C9 N4523A26Q1110 65DS1101 RFC 15 Response.pdf

PDF 168 KB Posted

Attached to
Bravo Dive Boat 65DS1101
Solicitation number
N4523A26Q1110
Issued by

About this file

This document is a Government Response to Requests for Clarification (RFCs) containing two specific questions from potential contractors. The first question concerns the thickness of windows, which the government resolved by directing the inquirer to Attachment-8 Amendment 0004 Drawings and References. The second question addresses a Statement of Work (SOW) requirement for a weld inspector qualified per AWS QC1, specifically questioning the ABYC standards compliance and inspection criteria. For this question, the government indicated that the RFC is under review and they intend to provide a response before the end of the solicitation.

View the file

Other files

File Type Posted
C9 N4523A26Q1110 65DS1101 RFC 17 Response.pdf PDF
C9 N4523A26Q1110 65DS1101 Amendment 0005.pdf PDF
C9 N4523A26Q1110 65DS1101 RFC 16 Response.pdf PDF
C9 N4523A26Q1110 65DS1101 Amendment 0004.pdf PDF
C9 N4523A26Q1110 65DS1101 Amendment 0003.pdf PDF
C9 N4523A26Q1110 65DS1101 RFC 13-14 Responses.pdf PDF
C9 N4523A26Q1110 65DS1101 Attachment-1 Statement of Work - Errata 2.pdf PDF
C9 N4523A26Q1110 65DS1101 Amendment 0002.pdf PDF
C9 N4523A26Q1110 65DS1101 RFC 9-12 Responses.pdf PDF
C9 N4523A26Q1110 65DS1101 Attachment-1 Statement of Work - Errata 1.pdf PDF
C9 N4523A26Q1110 65DS1101 Attachment-2 Price Worksheet - Amendment 0001.xlsx XLSX spreadsheet
C9 N4523A26Q1110 65DS1101 Amendment 0001.pdf PDF
C9 N4523A26Q1110 65DS1101 RFC 1-8 Responses.pdf PDF
C8 N4523A26Q1110 65SD1101 Attachment-9 Growth Management Program Tracking Log.xlsx XLSX spreadsheet
C8 N4523A26Q1110 65DS1101 Solicitation.pdf PDF
C8 N4523A26Q1110 65DS1101 Attachment-3 RFC Form.pdf PDF
C8 N4523A26Q1110 65DS1101 Attachment-5 Corporate Experience Data Sheet.pdf PDF
C8 N4523A26Q1110 65DS1101 Exhibit B GFP Attachment.pdf PDF
C8 N4523A26Q1110 65DS1101 Attachment-2 Price Worksheet.xlsx XLSX spreadsheet
C8 N4523A26Q1110 65DS1101 Attachment-1 Statement of Work.pdf PDF
C8 N4523A26Q1110 65DS1101 Attachment-6 Drawings_References Request.pdf PDF
C8 N4523A26Q1110 65SD1101 Attachment-8 Growth Management Request Form.docx DOCX document
C8 N4523A26Q1110 65DS1101 Attachment-7 BAVR Instructions.pdf PDF
C8 N4523A26Q1110 65DS1101 Attachment-4 Contract Performance Data Sheet.pdf PDF
C8 N4523A26Q1110 65DS1101 Exhibit A CDRLs_DIDs Request.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Government Response to RFCs

15) Question: We are unable to locate the thickness of the windows on the referenced drawings In order to get pricing for the new windows, we need to know glass thickness. Can this be provided?

Answer: The drawing showing window thickness is now available. Please see Attachment-8 Amendment 0004 Drawings and References.

16) Question: SOW States: A person qualified as weld inspector per AWS QC1 shall accomplish a visual inspection consisting of hull integrity, deck assessment, structural components to include keel, frames and bulkheads, seaworthiness, ABYC standards compliance and recommendations.

In conversations with multiple entities (CWI & Engineers), the feedback we have received is that it is not clear what the intention of the SOW requirement is. Can you clarify which ABYC standard specifically the requirement is calling out? (ABYC standards typically do not apply to hull integrity). Can you provide any clarifying information on what the baseline is for the inspection criteria?

Answer: This RFC is currently under review. The Government intends to provide a response before the end of the solicitation.

File details come from the government source that posted it. Updated .