M. MADISON
F D a ta
\T e c h S e rv ic e s \A
E \P
R O
J E C
T \M a jo r C a p P ro je c ts
\2 F re s n o C
-1 A
A B \D
R A W
IN
G
S \P
L U M
B
IN
G \2
P .d n
:0
1"
SHEET NUMBER
SHEET TITLE:
JOB NUMBER:
FILE DATE:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
FRESNO
AIR ATTACK BASE
C130 BARRACKS
2311 N CLOVIS AVENUE
FRESNO, CALIFORNIA 93727
FRESNO COUNTY
DATENO. DESCRIPTION
P
LO
T D A
TE
P R O
JE
C T P A
TH
A
REVISIONS
V E R
B C D E F G H I J K L
A B C D E F G H I J K L
DSA Approval
OSFM Approval
T
ECH
NICAL SERVICES
Capital
Outlay
Rea tr uc ti on
M an ag em en t
To we rs V
A
Y R
A
ND
MO
T.
ER
H
AG
LLG
MECHA N IC A L
S C A L E :
1NOT TO SCALE TANK SEISMIC RESTRAINT - MAXIMUM WEIGHT: 1200#
WATER HEATER SEISMIC RESTRAINT NOTES
1. WATER HEATERS SHALL BE BRACED FOR EARTHQUAKE LOADING PER THIS DETAIL.
2. THERE ARE TWO STRAPS REQUIRED FOR EACH LOCATION. ONE FULL WRAP FROM FRONT AND ONE FULL
WRAP FROM BACK. LOCATIONS ARE 9" BELOW THE TOP OF WATER HEATER AND 12" ABOVE THE BOTTOM.
LARGER TANKS REQUIRE ADDITIONAL STRAPS:
2.1. 52 TO 75 GALLON CAPACITY: ONE ADDITIONAL SET OF STRAPS PLACED MID-DISTANCE BETWEEN THE
TOP AND BOTTOM STRAP LOCATIONS.
2.2. 76 TO 100 GALLON CAPACITY: TWO ADDITIONAL SET OF STRAPS SPACED EQUAL DISTANCE BETWEEN
THE TOP AND BOTTOM STRAP LOCATIONS.
3. WHERE THE WATER HEATER IS INSTALLED ON A RAISED PLATFORM, ATTACH WATER HEATER TO PLATFORM, AND PLATFORM TO FLOOR.
4. DO NOT MOVE THE WATER HEATER CLOSER TO WALL OR COMBUSTIBLE MATERIALS WITHOUT VERIFYING
MANUFACTURER'S SPECIFICATIONS OF MINIMUM REQUIRED CLEARANCE TO WALL AND COMBUSTIBLE
MATERIALS.
5. PLUMBERS TAPE IS ALSO CALLED GALVANIZED STEEL HANGER STRAP.
6. ALTERNATE BRACING METHODS MAY ALSO BE ACCEPTABLE, AS RECOMMENDED BY WATER HEATER
MANUFACTURER AND SUBJECT TO REVIEW AND ACCEPTANCE BY DSA STRUCTURAL SAFETY SECTION AND
THE STATE REPRESENTATIVE.
7" MINIMUM DISTANCE, MEASURED FROM LINE
CONNECTING SUPPORTS TO FACE OF WATER
HEATER
LINE CONNECTING POINTS OF SUPPORT
MUST PASS THRU WATER HEATER TANK AS
SHOWN
12" MAXIMUM, 1" MINIMUM FROM
WATER HEATER TO COMBUSTIBLE
MATERIAL, TYPICAL AT BOTH
WALLS
FIRST STUD NOT BEHIND WATER HEATER, TYP.
2x STUD, TYP.
GYPSUM WALLBOARD,
TYP.
3/16" Ø x 6" LAG SCREW
W/ FLAT WASHER, TYP.
6"
MIN
2" MIN (TYP)
3/16" Ø x 6" LAG SCREW WITH FLAT WASHER, TYP.
NON COMBUSTIBLE SPACER OR
GYPSUM BOARD
WATER HEATER
WATER HEATER
2x4 WOOD LEDGER, 2 TOTAL
FIRST ONE CENTERED AT 2-1/4"
ABOVE THE UNIT GAS
CONNECTION, AND SECOND ONE
CENTERED AT 10-3/4" BELOW
THE TOP OF WATER HEATER
2x STUD, TYP.
3/4" x 24 GAUGE STEEL PLUMBERS TAPE
(PERFORATED METAL STRAP) 2 PIECES
AT EACH STRAP LOCATION. INSTALL PER
TAPE LAYOUT
PLUMBERS TAPE LAYOUT
(2 PIECES PER LOCATION)
1" M
IN
3/4" x 24 GAUGE STEEL PLUMBERS TAPE (PERFORATED
METAL STRAP) ENCIRCLE TANK ONE FULL WRAP FROM
FRONT AND ONE FULL WRAP FROM BACK, 2 PIECES
TOTAL AT EACH STRAP LOCATION, INSTALL PER TAPE
LAYOUT
PLUMBERS TAPE LAYOUT
(2 PIECES PER LOCATION)
PLUMBERS TAPE
STRAIGHT WALL LOCATION
CORNER LOCATION
3/16" Ø x 6" LAG SCREW W/ FLAT WASHER AT CENTER OF LEDGER TO CENTER
OF STUD, TYP OF 2.
2x4 WOOD LEDGER
PLUMBERS TAPE, TYP.
GYPSUM
WALLBOARD, TYP.
S C A L E :
2NOT TO SCALE HEAT PUMP WATER HEATER
S C A L E :
3 NOT TO SCALE EXPANSION TANK MOUNTING
HWR FROM
FIXTURES
CW SUPPLY
HW TO FIXTURES
HEAT PUMP
(OUTDOOR UNIT)
TANK
(INDOOR UNIT)
EXPANSION TANK PER MOUNTING
DETAIL 4/P502.
TE…
This is the start of the file's text. The full file is on GovTribe.