60025843.pdf

PDF 479 KB Posted

Attached to
Renovation & Addition to Protestant Chapel, 16 & 16A
Solicitation number
N6247020R6012
Issued by

View the file

Other files

File Type Posted
Amnd 0007 20R6012 FINAL.pdf PDF
08 62 00 Translucent Wall Panels.pdf PDF
60025844.pdf PDF
Amnd 0006 20R6012 FINAL.pdf PDF
60025840.pdf PDF
Protestant Chapel Revision 02 Combined Drawings 071020.pdf PDF
60025763A.pdf PDF
Amnd 0005 20R6012 FINAL.pdf PDF
Amnd 0004 20R6012 FINAL.pdf PDF
Amnd 0003 20R6012.pdf PDF
Amnd 0002 20R6012 FINAL.pdf PDF
Amnd 0001 20R6012 FINAL.pdf PDF
19-0038 Protestant Chapel Lead Paint Survey 031220.pdf PDF
N4008519B0038 Drawings.pdf PDF
RFP N6247020R6012.pdf PDF
19-0038 Protestant Chapel Asbestos Survey 031220.pdf PDF
Master PPI Form Template.xls XLS spreadsheet
N4008519B0038 Specs.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

LEGEND & ABBREVIATIONS

TELECOMMUNICATIONS

4" CONDUIT SLEEVE

TELE/DATA OUTLET, 5"X5"X2 7/8"D BOX WITH SINGLE GANG

PLASTER RING AND SINGLE GANG COVERPLATE TO MATCH

ELECTRICAL OUTLET COVERPLATE MATERIAL AND COLOR,

18" AFF, UON, WITH 1 1/4"C WITH (4) CAT6 UTP CABLES

(2-GREEN VOICE / 2-GREEN DATA), STUBBED ABOVE TO

CABLE TRAY AND TERMINATED WITH GROUNDING BUSHING.

TELEPHONE OUTLET, 5"X5"X2 7/8"D BOX WITH SINGLE GANG

PLASTER RING AND SINGLE GANG COVERPLATE TO MATCH

ELECTRICAL OUTLET COVERPLATE MATERIAL AND COLOR,

46" AFF, UON, WITH 1 1/4"C WITH (1) CAT6 UTP CABLE (GREEN

VOICE), STUBBED ABOVE TO CABLE TRAY AND TERMINATED

WITH GROUNDING BUSHING.

GENERAL SPECIAL SYSTEMS

THE GENERAL CONTRACTOR SHALL PROVIDE A COMPLETION SCHEDULE, BROKEN DOWN BY

VARIOUS CONSTRUCTION PHASES, FOR TURN OVER OF COMPLETED ROUGH-IN FOR

CONTRACTOR TO FINISH WORK. THE CONTRACTOR SHALL COORDINATE TURN OVER WITH

VENDORS, AND SHALL TURN OVER AREAS WITH ADEQUATE TIME FOR VENDOR FINISH WORK.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY EXTRA VENDOR COST RESULTING FROM

INCORRECT SYSTEMS ROUGH-IN.

THE GENERAL CONTRACTOR SHALL PROVIDE IN-WALL REINFORCEMENT AS NECESSARY FOR

ALL SYSTEMS CABINETS, SHELVES, BRACKETS, FURNITURE MOUNTS, ETC.. AND SHALL MOUNT

CABINETS, SHELVES, BRACKETS, AND FURNITURE MOUNTS IN ACCORDANCE WITH DRAWINGS,

VENDOR SUBMITTALS, AND ALL APPLICABLE CODES.

THE CONTRACTOR SHALL COORDINATE AND PROVIDE ALL REQUIRED RACEWAY SYSTEMS

FOR ALL SPECIAL SYSTEMS INCLUDING CONDUIT WITH PULL STRING, JUNCTION BOXES,

GROUNDING, BACKBOARDS, POWER CONNECTIONS, ETC. THE CONTRACTOR SHALL

COORDINATE ALL ROUGH-IN, BOX SIZES AND CONFIGURATIONS, CONDUIT SIZES AND

ROUTING WITH THE VENDOR PRIOR TO INSTALLATION OF THE RACEWAY SYSTEM.

THE CONTRACTOR SHALL PROVIDE ALL CABLING AND WIRING (EXCEPT POWER WIRING),

CABLE TRAY, JACKS, COVER PLATE COMPATIBLE WITH THE EQUIPMENT, DEVICES, RACKS,

AND COMPONENT EQUIPMENT UNLESS OTHERWISE NOTED.

FINAL DEVICE LOCATIONS AND ELEVATIONS SHALL BE COORDINATED WITH ARCHITECTURAL

PLANS, CASEWORK AND ELEVATIONS, AND VENDOR REQUIREMENTS.

TELEPHONE AND DATA SYSTEMS

THE TELEPHONE AND DATA SYSTEMS WILL BE THROUGH THE CONTRACTOR. THE

CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM AS INDICATED.

ALL CONDUITS SHALL BE 1 1/4" MINIMUM, SHALL HAVE A PULL WIRE AND SHALL BE

TERMINATED WITH INSULATED GROUNDING BUSHING. ALL TELEPHONE, DATA AND CABLE

TELEVISION BOXES SHALL BE 5" X 5" X 2 7/8" DEEP WITH A SINGLE GANG RISE AND BLANK

COVER PLATE UNLESS OTHERWISE INDICATED. COORDINATE CONDUIT QUANTITIES, SIZES

AND LOCATIONS.

STUB ALL CONDUITS WITH PULL WIRE FOR COMMUNICATIONS DEVICE OUT TO CABLE TRAY

AND PROVIDE INSULATED GROUND BUSHING. WHERE A FULL WALL SEPARATES THE CONDUIT

STUB OUT FROM THE DESTINATION ROOM, PROVIDE A 1 1/2" MINIMUM SLEEVE THROUGH THE

WALL, ABOVE AN ACCESSIBLE CEILING, TO ACCOMMODATE THE CABLING. PROVIDE ALL

CONDUITS AND SLEEVES PENETRATING RATED FIRE OR SMOKE WALLS WITH APPROVED FIRE

RETARDANT TO PROVIDE A UL RATED ASSEMBLY. MAINTAIN VENDOR RECOMMENDED

SEPARATION BETWEEN WIRING OF DIFFERENT SYSTEMS AND FROM INTERFERENCE

PRODUCING ELECTRICAL DEVICES SUCH AS FLUORESCENT LIGHTS, BALLASTS,

TRANSFORMERS, RELAYS, MOTOR CONTROLS, ETC..

GENERAL SPECIAL SYSTEM NOTES

REQ'D REQUIRED

PNL PANEL

NATIONAL ELECTRICAL CODENEC

GROUNDGND

EXIST EXISTING

EXISTING TO REMAINETR

CONDUIT C

UNLESS OTHERWISE NOTEDUON

AREA OF REFUGE ASSISTANCEARA

ABBREVIATIONS

ABOVE FINISHED GRADEAFG

ABOVE FINISHED FLOORAFF

FMCP FIRE ALARM/MASS NOTIFICATION CONTROL PANEL

BELOW FINISHED GRADEBFG

BUILDING ENTRANCE PROTECTORBEP

TELECOMMUNICATIONS MAIN GROUND BUS BAR

(4) 4 PAIR 24 AWG

COPPER CAT 6 UTP,

GREEN CABLES

(2) DUAL MOLDED

8P8C JACKS

385 A 386

387 A 388

5" X 5" X 2 7/8" BOX

GREEN COMPUTER

ICON

GREEN

TELEPHONE

ICON

1-1/4"C TO CABLE TRAY

5" X 5" X 2 7/8" BOX

MOUNTING

STUDS

GREEN TELEPHONE

(1) 4 PAIR 24 AWG

COPPER CAT 6 UTP,

GREEN CABLES

(1) GREEN CAT 6 UTP

RJ45 JACKS

FIRST FLOOR108

TMGB

BET

(4) CAT6 UTP

(TYP. FOR ALL TELE/DATA OUTLETS)

FLOOR

MOUNTED

RACK

EXISTING CHAPEL NEW BUILDING - 16A

BUILDING ENTRANCE TERMINAL

NOTE:

(2) 4"C, SCH. 80PVC, CONCRETE ENCASED 24" BFG MIN. (1) 4"C TO INCLUDE (1) 3" 3-CELL MAXCELL FABRIC INNERDUCT WITH

(1) 12 STRAND SMFO, OSP RATED CABLE. (1) 4"C WITH (1) 25 PAIR COPPER TELEPHONE CABLE, OSP RATED TO MANHOLE MH-584.

4"C, SCH. 80PVC, CONCRETE ENCASED 24" BFG MIN. (1) 4"C TO INCLUDE (1) 3" 3-CELL MAXCELL FABRIC INNERDUCT WITH (1) 12 STRAND SMFO, OSP RATED CABLE. (1) 4"C WITH (1) 25 PAIR COPPER TELEPHONE CABLE, OSP RATED BETWEEN BUILDING TELCOMM

ROOMS 108 AND 315

(1) 4 PAIR 24AWG COPPER

(TYP. FOR TELEPHONE

ONLY OUTLETS)

DDC

" M

IN

IM

U M

TRENCH WIDTH

COMPACTED BACKFILL, COMPACT

TO 95% WITH 12" MAXIMUM LIFTS

6"

4" DETECTABLE

WARNING TAPE, ORANGE

REMOVE EXISTING LANDSCAPE

AND PLANT LIFE AND SAVE FOR

REUSE AS APPLICABLE. AFTER

BACKFILL AND COMPACTION IS

COMPLETE, PROVIDE 4" OF

SCREEN TOP SOIL AND PROVIDE

LANDSCAPE AND PLANT LIFE TO

MATCH EXISTING.

SCREENED TOP SOIL, 4"

MINIMUM

FINISH GRADE

12" MINIMUM

#12AWG COPPER SOLID THW

TRACER WIRE

(2) 4"C SCH 80 PVC,

CONCRETE ENCASED

COPPER BASED BOLTS, NUTS, &

LOCK WASHERS (TYPICAL)

STAND-OFF INSULATOR, 1KV

MINIMUM (2" MINIMUM OFFSET)

(TYPICAL)

COPPER MAIN

TELECOMMUNICATIONS GROUND

BUS BAR ( )

4" x 12" x 1/4" THICK (TYPICAL)

TMGB

(1) #6 CU GND IN 3/4"C. CONNECT TO

ELECTRICAL PANEL GROUND ELECTRODE

SYSTEM PER NEC ARTICLE 800

TO BUILDING STEEL

TO CABLE TRAY

TO TELECOM CABINET

MOUNTING BRACKET(S)

FACTORY DRILLED HOLES

(TYPICAL)

CONTRACTOR SHALL SIZE

TELECOMMUNICATIONS GROUNDING

AND BONDING INFRASTRUCTURE PER

ANSI J-STD-607-D

TBB/TBC SIZE (AWG)TBB/TBC LENGTH M (FT)

LESS THAN 4 (13)

4 - 6 ( 14 - 20 ) 6 - 8 ( 21 - 26 ) 8 - 10 ( 27 - 33 )

10 - 13 ( 34 - 41 ) 13 - 16 ( 42 - 52 ) 16 - 20 ( 53 - 66 ) 20 - 26 ( 67 - 84 ) 26 - 32 ( 85 - 105 ) 32 - 38 ( 106 - 125 ) 38 - 46 ( 126 - 150 ) 46 - 53 ( 151 - 175 ) 53 - 76 ( 176 - 250 ) 76 - 91 ( 251 - 300 )

GREATER THAN 91 ( 301 )

TBB - TELECOMMUNICATIONS BONDING BACKBONE

TBC - TELECOMMUNICATIONS BONDING CONDUCTOR

750kcmil 600kcmil 500kcmil 350kcmil 300kcmil 250kcmil

4/0 3/0 2/0 1/0

PRECAST CONCRETE TYPE 2 HAND HOLE. SEE DETAIL THIS SHEET.

UGC UNDERGROUND COMMUNICATION PATHWAY

WIRE BASKET CABLE TRAY, 6" x 4"DEEP

W WIRELESS ACCESS POINT

DUCTBANK AS INDICATED

NOTE

1. CONTRACTOR SHALL PROVIDE PATHWAY FOR ALL LISTED SYSTEMS CABLING. TRAY MUST COMPLY WITH NEC FOR

CABLE TRAY FILL REQUIREMENTS. IN NO CASE MAY THE CABLE TRAY BE LESS THAN THE STATED MINIMUM SIZE.

4" MIN

PROVIDE MANUFACTURER

RECOMMENDED COUPLING TO

SECURELY CONNECT AND

GROUND SECTIONS OF CABLE

TRAY.

TYPICAL CONDUIT STUBBED THROUGH

WALL TO ABOVE CABLE TRAY WITH

BUSHING. PROVIDE #6 AWG GROUND

BETWEEN CONDUIT AND #2 AWG

CABLE TRAY GROUND WIRE.

#6 BOND GROUND

WIRE TO CABLE

TRAY GROUND WIRE

CABLE TRAY

GROUND WIRE, #2.

MOUNT TO SIDE

OF CABLE TRAYSIZE AS INDICATED

G

G

G

#6 BOND TO

CABLE TRAY

GROUND BONDING

CLAMP

1-1/4"C TO CABLE TRAY

COMBINATION TELEPHONE/DATA JACK

SCALE: NO SCALEB

DETAIL

SCALE: XXX X-XXXX

DETAIL NUMBER NAME

SCALE

SHEET REFERENCED FROM

GENERAL

TMGB

BET

HH

WALL TELEPHONE OUTLET

SCALE: NO SCALEA

TYPICAL GROUND BUS BAR DETAIL

SCALE: NO SCALECWIREBASKET CABLE TRAY DETAIL - ABOVE CEILING

SCALE: NO SCALEDPRECAST CONCRETE HANDHOLE DETAIL

SCALE: NO SCALEE

DUCTBANK TRENCH DETAIL - TYPE A

SCALE: NO SCALEF TELECOMMUNICATION RISER DIAGRAM

SCALE: NO SCALEG

4/30/20

TMGB

BET

FLOOR

MOUNTED

RACK

(4) CAT6 UTP

(TYP. FOR ALL TELE/DATA OUTLETS)

REVISION 1 6/6/20201

DIRECT DIGITAL CONTROLDDC

MANHOLE. EXISTING TO REMAINMH

4'-0"

6"

6"

6"6"

4'-0"

PLAN VIEW

SECTION VIEW

6" MINIMUM

6" MINIMUM

12" MAXIMUM

PRECAST CONCRETE RING

WATERSTOP AT ALL

CONSTRUCTION JOINTS, TYPICAL

PRECAST CONCRETE VAULT

DESIGNED TO MEET AASHTO HS-20

LOADING REQUIREMENTS WITH

REINFORCING STEEL PER

MANUFACTURER'S REQUIREMENTS,

MINIMUM CONCRETE

COMPRESSIVE STRENGTH SHALL

BE 5000 PSI

6" MINIMUM6" MINIMUM

4'-0"

MANHOLE FRAME AND COVER

FINISHED GRADE

12"Ø x 4-1/2" DEEP SUMP PIT, SLOPE BOTTOM TO SUMP

DUCTBANK, TYPICAL, REFER TO SITE

PLANS

COMMUNICATIONS

PULLING IRON, TYP OF (4)

30"Ø MINIMUM MANHOLE

COVER

6" MINIMUM

4'-0"

COMPACTED FILL

INCOMING AND EXITING

PVC DUCTBANK

CONDUITS (TYPICAL

ALL CONDUITS), REFER

TO DUCTBANK DETAIL

DUCT ENTRANCE

TELECOMMUNICATIONS BACKBOARD, 4' X 8' X 3/4" FIRE-RETARDANT

TYPE A-C, MOUNT BOTTOM OF PLYWOOD 18"AFF.

PVC BELL END, FLUSH

Sheets and Views
T-001 GENERAL NOTES, LEGEND AND ABBREVIATIONS

File details come from the government source that posted it. Updated .