P658 Nuclear Regional Maintenance Facility 1611490 NSB Kings Bay, GA
SECTION 10 44 16
FIRE EXTINGUISHERS
11/19
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 1 (2021) Fire Code
NFPA 10 (2022; ERTA 1 2021) Standard for Portable Fire Extinguishers
NFPA 101 (2021) Life Safety Code
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.157 (2003) Portable Fire Extinguishers
UNDERWRITERS LABORATORIES (UL)
UL 154 (2005; Reprint May 2021) UL Standard for Safety Carbon-Dioxide Fire Extinguishers
UL 299 (2012; May 2021) Dry Chemical Fire Extinguishers
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fire Extinguishers; G, NAV
Accessories; G, NAV
Cabinets; G, NAV
Wall Brackets; G, NAV
Schedule; G, NAV
SD-03 Product Data
Fire Extinguishers; G, NAV
SECTION 10 44 16 Page 1 06 June 2023
AlvarezA2 Underline
Accessories; G, NAV
Cabinets; G, NAV
Wall Brackets; G, NAV
Replacement Parts List; G, NAV
SD-04 Samples
Equipment Samples; G, NAV
SD-07 Certificates
Fire Extinguishers Certifications; G, NAV
Manufacturer's Warranty with Inspection Tag; G, NAV
1.3 DELIVERY, STORAGE, AND HANDLING
Protect materials from weather, soil, and damage during delivery, storage, and construction.
Deliver materials in their original packages, containers, or bundles bearing the brand name and the name and type of the material.
1.3.1 Samples
Provide the following equipment samples: one full-sized sample of each type of cabinet being installed; three samples of wall brackets and accessories of each type being used.
Use approved samples for installation, with proper identification and storage.
1.4 WARRANTY
Guarantee that Fire Extinguishers are free of defects in materials, fabrication, finish, and installation and that they will remain so for a period of not less than 6 years after completion.
Submit the manufacturer's warranty with inspection tag.
1.5 PROJECT SCHEDULE
For fire extinguishers. Coordinate final fire extinguisher schedule with fire protection cabinet schedule to ensure proper fit and function. Use same designations indicated on Drawings.
PART 2 PRODUCTS
Submit fabrication drawings consisting of fabrication and assembly details performed in the factory and product data for the following items:
Accessories, cabinets, Wall Brackets.
SECTION 10 44 16 Page 2 06 June 2023
2.1 SYSTEM DESCRIPTION
2.1.1 Types
Submit fire extinguishers certifications showing compliance with local codes and regulations.
Provide fire extinguishers conforming to NFPA 10 . Provide quantity and placement in compliance with the applicable sections of NFPA 1, NFPA 101 , and 29 CFR 1910.157 .
Provide carbon-dioxide type fire extinguishers compliant with UL 154 .
Provide dry chemical type fire extinguishers compliant with UL 299 .
2.1.2 Material
Provide corrosion-resistant steel extinguisher shell.
2.1.3 Size
10 pounds extinguishers.
2.1.4 Accessories
Forged brass valve
Fusible plug
Safety release
Pressure gage
2.2 EQUIPMENT
2.2.1 Cabinets
2.2.1.1 Material
Provide corrosion-resistant steel cabinets in non fire resisted-rated walls of a width 4 inches and greater.
2.2.1.2 Type
Provide semi-recessed cabinet for wall thicknesses between 4 inch and 6 inch. For walls thicker than 6 inches provide recessed cabinets.
2.2.1.3 Size
Dimension cabinets to accommodate the specified fire extinguishers.
2.2.2 Wall Brackets
Provide wall-hook fire extinguisher wall brackets in fire resisted-rated walls.
Provide wall bracket and accessories as approved.
SECTION 10 44 16 Page 3
2.2.2.1 Identification
Provide lettering complying with authorities having jurisdiction for letter style, size, spacing, and location. Locate as indicated by the drawings.
Identify bracket-mounted fire extinguishers with the words "FIRE EXTINGUISHER" in red letter decals applied to mounting surface.
Orientation: Vertical
PART 3 EXECUTION
3.1 INSTALLATION
Install fire extinguishers in locations indicated and in compliance with requirements of authorities having jurisdiction.
Comply with the manufacturer's recommendations for all installations.
3.2 PROTECTION
3.2.1 Repairing
Remove and replace damaged and unacceptable portions of completed work with new work at no additional cost to the Government.
Submit replacement parts list indicating specified items replacement part, replacement cost, and name, address and contact for replacement parts distributor.
3.2.2 Cleaning
Clean all surfaces of the work, and adjacent surfaces which are soiled as a result of the work. Remove from the site all construction equipment, tools, surplus materials and rubbish resulting from the work.
-- End of Section --
SECTION 10 44 16 Page 4
| 10 44 16 - FIRE EXTINGUISHERS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 DELIVERY, STORAGE, AND HANDLING |
| 1.3.1 Samples |
| 1.4 WARRANTY |
| 1.5 PROJECT SCHEDULE |
| PART 2 PRODUCTS |
| 2.1 SYSTEM DESCRIPTION |
| 2.1.1 Types |
| 2.1.2 Material |
| 2.1.3 Size |
| 2.1.4 Accessories |
| 2.2 EQUIPMENT |
| 2.2.1 Cabinets |
| 2.2.1.1 Material |
| 2.2.1.2 Type |
| 2.2.1.3 Size |
| 2.2.2 Wall Brackets |
| 2.2.2.1 Identification |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.2 PROTECTION |
| 3.2.1 Repairing |
| 3.2.2 Cleaning |