About this file

This is a One-Line Diagram for the University of New Hampshire's Combined Heat & Power Plant Equipment Replacement project, prepared at 60% design progress for review. The diagram illustrates the electrical integration of three 276kW induction generator units (MST275) operating at 480V, 3-phase, 60Hz, each connected through their respective control and breaker panels to a master intertie panelboard rated at 1200A and 65KAIC. The system includes a 1000 KVA transformer stepping down from 4160GY/2400V to 480Y/277V, a utility meter connection via Eversource, and a 155KW/194KVA Caterpillar standby diesel generator. The electrical distribution incorporates multiple switchboards and panelboards supplying various facility loads including condenser control systems, forced draft fans, boiler feed pumps, and building air conditioning units. Key infrastructure components include new and existing conduit runs (3" and 4" RMC), copper conductors ranging from #2 AWG to #750 KCMIL, and comprehensive grounding systems utilizing bare copper conductors, grounding rods, and building steel connections.

The design specifies extensive modifications to existing electrical infrastructure, including replacement of existing fuses with 1200A current limiting fuses, testing and potential replacement of existing phase conductors, installation of parallel conductor runs with bonding jumpers between transformer secondary lugs and the disconnect switch, and addition of a new 4" RMC conduit in parallel with existing conduits. New construction scope includes a generator service feeder, replacement of existing current transformers, a new generator interconnection panelboard rated at 800A across multiple sections, and a condenser control VFD panel with variable frequency drives serving three separate condenser units. All equipment identifiers and specifications are noted as requiring field verification by the electrical contractor prior to construction, with the document originating from existing customer documentation, utility information, and site investigation data. The project is located at the University of New Hampshire, Durham, NH, and is designated as drawing E003 with a project number T10953.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

52G1 500A

35KAIC

500:5

500:5

PM

4:1

T/C

T/C

42G1 500A

UNIT 1

276kW, 0.9PF

480V, 3PH, 60HZ

385FLA, 3565RPM

SEL-700G

UNIT CONTROL &

BREAKER PANEL

(52G1/UCP1)

PNLB1-52G1

(2) 3" EMT

(6) #250 AWG CU

(2) #2 AWG CU

CB1

600AF

500AT

LSI

DIRECTION OF

POWER FLOW

MST INTERTIE PANELBOARD - "PNLB-MST"

480Y/277VAC, 3PH, 4W, 60HZ

1200A, 65KAIC

NEMA 3R, UL67

52G2 500A

35KAIC

500:5

500:5

PM

4:1

T/C

T/C

42G2 500A

UNIT 2

276kW, 0.9PF

480V, 3PH, 60HZ

385FLA, 3565RPM

SEL-700G

UNIT CONTROL &

BREAKER PANEL

(52G2/UCP2)

PNLB2-52G2

(2) 3" EMT

(6) #250 AWG CU

(2) #2 AWG CU

CB2

600AF

500AT

LSI

52G3 500A

35KAIC

500:5

500:5

PM

4:1

T/C

T/C

42G3 500A

UNIT 3

276kW, 0.9PF

480V, 3PH, 60HZ

385FLA, 3565RPM

SEL-700G

UNIT CONTROL &

BREAKER PANEL

(52G3/UCP3)

PNLB3-52G3

(2) 3" EMT

(6) #250 AWG CU

(2) #2 AWG CU

CB3

600AF

500AT

LSI

HEATPLANT XFMR - "T-HP"

4160GY/2400:480Y/277V

65°C, 3PH, 60HZ

1000 KVA

5.7% Z, KNAN

**TO BE FIELD VERIFIED

15KV, MV-90

SECTION 1

800A

DS_MST-PNLB_MST

(**3) 4" RMC

**(QTY 2) EXISTING

(9) #600 KCMIL XHHW CU

(3) #2/0 AWG XHHW CU SSBJ

FERRAZ SHAWMUT

AMPTRAP #A4BY1200

1200A, 600VAC, 200KAIC

CLASS L

BPST DISCONNECT SW - "DS-ST"

SQD #H368NR

1200A RATED, 600VAC, 200KAIC

3PH, 3W, 60HZ

GROUND KIT INCLUDED

NEMA 3R

PRCLF

15KV, 165A

PM

(2) PT

480:120

(2) CT

1200:5

TO UNH SUB 1 VISTA

SWITCH VIA E.

ELECTRICAL YARD

SECTOR CAB

T_HP-DS_ST

(3) 4" RMC

(9) #750 KCMIL CU RHW

(3) #2/0 AWG CU SSBJ

(2) 4" RMC

(6) #600 KCMIL CU THHN

UTILITY METER

CLOSE COUPLED

EVERSOURCE

#78585046

TS-01

TRANSFER SWITCH

480VAC, 3PH, 3W, 60HZ

400A

GEN-01

STANDBY DIESEL GENSET

CATERPILLAR #SR-4

480/240VAC, 3PH, 60HZ

1800 RPM, 155KW/194KVA, 0.8PF

GG

GE #THPR3608G3T

MAIN DISC. SW.

600V, 3PH, 3W, 60HZ

800A, 200KAIC

60A

225A

60A

200A

400A 400A

100A

30A

30A

30A

60A 60A

SECTION 2

800A

SECTION 3

800A

CIRCUITS

CIRC PUMP #5

WELD PLUG

SCULP LAB

WOOD SHOP

TS SW (NRML PWR)

CIRC PUMP #1

CIRCUITS

HACKSAW

#2 BOILER FD PMP

FRCD DRAFT FAN #3

#2 LATHES MILL

TRK UNLD OIL PMP #1

PANEL P-DP-X

QUINCY #1

PB1 BLDG AC

PB2 BLDG AC

100A 60A

100A 100A

HEAT PLANT SWBD

GE AV-LINE

480VAC

3PH, 3W, 60HZ 800A

200KAIC

SECTION 4

400A

200A

40A

200A

60A

100A 100A

CIRCUITS

75KVA LV-TX

PANEL PP

QUINCY #2

FRCD DRAFT FAN #1

FRCD DRAFT FAN #2

EM FEED PUMP

NORMAL PWR

FROM SECTION 2

CRKT #7

N E

CB0

1200AF

1200AT

LSIG

CB4

250AF

250AT

LSI

20' MIN

UFFER

#6 AWG BARE CU

COLD WATER PIPE

10' MIN IN CONTACT W/EARTH

GROUNDING RODS

DRIVEN 8' MIN

BUILDING STEEL

10' MIN IN CONTACT W/EARTH

#3/0 AWG BARE CU

GAS LINE

GROUND BUS

#3/0 AWG BARE CU

#3/0 AWG BARE CU

#4AWG BARE CU

PNLB4-CDP1

(1) 3" EMT

(3) #250 AWG CU

(1) #2 AWG CU

VFD1 VFD2 VFD3

CONDENSER 1

CONTROL PANEL

BY THERMOFIN

QTY 8 - 3HP, 480VAC

CONDENSER 2

CONTROL PANEL

BY THERMOFIN

QTY 8 - 3HP, 480VAC

CONDENSER 3

CONTROL PANEL

BY THERMOFIN

QTY 8 - 3HP, 480VAC

VFD1-CCP1

(1) 2" EMT

(1) 4C #6 AWG

VFD CABLE

VFD2-CCP2

(1) 2" EMT

(1) 4C #6 AWG

VFD CABLE

VFD3-CCP3

(1) 2" EMT

(1) 4C #6 AWG

VFD CABLE

AIR COOLED CONDENSER

VFD PANEL - "CDP-01"

APPROXIMATE

GEO LOCATION:

43°8'12.05"N 70°56'10.09"W

APPROVED BY:

CHECKED BY:

CAD FILE:

DRAWN BY:

PROJECT NUMBER:

DESIGNED BY:

THIS DOCUMENT, AND THE ASSOCIATED DESIGNS, IS AN

INSTRUMENT OF SERVICES FOR THIS PROJECT AND SHALL

NOT BE USED FOR ANY OTHER PURPOSE WITHOUT

WRITTEN AUTHORIZATION FROM NLINE ENERGY, INC.

IF NOT ONE INCH ON THIS SHEET, ADJUST

SCALES ACCORDINGLY

BAR IS ONE INCH ON ORIGINAL DRAWING

DRAWING NO.SHEET SIZE

D

REVISIONS

DRAWING STATUS

STAMP

VERIFY SCALES

PROJECT

SHEET TITLE

PROJECT DATE:

PROJECT OWNER:

DESCRIPTIONNO. DATE BY

0 1"

PROJECT NAME:

ONELINE DIAGRAM - PROJECT

INTEGRATION

60% DESIGN - PROGRESS REVIEWKH05.28.25A

T10953 E002 - ONELINE - INTERCONNECTIONL.dwg

02/27/25

KMH

KMH

E003

FOR REVIEW

T10953 - UNH

(QTY 3) MST275 INDUCTION

UNIV. OF NEW HAMPSHIRE

22 COLOVOS RD

DURHAM, NH 03824-3515

Scale: NTS

ONELINE DIAGRAM - PROJECT INTEGRATION 1

KEYED NOTES:

1. TRANSPARENT OBJECTS AND THOSE DENOTED "(E)" ARE EXISTING.

2. THIS DIAGRAM IS CREATED FROM EXISTING DOCUMENTATION PROVIDED BY THE

CUSTOMER, THE UTILITY AND SITE INVESTIGATION DATA. EQUIPMENT IDENTIFIERS

AND DETAILED SPECIFICATIONS FOR EXISTING EQUIPMENT MAY NOT BE FULLY

ACCURATE COLLOQUIAL IDENTIFIERS FOR THE PURPOSES OF THIS PROJECT.

3. DETAILED SPECIFICATIONS FOR EQUIPMENT IMPACTED OR APART OF NEW

CONSTRUCTION SCOPE ARE TO BE FIELD VERIFIED BY THE ELECTRICAL CONTRACTOR

(EC) PRIOR TO CONSTRUCTION EFFORTS.

GENERAL NOTES:

EXISTING FUSED DISCONNECT SWITCH TO REMAIN. EXISTING FUSE TO BE

REPLACED WITH 1200A CURRENT LIMITING FUSE.

EXISTING PHASE CONDUCTORS (2 PER PHASE, #750KCMIL) TO BE TESTED (INSULATION

RESISTANCE) AND MAINTAINED IF PASSING. ADDITION PARALLEL RUN (1 PER PHASE,

#750KCMIL) AND SUPPLY SIDE BONDING JUMPERS (QTY 3, #2/0 AWG) TO BE PROVIDED

AND INSTALLED BETWEEN T-HP SECONDARY LUGS AND DS-ST.

NEW GENERATOR SERVICE FEEDER, "DS_MST-PNLB_MST":

1. TWO (2) EXISTING 4" RMC TO BE RE-USED.

2. EXISTING DECOMMISSIONED CONDUCTORS TO BE REMOVED.

3. PROVIDE AND INSTALL ONE (1) NEW 4" RMC INSTALLED IN

PARALLEL WITH EXISTING CONDUITS.

4. PROVIDE AND INSTALL ALL NEW PHASE CONDUCTORS AS

SPECIFIED.

4 EXISTING CT'S TO BE REPLACED.

5 NEW GENERATOR INTERCONNECTION PANELBOARD.

E004

E005

E006

6 NEW CONDENSER CONTROL VFD PANEL.

E007

AutoCAD SHX Text

FROM: 11G 86G PLC

AutoCAD SHX Text

FROM: 86G PLC

AutoCAD SHX Text

FROM: 11G 86G PLC

AutoCAD SHX Text

FROM: 86G PLC

AutoCAD SHX Text

FROM: 11G 86G PLC

AutoCAD SHX Text

FROM: 86G PLC

AutoCAD SHX Text

FROM: CONDENSER CONTROL RELAY

AutoCAD SHX Text

CB1 60A

AutoCAD SHX Text

FROM: CONDENSER CONTROL RELAY

AutoCAD SHX Text

CB2 60A

AutoCAD SHX Text

FROM: CONDENSER CONTROL RELAY

AutoCAD SHX Text

CB2 60A

AutoCAD SHX Text

PDB - 600V, 250A

AutoCAD SHX Text WAYLON BOWERS No. 17710

Mark Schow Cloud

Mark Schow Callout POTENTIAL SCOPE OF REPLACEMENT FOR ELECTRICAL TRANSFORMERS, GENERATORS, AND SWITCHBOARD

File details come from the government source that posted it. Updated .