Limited Lead Paint Survey MCB Camp Lejeune – Protestant Chapel, Building 16 & 16A
Renovation & Addition to Protestant Chapel, Building 16 & 16A Marine Corps Base – Camp Lejeune
Project #19-0038
Report Prepared By:
Christopher B. Walker
The Walker Group Architecture, Inc March 12th, 2020
WGA Project No. – 1907.PROT
Project Information
The Walker Group Architecture, Inc. was contracted by Marine Corps Base Camp Lejeune to conduct a lead paint survey for the Protestant Chapel and Annex Building. The specified building for inspection is under contract for repairs and renovations to the building. The survey was conducted to determine if building components were coated with lead-based paint.
The building consists of:
a. Building 16 is an operational Protestant Chapel and building 16A is the adjacent fellowship hall. The building consists of brick and CMU cavity wall construction with wood stud and gypsum board interior walls. Floors are VCT and carpet with rubber/wood base and ceilings are plaster.
Scope of Services
A. The survey was performed on November 1st, 2019, by Christopher B. Walker (NC Accredited Lead Inspector #110239 expires March 31, 2020. Samples were collected from areas defined by the scope of work.
Findings
A. The Walker Group Architecture collected paint chip samples from each surface visibly coated with a different color of paint and delivered them to EMSL Analytical, Inc. (AIHA ELLAP lab code no. 102564) for analysis for lead content by Flame AAS (SW 846 3050B*/7420) in accordance with EPA 3050B/Modified/7000B.
B. OSHA 29 CFR 1926.62 defines any detectable level of lead in paint a concern when renovations/demolitions will impact lead coated surfaces.
C. The detection limit is determined by weight of the sample, which is typically 0.01%.
See attached Lab Results for additional information.
D. Laboratory Results
Suspect Material Sampled Location Condition Concentration
% by Weight White Interior CMU Interior- Chapel 0.039% White Exterior Wood Trim- Chapel Exterior- Chapel 0.71% Black Interior Wood Interior-Chapel at Stair 0.021% White wood doors/Trim Interior- Annex <0.0080% Tan Gypsum Board Interior- Annex <0.0080% Blue gypsum board Interior- Annex <0.0080% White Exterior Wood Window Sill Exterior- Chapel 0.33% White Exterior Concrete Base Exterior- Chapel 0.061% White Exterior Metal Railing Exterior- Chapel <0.0080%
Based on the sample analysis, the following coatings should be considered Lead Based Paint.
White Interior CMU- Chapel White Exterior Wood Trim- Chapel Black Interior Wood- Chapel White Exterior Wood Window Sill- Chapel White Exterior Concrete Base- Chapel
Recommendations
A. Any demolition/renovation work in which lead coated surfaces are disturbed must be in compliance with all Federal, State, and Local regulations. All work should be conducted by workers trained in "lead safe practices" as outlined by
OSHA.
B. If additional suspect materials are discovered during demolition/renovation, they should be classified presumed to contain lead based paint until sampling by a state of North Carolina licensed Lead Inspector personnel and analysis by an Accredited and state of North Carolina licensed laboratory can be performed.
See attached for Plan Locations, Lead Laboratory Results, and Chain of Custody.
If further information is required, please contact me at 1-252-636-8778
Report Prepared by:
Christopher B. Walker North Carolina Lead Inspector Accreditation# 110239 The Walker Group Architecture, Inc.
PO Box 541 New Bern, NC 28560
ConcentrationAnalyzed Weight Reporting Detection LimitLab ID: LeadCollected
Attn: Chris Walker The Walker Group Architecture PO Box 541 New Bern, NC 28563
Received: 11/08/19 11:15 AM
Protestant Church
Fax: (252) 636-8992 Phone: (252) 636-8778
Project:
11/1/2019Collected:
Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*
EMSL Analytical, Inc.
706 Gralin Street, Kernersville, NC 27284 Phone/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com greensborolab@emsl.com
021907692 CustomerID: WALK85 CustomerPO:
ProjectID:
EMSL Order:
0.039 % wt11/12/2019 .3097 g021907692-0001 0.0080
Client Sample 11/1/2019 pb-01
% wt
0.028 % wt11/12/2019 .3135 g021907692-0002 0.0080
Client Sample 11/1/2019 pb-02
% wt
0.71 % wt11/12/2019 .3021 g021907692-0003 0.080
Client Sample 11/1/2019 pb-03
% wt
0.40 % wt11/12/2019 .2309 g021907692-0004 0.0087
Client Sample 11/1/2019 pb-04
% wt
0.017 % wt11/12/2019 .2148 g021907692-0005 0.0093
Client Sample 11/1/2019 pb-05
% wt
0.021 % wt11/12/2019 .3204 g021907692-0006 0.0080
Client Sample 11/1/2019 pb-06
% wt
<0.0080 % wt11/12/2019 .2604 g021907692-0007 0.0080
Client Sample 11/1/2019 pb-07
% wt
<0.0086 % wt11/12/2019 .2333 g021907692-0008 0.0086
Client Sample 11/1/2019 pb-08
% wt
<0.0080 % wt11/12/2019 .3013 g021907692-0009 0.0080
Client Sample 11/1/2019 pb-09
% wt
<0.0083 % wt11/12/2019 .2416 g021907692-0010 0.0083
Client Sample 11/1/2019 pb-10
% wt
<0.0080 % wt11/12/2019 .3185 g021907692-0011 0.0080
Client Sample 11/1/2019 pb-11
% wt
Page 1 of 2Test Report PB w/RD/I-7.32.3 Printed: 11/12/2019 4:16:17 PM
James Cole, Laboratory Manager or other approved signatory
*Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.008 % wt based on the minimum sample weight per our SOP. Unless noted, results in this report are not blank corrected. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities. Samples received in good condition unless otherwise noted. "<" (less than) result signifies the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. The QC data associated with the sample results included in this report meet the recovery and precision requirements unless specifically indicated otherwise.
Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC EMSL Lab ID 102564 is accredited by the AIHA Laboratory Accreditation Program (AIHA-LAP), LLC in the Environmental Lead accreditation program for Lead in Paint Chips.
Initial report from 11/12/2019 16:16:17 http://www.EMSL.com mailto:greensborolab@emsl.com
ConcentrationAnalyzed Weight Reporting Detection LimitLab ID: LeadCollected
Attn: Chris Walker The Walker Group Architecture PO Box 541 New Bern, NC 28563
Received: 11/08/19 11:15 AM
Protestant Church
Fax: (252) 636-8992 Phone: (252) 636-8778
Project:
11/1/2019Collected:
Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*
EMSL Analytical, Inc.
706 Gralin Street, Kernersville, NC 27284 Phone/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com greensborolab@emsl.com
021907692 CustomerID: WALK85 CustomerPO:
ProjectID:
EMSL Order:
<0.0080 % wt11/12/2019 .2693 g021907692-0012 0.0080
Client Sample 11/1/2019 pb-12
% wt
0.094 % wt11/12/2019 .2367 g021907692-0013 0.0084
Client Sample 11/1/2019 pb-13
% wt
0.33 % wt11/12/2019 .3016 g021907692-0014 0.0080
Client Sample 11/1/2019 pb-14
% wt
0.060 % wt11/12/2019 .2413 g021907692-0015 0.0083
Client Sample 11/1/2019 pb-15
% wt
0.061 % wt11/12/2019 .2182 g021907692-0016 0.0092
Client Sample 11/1/2019 pb-16
% wt
<0.0080 % wt11/12/2019 .2514 g021907692-0017 0.0080
Client Sample 11/1/2019 pb-17
% wt
<0.0085 % wt11/12/2019 .2354 g021907692-0018 0.0085
Client Sample 11/1/2019 pb-18
% wt
Guidelines for Federal USEPA/HUD Lead in Paint Chips =0.5 % Wt or =1.0 mg/cm² is the EPA definition of a lead-based paint.
Above EPA definition of a lead-based paintAbove RL but below EPA definition of a lead-based paint
Below Method Reporting Limit (RL)
These guidance limits are typically used in most scenarios. More stringent local or project specific guidelines may apply.
Please contact the laboratory for statement of uncertainty data for the utility of properly evaluating these results against any regulatory standards or guidelines.
No responsibility or liability is assumed for the manner in which the results are used or interpreted.
Page 2 of 2Test Report PB w/RD/I-7.32.3 Printed: 11/12/2019 4:16:17 PM
James Cole, Laboratory Manager or other approved signatory
*Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.008 % wt based on the minimum sample weight per our SOP. Unless noted, results in this report are not blank corrected. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities. Samples received in good condition unless otherwise noted. "<" (less than) result signifies the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. The QC data associated with the sample results included in this report meet the recovery and precision requirements unless specifically indicated otherwise.
Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC EMSL Lab ID 102564 is accredited by the AIHA Laboratory Accreditation Program (AIHA-LAP), LLC in the Environmental Lead accreditation program for Lead in Paint Chips.
Initial report from 11/12/2019 16:16:17 http://www.EMSL.com mailto:greensborolab@emsl.com
OrderID: 021907692
OrderID: 021907692
| Protestant Chapel Lead Survey |