This is Bid Addendum 1 for the Fresno Air Attack Base C-130 Barracks project in Fresno, California, prepared by the Department of General Services Division of the State Architect for the California Department of Forestry and Fire Protection (CAL FIRE). The addendum comprises detailed construction drawings and schedules covering plumbing, fire suppression, electrical systems, and voice/data/public address infrastructure for a new barracks building located at 2311 N. Clovis Avenue, Fresno, CA 93727. The project scope includes construction of the barracks/mess hall building with replacement and upgrading of underground community utilities (water, sewer, electric, gas, telephone/radio) and site work including grading, paving, curbs, walkways, drainage, irrigation, and site lighting. The work requires a California Contractors' State License Classification B, with fire protection specialty work classified as C-16. A mandatory site visit was scheduled for October 6, 2025, at 10:00 a.m., with a bid submission deadline of December 1, 2026, at 2:00 p.m., and virtual bid opening scheduled for December 1, 2026, at 3:00 p.m. Interested bidders are directed to access bid documents through Cal eProcure or contact Dennis Schrader at Dennis.Schrader@fire.ca.gov.

The state's construction estimate for this project is $5,192,000.00. The addendum documents detailed specifications for plumbing fixtures and systems (including water heaters, pumps, valves, and waste systems), fire sprinkler design requirements compliant with NFPA 13 and State Fire Marshal standards, electrical distribution and power systems with panel schedules and conduit routing, emergency lighting systems, and comprehensive voice/data network and public address system infrastructure. All materials and products specified require UL or CUL certification where applicable, and firestopping systems for fire-rated wall penetrations must receive State Fire Marshal approval before installation. The project is subject to seismic design requirements and all work must comply with the 2022 California Building Code and applicable state and local regulations.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P504

PLUMBING FIRESTOPPING

DETAILS

R. GALLAGHER

R. GALLAGHER

M. MADISON

F D a ta

\T e c h S e rv ic e s \A

E \P

R O

J E C

T \M a jo r C a p P ro je c ts

\2 F re s n o C

-1 A

A B \D

R A W

IN

G

S \P

L U M

B

IN

G \2

P .d w g

J u n

:1 P M

V2

1"

SHEET NUMBER

SHEET TITLE:

JOB NUMBER:

FILE DATE:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

FRESNO

AIR ATTACK BASE

C130 BARRACKS

2311 N CLOVIS AVENUE

FRESNO, CALIFORNIA 93727

FRESNO COUNTY

DATENO. DESCRIPTION

P

LO

T D A

TE

P R O

JE

C T P A

TH

A

REVISIONS

V E R

B C D E F G H I J K L

A B C D E F G H I J K L

DSA Approval

OSFM Approval

T

ECH

NICAL SERVICES

Capital

Outlay

Rea l Estate Surveying

Architecture&Enginee ring

Co ns tr uc ti on

M an ag em en t

To we rs V au lts

1131 S STREET, SACRAMENTO, CA 95811-2460

M 27273

A

Y R

A

ND

MO

T.

ER

H

AG

LLG

MECHA N IC A L

1. THE FIRESTOPPING DETAILS SHOWN ON THIS SHEET ARE FOR REFERENCE ONLY AND ARE NOT

FOR CONSTRUCTION. PREPARE COMPLETE SUBMITTAL DATA FOR APPROVAL, SHOWING

PROPOSED FIRESTOPPING PRODUCTS AND SYSTEMS, INCLUDING INSTALLATION DETAILS WITH

ASSOCIATED UL SYSTEM NUMBERS.

2. SUBMIT PROPOSED FIRESTOPPING SYSTEM DATA AND INSTALLATION DETAILS FOR REVIEW,

FIRST TO THE STATE FIRE MARSHAL FOR REVIEW. AFTER SFM APPROVAL, SUBMIT TO THE

PROJECT STATE REPRESENTATIVE FOR REVIEW. WORK SHALL NOT BE ALLOWED TO PROCEED

UNTIL ALL REQUIRED APPROVALS ARE OBTAINED.

3. THE FIRESTOPPING DETAILS SHOWN ARE TYPICAL DETAILS. VERIFY FIELD CONDITIONS AND

DIMENSIONS FOR COMPLIANCE WITH THE DETAILS, INCLUDING BUT NOT LIMITED TO THE

FOLLOWING:

· MINIMUM AND MAXIMUM WIDTH OF JOINTS.

· TYPE AND THICKNESS OF FIRE RATED CONSTRUCTION. THE MINIMUM ASSEMBLY RATING

OF THE FIRESTOP ASSEMBLY SHALL MEET OR EXCEED THE HIGHEST RATING OF THE

ADJACENT CONSTRUCTION.

4. PREPARATION OF CONTRACTOR'S DRAWINGS SHALL FOLLOW THE INTERNATIONAL FIRESTOP

COUNCIL (IFC) GUIDELINES FOR EVALUATING FIRESTOP SYSTEMS ENGINEERING JUDGMENTS.

5. REFERENCES TO BE USED SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:

· 2012 UNDERWRITER'S LABORATORIES FIRE RESISTANCE DIRECTORY, VOLUME 2

· NFPA 101 LIFE SAFETY CODE

· ALL GOVERNING STATE BUILDING CODES.

6. FIRESTOP SYSTEM INSTALLATION SHALL MEET REQUIREMENTS OF ASTM E-814 (UL1479)

TESTED ASSEMBLIES THAT PROVIDE A FIRE RATING EQUAL TO THAT OF CONSTRUCTION BEING

PENETRATED.

7. UPON COMPLETION OF WORK, AFFIX LABELS AT ALL RATED THROUGH PENETRATIONS. LABELS

SHALL PROMINENTLY DISPLAY THE FOLLOWING INFORMATION:

· "ATTENTION: FIRE RATED ASSEMBLY"

· UL SYSTEM #

· PRODUCT(S) USED

· HOURLY RATING (F-RATING)

· INSTALLATION DATE

SECTION A-A

A

A

1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE RATED GYPSUM BOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300, U400 OR V400 SERIES WALL OR PARTITION DESIGN IN THE UL

FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 IN. BY 4 IN. (51 MM BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC. STEEL STUDS TO BE MIN 3-1/2 IN. (89 MM) WIDE

SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* - THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 12-1/2 IN. (318 MM).

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED.

2. STEEL SLEEVE - (OPTIONAL) - CYLINDRICAL SLEEVE FABRICATED FROM MIN 0.019 IN.(0.49 MM) THICK (28 GAUGE) GALVANIZED SHEET STEEL AND HAVING A MIN 2 IN. (51 MM) LAP ALONG THE LONGITUDINAL SEAM. LENGTH OF STEEL SLEEVE TO BE EQUAL TO THICKNESS OF WALL OR UP TO 2 IN. (51 MM) LONGER THAN THE THICKNESS OF WALL SUCH THAT, WHEN INSTALLED, THE ENDS OF THE SLEEVE WILL BE FLUSH WITH WALL SURFACE OR PROJECT UP TO 1 IN. (25 MM) BEYOND THE SURFACE OF THE WALL ON EACH SIDE OF THE WALL ASSEMBLY. SLEEVE INSTALLED BY COILING THE SHEET STEEL TO A DIAM SMALLER THAN THE MAX 12-1/2 IN. (318 MM) DIAM THROUGH OPENING, INSERTING THE COIL THROUGH THE OPENING AND RELEASING THE COIL TO LET IT

UNCOIL AGAINST THE CIRCULAR CUTOUTS IN THE GYPSUM BOARD LAYERS

THE HOURLY T RATING IS 0 HR WHEN OPTIONAL SLEEVE IS USED.

3. THROUGH PENETRANTS - ONE METALLIC PIPE OR TUBING INSTALLED CONCENTRICALLY OR ECCENTRICALLY WITHIN OPENING. PENETRANT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL. THE FOLLOWING TYPES AND SIZES OF PENETRANTS MAY BE

USED:

A. STEEL PIPE - NOM 8 IN. (203 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 8 IN. (203 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. COPPER TUBING - NOM 4 IN. (102 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

D. COPPER PIPE - NOM 4 IN. (102 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

4. PIPE COVERING* - NOM 1 IN., 1-1/2 IN. OR 2 IN. (25 MM, 38 MM OR 51 MM) THICK HOLLOW CYLINDRICAL HEAVY DENSITY GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SSL TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. ANNULAR SPACE BETWEEN PIPE COVERING AND PERIPHERY OF OPENING TO BE MIN 0 IN. (POINT CONTACT) TO MAX 1-7/8 IN. (0 MM TO MAX 48 MM). WHEN THE STEEL SLEEVE (ITEM 2) IS USED THE ANNULAR SPAECE BETWEEN THE PIPE COVERING AND THE PERIPHERY OF THE OPENING IS TO BE MIN 1/8 IN. (3 MM) TO MAX 1-3/4 IN. (44 MM).

SEE PIPE AND EQUIPMENT COVERING-MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.

THE HOURLY T RATING IS 1-1/4 HR FOR PIPE COVERINGS OF NOM 1 IN. AND 1-1/2 IN. (25 MM AND 38 MM) THICK FOR 2 HR RATED ASSEMBLIES.

THE HOURLY T RATING IS 1-1/2 HR FOR PIPE COVERINGS OF NOM 2 IN. (51 MM) THICK FOR 2 HR RATED ASSEMBLIES.

THE HOURLY T RATING IS 1/2 HR FOR PIPE COVERINGS OF NOM 1 IN. AND 1-1/2 IN. (25 MM AND 38 MM) THICK FOR 1 HR RATED ASSEMBLIES.

THE HOURLY T RATING IS 3/4 HR FOR PIPE COVERINGS OF NOM 2 IN. (51 MM) THICK FOR 1 HR RATED ASSEMBLIES.

5. FILL, VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8 IN. (16 MM) THICKNESS OF CAULK APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PIPE COVERING

INTERFACE AT POINT CONTACT LOCATION ON BOTH SIDES OF WALL.

3M COMPANY - CP 25WB+, IC 15WB+ CAULK OR FB-3000 WT SEALANT

* BEARING THE UL CLASSIFICATION MARKING

A

A

SECTION A-A

1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE RATED GYPSUM BOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE

MANNER DESCRIBED IN THE INDIVIDUAL U300, U400 OR V400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL

INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 IN. BY 4 IN. (51

MM BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC. STEEL STUDS TO BE MIN 3-1/2 IN. WIDE (89 MM) SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* - THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS

SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 3-1/2 IN. (89 MM).

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED.

2. THROUGH PENETRANTS - ONE NONMETALLIC PIPE OR CONDUIT INSTALLED ECCENTRICALLY OR CONCENTRICALLY WITHIN OPENING. ANNULAR SPACE

BETWEEN PENETRANT AND PERIPHERY OF OPENING TO BE MIN 0 IN. (POINT CONTACT) TO MAX 1-1/8 IN. (0 MM TO MAX 29 MM). PENETRANT TO BE

RIGIDLY SUPPORTED ON BOTH SIDES OF WALL. THE FOLLOWING TYPES AND SIZES OF PENETRANTS MAY BE USED:

A. POLYVINYL CHLORIDE (PVC) PIPE - NOM 2 IN. (51 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID CORE OR CELLULAR CORE PVC PIPE FOR USE IN

CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEM.

B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE - NOM 2 IN. (51 MM) DIAM (OR SMALLER) SDR13.5 CPVC PIPE FOR USE IN CLOSED (PROCESS OR

SUPPLY) PIPING SYSTEMS.

C. RIGID NONMETALLIC CONDUIT+ - NOM 2 IN. (51 MM) DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT INSTALLED IN ACCORDANCE WITH ARTICLE

347 OF THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).

D. ACRYLONITRILE BUTADIENE STYRENE (ABS) PIPE - NOM 1-1/2 IN. (38 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID CORE OR CELLULAR CORE ABS

PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS.

E. ELECTRICAL NONMETALLIC TUBING (ENT)+ - NOM 1-1/4 IN (32 MM) DIAM (OR SMALLER) ENT INSTALLED IN ACCORDANCE WITH ARTICLE 331 OF

THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).

SEE ELECTRICAL NONMETALLIC TUBING (FKHU) CATEGORY IN THE ELECTRICAL CONSTRUCTION MATERIALS DIRECTORY FOR NAMES OF

MANUFACTURERS.

3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8 IN. (16 MM) THICKNESS OF CAULK APPLIED WITHIN ANNULUS, FLUSH WITH BOTH

SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT LOCATION ON

BOTH SIDES OF WALL.

3M COMPANY - IC 15WB+, CP 25WB+ CAULK OR FB-3000 WT SEALANT

(NOTE: CP 25WB+ NOT SUITABLE FOR USE WITH CPVC PIPES.)

* BEARING THE UL CLASSIFICATION MARKING

+ BEARING THE UL LISTING MARK

S C A L E :

2NOT TO SCALE F RATINGS - 1 HR & 2 HR (SEE ITEM 1 ), T RATINGS 0, 1/2, 3/4, 1-1/4 & 1-1/2 HR (SEE ITEMS 2 & 4)

1. WALL ASSEMBLY• -- THE FIRE-RATED GYPSUM BOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS

IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS• -- WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN 3-5/8 IN. WIDE AND SPACED MAX

24 IN. OC.WOOD JOISTS — NOMINAL 2 BY 10 IN. LUMBER JOISTS SPACED 16 IN. O.C. WITH NOMINAL 1 BY 3 IN. LUMBER BRIDGING AND WITH ENDS FIRESTOPPED.

B. INSULATION*• -- R13 (OR HIGHER) GLASS FIBER OR MINERAL FIBER BATT INSULATION FRICTION FITTED INTO STUD CAVITY.GYPSUM BOARD* — NOMINAL 4 FT WIDE BY 5/8 IN. THICK AS SPECIFIED IN THE INDIVIDUAL

FLOOR-CEILING DESIGN. FIRST LAYER OF WALLBOARD NAILED TO WOOD JOISTS. SECOND LAYER OF WALLBOARD (2 HR FIRE RATED ASSEMBLY ONLY) SCREW-ATTACHED TO FURRING CHANNELS. MAX DIAMETER OF OPENING IS 1 IN.

LARGER THAN OUTSIDE DIAMETER OF PENETRANT.

C. GYPSUM BOARD*• -- ONE LAYER OF NOM 5/8 IN. THICK GYPSUM BOARD, AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN. MAX DIAM OF OPENING IS 4-1/2 IN.

2. PIPING SYSTEM• -- TTHE PIPING SYSTEM FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS SHALL CONSIST OF THE FOLLOWING:

A. STEEL OR IRON PIPE• -- NOM 3 IN. DIAMETER (OR SMALLER) CAST OR DUCTILE IRON PIPE OR SCHEDULE 40 (OR HEAVIER) STEEL PIPE,INSTALLED WITHIN STUD CAVITY AND CONNECTED TO TEE. THE TEE PENETRATES WALL ON ONE

SIDE AND IS INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN THE TEE AND THE EDGE OF THE OPENING SHALL BE MIN 3/8 IN. TO MAX 5/8 IN.SOLE PLATE —

NOMINAL 2 BY 6 IN. OR PARALLEL 2 BY 4 IN. LUMBER PLATES, TIGHTLY BUTTED.

B. SHIELDED SLIP ON COUPLING• -- NOM 3 IN. DIAMETER (OR SMALLER) 32 GAUGE (OR HEAVIER) CORRUGATED STAINLESS STEEL SHIELDED RUBBER COUPLING. COUPLING TO BE SECURED TO TEE WITH STAINLESS STEEL HOSE

CLAMP AT ANY POINT BEYOND THE SURFACE OF WALL,OR MAY EXTEND A MAX OF 1 IN. INTO OPENING. WHEN COUPLING EXTENDS INTO OPENING, THE ANNULAR SPACE BETWEEN THE COUPLING AND THE EDGE OF THE OPENING

SHALL BE MIN 1/4 IN. TO MAX 1/2 IN.GYPSUM BOARD* — THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS SHALL BE AS SPECIFIED IN INDIVIDUAL WALL AND PARTITION DESIGN.

C. BRANCH PIPING• -- BRANCH PIPE IS SECURED TO SHIELDED SLIP ON COUPLING WITH STAINLESS STEEL HOSE CLAMP AND MAY CONSIST OF THE FOLLOWING:

1. POLYVINYL CHLORIDE (PVC) PIPE• -- NOM 3 IN. DIAMETER (OR SMALLER) SCHEDULE 40 SOLID CORE PVC PIPE.

2. STEEL OR IRON PIPE• -- NOM 3 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE OR SCHEDULE 40 (OR HEAVIER) STEEL PIPE.

3. FILL, VOID OR CAVITY MATERIAL* -- SEALANT• -- MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH SURFACE OF WALL.

SHERWIN WILLIAMS CO -- WHITE LIGHTNING FLAME BUSTER INTUMESCENT SILICONE

* INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING THE UL.

GENERAL FIRESTOPPING NOTES

S C A L E :

1NOT TO SCALE F RATINGS - 1 & 2 HR (SEE ITEM 1), T RATING - 0 HR

S C A L E :

4 NOT TO SCALE F RATING - 1 HOUR, T RATING - 1 HOUR

1. WALL ASSEMBLY -- THE 1 AND 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400

SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS -- WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN 3-5/8 IN. WIDE

AND SPACED MAX 24 IN. OC. ADDITIONAL FRAMING MEMBERS REQUIRED TO COMPLETELY FRAME OPENING.

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED.

B. GYPSUM BOARD* -- THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS REQUIRED. FOR THE INDIVIDUAL WALL AND PARTITION DESIGN. MAX SIZE OF OPENING IS 335 SQ. IN. WITH A MAX DIMENSION

OF 33-1/2 IN. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED. THE HOURLY T RATING IS 3/4 HR AND 1-1/2 HR FOR

1 AND 2 HR RATED ASSEMBLIES, RESPECTIVELY.

2. THROUGH PENETRANTS -- MAX FOUR PIPES OR TUBINGS INSTALLED ECCENTRICALLY OR CONCENTRICALLY WITHIN OPENING. PIPES OR TUBINGS TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.

THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR TUBING MAY BE USED:

A. STEEL PIPE -- NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE -- NOM 4 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON.

C. COPPER TUBING -- NOM 4 IN. DIAM (OR SMALLER) PIPE TYPE L (OR HEAVIER) COPPER TUBING.

D. COPPER PIPE -- NOM 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. PIPE COVERING -- THE FOLLOWING TYPES OF PIPE COVERINGS MAY BE USED.

A. PIPE COVERING* -- MAX 2 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH

METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. THE ANNULAR SPACE

BETWEEN THE INSULATED PENETRANTS AND THE EDGE OF THE THROUGH OPENING SHALL BE MIN 1/2 IN. TO MAX 2 IN. THE ANNULAR SPACE BETWEEN INSULATED PENETRANTS SHALL BE MIN 1/2 IN. TO MAX

2 IN.

SEE PIPE AND EQUIPMENT COVERING -- MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE

SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.

3. TUBE INSULATION-PLASTICS + -- NOM 3/4 IN. THICK ACRYLONITRILE BUTADIENE/POLYVINYL CHLORIDE (AB/PVC) FLEXIBLE FOAM FURNISHED IN THE FORM OF TUBING. THE ANNULAR SPACE BETWEEN THE

INSULATED PENETRANTS AND THE EDGE OF THE THROUGH OPENING SHALL BE MIN 1/2 IN. TO MAX 2 IN. THE ANNULAR SPACE BETWEEN INSULATED PENETRANTS SHALL BE 1/2 IN. TO MAX 2 IN.

SEE PLASTICS+ - (QMFZ2) CATEGORY IN THE PLASTICS RECOGNIZED COMPONENT DIRECTORY FOR NAMES OF MANUFACTURERS. ANY RECOGNIZED COMPONENT TUBE INSULATION MATERIAL MEETING THE

ABOVE SPECIFICATIONS OF HAVING A UL 94 FLAMMABILITY CLASSIFICATION OF 94-5VA MAY BE USED.

4. FIRESTOP SYSTEM -- THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:

A. PACKING MATERIAL -- MIN 3-5/8 IN. OR 4-1/8 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FOR 1 AND 2 HR RATED ASSEMBLIES, RESPECTIVELY, FIRMLY PACKED INTO OPENING AS A

PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.

B. FILL, VOID OR CAVITY MATERIAL* -- SEALANT -- MIN 5/8 IN. OR 1 IN. THICKNESS OF FILL MATERIAL FOR 1 AND 2 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH

SURFACES OF WALL. JOHNS MANVILLE -- FIRETEMP™ CI

* INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING THE UL.

S C A L E :

3 NOT TO SCALE F RATINGS - 1 & 2 HR, T RATING - 1 & 2 HR (SEE ITEM 1)

V3

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

12/23/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-1342

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-121081

04/15/2024

AutoCAD SHX Text: 1B AutoCAD SHX Text: 3 AutoCAD SHX Text: 2 AutoCAD SHX Text: 1A AutoCAD SHX Text: 1B AutoCAD SHX Text: 2 AutoCAD SHX Text: 3 AutoCAD SHX Text: 2 AutoCAD SHX Text: 1A AutoCAD SHX Text: 4 AutoCAD SHX Text: 5 AutoCAD SHX Text: 3

PLUMBING SCHEDULE

MARK NAME DESCRIPTION

NAMED PRODUCT (MANUFACTURER AND MODEL

NO.) (NOTE 1)

CONNECTIONS

WASTE VENT COLD

WATER

HOT

WATER

BF-1 BOTTLE FILLER

IN-WALL BOTTLE FILLING STATION, FILTERED, NON-REFRIGERATED STAINLESS. ANTI-BACTERIAL,FILTERED, CUMULATIVE COUNTER (FILL COUNT), HANDS FREE, LAMINAR FLOW, REAL DRAIN, VISUAL FILTER MONITOR. ELECTRONIC BOTTLE FILLER SENSOR ACTIVATION. PRODUCT SHALL BE IN-WALL MOUNT (FRAME & PLATE), FOR INDOOR APPLICATIONS, SERVING 1 STATION. UNIT SHALL BE CERTIFIED TO UL 399 AND CSA C22.2 NO. 120. UNIT SHALL BE LEAD-FREE DESIGN WHICH IS CERTIFIED TO NSF/ANSI 61 &372.

"ELKAY" MODEL LZWSDK 1-1/4" 1-1/4" 1/2"

KS-1/

KS-2

KITCHEN SINK(S), STAINLESS

STEEL COUNTERTOP

DOUBLE COMPARTMENT SINK(S) SHALL BE A PART OF, AND INTEGRAL WITH THE STAINLESS STEEL COUNTERTOP SYSTEM, AND SHALL COMPLY WITH THE REQUIREMENTS OF THE APPROPRIATE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS. FURNISH WITH DISPOSER AS NOTED ON

PLANS OR FURNISH WITH TYPE 316 STAINLESS STEEL DRAIN FITTING AS APPLICABLE.

"JUST" J-35-316 DRAIN FITTING 1-1/2" 1-1/4" - -

LAV-1 LAVATORY SINK

WHITE VITREOUS CHINA, OVAL SINGLE BOWL UNDERCOUNTER MOUNT, 19-1/4" x 16-1/4" UNIT DIMENSIONS, 17" x 14" BY 5-1/2" DEEP BOWL, BUILT-IN OVERFLOW. BRASS METAL POLISH CHROME FINISH GRID DRAIN ASSEMBLY. FURNISH WITH INSULATION/PROTECTION ON WATER AND WASTE PIPING LOCATED UNDER COUNTER, AND UNDERCOUNTER MOUNTING KIT AND TEMPLATE. UNIT SHALL COMPLY WITH ADA & TITLE 24 REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.

"AMERICAN STANDARD" OVALYN 0496.221 WITH 2411.015 GRID

DRAIN

1-1/4" 1-1/4" - -

LS-1 LAUNDRY SERVICE SINK

18 GAUGE TYPE 304 (18-8) STAINLESS STEEL SEAMLESS DIE-DRAWN CONSTRUCTION, HAND-BLENDED POLISHED FINISH WITH HIGHLIGHTED BOWL RIM, SINGLE BOWL UNDERCOUNTER MOUNT. 24" x 18" UNIT DIMENSIONS, 22" x 16" BY 10-1/2" DEEP BOWL, CENTER DRAIN OPENING.

TYPE 316 STAINLESS STEEL DRAIN FITTING, SOUND AND CONDENSATE UNDERCOATING. FURNISH WITH UNDERCOUNTER MOUNTING KIT AND TEMPLATE.

"JUST" UNDERMOUNT GROUP USX-1824-A WITH "JUST" J-35-316

DRAIN FITTING

1-1/2" 1-1/4" - -

MS-1 MOP SERVICE SINK

FLOOR MOUNTED SINGLE BOWL TYPE 304 ALL STAINLESS STEEL CONSTRUCTION, 16 GAUGE BOWL AND 18 GAUGE APRON THICKNESS. 33" x 25" x 16" UNIT DIMENSIONS, 28" x 20" x 12" DEEP BOWL, TILE EDGE ON REAR OF UNIT. ALL TIG WELDED CONSTRUCTION, SATIN FINISH.

FURNISH COMPLETE WITH MOP SINK DRAIN ASSEMBLY.

"ADVANCE TABCO" 9-OP-48 2" 1-1/2" - -

S-1 SINK, A.D.A. COMPLIANT

ENAMELED CAST IRON, SINGLE BOWL, UNDER-COUNTER MOUNT. 30-1/4" x 15-13/16" UNIT DIMENSIONS, 5-1/4" DEEP BOWL, RIGHT-CENTER DRAIN OPENING, WITH BOWL SLOPED TOWARDS DRAIN. SOLID BRASS DRAIN FITTING, WITH SOUND AND CONDENSATE UNDERCOATING.

FURNISH WITH UNDER-COUNTER MOUNTING KIT AND TEMPLATE. FURNISH INSULATION/PROTECTION ON WATER AND WASTE PIPING LOCATED UNDER COUNTER. UNIT SHALL COMPLY WITH ADA & TITLE 24 REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS. "KOHLER" RIVERBY K-8689-5U 1-1/2" 1-1/4" - -

WC-1

WATER CLOSET, A.D.A.

COMPLIANT

VITREOUS CHINA, FLOOR MOUNTED, 16-1/2" HIGH ELONGATED BOWL, SIPHON ACTION FLUSH, CLOSE COUPLED TANK. ULTRA HIGH EFFICIENCY 1.1 GPF MAX, BOLT CAPS, POLYPROPYLENE OPEN-FRONT EXTRA HEAVY DUTY SEAT LESS COVER WITH 304 SERIES STAINLESS STEEL HINGE POSTS. CHROME TRIP LEVER LOCATED ON "OPEN" SIDE OF FIXTURE. ANTI-MICROBIAL FINISH ON BOTH FIXTURE AND SEAT. ALL COMPONENTS SHALL BE WHITE. UNIT SHALL COMPLY WITH ADA & TITLE 24 REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.

"AMERICAN STANDARD" H2OPTIMUM SIPHONIC RIGHT HEIGHT

228AA.114 OR 228AA.115 WITH "AMERICAN STANDARD" 5905.110

SEAT

3" 2" 1/2" -

FA

U

C E

TS

D R

A

IN

S

FAU-1

FAUCET, KITCHEN SINK, SINGLE

HANDLE, ADA/CBC COMPLIANT,

SINGLE HOLE, COUNTERTOP

MOUNT

METAL CONSTRUCTION, "DURALAST" CONTROL CARTRIDGE, INTEGRAL BACKFLOW PREVENTION SYSTEM. SINGLE LEVER HANDLE MOUNTED ON RIGHT SIDE OF SPOUT BASE. 360 DEGREE ROTATING HIGH ARC 7-17/32" SPOUT MOUNTED MINIMUM 9-1/2" ABOVE COUNTERTOP DECK, PULL-DOWN SPRAY SPOUT WITH RETRACTABLE 68" BRAIDED HOSE AND SPRAY TO STREAM TOUCH CONTROL. SPOT RESISTANT STAINLESS STEEL FINISH. FLOW RESTRICTOR WITH 1.5 GPM MAXIMUM FLOW RATE. FURNISH WITH DECK PLATE OR ESCUTCHEON FOR SINGLE-HOLE

MOUNTING ON STAINLESS STEEL COUNTERTOP.

NOTE: FURNISH ONE FAUCET AT EACH SINK BOWL. UNIT SHALL COMPLY WITH ADA/CBC REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.

"MOEN" ALIGN 7565 SRS - - 1/2" 1/2"

FAU-2

FAUCET, LAVATORY, SINGLE

HANDLE, ADA/CBC COMPLIANT

SINGLE HOLE, COUNTERTOP

MOUNT

METAL CONSTRUCTION, CERAMIC CONTROL COMPONENTS, SINGLE SWIVEL STYLE LEVER HANDLE WITH RED & BLUE HOT/COLD INDICATORS. ROUND POST BODY WITH DECK PLATE OR ESCUTCHEON FOR SINGLE-HOLE MOUNTING ON COUNTERTOP. 4" SPOUT MOUNTED MINIMUM 3-3/4" ABOVE COUNTERTOP DECK. FLOW RESTRICTOR WITH 0.35 GPM MAXIMUM FLOW RATE, POLISHED CHROME FINISH. FURNISH WITH METAL GRID DRAIN ASSEMBLY. UNIT SHALL COMPLY WITH ADA/CBC REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS. "TOTO" OBERON-S TL363SDA03#CP - - 1/2" 1/2"

FAU-3

FAUCET, SINK, SINGLE HANDLE,

ADA/CBC COMPLIANT SINGLE

HOLE, COUNTERTOP MOUNT

METAL CONSTRUCTION, "DURALAST" CONTROL CARTRIDGE, SINGLE LEVER HANDLE MOUNTED ON RIGHT SIDE OF SPOUT BASE. 360 DEGREE ROTATING HIGH ARC 8" SPOUT MOUNTED MINIMUM 9-5/8" ABOVE COUNTERTOP DECK, FIXED SPOUT. SPOT RESISTANT STAINLESS STEEL FINISH. FLOW RESTRICTOR WITH 1.5 GPM MAXIMUM FLOW RATE. FURNISH WITH DECK PLATE ESCUTCHEON FOR SINGLE-HOLE MOUNTING ON COUNTERTOP. UNIT SHALL COMPLY WITH ADA/CBC REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS. "MOEN" ALIGN 7365 SRS - - 1/2" 1/2"

FAU-4

FAUCET, SINK, GOOSENECK

SPOUT, ADA/CBC COMPLIANT

SINGLE-HOLE COUNTERTOP

MOUNT

METAL CONSTRUCTION, QUARTER TURN CERAMIC CONTROL COMPONENTS, 4-INCH VANDAL PROOF WRISTBLADE HANDLES. COUNTERTOP MOUNTED FAUCET SINGLE-HOLE FIXED CENTER-SET. 8" RIGID/SWING GOOSENECK SPOUT MOUNTED MINIMUM 9-1/4" ABOVE SINK DECK, CHROME STEEL FINISH. FLOW RESTRICTOR WITH 1.5 GPM MAXIMUM FLOW RATE WITH INTEGRAL AERATOR. 3/8" COMPRESSION FLEXIBLE STAINLESS STEEL SUPPLY H0SES. UNIT SHALL COMPLY WITH ADA/CBC REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS. "CHICAGO" MECHANICAL FAUCET 50-GN8AE35-317XKAB - - 1/2" 1/2"

FAU-5

FAUCET, MOP SINK, WALL

MOUNTED

CAST BRASS BODY, EXPOSED YOKE WALL MOUNT, 9-3/4" SPOUT WITH BUCKET HOOK, TOP BRACE AND THREADED HOSE END. 1/4-TURN CERAMIC DISC VALVE CARTRIDGES, VANDAL RESISTANT METAL LEVER HANDLES WITH HOT AND COLD INDICATORS. INTEGRAL SERVICE STOPS AND VACUUM BREAKER. OFFSET SHANKS WITH INTEGRAL CHECK VALVES. /2" FEMALE INLETS WITH WALL FLANGES, ADJUSTABLE ROUGH-IN 6' TO 10". POLISHED CHROME FINISH. FURNISH WITH 1/2" BLACK HEAVY DUTY UTILITY HOSE 36" LONG, WITH 3/4" FEMALE HOSE FITTING ON ONE END AND OPEN ON THE OTHER END, RATED AT 175# MAX WORKING PRESSURE, AND STAINLESS STEEL WALL MOUNT HOSE HANGER.

"AMERICAN STANDARD" UTILITY FAUCET 8354.112

WITH "ELKAY" LK402 UTILITY HOSE AND LK404 HOSE HANGER

- - 1/2" 1/2"

FR-1 FLOOR RECEPTOR, 3" CAST IRON BODY, ACID RESISTING ENAMELED INTERIOR. 12-1/2" SQUARE TOP, 10" DEEP SUMP, FLANGE WITH SEEPAGE OPENINGS, ALUMINUM DOME STRAINER, NICKEL BRONZE RIM AND GRATE, FURNISH WITH SECURED HALF GRATE, TRAP PRIMER CONNECTION, CAULK OUTLET "J.R. SMITH" SANI-CEPTOR 3160C-12 3" 2" - -

IMO-1 ICE MAKER WALL OUTLET BOX

20 GAUGE G90 HOT DIPPED GALVANIZED STEEL CONSTRUCTION, WITH FACTORY INSTALLED WATER SHUT-OFF VALVE. 1/2" NPT INLET x 1/4" COMPRESSION OUTLET. FURNISH COMPLETE WITH VALVES, LOCKNUTS AND O-RINGS AS REQUIRED, COORDINATE MOUNTING LOCATION WITH

ICE MAKER OR REFRIGERATOR BEING SERVED.

"IPS CORPORATION" GUY GRAY BIM 875 - - 1/2" 1/2"

SD-1 SHOWER DRAIN - LINEAR 316L STAINLESS STEEL WEDGE WIRE GRATE GATE. MODIFY LENGTH ON SITE TO FIT SHOWER. ASSEMBLY INCLUDES GRATE, PVC CHANNEL, PVC STOP END, AND PVC THREADED OUTLET. "INFINITY DRAIN" S-AG 10096 2" 1-1/2" - -

SH-1

SHOWER SYSTEM, A.D.A.

COMPLIANT

SHOWER-HAND SHOWER SYSTEM WITH CYLINDER STYLE LEVER HANDLES. PRESSURE BALANCING MIXING VALVE WITH BRASS, BRONZE AND STAINLESS STEEL CONSTRUCTION, METAL ESCUTCHEON, SINGLE LEVER HANDLE, ADJUSTABLE STOP SCREW, INTEGRAL SERVICE STOPS.

SEPARATE DUAL-OUTLET DIVERTER VALVE. THREE-MODE SHOWER HEAD WITH ARM AND FLANGE, WALL/HAND SHOWER WITH FLEXIBLE 5-FOOT METAL HOSE, IN-LINE VACUUM BREAKER WALL CONNECTOR AND FLANGE, AND CRADLE FOR HAND SHOWER MOUNTING, 30" SLIDE BAR FOR CRADLE MOUNTING, POLISHED CHROME FINISH. FLOW RESTRICTOR WITH 1.5 GPM MAXIMUM FLOW RATE. INSTALLATION SHALL INCLUDE GRAB BARS AND SEAT, AND ALL ASSOCIATED ACCESSORIES, CONNECTORS AND PIPING FOR A COMPLETE SYSTEM.. UNIT SHALL COMPLY WITH

ADA & TITLE 24 REQUIREMENTS FOR ACCESSIBLE INSTALLATIONS.

"SYMMONS" DIA 3505-H321-V-CYL-B-X-1.5-352SH-3 - - 1/2" 1/2"

WOB-1

WASHING MACHINE WALL OUTLET

BOX

20 GAUGE G90 HOT DIPPED GALVANIZED STEEL CONSTRUCTION. 1/2" MIP/SWEAT INLETS x 1/2" HOSE OUTLETS FOR WASHING MACHINE, 2" MALE THREADED DRAIN CONNECTION WITH 24" HIGH STANDPIPE. FURNISH COMPLETE WITH VALVES, LOCKNUTS AND O-RINGS, COORDINATE MOUNTING LOCATION WITH WASHING MACHINE BEING SERVED. ALL INSTALLATION SHALL BE PER MANUFACTURER INSTRUCTIONS.

"IPS CORPORATION" GUY GRAY B200 2" 1-1/2" 1/2" 1/2"

HB-1 HOSE BIB

HOSE VALVES INCLUDE A HEAVY ROUGH BRASS BODY, FURNISHED WITH A LOCKSHIELD BONNET AND REMOVABLE LOOSE KEY WHEEL HANDLE. VALVES CLOSE WITH THE WATER PRESSURE AND FEATURE A REPLACEABLE CARTRIDGE WHICH CONTAINS ALL WEARING PARTS INCLUDING THE SEAT. INLET IS 3/4” NPTI, OUTLET IS 3/4” NPSH. VACUUM BREAKERS ARE ATMOSPHERIC TYPE AND CONFORM TO THE REQUIREMENTS OF ASSE STANDARD 1011. HOSE VALVES MEETS THE LEAD FREE REQUIREMENTS WHERE THE WETTED SURFACE OF THIS PRODUCT CONTACTED BY WATER CONTAINS LESS THAN 0.25% LEAD. CHECK LOCAL CODE AUTHORITY FOR VACUUM BREAKER REQUIREMENTS

"ACORN" 8121-LF - - 3/4" -

NOTES:

1. PROVIDE A NAMED PRODUCT OR A COMPARABLE PRODUCT OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.

1"

SHEET NUMBER

SHEET TITLE:

JOB NUMBER:

FILE DATE:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

FRESNO

AIR ATTACK BASE

C130 BARRACKS

2311 N CLOVIS AVENUE

FRESNO, CALIFORNIA 93727

FRESNO COUNTY

DATENO. DESCRIPTION

PL

OT

D

AT

E:

PR

OJ

EC

T

PA

TH

A

REVISIONS

VE

R

. 2

BCDEFGHIJKL

ABCDEFGHIJKL

DSA Approval

OSFM Approval

T ECHN I CA L S ERV I CES Cap i t a l Out lay Real Estate Surveying Architecture & Engineering Con st ru ct io n

Ma na ge me n t

T ow e r s

Va u l t s

A

Y

RA

N D

M O T.

E R H

A G

L LG

ME C H A N IC A L

PLUMBING SCHEDULES

R. GALLAGHER

R. GALLAGHER

M. MADISON

P601

N :\P

R O

JE

C

T\ A ct iv e\

F re sn o C

-1

A A

B \C

O N

S

TR

U C

TI

O

N \D

R A

W

IN

G S

\P

LU

M B

IN

G

\2

1P

1.

dw g S ep

4,

- 8 :2

7P M

V2

1 SEPT 2026 ADDENDUM 1

PLUMBING SCHEDULE

MARK NAME DESCRIPTION

NAMED PRODUCT (MANUFACTURER AND MODEL NO.)

(NOTE 1)

ASV-1 ANGLE STOP VALVE

1/4-TURN BALL STOP VALVE, MACHINED ONE-PIECE BRASS BODY, PRECISION-MACHINED BRASS BALL, CHROME PLATED FINISH. TWO HIGH PERFORMANCE O-RINGS, BLOW-OUT PROOF, PLATED, BRASS STEM. CHROME PLATED METAL HANDLE. 1/2" FIP THREADED INLET, COMPRESSION OUTLET SIZES AS REQUIRED AT EACH FIXTURE BEING SERVED. 40-180 DEG F TEMPERATURE RATING, 125 PSI MAX PRESSURE RATING. COMPLIANT WITH CALIFORNIA HEALTH AND SAFETY CODE 116875 REQUIREMENTS. "BRASSCRAFT" KT COMPLIANT SERIES

BV-1 BALL SHUT-OFF VALVE

TWO-PIECE FULL PORT, BRONZE BODY WITH CHROME PLATED SOLID MACHINED BALL. MSS SP-110, ANSI/NSF 61 "LEAD FREE" COMPLIANT. FEMALE NPT CONNECTIONS. 600 PSI CWP MAX PRESSURE, 500 DEG F MAX TEMPERATURE. PREMIUM MULTI-FILL MTFE SEATS AND SEALS, ADJUSTABLE PACKING, BLOW-OUT PROOF STEM DESIGN. SIZE TO MATCH PIPE BEING SERVED. "APOLLO" 77CLF SERIES

CVB-1 CURBED VALVE BOX

HIGH DENSITY REINFORCED CONCRETE BOX, 11-3/4" x 22-1/4" INSIDE DIMENSIONS, ETCHED POLYPROPYLENE FACE ANCHORED IN CONCRETE, 12" HIGH, NON-SETTLING SHOULDERS, ULTRA-VIOLET INHIBITOR, EXCEEDS ASTM-D1693 STANDARDS FOR STRESS CRACKING RESISTANCE.

FURNISH WITH MATCHING CAST IRON LID.

"CHRISTY" B16 BOX WITH B16C LID

FCO CLEANOUT TO FLOOR CAST IRON BODY, ROUND ADJUSTABLE SCORIATED SECURED NICKEL BRONZE TOP, TWIST-TO-FLOOR ADJUSTMENT, FLASHING FLANGE & CLAMP, SPEEDI-SET OUTLET, GASKET SEAL WITH BRONZE PLUG. SIZE TO MATCH WASTE PIPE BEING SERVED. "J.R. SMITH" 4032L

FCV-1 FLOW CONTROL VALVE

BRONZE BODY, VITON PACKING MATERIAL CARBON/GLASS FILLED PTFE SEATS. TIGHT SHUT-OFF, BALL DESIGN, BI-DIRECTIONAL, BLOW-OUT RESISTANT, WITH POSITION INDICATOR, MEMORY DEVICE, CHECKED METERING PORTS WITH DRIP CAPS, INTEGRAL DRAIN PORTS OPPOSITE METERING

PORTS, 3/4" NPT SIZE. APPROVED FOR DOMESTIC WATER SERVICE. "WATTS" CSM-61-M1-T

GCO CLEANOUT TO GROUND/GRADE CAST IRON BODY, GASKET SEAL WITH BRONZE PLUG, SPEEDI-SET OUTLET, SIZE TO MATCH WASTE PIPE BEING SERVED. MOUNTED WITH PRE-CAST CONCRETE CURBED VALVE BOX WITH CAST IRON LID. "J.R. SMITH" 4292L CLEANOUT WITH

"CHRISTY" G08 VALVE BOX WITH G05C LID

GD-1 GARBAGE DISPOSAL

CONTINUOUS FEED, WALL SWITCH ON-OFF CONTROL, 1.0 HP, 120 V / 1 PHASE / 60 HZ, 10.2 AMP (AVERAGE LOAD), AUTOMATIC GRINDER REVERSING, INTERMITTENT TIME RATING, 13" TALL, ANTI-VIBRATION MOUNTS AND FLEXIBLE CONNECTIONS, SOUND INSULATION, STAINLESS STEEL GRIND CHAMBER AND COMPONENTS, 40-OUNCE GRIND CHAMBER, MANUAL RESET MOTOR OVERLOAD PROTECTION, DISHWASHER DRAIN CONNECTION (NO NEED FOR AIR GAP ABOVE SINK). FURNISH WITH A POWER CORD. UL AND IAPMO LISTED, WARRANTY- 7-YEAR PARTS AND IN-HOME SERVICE. STAINLESS STEEL STOPPER, STAINLESS STEEL SINK FLANGE WITH QUICK-LOCK MOUNT.

INSINKERATOR "EVOLUTION EXCEL"

TBV-1 TEMPERED WATER BLENDING VALVE (NEAR WATER HEATER TANK) INTERNAL CHECK STOPS, LEAD-FREE BRASS/BRONZE BODY. 0.5 GPM MINIMUM FLOW RATE. 150 PSIG MAX OPERATING PRESSURE. 70-145 DEG F OUTLET TEMPERATURE. INLET AND OUTLET SIZES ACCORDING TO PLANS. ASSE LISTED 1017, NSF/ANSI 61, CALIFORNIA HEALTH AND SAFETY CODE 116875. TEMPERATURE SET-POINT ACCORDING TO WATER HEATER SCHEDULE. PROTECT SET-POINT WITH CAP.

"HONEYWELL" AM-1-LF

TBV-2 TEMPERED WATER BLENDING VALVE (ANTI-SCALD POINT-OF-USE)

INTERNAL CHECK STOPS, LEAD-FREE BRASS/BRONZE BODY WITH NICKEL PLATING, POLYSUFONE PISTON, STAINLESS STEEL SPRINGS AND SCREEN. 0.35 GPM MINIMUM FLOW RATE, 8 PSIG MAXIMUM PRESSURE LOSS AT 5 GPM FLOW RATE. 145 PSIG MAX OPERATING PRESSURE, 195 DEG F MAX INLET TEMPERATURE. INLET AND OUTLET SIZES ACCORDING TO PLANS. ASSE LISTED 1070, NSF/ANSI 61, CALIFORNIA HEALTH AND SAFETY CODE 116875. ANTI-SCALD TEMPERATURE SET-POINT = 105 DEG F. PROTECT SET-POINT WITH CAP. "ZURN" ZW1070XL

TP-1 TRAP PRIMER VALVE

MACHINED BRASS BODY, 60 MESH STAINLESS STEEL SCREEN, VACUUM BREAKER PORTS. UNIT SHALL CONTAIN NO SPRINGS, DIAPHRAGMS OR PLASTIC PARTS. 20-80 PSIG PRESSURE OPERATING RANGE, PRIMING VALVE AUTOMATICALLY ACTUATED BY MINIMUM 10 PSI PRESSURE FLUCTUATION. 1/2" MNPT INLET, 1/2" FNPT OUTLET. FURNISH COMPLETE WITH SERVICE SHUT-OFF VALVE AT INLET AND UNION CONNECTION AT DISCHARGE TO DRAIN TRAP. FURNISH WITH 12"x12" HINGED METAL ACCESS DOOR FOR CONCEALED UNIT "PRECISION PLUMBING PRODUCTS" PRIME-RITE PR-500

WCO CLEANOUT TO WALL

CAST IRON BODY CLEANOUT TEE, COUNTERSUNK BRONZE CLOSURE PLUG, SUITABLE FOR INSTALLATION ON WASTE/VENT VERTICAL PIPE RISER IN CONCEALED LOCATIONS, SIZE TO MATCH PIPE RISER. REMOVABLE ROUND STAINLESS STEEL ACCESS COVER MOUNTED ON SURFACE OF FINISH

WALL DIRECTLY SECURED BY SCREW TO TAPPING PROVIDED IN CLEANOUT PLUG.

"J.R. SMITH" 4531S

WHA-1 WATER HAMMER ARRESTER PDI STANDARD WH-201. ALL STAINLESS STEEL CONSTRUCTION, PNEUMATIC AND HYDRAULIC PRESSURE CONTROL. FACTORY CHARGED AND SEALED PRESSURIZED COMPRESSION CHAMBER, EXPANSION BELLOWS. PDI-A RATING, 3/4" THREADED CONNECTION. "J.R. SMITH" HYDROTROL 5005

NOTES:

1. PROVIDE A NAMED PRODUCT OR A COMPARABLE PRODUCT OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.

1"

SHEET NUMBER

SHEET TITLE:

JOB NUMBER:

FILE DATE:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

FRESNO

AIR ATTACK BASE

C130 BARRACKS

2311 N CLOVIS AVENUE

FRESNO, CALIFORNIA 93727

FRESNO COUNTY

DATENO. DESCRIPTION

PL

OT

D

AT

E:

PR

OJ

EC

T

PA

TH

A

REVISIONS

VE

R

. 2

BCDEFGHIJKL

ABCDEFGHIJKL

DSA Approval

OSFM Approval

T ECHN I CA L S ERV I CES Cap i t a l Out lay Real Estate Surveying Architecture & Engineering Con st ru ct io n

Ma na ge e r s

A

Y

RA

N D

M O T.

E R H

A G

L LG

ME C H A N IC A L

PLUMBING DETAILS

R. GALLAGHER

R. GALLAGHER

M. MADISON

P602

N :\P

R O

JE

C

T\ A ct iv e\

F re sn o C

-1

A A

B \C

O N

S

TR

U C

TI

O

N \D

R A

W

IN

G S

\P

LU

M B

IN

G

\2

1P

2.

dw g S ep

3,

- 9 :4

9A M

V2

DOMESTIC WATER PUMP SCHEDULE (SPECIFICATION SECTION 221123.21)

MARK NAME DESCRIPTION

NAMED PRODUCT

(MANUFACTURER AND MODEL

NO.) (NOTE 1)

ELECTRICAL CHARACTERISTICS CONNECTION SIZES

VOLTS / PHASE

/ HERTZ

POWER (HP) HOT WATER

SUPPLY

HOT WATER

RETURN

DOMESTIC HOT WATER

RE-CIRCULATION PUMP

ETL LISTED, MAINTENANCE FREE IN-LINE CIRCULATING PUMP SPECIFICALLY DESIGNED FOR POTABLE DOMESTIC WATER APPLICATIONS. 4 GPM NOMINAL CAPACITY, 150 PSI MAX WORKING PRESSURE AND 230 DEG F MAX WORKING TEMPERATURE. SEAL-LESS CONSTRUCTION, LEAD-FREE BRASS PUMP BODY, EPDM OR VITON O-RING, CERAMIC BEARING, NYLON/PPO IMPELLER. ALL OTHER WETTED PARTS SHALL BE TYPE 316 STAINLESS STEEL. UNIT SHALL USE PERMANENT MAGNET ELECTRONICALLY COMMUTATED MOTOR (ECM) TECHNOLOGY WITH SHAFT-LESS SPHERICAL MOTOR. SELF-REALIGNING BEARING AUTOMATICALLY COOLED BY SYSTEM FLUID. ROTOR MAGNETICALLY CENTERED ON THE BEARING. CONSTANT SPEED UNIT WITH INTEGRAL BUILT-IN ADJUSTABLE TEMPERATURE SENSOR, SET TO 105 DEG. UNIT SHALL INCLUDE BUILT-IN UNION CONNECTIONS, AIR PURGER AND CHECK VALVE. MOTOR SHALL HAVE AUTOMATIC OVERLOAD PROTECTION AND LOW IN-RUSH CURRENT. FURNISH PRE-WIRED WITH 6-FT ELECTRICAL PLUG. FURNISH WITH PROGRAMMABLE TIMER. TIMER SHALL BE MOUNTED ON MOTOR END CAP WITHOUT ANY ADDITIONAL WIRING REQUIRED. SEE ELECTRICAL SHEETS FOR DLCS CONTROL SCHEME/WIRING.

"TACO GENIE" 006-CT 115/1/60 1 / 40 1/2" MALE NPT 1/2" MALE NPT

NOTES:

1. PROVIDE A NAMED PRODUCT OR A COMPARABLE PRODUCT OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS.

ELECTRIC, DOMESTIC WATER HEATER SCHEDULE (SPECIFICATION SECTION 223300)

MARK

NAMED PRODUCT

(MANUFACTURER AND MODEL

NO.) (NOTES 1 AND 2)

TYPE

CAPACITY -

GALLONS

RECOVERY -

GPH AT 90

DEG. F

TEMPERATURE

RISE

FLOW RATE

(MINIMUM)

HEAT PUMP

CAPACITY -

BTU/H

HEAT PUMP

REFRIGERANT TYPE

TEMPERATURE

RISE - DEGREE

F AT GPM

HOT-WATER

TEMPERATURE

SETTING -

DEGREES F

TEMPERATURE

BLENDING

VALVE

SETTING -

DEGREES F

UNIFORM

ENERGY

FACTOR

(MINIMUM)

BLOCK OUT

TIMES (HEAT

PUMP OFF)

SETTING

POWER

DEMAND

- KW

ELECTRICAL CHARACTERISTICS

WEIGHT - LBS. ACCESSORIES

VOLTS / PHASE / HERTZ

MINIMUM

CIRCUIT

AMPACITY

BREAKER

SIZE

SANCO2 GS4-45HPC-US OUTDOOR UNIT AND

SAN-83SSAQA INDOOR STAINLESS STEEL

STORAGE TANK

HEAT PUMP,

STORAGE

83 20 - 15400 R744 (CO2) _ 150 108 3.85

3 P.M. TO 9 P.M.

(NOTE 3) - 208-230/1/60 7 15

110# OUTDOOR

UNIT

EXPANSION TANK

(ET-1) (223300)

NOTES:

1. PROVIDE A NAMED PRODUCT OR A COMPARABLE PRODUCT OR EQUAL PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN THE SPECIFICATIONS. 2. MUST BE LISTED IN THE CURRENT CALIFORNIA ENERY COMMISSION'S APPLIANCE EFFICIENCY DATABASE. 3. ADJUST BLOCK OUT TIMES TO AVOID PG&E'S TIME-OF-USE "PEAK" HOURS. CHECK CURRENT TIME-OF-USE RATE PLAN.

TANK

TANK

HPWH

HWRP

HPWH

LIBRARY

DINING

ROOM

KITCHEN

PHYSICAL

TRAINING

STOR

HALL 1

H A

LL

BATHRM

ENTRY

PANTRY

DAY ROOM

MECH

ELEC /

TELECOMM

BATHRM

STOR

BDRM 6BDRM 1

BDRM 4BDRM 3

BDRM 5BDRM 2

BATHRM

LAUN

H A

LL

F101

FIRE SPRINKLER PLAN

R. GALLAGHER

R. GALLAGHER

M. MADISON

N :\P

R O

JE

C

T\ A ct iv e\

F re sn o C

-1

A A

B \C

O N

S

TR

U C

TI

O

N \D

R A

W

IN

G S

\F

IR

E \2

1_

F1

.d w g S ep

1,

- 1 1:

A

M

V2

M 27273

A

Y

RA

N D

M O T.

E R H

A G

L LG

ME C H A N IC A L

1"

SHEET NUMBER

SHEET TITLE:

JOB NUMBER:

FILE DATE:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

FRESNO

AIR ATTACK BASE

C130 BARRACKS

2311 N CLOVIS AVENUE

FRESNO, CALIFORNIA 93727

FRESNO COUNTY

DATENO. DESCRIPTION

PL

OT

D

AT

E:

PR

OJ

EC

T

PA

TH

A

REVISIONS

VE

R

. 2

BCDEFGHIJKL

ABCDEFGHIJKL

DSA Approval

OSFM Approval

T ECHN I CA L S ERV I CES Cap i t a l Out lay Real Estate Surveying Architecture & Engineering Con st ru ct io n

Ma na ge e r s

1. AUTOMATIC FIRE SPRINKLER SYSTEM DESIGNED TO COVER AREAS DENOTED BY HATCH MARKS (/////), ABOVE AND BELOW CEILING, INCLUDING OVERHANGS, PATIOS, PORCHES, AND ALL SPACES REQUIRED BY NFPA 13, THE STATE FIRE MARSHAL (SFM) AND PROJECT SPECIFICATIONS.

2. LICENSED PROFESSIONAL FIRE SPRINKLER ENGINEER OF THE FIRE PROTECTION SYSTEM SHALL COORDINATE WITH THE ARCHITECTURAL REFLECTED CEILING PLAN, PLUMBING PLAN AND MECHANICAL PLAN FOR ANY

OBSTRUCTION ABOVE THE CEILING.

3. THE SPRINKLER SYSTEM DESIGN, INCLUDING SPRINKLER CONNECTIONS TO BUILDING SHALL BE IN COMPLIANCE WITH SEISMIC REQUIREMENTS. REFER TO STRUCTURAL SHEET S001 FOR DESIGN NOTES. SEE FIRE SPRINKLER NOTES AND DEFERRED SUBMITTAL NOTES ON THIS SHEET FOR MORE INFORMATION.

4. WITH THE EXCEPTION OF THE MAIN SPRINKLER RISER AREA, ALL OTHER PIPING INSTALLED IN THE BUILDING SHALL BE CONCEALED. ALL POSSIBLE PIPING ROUTING SHALL BE EVALUATED IN ORDER TO AVOID EXPOSING ANY PIPING. WHERE EXPOSED PIPING CAN NOT BE AVOIDED, CONTRACTOR SHALL NOTIFY STATE REPRESENTATIVE OF PROPOSED LOCATIONS WHERE PIPING SHALL BE EXPOSED PRIOR TO PRELIMINARY REVIEW. EXPOSED PIPING, IF NOT AVOIDABLE, SHALL BE KEPT TO A MINIMUM, AND MAY BE INSTALLED ONLY

AS ALLOWED IN WRITING BY THE STATE REPRESENTATIVE.

5. SEE CIVIL SHEETS FOR LOCATION OF FIRE DEPARTMENT CONNECTION.

099113 EXTERIOR PAINTING

211100 FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING

211313 WET-PIPE SPRINKLER SYSTEMS

1. WET-PIPE FIRE SPRINKLER DESIGN AREA. SEE FIRE SPRINKLER NOTES AND DEFERRED SUBMITTAL NOTES ON

THIS SHEET FOR MORE INFORMATION.

2. PROPOSED LOCATION OF FIRE RISER. SEE SHEET CU101 FOR FIRE WATER SUPPLY OUTSIDE THE BUILDING.

3. INSPECTORS TEST PORT AND AUXILIARY DRAIN LOCATION.

4. RATED FIRE WALL SEPARATION.

1. PROVIDE A HYDRAULICALLY DESIGNED SPRINKLER SYSTEM WITH A PERMANENTLY MARKED WEATHERPROOF METAL SIGN. SECURE WITH CORROSION-RESISTANT WIRE, CHAIN OR OTHER APPROVED MEANS. PLACE SUCH SIGNS AT THE ALARM VALVE, DRY PIPE VALVE, PREACTION VALVE, OR DELUGE VALVE SUPPLYING THE CORRESPONDING HYDRAULICALLY DESIGNED AREA. INCLUDE THE FOLLOWING INFORMATION ON THE SIGN:

1.A. LOCATION OF THE DESIGN AREA OR AREAS.

1.B. DISCHARGE DENSITIES OVER THE DESIGN AREA OR AREAS.

1.C. REQUIRED FLOW AND RESIDUAL PRESSURE DEMAND AT THE BASE OF THE RISER.

1.D. HOSE STREAM DEMAND INCLUDED IN ADDITION TO THE SPRINKLER DEMAND.

2. THE AUTOMATIC FIRE SPRINKLER SYSTEM SHALL CONFORM TO THE REQUIREMENTS OF NFPA 13 AND STATE

FIRE MARSHAL. SPRINKLERS SHALL BE QUICK-RESPONSE.

3. DO NOT BEGIN INSTALLATION OF THE AUTOMATIC SPRINKLER SYSTEM UNTIL THE COMPLETE PLANS AND SPECIFICATIONS (INCLUDING WATER SUPPLY INFORMATION AND TYPE OF SYSTEM, IF ANY) HAVE BEEN

APPROVED BY STATE FIRE MARSHAL.

4. DO NOT BURY FIRE WATER MAIN UNTIL INSPECTED AND APPROVED BY STATE FIRE MARSHAL.

5. TEST THE SYSTEM IN THE PRESENCE OF STATE FIRE MARSHAL, LOCAL AUTHORITY HAVING JURISDICTION AND

THE STATE REPRESENTATIVE AT VARIOUS STAGES OF CONSTRUCTION AND UPON COMPLETION.

6. PROVIDE FIRESTOPPING DESIGN AND DETAILS SHOWING THE REQUIRED CLEARANCES AND FLEXIBLE FIRE STOP SYSTEM/SEALANT WHERE SPRINKLER PIPING PENETRATES RATED WALLS AND WHERE OPENINGS ARE REQUIRED TO BE PROTECTED (2022 CBC, SECTION 714). SEE SHEET A101 FOR RATED WALL LOCATIONS AND

LEGEND.

7. PROVIDE A CABINET WITH STOCK OF SPARE SPRINKLERS, SPECIAL SPRINKLER WRENCH AND LIST OF SPRINKLERS. LOCATE AND LABEL THE CABINET NEAR THE FIRE SPRINKLER RISER OR IN THE PUMP ROOM.

PROVIDE NUMBER, TYPE OF SPRINKLERS AND LIST CONFORMING TO 2022 NFPA 13, SECTION 6.2.9.

AUTOMATIC FIRE SPRINKLER SYSTEM AND FIRE ALARM ARE DEFFERED-APPROVAL ITEMS.

HIRE LICENSED PROFESSIONALS AS REQUIRED TO DESIGN AND CONSTRUCT THE SYSTEMS INCLUDING PROVIDING SERVICES FOR PREPARING DRAWINGS AS NECESSARY FOR APPROVAL FROM THE STATE FIRE MARSHAL OFFICE

(SFM) HAVING JURISDICTION OVER THE PROJECT.

DO NOT INSTALL DEFERRED SUBMITTAL ITEMS UNTIL THE DESIGNATED SUBMITTAL DOCUMENTS HAVE BEEN

APPROVED BY THE SFM.

ALL COMPONENTS MUST BE LISTED PRODUCTS AND APPROVED BY SFM.

INCLUDE WITH THE SUBMITTAL:

1. COMPREHENSIVE ENGINEERING ANALYSIS BY CALIFORNIA LICENSED ENGINEERS USING PERFORMANCE

REQUIREMENTS AND DESIGN CRITERIA INDICATED ON THESE DRAWINGS AND RELATED SPECIFICATION

SECTIONS.

2. COMPLETE CALCULATIONS FOR HYDRAULIC, BATTERY, VOLTAGE DROP, SEISMIC BRACING AND SUPPORTS, ETC.

3. CUTSHEETS FOR MATERIALS AND PRODUCTS USED IN THE SYSTEM(S).

4. FIRESTOPPING LOCATIONS AND DETAILS FOR PENETRATIONS THROUGH FIRE-RATED WALLS, FLOOR AND

CEILING ASSEMBLIES.

5. PROPOSED FIRE WATER PIPING, VALVES AND APPURTENCES.

SUBMIT FIRE SPRINKLER AND FIRE ALARM SYSTEMS **AS-BUILT INCLUDING ANY MECHANICAL, ELECTRICAL AND

PLUMBING MODIFICATION TO ACCOMMODATE THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS.

GENERAL SHEET NOTES

REFERENCE KEYNOTES

SHEET KEYNOTES

FIRE SPRINKLER NOTES

DEFERRED SUBMITTAL NOTES

SCALE: 3/16" = 1'-0"

FIRE SPRINKLER PLAN

MAIN SPRINKLER RISER WITH

INDICATING VALVE AND CHECK

VALVE AT BASE OF RISE

MAIN FW LINE, FOR CONTINUATION

SEE CIVIL DRAWINGS

4FIRE WALL SEPARATION

PLAN

NORTH

DISTRIBUTION & EQUIPMENT

DESCRIPTIONSYMBOL

DIAGRAMS

DESCRIPTIONSYMBOL

R

C

M M

BRANCH CIRCUIT PANELBOARDS, SURFACE AND RECESS

MOUNTED, DASHED LINES INDICATE REQUIRED CLEARANCE

TRANSFORMER WITH REQUIRED CLEARANCES SHOWN

SERVICE AND/OR DISTRIBUTION EQUIPMENT WITH METER

CONNECTION TO MOTOR PROVIDED BY ELECTRICAL

DISCONNECT SWITCH, SIZE AS NOTED. WHEN NOT SHOWN,

SIZE FOR CONNECTED MOTOR(S), PER ARTICLE 430 OF CEC.

FUSED DISCONNECT SWITCH, FRAME SIZE AS NOTED.

SIZE FUSE PER EQUIPMENT MANUFACTURER'S

RECOMMENDATIONS.

CIRCUIT BREAKER, SIZE AS NOTED. SIZE PER EQUIPMENT

MANUFACTURER'S RECOMMENDATIONS.

SWITCH

OVERLOADS

NORMALLY CLOSED CONTACTOR OR RELAY CONTACTS

NORMALLY OPEN CONTACTOR OR RELAY CONTACTS

BUS BAR

CONTACTOR COIL

RELAY COIL

UTILITY CO. APPROVED SOCKET WITH METER INSTALLED.

SQUARE = REMOTE MOUNTED

DELTA CONNECTION

GROUNDED WYE CONNECTION

CONNECTION TO GROUND

CIRCUIT BREAKER, WITH TRIP POINT (AT), FRAME

AMPERE RATING (AF), AND NUMBER OR POLES (#P)

100AT

225AF

3P

ABBREVIATIONS

GENERAL PROJECT NOTES

A. REFER TO DETAIL DRAWINGS FOR ADDITIONAL INFORMATION. ALL DETAILS APPLY FOR ALL APPLICABLE SITUATIONS WHETHER REFERENCED OR NOT, UON.

B. REFER TO ARCHITECTURAL FLOOR PLANS, INTERIOR ELEVATIONS, AND DETAIL DRAWINGS PRIOR TO ROUGH-IN FOR EXACT LOCATION OF RECEPTACLES, FLOOR BOXES, AND OUTLETS. NOTIFY STATE

REPRESENTATIVE OF ANY CONFLICTS.

C. THESE DOCUMENTS REFLECT THE FINAL ANTICIPATED LAYOUT OF SYSTEMS AND APPURTENANCES FOR THIS PROJECT. IT IS NOT THE INTENT OF THESE DOCUMENTS TO INDICATE SPECIFIC SCOPE OF WORK REQUIRED ON A PHASE BY PHASE BASIS. THE FINAL DESIGN INDICATED DOES ALLOW FOR THE WORK TO BE INSTALLED IN A PHASED APPROACH. CONTRACTOR SHALL DETERMINE ADDITIONAL SCOPE OF WORK REQUIRED TO ACCOMMODATE ALL PHASING ASPECTS OF THE PROJECT AND INCLUDE THAT SCOPE IN THEIR BID.

D. THE CIRCUITING SHOWN IS DIAGRAMMATIC. THE DRAFTING METHOD WHICH MOST SIMPLY CONVEYS THE CIRCUITING INTENT IS EMPLOYED. WHERE DEVICES OR EQUIPMENT ARE SHOWN UNCONNECTED, CONNECT (IN A MANNER CONSISTENT WITH THE MATERIALS AND METHODS INDICATED IN THE PLANS AND SPECIFICATIONS) FROM THE WIRING EXTENSION POINT SHOWN TO EACH DEVICE USING 1) MC CABLE IN HARD AND ACCESSIBLE CEILING AREAS -OR- 2) CONDUIT & WIRE ONLY IN EXPOSED AREAS. EMT CONDUIT AND WIRE SHALL BE USED FROM A PANEL TO A J-BOX IN AN ACCESSIBLE PORTION OF THE CEILING. MC CABLE MAY BE USED ONLY FROM THE J-BOX TO THE DEVICE OR IN BETWEEN DEVICES. AS-BUILT DRAWINGS SHALL INCLUDE THE LOCATION OF

THESE JUNCTION BOXES AND WHICH RECEPTACLES OR DEVICES THEY FEED.

E. CONTRACTOR IS RESPONSIBLE FOR REVIEWING ARCHITECTURAL DRAWINGS TO CONFIRM CEILING TYPES IN ALL ROOMS (ACCESSIBLE, EXPOSED, OR "HARD") AND TO EMPLOY APPROPRIATE WIRING METHODS FOR EACH TYPE. ENSURE ALL J-BOXES ARE ACCESSIBLE AFTER WORK BY ALL OTHER TRADES IS COMPLETED. DO NOT INSTALL J-BOXES ON "HARD" CEILINGS. ALL WIRING MUST BE ACCESSIBLE THROUGH DEVICE VIA "DAISY-CHAIN" METHOD OR VIA DEDICATED HOME-RUNS FROM PANEL TO EACH DEVICE. J-BOXES MAY BE LOCATED ABOVE ACCESS DOORS INSTALLED BY OTHER TRADES, PROVIDED THE J-BOX INSTALLATION DOES NOT INTERFERE WITH ACCESS THROUGH DOOR.

F. THE COMPLETED INSTALLATION SHALL CONFORM TO THE LATEST ADOPTED EDITIONS OF ALL APPLICABLE STATE, COUNTY AND CITY CODES, ORDINANCES, AND REGULATIONS INCLUDING

NECESSARY PERMITS AND INSPECTIONS REQUIRED BY THE GOVERNING AUTHORITIES.

G. INSTALL ALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS.

H. ALL ELECTRICAL COMPONENTS SHALL BE BRACED OR ANCHORED PER THE DETAILS ON THE APPROVED CONSTRUCTION DOCUMENTS AND MANUFACTURERS REQUIREMENTS.

I. REFER TO MECHANICAL DRAWINGS FOR MOUNTING AND EQUIPMENT DETAILS. SINCE WALL MOUNTED CONTROLS FROM ELECTRICAL AND MECHANICAL PLANS ARE OFTEN CO-LOCATED, CONTRACTOR SHALL REVIEW BOTH PLANS PRIOR TO ROUGH-IN TO ENSURE EQUIPMENT IS PROPERLY LOCATED AND ADEQUATE SPACE IS PROVIDED. UON EQUIPMENT ADJACENT TO DOORWAYS SHALL BE PLACED AS FOLLOWS (CLOSEST TO DOOR FIRST): LIGHT CONTROL/SENSOR, PA VOLUME, THERMOSTAT/FAN CONTROL.

J. IN COMMON PARTY WALLS AND CEILINGS PROVIDE PUDDY PADS AROUND JUNCTION BOXES, RECEPTACLES, AND TELECOM OUTLETS. RECEPTACLES AND TELECOM OUTLETS SHALL BE INSTALLED SUCH THAT THERE IS A MINIMUM SPACING OF 24 INCHES, FROM BACK OF ONE OUTLET TO THE OTHER.

K. ALL NEW RACEWAYS AND CONDUCTORS SHALL BE INSTALLED CONCEALED WITHIN WALLS, INCLUDING FURRED SECTIONS WHERE APPLICABLE. CONDUITS SHALL BE INSTALLED AT A 90° ANGLE TO

BUILDING LINES.

L. DEDICATED HOT(S) AND NEUTRAL SHALL BE RUN WITH EVERY BRANCH CIRCUIT. WHILE 240V CIRCUITS SHALL HAVE A DEDICATED EGC, ONLY ONE EGC IS REQUIRED PER CONDUIT FOR 120V CIRCUITS, I.E. WHEN MULTIPLE 120V CIRCUITS ARE RUN IN A SINGLE CONDUIT, ONLY ONE EGC IS REQUIRED. METAL CONDUIT MAY NOT BE USED AS AN EGC.

M. UP SIZE WIRE FOR VOLTAGE DROP, AS REQUIRED, BASED ON FINAL ROUTING OF WIRES. PROVIDE SPECIAL RECEPTACLES THAT MATCH CORD AND CAP PROVIDED WITH EQUIPMENT, UON. USE

ADJACENT NEMA CONFIGURATION NUMBER, IF ONE IS SHOWN.

N. PER ARTICLE 110.26 IN THE APPLICABLE VERSION OF CEC, PROVIDE CODE REQUIRED WORKING AND DEDICATED EQUIPMENT SPACE FOR ALL ELECTRICAL EQUIPMENT. CONTRACTOR TO VERIFY ADEQUATE SPACING PRIOR TO ROUGH-IN AND INSTALLATION. NOTIFY STATE REPRESENTATIVE OF ANY CONFLICTS.

O. ALL EXTERIOR MOUNTED EQUIPMENT AND CONDUIT SHALL BE WEATHERPROOF WITH A MINIMUM RATING OF NEMA 3R.

P. A PULL ROPE SHALL BE INSTALLED IN ALL NEW RACEWAYS AND IN EXISTING RACEWAYS WHENEVER NEW CABLE IS PULLED AND/OR EXISTING CABLE IS REMOVED.

Q. ROUTE ALL CONDUITS UP THROUGH EQUIPMENT CURBS. COORDINATE LOCATION TO AVOID CONFLICTS AND ALLOW FOR CODE CLEARANCES AND MAINTENANCE ACCESS.

R. LUMINAIRES WITH "EM" ADJACENT TO IT INDICATES A REQUIRED CONNECTION TO AN UNSWITCHED HOT CONDUCTOR UON.

S. EXTERIOR MOUNTED RECEPTACLES SHALL BE WEATHERPROOF, GFI PROTECTED, AND EMPLOY A WEATHERPROOF "WHILE IN USE" COVER PER APPLICABLE VERSION OF CEC.

T. WHEN MORE THAN ONE DECORA STYLE LIGHTING CONTROL IS SHOWN IMMEDIATELY ADJACENT TO OTHER DECORA STYLE LIGHTING CONTROLS, ON THE SAME SECTION OF WALL, THEY SHALL BE INSTALLED WITHIN A MULTI-GANG BOX WITH A MULTI-GANG WALLPLATE CORRESPONDING TO THE NUMBER OF DEVICES. MULTIPLE BOXES AND 1-GANG WALLPLATES ARE NOT ACCEPTABLE UON.

FIRE ALARM SYSTEM

DESCRIPTIONSYMBOL

EOLR

HP

LP

MR

MM

F

CO

CO

REFERENCE SYMBOLS

DESCRIPTIONSYMBOL

SYMBOL DESCRIPTION

WIRING

SHEET KEYNOTE REFERENCE

REFER TO DETAIL NO. ON DRAWING INDICATED NOT ALL

DETAIL REFERENCES ARE SHOWN. ALL DETAILS APPLY TO

ALL APPLICABLE SITUATIONS, UON

MECHANICAL EQUIPMENT IDENTIFICATION TAG

ELECTRICAL SWITCHES: CONTROLS AND SWITCHES INTENDED TO BE USED BY

THE OCCUPANT OF A ROOM OR AREA TO CONTROL LIGHTING AND RECEPTACLE

OUTLETS, APPLIANCES OR COOLING, HEATING AND VENTILATING EQUIPMENT,

SHALL COMPLY WITH APPLICABLE VERSION OF CBC SECTION 11B-308 EXCEPT

THE LOW REACH (15" MIN) SHALL BE MEASURED TO THE BOTTOM OF THE

OUTLET BOX AND THE HIGH REACH (48" MAX) SHALL BE MEASURED TO THE

TOP OF THE OUTLET BOX.

ELECTRICAL RECEPTACLE OUTLETS: ELECTRICAL RECEPTACLE OUTLETS ON

BRANCH CIRCUITS OF 30 AMPERES OR LESS AND COMMUNICATION SYSTEM

RECEPTACLES SHALL COMPLY WITH APPLICABLE VERSION OF CBC SECTION

11B-308 EXCEPT THE LOW REACH SHALL BE MEASURED TO THE BOTTOM OF

THE OUTLET BOX AND THE HIGH REACH SHALL BE MEASURED TO THE TOP OF

THE OUTLET BOX.

FORWARD REACH: WHERE A FORWARD REACH IS UNOBSTRUCTED, THE HIGH

FORWARD REACH SHALL BE 48 INCHES MAXIMUM AND THE LOW FORWARD

REACH SHALL BE 15 INCHES MINIMUM ABOVE THE FINISH FLOOR OR GROUND.

OVERCURRENT DEVICES: SHALL BE READILY ACCESSIBLE AND SHALL BE

INSTALLED SO THAT THE CENTER OF THE GRIP OF THE OPERATING HANDLE OF

THE SWITCH OR CIRCUIT BREAKER, WHEN IN ITS HIGHEST POSITION, IS NOT

MORE THAN 6 FEET AND 7 INCHES ABOVE THE FLOOR OR WORKING PLATFORM.

70AF

100AS

3P

FUSED DISCONNECT, WITH FUSE SIZE (AF), SWITCH

AMPERE RATING (AS), AND NUMBER OF POLES (#P)

TRANSFORMER WITH GROUNDED NEUTRAL

ELECTRICAL DEVICES

REACH RANGES GUIDELINES

FIRE ALARM CONTROL PANEL

HORN/STROBE (CEILING MOUNTED, CANDELA = 15)

FIRE SPRINKLER LOW PRESSURE (DRY SYSTEMS ONLY)

FIRE SPRINKLER HIGH PRESSURE (DRY SYSTEMS ONLY)

RELAY MODULE

MONITOR MODULE

END OF LINE RESISTOR

MANUAL FIRE ALARM PULL BOX

STROBE ONLY (WALL MOUNTED, CANDELA = 15)

HORN/STROBE (WALL MOUNTED, CANDELA = 15)

HORN ONLY (WALL MOUNTED)

MULTI-CRITERIA DETECTOR (SMOKE,CO,LIGHT/FLAME,HEAT)

OUTDOOR WATERFLOW HORN/STROBE

OUTDOOR FIRE SPRINKLER ALARM BELL

DUCT SMOKE…