This is a solicitation for construction services for two earth covered magazines and a munitions assembly conveyor shelter at Royal Australian Air Force Base Tindal in Northern Territory, Australia. The project includes construction of the magazines and shelter, extension of electrical and telecommunication services to the site, and compliance with DoD antiterrorism and force protection requirements. The solicitation also contains two priced options - one for a freestanding steel munitions assembly conveyor shelter and another for design, installation, testing and training of an electrical security system. Responses to the solicitation are due within 360 days of contract award. The resulting contract will be subject to Federal Acquisition Regulations and Department of Defense and Naval Facilities Engineering Command supplement regulations.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
19RXXX1
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
RFP N62742-20-R-1303, NAVFAC WORK ORDER NUMBER 1606623, FY20 MCON PROJECT P-80300 EARTH COVERED MAGAZINES AT
ROYAL AUSTRALIAN AIR FORCE BASE, TINDAL, NORTHERN TERRITORY, AUSTRALIA
Continued on page 2.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 10-Feb-2020
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X N6274220R1303
X 9B. DATED (SEE ITEM 11)
12-Dec-2019
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
10-Feb-2020
CODE
HAND DELIVER
NAVFAC PACIFIC
CONSTRUCTION CONTRACTS BR (ACQ33)
4256 RADFORD DR, BLDG 62
HONOLULU HI 96818-3296
N62742 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
N6274220R1303
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
The following items are applicable to this modification:
PROJECT TABLE OF CONTENTS
Section 07 41 13 METAL ROOF PANELS Amendment 007 is hereby deleted, and replaced with the attached Section 07 41 13 METAL ROOF PANELS Amendment 008.
FY20 MCAF PAF180300, APSI Earth Covered Magazines 1606623 RAAF Tindal, Australia
SECTION 07 41 13
METAL ROOF PANELS
05/11
AMENDMENT 008
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7 (2017) Minimum Design Loads for Buildings and Other Structures
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A1008/A1008M (2016) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
ASTM A755/A755M (2016; E 2016) Standard Specification for Steel Sheet, Metallic Coated by the Hot-Dip Process and Prepainted by the Coil-Coating Process for Exterior Exposed Building Products
ASTM A924/A924M (2017a) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM B117 (2016) Standard Practice for Operating Salt Spray (Fog) Apparatus
ASTM D1308 (2013) Effect of Household Chemicals on Clear and Pigmented Organic Finishes
ASTM D1654 (2008; R 2016; E 2017) Standard Test Method for Evaluation of Painted or Coated Specimens Subjected to Corrosive
JEG# WFXO6303 SECTION 07 41 13 Page 1 Amendment 008
Environments
ASTM D2244 (2016) Standard Practice for Calculation of Color Tolerances and Color Differences from Instrumentally Measured Color Coordinates
ASTM D2247 (2015) Testing Water Resistance of Coatings in 100% Relative Humidity
ASTM D2794 (1993; R 2010) Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact)
ASTM D3359 (2017) Standard Test Methods for Rating Adhesion by Tape Test
ASTM D3363 (2005; E 2011; R 2011; E 2012) Film Hardness by Pencil Test
ASTM D4214 (2007; R 2015) Standard Test Method for Evaluating the Degree of Chalking of Exterior Paint Films
ASTM D4587 (2011) Standard Practice for Fluorescent UV-Condensation Exposures of Paint and Related Coatings
ASTM D522/D522M (2014) Mandrel Bend Test of Attached Organic Coatings
ASTM D523 (2014; R 2018) Standard Test Method for Specular Gloss
ASTM D5894 (2016) Standard Practice for Cyclic Salt Fog/UV Exposure of Painted Metal, (Alternating Exposures in a Fog/Dry Cabinet and a UV/Condensation Cabinet)
ASTM D610 (2008; R 2012) Evaluating Degree of Rusting on Painted Steel Surfaces
ASTM D714 (2002; R 2017) Standard Test Method for Evaluating Degree of Blistering of Paints
ASTM D822 (2013) Filtered Open-Flame Carbon-Arc Exposures of Paint and Related Coatings
ASTM D968 (2017) Standard Test Methods for Abrasion Resistance of Organic Coatings by Falling Abrasive
ASTM E2140 (2001; R 2017) Standard Test Method for Water Penetration of Metal Roof Panel Systems by Static Water Pressure Head
ASTM E84 (2018a) Standard Test Method for Surface Burning Characteristics of Building Materials
JEG# WFXO6303 SECTION 07 41 13 Page 2
ASTM G152 (2013) Operating Open Flame Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials
ASTM G153 (2013) Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials
AUSTRALIAN STANDARDS (AS)
AS 1170.2 Structural Design Actions - Part 2: Wind Actions
AS 1397 Continuous Hot-dip Metallic Coated Steel Sheet And Strip - Coatings Of Zinc And Zinc Alloyed With Aluminium And Magnesium
AS 1445 Hot-dipped Zinc-coated, Aluminium/zinc-coated or Aluminium/zinc/magnesium-coated Steel Sheet
AS 1554.1 Structural Steel Welding – Welding of Steel Structures
AS 1562.1 Design and Installation of Sheet Roof and Wall Cladding
UNDERWRITERS LABORATORIES (UL)
UL Bld Mat Dir (updated continuously online) Building Materials Directory
1.2 DESCRIPTION OF METAL ROOF SYSTEM
1.2.1 Performance Requirements
Steel panels and accessory components must conform to the following standards:
ASTM A1008/A1008M
ASTM A123/A123M
ASTM A36/A36M
ASTM A755/A755M for metallic coated steel sheet for exterior coil prepainted applications.
ASTM A924/A924M for metallic coated steel sheet ASTM D522/D522M for applied coatings UL Bld Mat Dir
1.2.1.1 Hydrostatic Head Resistance
No water penetration when tested according to ASTM E2140. Submit leakage test report upon completion of installation.
1.2.1.2 Wind Uplift Resistance
Uplift force due to wind action governs the design for panels. Submit wind uplift test report prior to commencing installation.
JEG# WFXO6303 SECTION 07 41 13 Page 3
Provide roof AS 1170.2 system and attachments that resist the wind loads as determined by ASCE 7, in pounds per square foot. Metal roof panels and component materials must also comply with the requirements in AS 1562.1 as part of a panel roofing system.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Roofing Panels; G
Flashing and Accessories; G
Gutter/Downspout Assembly; G
SD-03 Product Data
Submit manufacturer's catalog data for the following items:
Roof Panels; G
Factory-Applied Color Finish; G
Accessories; G
Fasteners; G
Pressure Sensitive Tape; G
Coil Stock; G
Galvanizing Repair Paint; G
SD-04 Samples
Roof Panels; G
Factory-applied Color Finish, Samples, 230 mm lengths, full width;
G
Accessories; G
Fasteners; G
Gaskets and Sealant/Insulating Compounds; G
SD-05 Design Data
Wind Uplift Resistance; G
SD-06 Test Reports
JEG# WFXO6303 SECTION 07 41 13 Page 4
Leakage Test Report; G
Wind Uplift Test Report; G
Factory Finish and Color Performance Requirements; G
SD-07 Certificates
Roof Panels; G
Coil Stock Compatibility; G
Qualification of Manufacturer; G
Qualification of Applicator; G
SD-08 Manufacturer's Instructions
Installation Manual; G
SD-09 Manufacturer's Field Reports
Manufacturer's Field Inspection Reports; G
SD-11 Closeout Submittals
Warranties; G
Information Card; G
1.4 QUALITY ASSURANCE
1.4.1 Qualification of Manufacturer
Submit documentation verifying metal roof panel manufacturer has been in the business of manufacturing metal roof panels for a period of not less than 5 years.
Manufacturer must also provide engineering services by an authorized engineer, currently licensed in the geographic area of the project, with a minimum of five (5) years experience as an engineer knowledgeable in roof wind design analysis, protocols and procedures in AS 1562.1 . Engineer must provide certified engineering calculations for the project conforming to the stated references.
1.4.1.1 Manufacturer's Technical Representative
The manufacturer's technical representative must be thoroughly familiar with the products to be installed, installation requirements and practices, and with any special considerations in the geographical area of the project. The representative must perform field inspections and attend meetings as specified.
1.4.1.2 Single Source
Provide roofing panels, clips, closures, and other accessories that are standard products of the same manufacturer, and the most recent design of the manufacturer to operate as a complete system for the intended use.
JEG# WFXO6303 SECTION 07 41 13 Page 5
1.4.2 Qualification of Applicator
Metal roof system applicator must be approved, authorized, or licensed in writing by the roof panel manufacturer and have a minimum of three years experience as an approved, authorized, or licensed applicator with that manufacturer, approved at a level capable of providing the specified warranty. Supply the names, locations and client contact information of 5 projects of similar size and scope constructed by applicator using the manufacturer's roofing products submitted for this project within the previous three years.
1.4.3 Field Verification
Prior to the preparation of drawings and fabrication, verify location of roof framing, roof openings and penetrations, and any other special conditions. Indicate all special conditions and measurements on final shop drawings.
1.4.4 Qualifications for Welding Work
Perform welding procedures in conformance to AWS D1.1/D1.1M or AS 1554.1 for steel.
Operators are permitted to make only those types of weldments for which each is specifically qualified.
1.4.5 Pre-roofing Conference
After approval of submittals and before performing roofing system installation work, hold a pre-roofing conference to review the following:
a. Drawings, specifications, and submittals related to the roof work.
Submit, as a minimum; sample profiles of roofing panels, with factory-applied color finish samples, flashing and accessories, gutter/downspout assembly samples, typical fasteners and pressure sensitive tape, sample gaskets and sealant/insulating compounds. Also include data and 1/2 pint sample of galvanizing repair paint, and technical data on coil stock and coil stock compatibility, and manufacturer's installation manual.
b. Roof system components installation;
c. Procedure for the roof manufacturer's technical representative's onsite inspection and acceptance of the roofing substrate, the name of the manufacturer's technical representatives, the frequency of the onsite visits, distribution of copies of the inspection reports from the manufacturer's technical representative;
d. Contractor's plan for coordination of the work of the various trades involved in providing the roofing system and other components secured to the roofing; and
e. Quality control plan for the roof system installation;
f. Safety requirements.
Coordinate pre-roofing conference scheduling with the Contracting Officer. Attendance is mandatory for the Contractor, the Contracting Officer's designated personnel, personnel directly responsible for the
JEG# WFXO6303 SECTION 07 41 13 Page 6 installation of metal roof system, flashing and sheet metal work, electrical work, other trades interfacing with the roof work, and representative of the metal roofing manufacturer. Before beginning roofing work, provide a copy of meeting notes and action items to all attending parties. Note action items requiring resolution prior to start of roof work.
1.5 DELIVERY, HANDLING, AND STORAGE
Deliver, store, and handle panel materials, bulk roofing products, accessories, and other manufactured items in a manner to prevent damage and deformation, as recommended by the manufacturer, and as specified.
1.5.1 Delivery
Package and deliver materials to the site in undamaged condition. Provide adequate packaging to protect materials during shipment. Do not uncrate materials until ready for use, except for inspection. Immediately upon arrival of materials at jobsite, inspect materials for damage, deformation, dampness, and staining. Remove affected materials from the site and immediately replace. Remove moisture from wet materials not otherwise affected, restack and protect from further moisture exposure.
1.5.2 Handling
Handle materials in a manner to avoid damage. Select and operate material handling equipment so as not to damage materials or applied roofing.
1.5.3 Storage
Stack materials stored on site on platforms or pallets, and cover with tarpaulins or other weathertight covering which prevents trapping of water or condensation under the covering. Store roof panels so that water which may have accumulated during transit or storage will drain off. Do not store panels in contact with materials that might cause staining. Secure coverings and stored items to protect from wind displacement.
1.6 PROJECT CONDITIONS
Weather Limitations: Proceed with installation only when existing and forecast weather conditions permit metal roof panel work to be performed according to manufacturer's written instructions and warranty requirements, and specified safety requirements.
1.7 FABRICATION
Fabricate and finish metal roof panels and accessories on a factory stationary industrial type rolling mill to the greatest extent possible, per manufacturer's standard procedures and processes, and as necessary to fulfill indicated performance requirements. Comply with indicated profiles, dimensional and structural requirements.
Provide panel profile, as indicated on drawings. Fabricate panel side laps with factory installed captive gaskets providing a weather tight seal and preventing metal-to metal contact, and minimizing noise from movements within the panel assembly.
JEG# WFXO6303 SECTION 07 41 13 Page 7
1.7.1 Finishes
Finish quality and application processes must conform to the related standards specified within this section. Noticeable variations within the same piece are not acceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved samples and are assembled or installed to minimize any contrasting variations.
1.7.2 Accessories
Fabricate flashing and trim as applicable to the design, dimensions, metal, and other characteristics of the item indicated.
a. Form exposed sheet metal accessories which are free from excessive oil canning, buckling, and tool marks, and are true to line and levels indicated, with exposed edges folded back to form hems.
b. End Seams: Fabricate nonmoving seams with flat-lock seams. Form seams and seal with epoxy seam sealer.
c. Sealed Joints: Form non-expansion, but movable joints in metal to accommodate elastomeric sealant.
d. Conceal fasteners and expansion provisions where possible. Exposed fasteners are not allowed on faces of accessories exposed to view.
e. Fabricate cleats and attachments devices of size and metal thickness recommended by SMACNA or by metal roof panel manufacturer for application, but not less than the thickness of the metal being secured.
1.8 WARRANTIES
Provide metal roof system material and workmanship warranties meeting specified requirements. Provide revision or amendment to manufacturer's standard warranty as required to comply with the specified requirements.
1.8.1 Metal Roof Panel Manufacturer Warranty
Furnish the metal roof panel manufacturer's 20-year no dollar limit roof system materials and installation workmanship warranty, including flashing, components, trim, and accessories necessary for a watertight roof system construction. Make warranty directly to the Government, commencing at time of Government's acceptance of the roof work. The warranty must state that:
a. If within the warranty period, the metal roof system, as installed for its intended use in the normal climatic and environmental conditions of the facility, becomes non-watertight, shows evidence of moisture intrusion within the assembly, displaces, corrodes, perforates, separates at the seams, or shows evidence of excessive weathering due to defective materials or installation workmanship, the repair or replacement of the defective and damaged materials of the metal roof system and correction of defective workmanship is the responsibility of the metal roof panel manufacturer. All costs associated with the repair or replacement work are the responsibility of the metal roof panel manufacturer.
b. If the manufacturer or his approved applicator fail to perform the
JEG# WFXO6303 SECTION 07 41 13 Page 8 repairs within 72 hours of notification, emergency temporary repairs performed by others does not void the warranty.
1.8.2 Manufacturer's Finish Warranty
Provide a manufacturer's no-dollar-limit 20 year warranty for the roofing system. Issue the warranty directly to the Government at the date of Government acceptance, warranting that the factory color finish, under normal atmospheric conditions at the site, will not crack, peel, or delaminate; chalk in excess of a numerical rating of 8 when measured in accordance with ASTM D4214; or fade or change colors in excess of 5 NBS units as measured in accordance with ASTM D2244.
1.8.3 Continuance of Warranty
Repair or replacement work that becomes necessary within the warranty period must be approved, as required, and accomplished in a manner so as to restore the integrity of the roof system assembly and validity of the metal roof system manufacturer warranty for the remainder of the manufacturer warranty period.
1.9 CONFORMANCE AND COMPATIBILITY
Provide the entire metal roofing and flashing system in accordance with specified and indicated requirements, including wind resistance requirements. Perform work not specifically addressed and any deviation from specified requirements in general accordance with recommendations of AS 1562.1 , the metal panel manufacturer's published recommendations and details, and compatible with surrounding components and construction.
Submit any deviation from specified or indicated requirements to the Contracting Officer for approval prior to installation.
1.10 SCHEDULE
Some metric measurements in this section are based on mathematical conversion of English unit measurements, and not on metric measurement commonly agreed to by the manufacturers or other parties. The English and metric units for the measurements shown are as follows:
PRODUCTS ENGLISH UNITS METRIC UNITS
a. Sheet Aluminum 0.040 inch 1.0 mm
b. Panels 12 inches 300 mm
- vertical legs 2 inches 50 mm
- stiffening ribs 4 inches 100 mm
c. Screws No. 14 0.242 mm
No. 12 0.216 mm
d. Bolts 1/4 inch 6 mm
JEG# WFXO6303 SECTION 07 41 13 Page 9
e. Studs 3/16 inch 5 mm
f. Fasteners 1/2 inch 13 mm
One inch 25 mm
g. Rivets 1/16 inch 5 mm
1/8 inch 3 mm
PART 2 PRODUCTS
2.1 ROOF PANELS
2.1.1 Steel Sheet Panels
Roll-form steel sheet roof panels to the specified profile, grade G550 0.60
0.48 mm thickness and depth as indicated.
Provide steel panels with a minimum recycled content of 30 percent.
Material must be plumb and true, and within the tolerances listed:
a. Galvanized steel sheet conforming to AS 1445 .
b. Individual panels to have continuous length sufficient to cover the entire length of any unbroken roof slope with no joints or seams and formed without warping, waviness, or ripples that are not a part of the panel profile and free from damage to the finish coating system.
c. Provide panels with thermal expansion and contraction consistent with the type of system specified, and the following profile:
(1) profile and coverage to be a minimum height and width from the manufacturer's standard for the indicated roof slope.
(2) profile to be a 22.2 mm high corrugated rib at 50.8 mm o.c., 987.5 mm overall width with 915 mm exposed panel and exposed fasteners.
2.2 FACTORY FINISH AND COLOR PERFORMANCE REQUIREMENTS
All panels are to receive a factory applied Colorbond finish consisting of a baked topcoat with a manufacturer's recommended prime coat conforming to the following:
a. Metal Preparation: All metal is to have the surfaces carefully prepared for painting on a continuous process coil coating line by alkali cleaning, hot water rinsing, application of chemical conversion coating, cold water rinsing, sealing with an acid rinse, and thorough drying.
b. Prime Coating: A base coat of epoxy paint, specifically formulated to interact with the top-coat, is to be applied to the prepared surfaces by roll coating to a dry film thickness of 0.20 plus 0.05 mils. Oven cure the prime coat prior to application of the finish coat.
c. Exterior Finish Coating: Apply the exterior finish coating over the primer by roll coating to a dry film thickness of 0.80 plus 0.05 mils
JEG# WFXO6303 SECTION 07 41 13 Page 10
(3.80 plus 0.05 mils for Vinyl Plastisol) for a total dry film thickness of 1.00 plus 0.10 mils (4.00 plus 0.10 mils for Vinyl Plastisol). Oven cure this exterior finish coat.
d. Color: The exterior finish chosen from the manufacturer's standard color chart.
e. Physical Properties: Coating must conform to the industry and manufacturer's standard performance criteria as listed by the following certified test reports:
General: ASTM D5894 and ASTM D4587
Abrasion: ASTM D968 2000 g
Adhesion: ASTM D3359 No f l aki ng or peel i ng
Chalking: ASTM D4214 Less t han or equal t o 4
Chemical Pollution: ASTM D1308 No l oss or adhesi on or cor r osi on of base
Color Change and Conformity:
ASTM D2244 Del t aE CI El ab 2000: Li ght col our : l ess t han or equal t o 4 uni t s
Creepage: ASTM D1654 Less t han or equal t o 1 mm
Cyclic Corrosion Test: ASTM D5894 Bl i st er Densi t y: Less t han or equal t o 2.
Bl i st er Si ze: Less t han or equal t o S2.
Under cut Fr om Scor e: Less t han or equal t o 1 mm.
No l oss of adhesi on or cor r osi on of base met al .
Flame Spread: ASTM E84 0
Flexibility: ASTM D522/D522M Maxi mum 10T ( no cr acki ng)
Formability: ASTM D522/D522M
Gloss at 60 and 85 degrees:
ASTM D523 Nor mal pl us or mi nus 10 uni t s
JEG# WFXO6303 SECTION 07 41 13 Page 11
Humidity: ASTM D2247 and ASTM D714 Bl i st er Densi t y: Less t han or equal t o 3.
Bl i st er Si ze: Less t han or equal t o S2.
Under cut Fr om Scor e: Less t han or equal t o 2 mm.
No l oss of adhesi on or cor r osi on of base met al .
Oxidation: ASTM D610
Pencil Hardness: ASTM D3363 HB or har der
Reverse Impact: ASTM D2794 Gr eat er t han or equal t o 10 joule
Salt Spray: ASTM B117
Weatherometer: ASTM G152, ASTM G153 and
ASTM D822
2.2.1 Specular Gloss
Finished roof surfaces to have a specular gloss value of 10 or less at an angle of 85 degrees when measured in accordance with ASTM D523.
2.3 MISCELLANEOUS METAL FRAMING
2.3.1 General
Provide cold formed metallic-coated steel sheet conforming to AS 1397 .
2.3.2 Fasteners and Miscellaneous Metal Framing
Provide compatible type, corrosion resistant, of sufficient size and length to penetrate the supporting element a minimum of 25 mm with other required properties to fasten miscellaneous metal framing members to substrates in accordance with the roof panel manufacturer's and wind uplift requirements.
2.3.2.1 Exposed Fasteners
Provide corrosion resistant coated steel fasteners for roof panels, compatible with the sheet panel or flashing material and of the type and size recommended by the manufacturer to meet the performance requirements and design loads. Provide fasteners for accessories that are the manufacturer's standard. Provide an integral metal washer, matching the color of attached material with compressible sealing EPDM gasket approximately 2.5 mm thick for exposed fasteners.
2.3.2.2 Screws
Provide corrosion resistant screws, coated steel of the type and size recommended by the manufacturer to meet the performance requirements.
JEG# WFXO6303 SECTION 07 41 13 Page 12
2.3.2.3 Rivets
Provide closed-end type rivets, corrosion resistant coated steel where watertight connections are required.
2.3.2.4 Attachment Clips
Provide hot-dip galvanized, clips. Size, shape, thickness and capacity must meet the thickness and design load criteria specified.
2.3.3 Electrodes for Manual, Shielded Metal Arc Welding
Utilize electrodes for manual, shielded metal arc welding meeting the requirements of AS 1554.1 , that are covered, mild-steel electrodes.
2.4 ACCESSORIES
Provide accessories compatible with the metal roof panels. Sheet metal flashing, trim, metal closure strips, caps, and similar metal accessories must be not less than the minimum thicknesses specified for roof panels.
Provide exposed metal accessories to match the panels furnished. Provide molded foam rib, ridge and other closure strips that are closed-cell or solid-cell synthetic rubber or neoprene premolded to match configuration of the panels and not absorb or retain water.
2.4.1 Pre-manufactured Accessories
Provide pre-manufactured accessories that are manufacturer's standard for intended purpose, compatible with the metal roof system and approved for use by the metal roof panel manufacturer.
2.4.2 Metal Closure Strips
Provide factory fabricated steel closure strips of the same gauge, color, finish and profile as the specified roof panel.
2.4.3 Rubber Closure Strips
Provide closed-cell, expanded cellular rubber closure strips extruded or molded to the configuration of the specified roof panel profile and in lengths supplied by roof panel manufacturer.
2.4.4 Roof Safety Mesh
Provide 2 mm diameter woven, stainless steel 150 by 300 mm wire mesh.
Attach per manufacturer's instruction using recommended fastener.
2.5 JOINT SEALANTS
2.5.1 Sealants
Sealants are to be an approved gun type for use in hand or air pressure caulking guns at temperatures above 4 degrees C (or frost-free application at temperatures above minus 12 degrees C) with a minimum solid content of 85 percent of the total volume. Ensure sealant dries with a tough, durable surface skin which permits it to remain soft and pliable underneath, providing a weather tight joint. No migratory staining, is permitted on painted or unpainted metal, stone, glass, vinyl or wood.
JEG# WFXO6303 SECTION 07 41 13 Page 13
Prime all joints to receive sealants with a compatible one-component or two-component primer as recommended by the roof panel manufacturer.
2.5.1.1 Shop Applied Sealants
Provide sealant for shop-applied caulking that is an approved gun grade, non-sag one-component polysulfide or silicone and with a curing time which ensures the sealants plasticity at the time of field erection. Color to match panel color.
2.5.1.2 Field Applied Sealants
Provide sealants for field-applied caulking that is an approved gun grade, non-sag on-component polysulfide or two component polyurethane with an initial maximum Shore A durometer hardness of 25. Color to match panel color.
2.5.1.3 Tape Sealants
Provide pressure sensitive, 100 percent solid tape sealant with a release paper backing; permanently elastic, non-sagging, non-toxic and non-staining as approved by the roof panel manufacturer.
2.5.2 Sheet Metal Flashing and Trim
2.5.2.1 Fabrication, General
Custom fabricate sheet metal flashing and trim to comply with recommendations within the SMACNA 1793 that apply to design, dimensions, metal type, and other characteristics of design indicated. Shop fabricate items to the greatest extent possible. Obtain and verify field measurements for accurate fit prior to shop fabrication. Fabricate flashing and trim without excessive oil canning, buckling, and tool marks, true to line and levels indicated, with exposed edges folded back to form hems.
2.5.2.2 Roof Drainage Sheet Metal Fabrications
Gutters: Fabricate to cross section indicated, with riveted joints, complete with end pieces, outlet tubes, and other special accessories as required. Fabricate in minimum 2440 mm long sections. Fabricate expansion joints and accessories from the same metal as gutters, unless otherwise indicated.
Downspouts: Fabricate circular downspouts complete with mitered elbows.
Furnish with metal hangers of same material as downspouts and anchors.
2.6 FINISH REPAIR MATERIAL
Only use repair and touch-up paint supplied by the roof panel manufacturer and is compatible with the specified system.
PART 3 EXECUTION
3.1 EXAMINATION
Examine substrates, areas, and conditions, with installer present, for compliance with requirements for installation tolerances, metal roof panel
JEG# WFXO6303 SECTION 07 41 13 Page 14 supports, and other conditions affecting performance of the work. Ensure surfaces are suitable, dry and free of defects and projections which might affect the installation.
Examine primary and secondary roof framing to verify that rafters, purlins, angels, channels, and other structural support members for panels and anchorages have been installed within alignment tolerances required by metal roof panel manufacturer, and AS 1445 .
Examine solid roof sheathing to verify that sheathing joints are supported by framing or blocking; and that installation is within flatness tolerances required by metal roof panel manufacturer.
Examine rough-in for components and systems penetrating metal roof panels to verify actual locations of penetrations relative to seam locations of panels prior to installation.
Submit a written report to the Contracting Officer, endorsed by the installer, listing conditions detrimental to the performance of the work.
Proceed with installation only after defects have been corrected.
Do not install items that show visual evidence of biological growth.
3.2 INSTALLATION
Perform installation meeting specified requirements and in accordance with the manufacturer's installation instructions and approved shop drawings.
Do not install damaged materials. Insulate dissimilar materials which are not compatible when contacting each other by means of gaskets or sealing/insulating compounds. Keep all exposed surfaces and edges clean and free from sealant, metal cuttings, hazardous burrs, and other foreign material. Remove stained, discolored, or damaged materials from the site.
3.2.1 Preparation
Clean all substrate substances which may be harmful to roof panels including removing projections capable of interfering with roof panel attachment.
Install sub-purlins, eave angles, furring, and other miscellaneous roof panel support members and anchorage according to metal roof panel manufacturer's written instructions.
3.3 PROTECTION OF APPLIED MATERIALS
Do not permit storing, walking, wheeling, and trucking directly on applied roofing/insulation materials. Provide temporary walkways, runways, and platforms of smooth clean boards or planks as necessary to avoid damage to applied roofing/insulation materials, and to distribute weight to conform to indicated live load limits of roof construction.
3.4 FASTENER INSTALLATION
Anchor metal roof panels and other components of the Work securely in place, using approved fasteners according to manufacturer's written instructions.
JEG# WFXO6303 SECTION 07 41 13 Page 15
3.4.1 Welding
Perform procedures for manual, shielded metal-arc welding, the inspection and testing of welds made, and the methods used in correcting welding work in accordance with AS 1554.1 .
3.5 FLASHING, TRIM, AND CLOSURE INSTALLATION
3.5.1 General Requirements
Comply with performance requirements, manufacturer's written installation instructions, and AS 1445 . Provide concealed fasteners where possible.
Set units true to line and level as indicated. Install work with laps, joints, and seams that will be permanently water tight and weather resistant. Work is to be accomplished to form weather tight construction without waves, warps, buckles, fastening stresses or distortion, and to allow for expansion and contraction. Perform cutting, fitting, drilling, and other operations in connection with sheet metal required to accomplish the work in conformance with the manufacturers written instructions.
3.5.2 Metal Flashing
Install exposed prefinished metal flashing at building corners, rakes, eaves, junctions between metal siding and roofing, valleys and changes off slope or direction in metal roofing, building expansion joints and gutters.
Utilize exposed metal flashing that is the same material, color, and finish as the specified metal roofing panels. Furnish flashing in minimum
2.44 m lengths. Exposed flashing must have 25 mm locked and blind end joints as per manufacturer's recommendations, with expansion joints at intervals of no greater than 4.88 m.
Fasten flashing at not more than 200 mm on center for roofs, except where flashing is held in place by the same screws used to secure panels. Bed exposed flashing and flashing subject to rain penetration in specified joint sealant. Isolate flashing which is in contact with dissimilar metals by means of the specified asphalt mastic material to prevent electrolytic deterioration.
Form drips to the profile indicated, with the edge folded back 15 mm to form a reinforced drip edge.
3.6 ROOF PANEL INSTALLATION
Provide metal roof panels of full length from eave to ridge or eave to wall as indicated, unless otherwise indicated or restricted by shipping limitations. Anchor metal roof panels or other components of the Work securely in place, with provisions for thermal and structural movement.
Steel Roof Panels: Use stainless steel fasteners for exterior surfaces and galvanized fasteners for unexposed surfaces.
Anchor Clips: Anchor metal roof panels and other components of the Work securely in place, using approved fasteners according to manufacturer's written instructions. Provide all blocking and nailers as required.
Metal Protection: Where dissimilar metals contact each other or possibly corrosive substrates, protect against galvanic action by
JEG# WFXO6303 SECTION 07 41 13 Page 16 permanent separation as recommended by the metal roof panel manufacturer.
Joint Sealers: Install gaskets, joint fillers, and sealants where indicated and required for weatherproof performance of metal roof panel system. Provide types of gaskets, fillers, and sealants indicated or, if not indicated, types recommended by metal roof panel manufacturer.
3.6.1 Handling and Erection
Erect roofing system in accordance with the approved erection drawings, printed instructions and safety precautions of the manufacturer.
Do not subject panels to overloading, abuse, or undue impact. Do not apply bent, chipped, or defective panels. Replace and remove from the site any damaged panels at the Contractor's expense. Erect panels true, plumb, and in exact alignment with the horizontal and vertical edges of the building, securely anchored, and with indicated rake, eave, and curb overhang. Allow for thermal movement of the roofing, movement of the building structure, and provide permanent freedom from noise due to wind pressure.
Do not permit storage, walking, wheeling or trucking directly on applied roofing materials. Provide temporary walkways, runways, and platforms of smooth clean boards or planks as necessary to avoid damage to the installed roofing materials, and to distribute weight to conform to the indicated live load limits of the roof construction.
Lay roof panels with corrugations in the direction of the roof slope. Lap ends of exterior roofing not less than 250 mm; lap sides of standard exterior corrugated panels not less than 2-1/2 corrugations.
Field cutting of metal roof panels by torch is not permitted. Field cut only as recommended by manufacturer's written instructions.
3.6.2 Closure Strips
Install metal closure strips at open ends of metal ridge rolls; open ends of corrugated or ribbed pattern roofs, and at intersection of wall and roof, unless open ends are concealed with formed eave flashing; rake of metal roof unless open end has a formed flashing member; and in other required areas.
Install closure strips at intersection of the wall with metal roofing; top and bottom of metal siding; heads of wall openings; and in other required locations.
3.6.3 Workmanship
Make lines, arises, and angles sharp and true. Free exposed surfaces from any visible wave, warp, buckle and tool marks. Fold back exposed edges neatly to form a 12.5 mm hem on the concealed side. Make sheet metal exposed to the weather watertight with provisions for expansion and contraction.
Make surfaces to receive sheet metal plumb and true, clean, even, smooth, dry, and free of defects and projections which might affect the application. For installation of items not shown in detail or not covered
JEG# WFXO6303 SECTION 07 41 13 Page 17 by specifications conform to the applicable requirements of AS 1445 .
Provide sheet metal flashing in the angles formed where roof decks abut walls, curbs, ventilators, pipes, or other vertical surfaces and wherever indicated and as necessary to make the work watertight.
3.7 ACCEPTANCE PROVISIONS
3.7.1 Erection Tolerances
Erect metal roofing straight and true with plumb vertical lines correctly lapped and secured in accordance with the manufacturer's written instructions. Horizontal lines must not vary more than 3.2 mm in 12.2 m.
3.7.2 Leakage Tests
Finished application of metal roofing is to be subject to inspection and test for leakage by the Contracting Officer or his designated representative, and Architect/Engineer. Inspection and tests will be conducted without cost to the Government.
Inspection and testing is to be made promptly after erection to permit correction of defects and removal/replacement of defective materials.
3.7.3 Repairs to Finish
Scratches, abrasions, and minor surface defects of finish may be repaired with the specified repair materials and as recommended by the metal roof panel manufacturer. Finished repaired surfaces must be uniform and free from variations of color and surface texture. Repaired metal surfaces that are not acceptable to the project requirements are to be immediately removed and replaced with new material.
3.7.4 Paint Finished Metal Roofing
Paint finished metal roofing will be tested for color stability by the Contracting Officer during the manufacturer's specified guarantee period.
Remove and replace panels that indicate color changes, fading, or surface degradation, determined by visual examination with new panels at no expense to the Government. New panels will be subject to the specified tests for an additional year from the date of their installation.
3.8 CLEAN UP AND DISPOSAL
Clean exposed sheet metal work at completion of installation. Remove metal shavings, filings, nails, bolts, and wires from roofs. Remove grease and oil films, excess sealants, handling marks, contamination from steel wool, fittings and drilling debris and scrub the work clean.
Exposed metal surfaces must be free of dents, creases, waves, scratch marks, solder or weld marks, and damage to the finish coating. Touch up scratches in panel finish with manufacturer supplied touch-up paint system to match panel finish. Treat exposed cut edges with manufacturer supplied clear coat.
Collect all scrap/waste materials and place in containers. Promptly dispose of demolished and scrap materials. Do not allow scrap/waste materials to accumulate on-site; transport immediately from the government property and legally dispose of them.
JEG# WFXO6303 SECTION 07 41 13 Page 18
3.9 FIELD QUALITY CONTROL
3.9.1 Manufacturer's Inspection
Manufacturer's technical representative must visit the site a minimum of three times during the installation for purposes of reviewing materials installation practices and adequacy of work in place. Make inspections during the first 20 squares of roof panel installation, at mid-point of the installation, and at substantial completion, at a minimum. Additional inspections are required for each 100 squares of total roof area with the exception that follow-up inspections of previously noted deficiencies or application errors must be performed as requested by the Contracting Officer. After each inspection, submit a report, signed by the manufacturer's technical representative to the Contracting Officer within 3 working days. Note in the report overall quality of work, deficiencies and any other concerns, and recommended corrective action.
Submit three signed copies of the manufacturer's field inspection reports to the Contracting Officer within one week of substantial completion.
3.10 INFORMATION CARD
For each roof, furnish a typewritten information card for facility records and a card laminated in plastic and framed for interior display at roof access point, or a photoengraved 1 mm thick aluminum card for exterior display. Format as directed in paragraph FORM ONE.
Make card 215 mm by 275 mm minimum, identifying facility name and number;
location; contract number; approximate roof area; detailed roof system description, including roof panel manufacturer and product name, date of completion; installing contractor identification and contact information;
manufacturer warranty expiration, warranty reference number, and contact information. Install card at location as directed by the Contracting Officer and provide a paper copy to the Contracting Officer.
3.10.1 Form One
JEG# WFXO6303 SECTION 07 41 13 Page 19
FORM 1 - PREFORMED STEEL PANEL ROOFING SYSTEM AND COMPONENTS
1. Contract Number:
2. Building Number & Location:
3. NAVFAC Specification Number:
4. Deck/Substrate Type:
5. Slopes of Deck/Roof Structure:
6. Insulation Type & Thickness:
7. Insulation Manufacturer:
8. Vapor Retarder: ( )Yes ( )No
9. Vapor Retarder Type:
10. Preformed Steel Standing Seam Roofing Description:
a. Manufacturer (Name, Address, & Phone No.):
b. Product Name:
c. Width:
d. Gage:
e. Base Metal:
f. Method of Attachment:
11. Repair of Color Coating:
a. Coating Manufacturer (Name, Address & Phone No.):
b. Product Name:
c. Surface Preparation:
d. Recoating Formula:
e. Application Method:
12. Statement of Compliance or Exception:_________________________________
13. Date Roof Completed:
14. Warranty Period: From_______________ To_______________
15. Roofing Contractor (Name & Address):
16. Prime Contractor (Name & Address):
Contractor's Signature _________________________ Date:
Inspector's Signature _________________________ Date: Text
-- End of Section --
JEG# WFXO6303 SECTION 07 41 13 Page 20
| 07 41 13_AMD 008.pdf |
| 07 41 13 - METAL ROOF PANELS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 DESCRIPTION OF METAL ROOF SYSTEM |
| 1.2.1 Performance Requirements |
| 1.2.1.1 Hydrostatic Head Resistance |
| 1.2.1.2 Wind Uplift Resistance |
| 1.3 SUBMITTALS |
| 1.4 QUALITY ASSURANCE |
| 1.4.1 Qualification of Manufacturer |
| 1.4.1.1 Manufacturer's Technical Representative |
| 1.4.1.2 Single Source |
| 1.4.2 Qualification of Applicator |
| 1.4.3 Field Verification |
| 1.4.4 Qualifications for Welding Work |
| 1.4.5 Pre-roofing Conference |
| 1.5 DELIVERY, HANDLING, AND STORAGE |
| 1.5.1 Delivery |
| 1.5.2 Handling |
| 1.5.3 Storage |
| 1.6 PROJECT CONDITIONS |
| 1.7 FABRICATION |
| 1.7.1 Finishes |
| 1.7.2 Accessories |
| 1.8 WARRANTIES |
| 1.8.1 Metal Roof Panel Manufacturer Warranty |
| 1.8.2 Manufacturer's Finish Warranty |
| 1.8.3 Continuance of Warranty |
| 1.9 CONFORMANCE AND COMPATIBILITY |
| 1.10 SCHEDULE |
| PART 2 PRODUCTS |
| 2.1 ROOF PANELS |
| 2.1.1 Steel Sheet Panels |
| 2.2 FACTORY FINISH AND COLOR PERFORMANCE REQUIREMENTS |
| 2.2.1 Specular Gloss |
| 2.3 MISCELLANEOUS METAL FRAMING |
| 2.3.1 General |
| 2.3.2 Fasteners and Miscellaneous Metal Framing |
| 2.3.2.1 Exposed Fasteners |
| 2.3.2.2 Screws |
| 2.3.2.3 Rivets |
| 2.3.2.4 Attachment Clips |
2.3.3 Electrodes for Manual, Shielded Metal Arc Welding
| 2.4 ACCESSORIES |
| 2.4.1 Pre-manufactured Accessories |
| 2.4.2 Metal Closure Strips |
| 2.4.3 Rubber Closure Strips |
| 2.4.4 Roof Safety Mesh |
| 2.5 JOINT SEALANTS |
| 2.5.1 Sealants |
| 2.5.1.1 Shop Applied Sealants |
| 2.5.1.2 Field Applied Sealants |
| 2.5.1.3 Tape Sealants |
| 2.5.2 Sheet Metal Flashing and Trim |
| 2.5.2.1 Fabrication, General |
| 2.5.2.2 Roof Drainage Sheet Metal Fabrications |
2.6 FINISH REPAIR MATERIAL
| PART 3 EXECUTION |
| 3.1 EXAMINATION |
| 3.2 INSTALLATION |
| 3.2.1 Preparation |
| 3.3 PROTECTION OF APPLIED MATERIALS |
| 3.4 FASTENER INSTALLATION |
| 3.4.1 Welding |
| 3.5 FLASHING, TRIM, AND CLOSURE INSTALLATION |
| 3.5.1 General Requirements |
| 3.5.2 Metal Flashing |
| 3.6 ROOF PANEL INSTALLATION |
| 3.6.1 Handling and Erection |
| 3.6.2 Closure Strips |
| 3.6.3 Workmanship |
| 3.7 ACCEPTANCE PROVISIONS |
| 3.7.1 Erection Tolerances |
| 3.7.2 Leakage Tests |
| 3.7.3 Repairs to Finish |
| 3.7.4 Paint Finished Metal Roofing |
| 3.8 CLEAN UP AND DISPOSAL |
| 3.9 FIELD QUALITY CONTROL |
| 3.9.1 Manufacturer's Inspection |
| 3.10 INFORMATION CARD |
| 3.10.1 Form One |