EW602 Rev 1.pdf
PDF 142 KB Posted
- Attached to
- Amendment 0010 -Use the applicable Small Business Forms attached Federal contract opportunity
- Solicitation number
- n44255
About this file
This one-line diagram depicts the electrical system for a pier and maintenance facility project. The project involves constructing a general purpose berthing pier and trestle with controlled access, along with a vessel maintenance facility, parking area, and fuel distribution and storage system. The facilities will support maritime force protection and nuclear weapons security missions. Key elements of the electrical system include a 1.5 megavolt-ampere 480V:12.47kV generator, 1100 kilowatt 480Y/277V generator, 500 kilovolt-ampere transformers, medium voltage switchgear, and underground feeders. The diagram shows the interconnections between this equipment and identifies scope items such as replacing feeders and installing a government-furnished generator.
View the file
Other files for this federal contract opportunity
Show all 50
Amendment 0010 -Use the applicable Small Business Forms attached has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P3 M1
P3 M4
Q3 M1
R3 M1
R3 M1A
R3 M1C
500 KVA
B7125
JC-1
P3 T1
P4 M3
Q3 M2
F514
F5
F5
F5
F5
F5
F516
F5
F5
F5
F5
F5
R3 M1D
P3 M2
F514
SEE DWG
EW601 FOR
CONTINUATION
SEE DWG
EW601 FOR
CONTINUATION
SEE DWG
EW603 FOR
CONTINUATION
SEE DWG
EW603 FOR
CONTINUATION
B7136
PAD
MOUNTED
SWITCH
TO EXIST.
PIER 500KVA
XFMR
TO EXIST.
B7136
500KVA
XFMR
TO PIER UNIT
SUBSTATION
SEE DWG
EW604 FOR
CONTINUATION
WATERFRONT FUEL FARM SWGR & GENERATOR (WFFSG)
WFFSGT
1500 KVA
480V:12.47KV
G1
FWE8
F514a
WFFG
1100 KW
480Y/277V, 3Ø, 4W
45 KVA
12:47KV:
208Y/120, 3Ø, 4W
P3 M3
WFFSG208PNL
SEE DETAIL
C4/EW611 FOR
CONTINUATION
TO B7690
TO B7661
FWE8
FWE8
JC-2 8
F514a FWE8 FWFFG
5 SETS (3) #500kCMIL
+ (1) #3/0 EGC
(3) #2 15kV CU +
(1) #2 GND
(3) #500 15kV CU +
(1) #4/0 GND
(3) #2 15kV CU +
(1) #2 GND
PROVISIONED
SPACE
(3) #500 15kV CU +
(1) #4/0 GND
(3) #500 15kV CU +
(1) #4/0 GND
P-01
P3
T2
P3 M2A
SCALE:
EPROJECT NO.:
CONSTR. CONTR. NO.
NAVFAC DRAWING NO.
SHEET OF
DRAWFORM REVISION: 31 JANUARY 2017
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
AS NOTED
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
D E P A R T M E N T
O F
T H E
N A V Y
N A V F A C
N W
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S
IL
V E R D A L E W A S H
IN
G T O N
N A V A L
B A S E
K
IT
S A P B A N G O R
S
IL
V E R D A L E W A S H
IN
G T O N
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
S
YM
D
ES
C R
IP
TI
O N
D A
TE
A P P R
FIRE PROTECTION
XXXXXXX
DAVID GIBSON/TYSON BOLING
XXX
XXX
CHK
:3 :0
P M
C U s e rs jb o u rg e o is D o c u m e n ts P M O D P
IE
R E L E C R jb o u rg e o is V F X .r vt
F Y
M
C O
N P
R O
J E
C T
P -9
T P
P P
IE
R
A N
D M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
5K V
EL
EC
TR
IC
A L O N E-
LI
N E C
N A V A L
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O M M A N D
N O R
TH
W
ES
T
BCPSMB BGA
EW602
1389895
245 269
UNDER PIER LIGHTING SUBMITTAL - NOT FOR CONSTRUCTION - 07/12/19
BCP BGA
G. HANNAN
SCALE: NONE
15KV ELECTRICAL ONE-LINE C
A1
EW601, EW603, EW604,
EW611
GENERAL NOTES:
SHEET KEYNOTES:
1. DEMOLISH EXISTING FEEDER CONDUCTORS.
2. PROVIDE MEDIUM VOLTAGE SWITCHGEAR PER
SPECIFICATION SECTION 26 05 48.00 10.
3. PROVIDE PAD MOUNTED TRANSFORMER.
4. INSTALL GOVERNMENT FURNISHED GENERATOR.
5. PROVIDE REPLACEMENT FEEDER LABELS IN MANHOLE WITH
NEW FEEDER NUMBER.
6. TAP EXISTING FEEDER F514.
7. SERVICE THE EXISTING GE POWER BREAK GENERATOR
CIRCUIT BREAKER AND ADD OPTIONS AS DETAILED IN THE
GENERATOR AND SWITCHGEAR SEQUENCE OF OPERATION
AND THE REQUIREMENTS SHOWN IN THE PROTECTIVE
RELAYING DIAGRAM AND DC DIAGRAMS. BREAKER INFO:
CATALOG NUMBER TP2020SS, SERIAL NUMBER V89037
AND TRIP UNIT RMS-9 MICROVERSATRIP.
8. UPDATE FEEDER LABELS FROM F514 TO FWE8.
9. CONTRACTOR TO PICKUP GENERATOR FROM BEHIND
BUILDING B2001, MOVE AND INSTALL ON THIS PROJECT.
1. ALL EQUIPMENT IS EXISTING UNLESS NOTED OTHERWISE.
GENERATOR AND SWITCHGEAR
SEQUENCE OF OPERATION:
1. NORMAL CONDITION:
A. BREAKER F514a IS CLOSED AND SERVING NORMAL POWER.
B. BREAKER FWFFG IS CLOSED AND ENERGIZING THE GENERATOR STEP UP
TRANSFORMER.
C. BREAKER WFFG IS OPEN.
D. THE GENERATOR IS NOT RUNNING AND IN AUTOMATIC.
E. BREAKER 514A IS EITHER OPEN OR CLOSED.
2. LOSS OF POWER ON F514 WHILE CONTROL IS IN AUTOMATIC.
A. AFTER A UTILITY LOSS TIME DELAY, 5 SECONDS, OPERATOR ADJUSTABLE, THE
GENERATOR START SIGNAL IS SENT.
B. ONCE THE GENERATOR HAS REACHED OPERATING VOLTAGE AND FREQUENCY.
C. OPEN BREAKER F514a.
D. CLOSE BREAKER WFFG.
3. RESTORATION OF POWER TO F514a WHILE CONTROL IS IN AUTOMATIC AND CLOSED
TRANSITION IS SELECTED.
A. AFTER A STABLE AND UTILITY STABILIZATION DELAY, (VOLTAGE AND FREQUENCY
STABILIZATION) 15 MINUTES, EXPIRES
B. GENERATOR SYNCHRONIZES WITH THE UTILITY.
C. ONCE SYNCHRONIZATION OBTAINED MADE BREAKER F514a IS CLOSED.
D. GENERATOR RAMPS LOAD OFF GENERATOR TILL LOAD IS UNDER 100kW.
E. BREAKER WFFG IS OPENED.
F. THE GENERATOR ENTERS A 5 MINUTE COOL DOWN PHASE.
G. ONCE THE COOLDOWN PHASE HAS EXPIRED THE GENERATOR WILL SHUTDOWN.
4. RESTORATION OF POWER TO F514a WHILE CONTROL IS IN AUTOMATIC AND OPEN
TRANSITION IS SELECTED.
A. AFTER A STABLE AND UTILITY STABILIZATION DELAY, (VOLTAGE AND FREQUENCY
STABILIZATION) 15 MINUTES, EXPIRES
B. BREAKER WFFG IS OPENED.
C. BREAKER F514a IS CLOSED.
D. THE GENERATOR ENTERS A 5 MINUTE COOL DOWN PHASE.
E. ONCE THE COOLDOWN PHASE HAS EXPIRED THE GENERATOR WILL SHUTDOWN.
5. GENERATOR NO-LOAD TEST
A. UPON THE OPERATOR SELECTING THE NO-LOAD TEST IN THE HMI OR ON THE
MIMIC PANEL THE GENERATOR IS STARTED BUT BREAKER WFFG IS LEFT OPEN.
B. IF THE POWER TO FEEDER F514a IS LOST THE GENERATOR WILL PROCEED AS
IN CONDITION 2 ABOVE. HOWEVER UPON RESTORATION OF POWER IT WILL
TRANSITION BACK TO UTILITY POWER AS IN CONDITION 3 OR 4 ABOVE BUT THE
GENERATOR WILL BE LEFT RUNNING.
C. UPON THE OPERATOR SELECTING THE AUTOMATIC POSITION IN EITHER THE HMI
OR THE MIMIC PANEL THE GENERATOR WILL STAY IN OPERATION PER SEQUENCE
2 IF NO POWER IS DETECTED ON F514a OR IMMEDIATELY SHUTDOWN IF POWER
IS DETECTED.
6. GENERATOR OFFLINE LOAD TEST CLOSED TRANSITION
A. UPON THE OPERATOR SELECTING THE LOAD TEST IN THE HMI OR ON THE MIMIC
PANEL THE GENERATOR IS STARTED.
B. ONCE THE GENERATOR HAS REACHED OPERATING VOLTAGE, FREQUENCY AND IS
IN SYNC WITH THE UTILITY.
C. CLOSE BREAKER WFFG.
D. OPEN BREAKER F514a.
7. GENERATOR RETURN TO NORMAL AFTER OFFLINE LOAD TEST IN CLOSED TRANSITION.
A. AFTER THE CONTROL IS RETURNED TO AUTOMATIC GENERATOR PERFORMS SAME
SEQUENCE AS IN 3 ABOVE EXCEPT WITHOUT THE UTILITY STABILIZATION DELAY.
8. GENERATOR OFFLINE LOAD TEST OPEN TRANSITION
A. UPON THE OPERATOR SELECTING THE LOAD TEST IN THE HMI OR ON THE MIMIC
PANEL THE GENERATOR IS STARTED.
B. ONCE THE GENERATOR HAS REACHED OPERATING VOLTAGE AND FREQUENCY.
C. OPEN BREAKER F514a.
D. CLOSE BREAKER WFFG.
9. EXITING GENERATOR LOAD TEST OPEN TRANSITION
A. IF POWER IS AVAILABLE ON FEEDER 514a THE GENERATOR WILL SHUTDOWN
PER SECTION 3 ABOVE.
B. IF POWER IS NOT AVAILABLE ON FEEDER 514a THE GENERATOR WILL CONTINUE
TO SUPPLY POWER PER SECTION 2 ABOVE.
10. GENERATOR ONLINE LOAD TEST
A. UPON THE OPERATOR SELECTING THE ONLINE LOAD TEST IN THE HMI OR ON
THE MIMIC PANEL THE GENERATOR IS STARTED.
B. ONCE THE GENERATOR HAS REACHED OPERATING VOLTAGE, FREQUENCY AND IS
IN SYNC WITH THE UTILITY.
C. CLOSE BREAKER WFFG.
D. OPEN BREAKER F514a.
11. EXISTING GENERATOR ONLINE LOAD TEST
A. AFTER THE CONTROL IS RETURNED TO AUTOMATIC GENERATOR PERFORMS SAME
SEQUENCE AS IN 3 ABOVE EXCEPT WITHOUT THE UTILITY STABILIZATION DELAY.
12. IF THE STOP COMMAND IS SENT
A. IF THE STOP COMMAND IS SENT FROM EITHER THE HMI OR MIMIC PANEL THE
GENERATOR BREAKER WFFG WILL OPEN AND THE GENERATOR WILL IMMEDIATELY
SHUTDOWN.
HMI REQUIREMENTS:
1. NORMAL CONDITION: HMI IS IN A SCREEN SAVING MODE OR IN
STANDBY.
2. UPON TOUCHING OR POWERING SCREEN BACK UP.
A. ONELINE OF THE GEAR IS PROVIDED
B. BREAKER STATUS IS SHOWN: OPEN, CLOSED AND PROTECTION
TRIP.
C. GENERATOR STATUS DISPLAYED INCLUDING STOPPED, STANDBY,
RUNNING AND FAULT STATUS.
D. VOLTAGE IS SHOWN FOR THE INCOMING FEEDER 514, BUS AND
THE GENERATOR.
3. SECOND PAGE SHOULD PROVIDE THE FOLLOWING:
A. A GRAPH OF ANY OF THE VOLTAGE AND METERING POINTS
ABOVE FOR THE LAST 24 HOURS.
4. ALARM LOG PAGE SHOWING AT LEAST THE LAST 100 OPERATIONS
AND ALARMS.
5. AFTER ENTERING LOGIN AND PASSWORD INFORMATION THE
FOLLOWING ADDITIONAL FUNCTIONS WILL BE AVAILABLE.
A. PUSHBUTTONS TO ENTER EACH OF THE SEQUENCES ABOVE.
B. CHANGING OF THE FOLLOWING TIMERS:
a. UTILITY STABILIZATION DELAY
b. UTILITY LOSS TIME DELAY
c. GENERATOR COOL DOWN PERIOD
TRANSMIT THE FOLLOWING DATA TO 1305
1. FROM EACH PROTECTIVE RELAY
* METER DATA
* BREAKER STATUS
* RELAY STATUS
* FAULT TYPE
2. GENERATOR DATA
* GENERATOR ALARMS
* GENERATOR RUNNING
* GENERATOR E-STOP STATUS
ELECTRICAL DATA TO 1305
P
AL
P
PI
| P907-MOD01-PIER-1389895-ELEC-R19_jbourgeois2V9FX |
| EW602 - 15KV ELECTRICAL ONE-LINE C |
File details come from the government source that posted it. Updated .