General Asbestos Survey for Asbestos-Containing Materials
Prepared for:
Marshall Space Flight Center, AL
Building 4765 Marshall Space Flight Center
GSE - 017
May 31, 2009
Prepared by
Great Southern Engineering, Inc.
3795 Gordon Terry Parkway
Trinity, Alabama 35673
TABLE OF CONTENTS
1. Introduction
2. Summary
2.1. Suspect ACMs
2.2. Recommendations
3. Survey Scope
4. Limitations
5. Survey and Sample Collection Procedure
6. Previous Survey / Plans Review
7. Suspect ACM Materials Not Sampled
8. Survey Sampling Results
9. Appendices
Task Order GSE 017 Page 1 of 20
GENERAL ASBESTOS SURVEY OF
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
1. Introduction
In accordance with GSE Task Order No.GSE-017 dated August 15, 2008, Great Southern Engineering, Inc. (GSE) has performed an asbestos survey of Building 4765 located at George C.
Marshall Space Flight Center, Marshall Space Flight Center, Alabama. The 6,650 square feet building was identified to have been originally constructed in 1995. A total of 24 samples were collected from the building.
The objective of the Asbestos Survey is to determine the location and quantity of asbestos-containing materials at the Property building.
GSE’s Scope of Work included:
Visual inspection and identification of suspect asbestos-containing materials (ACMs) in the Property building and collected a representative number of samples for analysis.
As part of this asbestos survey, GSE personnel collected samples of all suspect friable and suspect damaged non-friable building materials at the Property. The remaining suspect non-friable materials were not be sampled as part of this asbestos survey
Estimated quantities and locations of ACM.
Assessed the condition of the ACM identified.
Assigned a hazard rating to each type of ACM.
This report has been prepared for the use of George C. Marshall Space Flight Center. Our investigation was performed using the degree of care and skill ordinarily exercised under similar circumstances by professional consultants practicing in this or similar localities. No other warranty or guarantee, expressed or implied, is made as to the conclusions included in this report.
Task Order GSE 017 Page 2 of 20
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
The GSE, Inc. did not perform destructive sampling procedures at the site; therefore, regardless of the thoroughness of this survey, it is possible that suspected asbestos-containing materials (ACMs) might exist in the building beneath the floors, behind walls, within pipe chases, or in other inaccessible locations. If, during renovation or demolition activities, materials not addressed in this survey are discovered, these materials should be sampled and analyzed for asbestos content prior to disturbance.
Surveyed by:
John A Jackson
University of Alabama Safe State Program Accredited Inspector
Accreditation #AIN0908531941
Written by:
Manju Ramasamudra
University of Alabama Safe State Program Accredited Inspector/Management Planner
Accreditation #APL0308R5089
Task Order GSE 017 Page 3 of 20
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
2. Summary
GSE performed an Asbestos Survey and Hazard Assessment at Building 4765 in Marshall Space Flight Center, Alabama on April 14, 2009. Sample collection was completed by licensed personnel – John A Jackson. The following report summarizes the independent conclusions representing GSE’ best professional judgment based on information and data available to us during the course of this survey. Factual information regarding operations, conditions, and tests data provided by the client, owner or their representative has been assumed to be correct and complete.
Additionally, the conclusions presented are based on the conditions that existed on the date(s) of the assessment.
The 6,650 square feet building was identified to have been originally constructed in 1995. A total of 24 samples were collected from the building.
No homogeneous materials were identified as asbestos-containing materials.
Task Order GSE 017 Page 4 of 20
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
2.1. Suspect ACMs
The following information is included for informational purposes:
A. The following suspect asbestos-containing materials were not sampled as part of this scope of work:
Suspect fibrous electrical cable covering (danger of electrocution) were not sampled.
These materials are not subject to regulation under NESHAP for demolition and renovation as long as they are in good condition and are not subject to sanding, grinding, cutting, or abrading.
Since ordinary demolition activities do not include sanding, grinding, cutting, and abrading, these materials may remain in place during building demolition, as long as they remain in good condition and are not friable.
If the material is in poor condition and is friable at the time of demolition or renovation, or if it will be subjected to sanding, grinding, cutting, or abrading, it should first be removed by a licensed asbestos removal contractor and disposed of as asbestos-containing waste.
When removing asphalt-roofing products, the material should be removed using a method that does not subject the material to sanding, cutting, grinding, or abrading (hand tools).
Asbestos-containing roofing may be disposed of as construction debris.
2.2. Recommendations
The following additional actions are recommended:
No further actions are recommended at this time.
Task Order GSE 017 Page 5 of 20
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
3. Survey Scope
This survey was conducted for the purpose of identifying asbestos-containing materials (ACM) throughout the building and to conduct a hazard assessment on existing ACM. The survey was non-destructive in nature and limited only to those areas that were readily accessible.
Specific areas to which access was limited by occupant request, unavailability of keys, or by site conditions included the following:
Behind the walls
Beneath the floors
Any suspect ACM not sampled as part of the assessment and if any additional suspect materials were to be identified behind walls and beneath the floors should be sampled prior to repair, renovation, or demolition activities.
Task Order GSE 017 Page 6 of 20
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
4. Limitations
GSE did not attempt to disassemble mechanical equipment, open pipe chases or assess materials within wall voids. Regardless of the thoroughness of a survey, the possibility exists that some areas containing asbestos were not identified, inaccessible or different from those at specific locations. The findings and opinions presented are relative to the dates of our site work and should not be relied upon to represent conditions at substantially later dates due to changes in the condition ACM may change over time, renovations and repairs.
This report is for the exclusive use of the client and its agents and use by any unauthorized parties in whole or in part, except as directed by legal jurisdiction, is at the sole risk of the user.
If this assessment includes reliance on work products and/or documents prepared by others, GSE has no responsibility for the accuracy of information contained therein.
Although this assessment has attempted to identify the presence or absence of ACM, potential sources of ACM may have escaped detection due to: (1) the scope of this assessment, (2) the inaccuracy of records, interviews, work products or documents made available to GSE for this report, (3) the presence of undetected or unreported renovations and repairs, (4) inaccessible areas, and/or (5) deliberate concealment of detrimental information.
Estimates presented in this report are based upon observations during the survey and owner-provided information. These reasonable estimates may be affected by unanticipated conditions potentially present in inaccessible or un-surveyed areas. GSE does not warrant or guarantee the quantity estimates. The use of such estimates shall be at the user's own risk and shall constitute a release and agreement to defend and indemnify GSE from and against any liability. If questions arise during the planning for renovation, demolition, or other construction activities, GSE should be notified to permit review of the data and present recommendations.
Interior of the following rooms were inaccessible during our Asbestos Survey on April 14, 2009: None.
Task Order GSE 017 Page 7 of 20
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
5. Survey and Sample Collection Procedure
Based on United States Environmental Protection Agency (USEPA) guidance documents, GSE considered all material applications identified during the visual assessment were suspect ACM and sampled as described below.
Bulk samples were collected of any materials, which were suspected of containing asbestos with the exception of fire doors. Fire doors were not sampled because the damage caused by sampling would render these materials friable and may also void the fire rating. Since these materials were not sampled, they should be assumed to be asbestos containing, unless sampled and proven otherwise. Sampling of these assumed ACMs should be performed prior to any renovation or other activity that may cause a material disturbance.
Samples of the remaining suspect ACM were taken in accordance with USEPA recommendations.
The number and location of samples collected was based on the type of material, the manner of application, and the homogeneity of the ACM (similarity of color, texture, and type). Each sample was collected and placed into an individual sample container. The sample location was noted on the field survey form and assigned an individual identification number. This number was affixed to the sample container as the sample was collected. The survey form was also used to note the material type and general condition of the material. During the inspection, each suspect material's accessibility, location, and friability were recorded. This information was used to assess the potential hazard of the ACM and to prioritize response action recommendations.
The USEPA defines asbestos-containing materials (ACM) as those that contain greater than one percent asbestos. Friable materials are defined as those that can be crumbled or reduced to powder by hand pressure.
GSE utilized the “positive-stop” method of sample analysis. In this method, analysis is stopped on a group of samples once the first positive (e.g., greater than 1% asbestos) sample is analyzed.
According to the USEPA, if one sample of a homogenous material is identified to be asbestos containing, the entire material must be considered asbestos containing. By using the positive-stop method, GSE reduces the Client’s laboratory analysis cost by not analyzing the additional samples.
Samples collected were carried and submitted under Chain-of-Custody to Steve Moody Micro Services LLC, Farmers Branch, Texas for analysis of asbestos using USEPA Method 40 CFR, Chapter 1, Part 763, Subpart F, Appendix A, also known as Polarized Light Microscopy (PLM).
Steve Moody Micro Services LLC is certified by the National Voluntary Laboratory Accreditation Program (NVLAP) and licensed by the Department of State Health Services.
Task Order GSE 017 Page 8 of 20
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
6. Previous Survey / Plans Review
GSE was not provided with any previously conducted asbestos surveys of the Property. As-built/renovation-site plans and construction drawings were reviewed at the Facilities Department Drawing Room. Review of these documents did not identify building material specifications requiring the use of ACM. However, this does not preclude or prevent the potential use of ACM.
Task Order GSE 017 Page 9 of 20
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
7. Suspect ACM Materials Not Sampled
During the course of the property visit, GSE performed a preliminary review of interior, accessible areas of the subject building for the presence of suspect asbestos-containing materials (ACMs). This asbestos survey was conducted for overview purposes only; additional suspect materials may exist in concealed locations (behind walls and above ceilings, beneath the floors, within machinery, etc.). Also, not all suspect materials may have been sampled due to the condition or the location of the suspect materials. Destructive sampling of suspect ACMs was not performed. GSE will not be responsible for damaging materials or causing the materials to become friable. The USEPA defines asbestos-containing material as material containing greater than one percent asbestos. This review was not a pre-demolition/renovation survey or for regulatory submittal purposes.
Suspect and/or presumed ACMs were observed within the subject building during the property visit. These suspect and/or presumed ACMs that were not sampled as part of this asbestos survey are listed in the following table.
Sample Description Physical Condition
Friable Yes/No
Type of
ACM
Sample ID
4765Building Number
Caulking, On Exterior Wall Joints UPS4 NoM
Wiring, Fibrous Electrical Cable Covering UPS6 NoM
Mastic, Mirror Mastic UPS8 NoM
Leveling Compound, Below ceramic tile flooring UPS13 NoM
Task Order GSE 017 Page 10 of 20
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
8. Survey Sampling Results
The results of the Survey are presented in the tables on the following pages. The tables describe the entire suspect Asbestos-Containing Materials (ACMs) identified in the building and list respective sample numbers and laboratory results. Sample numbers presented in the tables correspond to the sample numbers on attached Laboratory Analysis Forms. Also presented in the tables is the estimated quantity and assessed friability for each suspect ACM. For each suspect material identified as ACM, the assessed hazard potential is presented along with GSE’ recommended response action. Hazard potential for each material application is based on the material condition and accessibility to the public and maintenance personnel.
Glossary of Items for the following Table
Type of Asbestos (1) CH = Chrysotile AM = Amosite CR = Crocidolite AN = Anthophyllite TR = Tremolite AC = Actinolite ND = No Asbestos Detected PC = Point Count Method
Type of ACM (2) M = Miscellaneous S = Surfacing TSI = Thermal Systems Insulation
Friability (3) F = Friable NF = Non Friable
Physical Condition (4) U = Good D = Damaged SD = Significantly Damaged
Potential for Disturbance (5) NPD = No Potential for Disturbance PD = Potential for Disturbance PSD = Potential for Significant Disturbance
Assessment Category (6) 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM 3 = Significantly damaged friable surfacing ACBM 4 = Damaged or significantly damaged friable miscellaneous ACBM 5 = ACBM with potential for damaged 6 = ACBM potential for significant damage 7 = Any remaining friable ACBM or friable suspected
ACBM
X = not applicable
Unit of Measurement SF = Square Feet
LF = Linear Feet
Sample Description
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4765Building Number
Homogeneous Area 1
Pipe Insulation with White Mastic
Yes TSI No U XRoom: 109 Grid: C2-2
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
1 PD
Yes TSI No U XRoom: 109 Grid: C3-2
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
2 PD
Yes TSI No U XRoom: 109 Grid: WF3-3
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
3 PD
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4765Building Number
Homogeneous Area 2
HVAC Duct Insulation with White Mastic
Yes TSI No U XRoom: 109 Grid: F1-1
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
4 PD
Yes TSI No U XRoom: 109 Grid: F2-3
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
5 PD
Yes TSI No U XRoom: 109 Grid: F1-3
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
6 PD
Homogeneous Area 3
2' X 2' Ceiling Tile with Random Dots
Yes M Yes U XRoom: 105 Grid: C3-1
ND - Acoustic Tile7 PD
Yes M Yes U XRoom: 106 Grid: C4-1
ND - Acoustic Tile8 PD
Yes M Yes U XRoom: 107 Grid: C1-1
ND - Acoustic Tile9 PD
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4765Building Number
Homogeneous Area 4
Wallboard System with Associated Joint Compound
Yes M No U XRoom: 101C Grid: WL3-2
ND - Drywall Material ND - Joint Compound
10 PD
Yes M No U XRoom: 101A Grid: WE1-3
ND - Joint Compound
11 PD
Yes M No U XRoom: 101A Grid: WE1-2
ND - Drywall Material ND - Joint Compound
12 PD
Homogeneous Area 5
Sealant Red on Wall Yes M No U XRoom: 101B Grid: WR2-2
ND - Sealant13 PD
Yes M No U XRoom: 101B Grid: WL2-2
ND - Sealant14 PD
Yes M No U XRoom: 101B Grid: WL2-2
ND - Sealant15 PD
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4765Building Number
Homogeneous Area 6
Caulking Around Doors and Wall Panels
Yes M No U XRoom: 101 Grid: WR2-1
ND - Caulking16 PD
Yes M No U XRoom: 101 Grid: WL2-2
ND - Caulking17 PD
Yes M No U XRoom: 101 Grid: WL2-3
ND - Caulking18 PD
Homogeneous Area 7
Mastic Gray Mastic on HVAC Ducts
Yes M No U XRoom: 105 Grid: C2-4
ND - Gray Mastic19 PD
Yes M No U XRoom: 106 Grid: C2-3
ND - Gray Mastic20 PD
Yes M No U XRoom: 108 Grid: C3-4
ND - Gray Mastic21 PD
Sample Location
Sample Analyzed
Yes/No
Estimated Quantity of
ACM
Assessment Category
Physical Condition
Friable Yes/No
Type of
ACM
% and Type of Asbestos Detected
Sample ID Potential For
Distrubance
4765Building Number
Homogeneous Area 8
Insulation Tank insulation - End
Yes TSI No U XRoom: 109 Grid: F3-3
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
22 PD
Insulation Tank insulation - Side
Yes TSI No U XRoom: 109 Grid: F3-3
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
23 PD
Insulation Tank insulation - End
Yes TSI No U XRoom: 109 Grid: F3-2
ND - Insulation ND - Paper/ Foil Wrap ND - White Mastic
24 PD
1. CH = Chrysotile; AM = Amosite; CR = Crocidolite; AN = Anthophyllite; TR = Tremolite; AC = Actinolite; ND = No Asbestos Detected; or PC = Point Count Method
2. M = Miscellaneous; S = Surfacing; or TSI = Thermal Systems Insulation
3. F = Friable or NF = Non Friable
4. U = Good; D = Damaged; or SD = Significantly Damaged
5. NPD = No Potential for Disturbance; PD = Potential for Disturbance; or PSD = Potential for Significant Disturbance
6. 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 = Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM potential for significant damage, 7 = Any remaining friable ACBM or friable suspected ACBM, or X = not applicable
SF = Square Feet LF = Linear Feet
9. Appendices
Appendix A— Laboratory Results and Chain of Custody Appendix B— ACM Sample Location Drawings Appendix C— ACM Location Diagrams Appendix D— Photographs Appendix E— Certificates and Licenses
Appendix A
Laboratory Results
PLM Summary Report NVLAP Lab No. 102056
TDSHS License No. 30-0084
Client :
Project :
Project # :
Identification :
Test Method :
Great Southern Engineering
MSFC, Building 4765
GSE-017
Asbestos, Bulk Sample Analysis
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 4/16/2009, twenty four (24) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS.
The PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Steve Moody Micro Services, LLC
Lab Job No. :
Report Date :
09B-04222
04/14/2009
04/17/2009
2051 Valley View Lane
Farmers Branch, TX 75234 (Phone 972-241-8460)
01 Mastic (White) on Pipe Insulation None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
02 Mastic (White) on Pipe Insulation None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
03 Mastic (White) on Pipe Insulation None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
04 Cover on HVAC Duct (White) None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
05 Cover on HVAC Duct (White) None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
06 Cover on HVAC Duct (White) None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
07 2' x 2' Ceiling Tile (Texture and Random Dots) None Detected - Acoustic Tile
08 2' x 2' Ceiling Tile (Texture and Random Dots) None Detected - Acoustic Tile
09 2' x 2' Ceiling Tile (Texture and Random Dots) None Detected - Acoustic Tile
10 Drywall System None Detected - Drywall Material
None Detected - Joint Compound
11 Drywall System None Detected - Joint Compound
12 Drywall System None Detected - Drywall Material
None Detected - Joint Compound
13 Sealant (Red) None Detected - Sealant
14 Sealant (Red) None Detected - Sealant
PLM Summary Report NVLAP Lab No. 102056
TDSHS License No. 30-0084
Client :
Project :
Project # :
Identification :
Test Method :
Great Southern Engineering
MSFC, Building 4765
GSE-017
Asbestos, Bulk Sample Analysis
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 4/16/2009, twenty four (24) bulk material samples were submitted by John Jackson of Great Southern Engineering for asbestos analysis by PLM/DS.
The PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Steve Moody Micro Services, LLC
Lab Job No. :
Report Date :
09B-04222
04/14/2009
04/17/2009
2051 Valley View Lane
Farmers Branch, TX 75234 (Phone 972-241-8460)
15 Sealant (Red) None Detected - Sealant
16 Caulking (Gray) around Doors and wall Panels None Detected - Caulking
17 Caulking (Gray) around Doors and wall Panels None Detected - Caulking
18 Caulking (Gray) around Doors and wall Panels None Detected - Caulking
19 Mastic (Gray) on Ducts None Detected - Grey Mastic
20 Mastic (Gray) on Ducts None Detected - Grey Mastic
21 Mastic (Gray) on Ducts None Detected - Grey Mastic
22 Tank Insulation None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
23 Tank Insulation None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
24 Tank Insulation None Detected - Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
Heather DeinesAnalyst(s):
Lab Director : Steve Moody Approved Signatory :
Thank you for choosing Steve Moody Micro Services
These samples were analyzed by layers. Quantification, unless otherwise noted, is performed by calibrated visual estimate. Results may not be reproduced except in full. This test report relates only to the samples tested. These test results do not imply endorsement by NVLAP or any agency of the U.S. Government. Accredited by the
National Voluntary Laboratory Accreditation Program for Bulk Asbestos Fiber Analysis under Lab Code 102056.
Lab Manager : Bruce Crabb Approved Signatory :
Steve Moody Micro Services, LLC PLM Detail Report NVLAP Lab No. 102056
TDSHS License No. 30-0084
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4765
Lab Job No. :
Report Date :
09B-04222
04/17/2009
Mineral Wool Fibers01 Insulation (Yellow) 85% 04/1795% HD
Resin Binders01 Insulation (Yellow) 85% 04/175% HD
Cellulose Fibers01 Paper / Foil Wrap (White / Silver) 10% 04/1750% HD
Glass Wool Fibers01 Paper / Foil Wrap (White / Silver) 10% 04/1720% HD
Metal Foil01 Paper / Foil Wrap (White / Silver) 10% 04/1730% HD
Cellulose Fibers01 White Mastic (White) 5% 04/175% HD
Pigment / Binders01 White Mastic (White) 5% 04/1795% HD
Mineral Wool Fibers02 Insulation (Yellow) 85% 04/1795% HD
Resin Binders02 Insulation (Yellow) 85% 04/175% HD
Cellulose Fibers02 Paper / Foil Wrap (White / Silver) 10% 04/1750% HD
Glass Wool Fibers02 Paper / Foil Wrap (White / Silver) 10% 04/1720% HD
Metal Foil02 Paper / Foil Wrap (White / Silver) 10% 04/1730% HD
Cellulose Fibers02 White Mastic (White) 5% 04/175% HD
Pigment / Binders02 White Mastic (White) 5% 04/1795% HD
Mineral Wool Fibers03 Insulation (Yellow) 85% 04/1795% HD
Resin Binders03 Insulation (Yellow) 85% 04/175% HD
Cellulose Fibers03 Paper / Foil Wrap (White / Silver) 10% 04/1750% HD
Glass Wool Fibers03 Paper / Foil Wrap (White / Silver) 10% 04/1720% HD
Metal Foil03 Paper / Foil Wrap (White / Silver) 10% 04/1730% HD
Cellulose Fibers03 White Mastic (White) 5% 04/175% HD
Pigment / Binders03 White Mastic (White) 5% 04/1795% HD
Mineral Wool Fibers04 Insulation (Yellow) 85% 04/1795% HD
Resin Binders04 Insulation (Yellow) 85% 04/175% HD
Cellulose Fibers04 Paper / Foil Wrap (Tan / Silver) 10% 04/1760% HD
Glass Wool Fibers04 Paper / Foil Wrap (Tan / Silver) 10% 04/1720% HD
Metal Foil04 Paper / Foil Wrap (Tan / Silver) 10% 04/1720% HD
Cellulose Fibers04 White Mastic (White) 5% 04/175% HD
Pigment / Binders04 White Mastic (White) 5% 04/1795% HD
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4765
Lab Job No. :
Report Date :
09B-04222
04/17/2009
Mineral Wool Fibers05 Insulation (Yellow) 85% 04/1795% HD
Resin Binders05 Insulation (Yellow) 85% 04/175% HD
Cellulose Fibers05 Paper / Foil Wrap (Tan / Silver) 10% 04/1760% HD
Glass Wool Fibers05 Paper / Foil Wrap (Tan / Silver) 10% 04/1720% HD
Metal Foil05 Paper / Foil Wrap (Tan / Silver) 10% 04/1720% HD
Cellulose Fibers05 White Mastic (White) 5% 04/175% HD
Pigment / Binders05 White Mastic (White) 5% 04/1795% HD
Mineral Wool Fibers06 Insulation (Yellow) 85% 04/1795% HD
Resin Binders06 Insulation (Yellow) 85% 04/175% HD
Cellulose Fibers06 Paper / Foil Wrap (Tan / Silver) 10% 04/1760% HD
Glass Wool Fibers06 Paper / Foil Wrap (Tan / Silver) 10% 04/1720% HD
Metal Foil06 Paper / Foil Wrap (Tan / Silver) 10% 04/1720% HD
Cellulose Fibers06 White Mastic (White) 5% 04/175% HD
Pigment / Binders06 White Mastic (White) 5% 04/1795% HD
Cellulose Fibers07 Acoustic Tile (Light Grey) 100% 04/1750% HD
Mineral Wool Fibers07 Acoustic Tile (Light Grey) 100% 04/1730% HD
Perlite07 Acoustic Tile (Light Grey) 100% 04/1720% HD
Cellulose Fibers08 Acoustic Tile (Light Grey) 100% 04/1750% HD
Mineral Wool Fibers08 Acoustic Tile (Light Grey) 100% 04/1730% HD
Perlite08 Acoustic Tile (Light Grey) 100% 04/1720% HD
Cellulose Fibers09 Acoustic Tile (Light Grey) 100% 04/1750% HD
Mineral Wool Fibers09 Acoustic Tile (Light Grey) 100% 04/1730% HD
Perlite09 Acoustic Tile (Light Grey) 100% 04/1720% HD
Glass Wool Fibers10 Drywall Material (White) 10% 04/172% HD
Cellulose Fibers10 Drywall Material (White) 10% 04/171% HD
Gypsum / Binders10 Drywall Material (White) 10% 04/1797% HD
Cellulose Fibers10 DW Paper Facing (Tan) 15% 04/17100% HD
Calcite / Talc / Binders10 Joint Compound (White) 75% 04/17100% HD
Calcite / Talc / Binders11 Joint Compound (White) 100% 04/17100% HD
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4765
Lab Job No. :
Report Date :
09B-04222
04/17/2009
Glass Wool Fibers12 Drywall Material (White) 10% 04/172% HD
Cellulose Fibers12 Drywall Material (White) 10% 04/171% HD
Gypsum / Binders12 Drywall Material (White) 10% 04/1797% HD
Cellulose Fibers12 DW Paper Facing (Tan) 15% 04/17100% HD
Calcite / Talc / Binders12 Joint Compound (White) 75% 04/17100% HD
Graphite13 Sealant (Red-Brown) 100% 04/1710% HD
Calcite / Binders13 Sealant (Red-Brown) 100% 04/1790% HD
Graphite14 Sealant (Red-Brown) 100% 04/1710% HD
Calcite / Binders14 Sealant (Red-Brown) 100% 04/1790% HD
Graphite15 Sealant (Red-Brown) 100% 04/1710% HD
Calcite / Binders15 Sealant (Red-Brown) 100% 04/1790% HD
Polyethylene Fibers16 Caulking (Grey) 100% 04/1710% HD
Calcite / Binders16 Caulking (Grey) 100% 04/1790% HD
Polyethylene Fibers17 Caulking (Grey) 100% 04/1710% HD
Calcite / Binders17 Caulking (Grey) 100% 04/1790% HD
Polyethylene Fibers18 Caulking (Grey) 100% 04/1710% HD
Calcite / Binders18 Caulking (Grey) 100% 04/1790% HD
Calcite19 Grey Mastic (Grey) 100% 04/1760% HD
Glue Binders19 Grey Mastic (Grey) 100% 04/1740% HD
Calcite20 Grey Mastic (Grey) 100% 04/1760% HD
Glue Binders20 Grey Mastic (Grey) 100% 04/1740% HD
Calcite21 Grey Mastic (Grey) 100% 04/1760% HD
Glue Binders21 Grey Mastic (Grey) 100% 04/1740% HD
Project # : GSE-017
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report 2051 Valley View Lane
Farmers Branch, TX 75234
Client :
Project :
Great Southern Engineering
MSFC, Building 4765
Lab Job No. :
Report Date :
09B-04222
04/17/2009
Mineral Wool Fibers22 Insulation (Yellow) 85% 04/1795% HD
Resin Binders22 Insulation (Yellow) 85% 04/175% HD
Cellulose Fibers22 Paper / Foil Wrap (White / Silver) 10% 04/1750% HD
Glass Wool Fibers22 Paper / Foil Wrap (White / Silver) 10% 04/1720% HD
Metal Foil22 Paper / Foil Wrap (White / Silver) 10% 04/1730% HD
Cellulose Fibers22 White Mastic (White) 5% 04/175% HD
Pigment / Binders22 White Mastic (White) 5% 04/1795% HD
Mineral Wool Fibers23 Insulation (Yellow) 85% 04/1795% HD
Resin Binders23 Insulation (Yellow) 85% 04/175% HD
Cellulose Fibers23 Paper / Foil Wrap (White / Silver) 10% 04/1750% HD
Glass Wool Fibers23 Paper / Foil Wrap (White / Silver) 10% 04/1720% HD
Metal Foil23 Paper / Foil Wrap (White / Silver) 10% 04/1730% HD
Cellulose Fibers23 White Mastic (White) 5% 04/175% HD
Pigment / Binders23 White Mastic (White) 5% 04/1795% HD
Mineral Wool Fibers24 Insulation (Yellow) 85% 04/1795% HD
Resin Binders24 Insulation (Yellow) 85% 04/175% HD
Cellulose Fibers24 Paper / Foil Wrap (White / Silver) 10% 04/1750% HD
Glass Wool Fibers24 Paper / Foil Wrap (White / Silver) 10% 04/1720% HD
Metal Foil24 Paper / Foil Wrap (White / Silver) 10% 04/1730% HD
Cellulose Fibers24 White Mastic (White) 5% 04/175% HD
Pigment / Binders24 White Mastic (White) 5% 04/1795% HD
Appendix B
ACM Sample Location Drawings
First Floor Building 4765
Marshall Space Flight Center Marshall Space Flight Center, AL
Task Order #GSE-017
101A
101C
10 11 12 13 14, 15
20 9 22 6 4 1 5 22 24 2
Appendix C
ACM Location Diagrams
NOT APPLICABLE
Appendix D
Photographs
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
PHOTO 1. 2’ X 2’ Ceiling tile with texture finish PHOTO 2. Gray mastic on HVAC ducts
PHOTO 3. Wallboard system PHOTO 4. Red sealant at wall penetrations
PHOTO 5. Pipe insulation with white mastic PHOTO 6. Gray caulking around doors and wall panels
Building 4765, George C. Marshall Space Flight Center, Marshall Space Flight Center, Alabama
PHOTO 7. Tank insulation PHOTO 8. White HVAC duct insulation
Appendix E
License and Certifications
| 1. Introduction |
| 2. Summary |
| 2.1. Suspect ACMs |
| 2.2. Recommendations |
| 3. Survey Scope |
| 4. Limitations |
| 5. Survey and Sample Collection Procedure |
| 6. Previous Survey / Plans Review |
| 7. Suspect ACM Materials Not Sampled |
| 8. Survey Sampling Results |
| 9. Appendices |
| Appendix A Laboratory Results |
| Appendix B ACM Sample Location Drawings |
| Appendix C ACM Location Diagrams |
| Appendix D Photographs |
| Appendix E License and Certifications |