This amendment provides revised small business subcontracting plan templates for offerors to use in response to solicitation number N44255. The solicitation is for construction services to build a general purpose berthing pier and trestle with controlled access, as well as a vessel maintenance facility and fuel distribution and storage system. The facilities will support the Maritime Force Protection Unit at Naval Base Kitsap in Bangor, Washington. Offerors must use the applicable revised small business subcontracting plan templates attached to this amendment when submitting their proposals.
View the file
Other files for this federal contract opportunity
Show all 50
Amendment 0010 -Use the applicable Small Business Forms attached has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PPI
Gov't
Tracking#
Govt Response:
1) Spec Section, Spec Title, para 3, page Please see attached RFI from Skyline Steel regarding steel pipe piles dated 22 July, 2020.
Reference Specification Section 31 62 16.19 Steel Pipe Piles Section 2.1.7 Testing Requirements 5
See revision to spec section 31 62 16.19, see solicitation amendment #006
The coating length for steel pipe piles is estimated per pile on sheet SW601, however, Section 31 62 16.19 2.4 COATING
OF PIPE PILING states that piles should be coated to 20’ below the mudline and include a 5’ tolerance, unless noted otherwise in the drawings.
Please confirm that the coating lengths shown on SW601 are the lengths to be used for estimation purposes. 18
See revision to sheet SW601, see solicitation amendment
#006
Reference: Plan Sheet EW602
Sheet Keynote 9 calls for contractor to relocate existing generator from behind building B2001.
Please provide picture, dimensions, weight and model number of existing generator. 22
See Solicitation Amendment #006, "100kW Generator
Photo Collection" for several photos of inside and outside the generator. Model number for the generator is HC734A
1110kW Genset. Caterpillar serial no. 24Z02276.
Reference: Plan Sheet EB101
Sheet Keynote 6 references P-876 Project As-builts to determine location of U2/M1. Please provide P-876 As-builts. 23
See Solicitation Amendment #006, P876 AS-Built Drawing
E130
Reference: Plan Sheet EW404
Sheet Keynote 1 calls out the provision/installation of two breakers to existing Panel B.
Please provide the panel schedule for Panel B including A.I.C. rating and manufacturer. 24
Assume breaker is 22kA for pricing. Field verify once project is awarded for exact breaker details.
Reference: Plan Sheet EW611, Detail A2
Detail A2/EW611 calls for existing generator WFFG 1100KW to have governor and voltage regulator replaced with new units.
Please provide manufacturer part numbers for the new governor and voltage regulator that will allow closed transitions and parallel operation. 25
Per specification Section 26 32 13.00 paragraph 2.2.2 &
2.2.3 Contractor to select new governor and voltage
regulator as required to perform the sequence of operations on the drawings and match this paticular engine.
Reference: Plan Sheet EW601, EW602, EW603
Plan sheets referenced above have "Preliminary Not For Construction" stamps and the words "Under Pier Lighting
Submittal - Not For Construction - 07/12/19". Plan sheet EW602 contains power and equipment data for installation of the Waterfront Fuel Farm Switchgear and Generator. Please clarify what sheets are "Not For Construction". 37
See revised sheets EW601, EW602, EW603. See solicitation amendment #006.
Reference: Sheet SW526, Section A1. Is the first stage concrete pour for the edge beam designed to support 2’ thick concrete deck pour above?38
See revision to sheet SW526, see solicitation amendment
#006
Ref: Section 01 57 19. The included file with the ESA/MMPA Monitoring Plan requirements appears to be corrupt or is otherwise not readable in PDF. Please provide a clean copy of this document. 39
See revised ESA/MMPA Document. See solicitation amendment #006.
Is there a full Geotechnical Report for the piling / wharf structure that can be made available to proposers? 40 see solicitation amendment #006 for Reports
Specification Section 02 65 00, Underground Storage Tank Decommissioning, states: “The Subsurface conditions are represented in GeoEngineers Draft report titled 'Underground Storage Tank Pre-Decommissioning Environmental
Services…”. Please provide the described report to aid in preparation of proposals. 44 see solicitation amendment #006 for Reports
Specification Section 31 00 00 Earthwork states: “The subsoil investigation report is available to the Contractor.” Please provide the described report to aid in preparation of proposals 45 see solicitation amendment #006 for Reports
CLIN 0001 P907 - Pier and Trestle
CLIN 0002 Vessel Maintenance Facility
The project drawings are divided into Volume 1 (Waterfront) and Volume 2 (VMF).
There is no guidance within the project specification, RFP, or drawings indicating what work is to be priced in these two
CLIN's.
Is all the scope shown in Volume 2 to be included in CLIN 2?
This scope includes, for example:
1. Contractor's laydown area and its associated clear and grub, and TESC measures.
2. Extension of the 2 lane road connecting the P834 project to Sturgeon Street.
If there is scope included in the Volume 2 drawing package that is to be provided in CLIN 1, please clarify the division of scope. 50
Information needed to completely price CLIN 0001 P907 -
Pier and Trestle can be found in the drawing package labeled "Volume 1 (Waterfront). Information needed to completely price CLIN 0002 P907 - Veseel Maintenance
Facility can be found in the drawing package labeled
"Volume 2 (VMF).
Reference: Specification 26 08 00 Apparatus Inspection and Testing
Specification 26 08 00 3.1a calls out tests to be performed on the generator by the start-up engineer. Please provide specification for load bank testing. 51
Load bank is required to preform the test spelled out under
26 32 13.00 paragraph 3.5.2-e. Contractor to determine the load bank to adequately preform the test specified.
Reference: Plan Sheet EW602
Sheet Keynote 9 calls for contractor to pickup generator from behind Building B2001. Please provide location of Building
B2001. 52
Generator location is shown on GW001 as building number
B1056. However B1056 nameplate was from its former life and is not an offical building number anymore. Note building B2001 is at this location.
Reference: Plan Sheet EW611
Please provide plan legend for SCADA cables. 53
See revised drawing EW611. See solicitation amendment
#006.
The PWE (pressure washer enclosure) is shown on drawing AB111 but it is not addressed on the structural drawings.
What is the foundation required for the PWE? Is it a 6” unreinforced concrete slab? Please provide details and dimensions. 55
See revised drawing SB105. See solicitation amendment
#006.
The Door Schedule on AB602 indicates that door number 114-3 is an “Overhead Coiling Counter Height”. The elevations on AB302 and AB602 along with the AB101 plan view and C1/AB301 appear to show a counter. However, there is no counter detailed or specified. Is a counter required at this location? If so, is it plastic laminate, solid surface, stainless steel or some other material? If a counter is required in this location, please provide details. 56
See revised drawing AB501 and AB101. See solicitation amendmnet #006.
On CS102, Keynote 30 is called out in two locations. One is pointing to a location that is called out on drawing EB101 as a
Pad Mounted Transformer. Should Keynote 29 be called out at this location instead? 57
See revised drawing CS102 and CS103. See Solicitation amendment #006.
The Keynote hexagon on A4/AB111 is blank. Should this be keynote 2? 58
See revised drawings AB111, SB105, and AB104. See solicitation amendment #006.
Keynote 22 on CS101 calls out “concrete ramp (4,000 psi)”. Is any steel reinforcing required? What is the concrete thickness? Can we assume that the concrete entry pad detail per A1/CS501 can be applied and that the ramps are 6” thick with no reinforcing? 59
See revised drawing CS103 and CS501. See Solicitation amendment #006.
C4/AB502 shows expanded metal mesh. Expanded metal mesh is also called out by keynote 1 on elevation A2/AB404.
We do not find a specification for this material. Please provide. 60
See revised drawing AB502. See solicitation amendmnet
#006.
Sheet note 3 on drawing AB101 states: “Provide 8’-0” H. ¾” painted plywood protection board at all pre-engineered exterior walls, typ”. The same note occurs on AB603. The Room Finish Schedule on AB603 shows ¾” plywood wainscot on some but not all pre-engineered exterior walls (rooms 108, 109, 110, 111, 112, 113 and 114). Are we correct in assuming that the Room Finish Schedule governs? 61
See revised drawing AB101. See Solicitation amendment
#006.
The Finish Schedule on drawing AB603 calls for high impact protection wall panel wainscot (WP1) in rooms 104, 105 and
106. It seems odd that the Women’s Room would get wainscot but the Men’s Room would not. Are we correct in assuming that room 103 should get WP1 and 106 should not? 62
See revised drawing AB603. See solicitation amendmnet
#006.
Aluminum guardrail is shown on top of the retaining wall per A2/SB501. We do not find a specification for this material.
Please provide. 63
See revised specification section 05 52 00. See solicitation amendmnet #006.
Section 01 57 19 references the final Marine Mammal Monitoring Plan that will be provided to the contractor after award. Please provide the MMMP document so proposers can quantify and price the monitoring work or provide details for the types, locations, and number of monitors proposers should include as a basis for bids. 64
Marine Mammal monitoring requirements are summarized the "Endangered Species Act (ESA)/Marine Mammal
Protection Act (MMPA) Monitoring and Construction
Restriction Requirements attachment to specification section 01 57 19.01 20.
Section 01 57 19 references the final Marine Mammal Monitoring Plan that will be provided to the contractor after award. Please provide the MMMP document so proposers can quantify and price the monitoring work or provide details for the types, locations, and number of monitors proposers should include as a basis for bids. 65
Marine Mammal monitoring requirements are summarized the "Endangered Species Act (ESA)/Marine Mammal
Protection Act (MMPA) Monitoring and Construction
Restriction Requirements attachment to specification section 01 57 19.01 20.
The only specified laydown/staging space available for this contract is shown in Volume 2 drawings adjacent to the VMF building. This area would need to be logged/cleared to create usable laydown space. Given the current bid date and 180 day evaluation period, award of the contract would be anticipated in March of 2021. Per spec, logging is not allowed annually from April 01 through Sept 23. This means the specified laydown area will not be available for use until after
Sept 23, 2021. Is there another staging area the Government will make available to the contractor prior to Sept 2021? 66
A temporary small staging area will be provided for this time between contract award and logging operations.
Location and size are unknown at this time.
Sheet CW570 indicates (2) 10,000 gallon DFM tanks to be decommissioned. Please clarify the requirements (if any) for sequence of work to decommission these tanks relative to work to construct the new fueling system at the KB Docks. 67 See revised specification 01 14 00, see amendment #006.
Reference: EW401, Sheet Keynote 8
Sheet Keynote 8 calls to provide handhole. Please provide size and ID# of handhole. 68
See revised sheet EW401 for handhole size. Lighting handhole does not have an ID. See solicitation amendment
#006.
Reference: EW627
Please provide elevation and detail drawings of enclosures E-01 to E-08 and notes as to what devices are to be installed in each enclosure.
Please provide locations of the following:
Enclosure E-05 in utility building
Enclosure E-06 at pier switchgear
Pullbox PB-04 on the trestle 69
Elevations of enclosures are not required. SYSTEMS -
ENCLOSURE/PULL BOX/VAULT SCHEDULE indicate the size and height of boxes. The notes column indicates what the box is for. The SYSTEMS CABLE SCHEDULE on the same page indicates the required cables and termination devices.
See revised sheet EW401 for E-05 location. See revised sheet EW131 for PB-04 location and Sheet EW627 and
EW628. See revised sheet EW132 for E-06 location. See amendment #006.Reference: Plan sheet EW404
Please add raceways on plan sheet EW404 to Systems Pathway schedule or identify the raceway sizes. 70
See revised drawing EW404. See solicitation amendment
#006.
Reference: Plan sheet EW405, EW612, EW621
Please confirm that DISP-1, DISP-2, DISP-3, and DISP-4 referenced on plan sheets EW405 and EW621 are the same as
DFD1, DFD2, DFD3, and DFD4 on plan sheet EW612. "DFD" is not referenced on any other plan sheet.
Please add FSV2 to one-line for Panel A3. (FSV2 is shown on EW405 and EW621) 71
See revised drawing EW612. See solicitation amendment
#006
Reference: Plan sheet EW602, Sheet Keynote 2.
Sheet Keynote 2 call for provision of Medium Voltage Switchgear per specification section 26 05 48.00 10. Specification section 26 05 48.00 10 is Seismic and Antiterrorism Protection for Electrical Equipment. Please provide a specification section for Medium Voltage Switchgear. 72
See revised drawing EW602. See solicitation amendment
#006.
Reference: Plan sheet EW124
Please provide pathway ID for raceway between under pier luminaires west of raceway L-47. 73
See revised drawing EW124 amd EW629. See solicitation amendment #006.
Reference: Plan Sheet EW602
Please provide serial number and age of existing generator to be relocated. Please provide picture of control panel internal components and terminal strips. 74 See PPI Response #22. See solicitation amendment #006.
Reference: Plan sheet CW121 & CW161
Although showing the same general area, the Concrete Pads shown on drawings CW121 and CW161 differ in dimension.
Drawing CW161 makes references to details on drawing CW566.
Please confirm if the dimensions shown on drawing CW161 are correct. 75
See revised drawing CW161. See solicitation amendment
#006.
Reference: Plan Sheet EW001 - Raceways legend, EW Series Plan Sheets
"Conduit turning up" and "Conduit turning down" symbols appear the same. Please clearly identify symbols and update
EW series sheets where these symbols appear. Conduit turning up or conduit turning down
See revised drawing EW001. See solicitation amendment
#006.
Reference: Plan Sheet EW141
Plan sheet EW141 shows Sheet Keynote 3 referenced eight times but does not provide a description under "Sheet
Keynotes". Please provide a description for Sheet Keynote 3. 77
See revised drawing EW141. See solicitation amendment
#006.
Sheet CE103, Volume 2 shows (5) each existing storage containers in the proposed site for the VMF that contractors are required to relocate. During the site visit on 8/10/2020, it was noted that several additional pieces of equipment are also currently stored at this location. Please confirm all add'l materials and equipment that are not noted on the drawings will be relocated by the Government prior to construction. 79
Yes, all additional equipment will be relocated by the
Government.
Section 09 97 13.26 – Coating of Steel Waterfront Structures, Zero VOC, Splash Zone Coating Per section 1.4.6.10
Qualifications of Coating Contractors and Facilities requires that the coating facility be SSPC QP3 and SSPC QS1 for shop coating.
There is currently no shop in WA, OR or Idaho that has SSPC QP3 and SSPC QS1 certifications.
https://www.sspc.org/search-certifications/ (SSPC website where you can search members with certifications).
Therefore, there is no shop that is qualified the coat the piles in the Pacific NW for TPP Pier.
Would it be acceptable to use a coating specification for the piling similar to FY17 MCON P-834 Seawolf Class Service Pier
Bangor? There area number of facilities locally in the NW that can provide coating and inspection per the P834 spec which will be more efficient and economical for NAVFAC. 80 No, the coating shall be as specified in section 09 97 13.26.
2” Conduit is shown on drawing EW504 for the Fire Alarm Master Box. 1” Conduit (T-57) on drawing EW628 & EW131.
Please advise which one is correct? 81
See revised sheet EW628. See solicitation amendment
#006.
We don’t see any wire for the systems per the schedule on drawing EW628. Please advise what wire if any goes into the systems conduit? 82
Refer to EW627 "Systems Cable Schedule" for required cables.
Electronics Technician Room 107 - Ref AB603 AB101,AB301
Plan view AB101 and section AB301 section C1 appear to show a counter in the Electronics Technician Room 107. Please confirm there is a counter and provide materials and dimensions. 84 See revised sheet AB101. See solicitation amendment #006.
Ref AB603 Material and Finish Schedule-
Material schedule calls out SR1 sheet rubber flooring by Nora Industries, however room finish schedule does not designate any room with sheet rubber flooring. Please indicate where SR1 is used. 85
See revised sheet AB603. See solicitation amendmnet #006.
Section 33 11 00, Part 2.1.1.1.2, states: "Provide restrained joints for pipe and fittings unless otherwise indicated.
Provide flanged joints where indicated.
Sub-line “a” Restrained Joints: Pipe and fitting restrained joints shall be per manufacturer's proprietary design dimensions and configuration. Rubber gaskets, and lubricant for joint assembly, shall be in accordance with
AWWA C111/A21.11
Sub-line “d.” Mechanical Joints: Mechanical joints shall not be used.
With regard to the upland (direct bury), is it acceptable to use Mechanical Joint fittings with Megalug style joint restraints to fulfill the requirement for restrained joints?
Provide restrained joints as specified. See DIPRA (Ductile
Iron Pipe Research Association) publication entitled
"Ductile Iron Pipe Joints And Their Uses" for a description of "Restrained Joints".
Ref C3 on SB004, Ref AB103
Ref SB103-notes 10 and 11
Ref AB501, AB 301
Note10 says to provide flat lid and framing over M E & COMM room per MBM and Note 11 says lid over mechanical room to be designed for loads imposed by mechanical equipment.
Enlarged plan for this area on AS401 has a cut, C3/AB501, through the mechanical platform over Room 119, which shows the structural moment frame support for M2 Mechanical platform. On the same plan there is a cut A1 / AB 301 through
Communications room #120 which does not show lid framing.
Does the lid framing in detail shown on C3/AB501 apply to Rooms 120,121, 122?
East wall of room 114 designates wall type as B1. Is wall type for the wall that borders between room 114 and rooms
119, 120, 121, and 122 all B1?
Lid framing in rooms 120, 121, and 122 should be similar to detail C2/AB501, where 1 layer of gypsum board attaches to metal joinsts. Yes, the south wall of room 114 between rooms 119-122 and is noted as such on AB101 (see wall tag in room 121)
Reference: Plan sheet EW405
Are Type W cables from Panel A3 to Fuel Dispensers 1-4 to be supported or secured to KB Dock? Please provide detail if cables are to be supported or secured. 89
Yes, cables are to be supported to the KB dock. There currently is a non-metallic grating walkway over the dock.
Cables shall be supported to dock below the grating.
Contractor to support with UL approved cable clamp to match existing cabling infrastructure.
Reference: Plan Sheet MW112
Sheet Keynote 7 calls for cables in conduit to run from sensors to leak detection monitoring/alarm panel. Please provide routing and schedule for these raceways. 90
See drawing EW404. Provide flexible control cable on floats per spec section 26 27 29 2.5.7 and 3.1.1
Reference: Plan Sheet EW612
Existing Mound A1-A feeds new panel A3. Shall the (3)#2 + (1)#6EGC be a Type W cable or be run in flex conduit? 91
Provide 2" RTRC nipple between new panel and existing mound. Metallic flex is not allowed because of corrosion issues.
Reference: Plan Sheet EW506, Specification Section 26 56 00 Exterior Lighting
Detail C2/EW506 calls for Fiberglass Pole. Specification 26 56 00 references steel poles and metal poles but not fiberglass poles.
1. Please add specifications for fiberglass poles.
2. Please add taper dimensions/diameter of fiberglass pole to Detail C2.
3. Please give cross sectional area and color to Detail C2 per callout. 92
Poles shall be fiberglass. See revised Specification Section
26 56 00. See amendment #006.
Reference: Plan Sheet EW613, EW625
Plan Sheet EW625 Electrical Pull Box Schedule Lists Vault P-02 and Vault P-03. Plan sheet EW613 shows grounding to
Vault P-03 and P-04. Please confirm that these vaults should be labeled P-02 and P-03, respectively, on sheet EW613. 93
Vault names changed to P-02 and P-03. See revised sheet
EW613. See amendment #006.
Reference: FB502, PB901, PB902, MB701-MB706
It does not appear there is any DDC interface with the FACP, domestic water, natural gas, and compressed air control.
Please confirm DDC integration is not required for these systems.
Fire Alarm Control Panel: No DDC connection.
Natural Gas: Specification 23 11 25 section 2.7.2.1 states to provide "gas meters capable of interfacing the output signal, equivalent to volumetric flow rate, with the existing
UMCS / EMCS".
Domestic Water System: PB602 Water Heater Schedule keynote 1 "provide communication system for DDC monitoring". See revised controls sheet A4/MB703 for domestic hot water circ pump. See amendment #006.
Domestic Water Meter: PB603 Water Meter Schedule keynote 1 "Provide with AMI metering capability". Provide
DDC monotoring of water usage.
Air Compressor: PB602 Air Compressor Schedule note 2
"...electronic controls with screen display mounted on enclosure including interface with building DDC system."
Provide DDC monitoring of Air Compressor.
Reference: Plan Sheet CW154, EW101, EW111
The heated enclosure on sheet CW154 is not shown on the electrical drawings EW101 and EW111.
Please provide raceway and circuit information for powering the heated enclosure for above ground backflow prevention assembly. 96
See revised sheets EW111, EW401, EW621 and EW623. See amendment #006.
Per Specification STEEL PIPE PILES 31 62 16.19 - 3.4.1e, "Perform PDA work at locations indicated to be selected by the
Contracting Officer."
Please confirm the following:
- That piles selected can be driven in accordance with Contractor's proposed schedule and/or Contracting Officer will work with Contractor to determine PDA sequence
- That PDA piles do not need to be driven prior to all other piles 97
Yes, the contracting officer will work with the contractor to determine PDA sequence, and the PDA pile do not need to be driven prior to other piles.
Reference: Plan Sheets EW101, A1/EW401
Question 1: Plan Sheet EW101 calls out ductbank from B7136 Pad Mounted Switch to pier as (4)5". In detail A1/EW401, the same ductbank is called out as (2)5". Please clarify if this ductbank is (2)5" or (4)5".
Question 2: Plan Sheet EW101 calls out ductbank from existing KB dock to new pier as (3)4" and (2)5". In detail
A1/EW401, the same ductbank is called out as (1)2", (3)4", and (2)5". Please clarify what callout is correct for this ductbank. 99
Provide (4) 5"C. See revised sheet EW401. Provide the (1)
2"C for fire alarm. See revised sheet EW101. See amendment #006.
Per Specification Work Restrictions Section 01 14 00 - 1.4.2.2 Searches and Inspections, "All marine vessels are subject to search and inspection by security personnel."
What are the requirements and expected duration of inspection for vessels entering the project site? 100
Security requirements are similar to all other gates on base which vehicles/vessels are subject to inspection. All personnel must be properly badged for the area. Vessel inspections typically do not exceed 1 hour not including gate openings which must be scheduled.
1. Reference: Drawing MW401 Underground storage tanks UST-3 and OWS-1 and Spec section 33 56 10
Factory Fabricated Fuel Storage Tanks and Oil/Water separator
Question: Spec section 33 56 10 is silent on material type to be provided for underground vent piping. Please provide specification section that contains pipe and fitting material to be provided for underground tank vent piping system?
2. Reference: Specification section 33 31 23.00 10 Sanitary Sewer Force Main and Oily Waste Piping – Sub section 2.9.1 Pipe Coatings and Linings Steel, interior and exterior: Liquid epoxy AWWA C210.
Question: Is this coating specification required on exterior and interior of carrier pipe included in Sanitary Sewer/
Oily Waste double wall piping systems? 101
(1) OWS-1 underground vent piping shall be the same material as the OW double wall piping (Section 33 31
23.00 10). OWS-1 aboveground vent piping shall be the same material as the OW single wall carrier piping (Section
33 31 23.00 10) with epoxy coatings as specified in
Section 09 96 00 for ferrous surface coatings. UST-3 underground vent piping shall be the same material as the
SS double wall piping (Section 33 31 23.00 10). UST-3 aboveground vent piping shall be the same material as the
SS single wall carrier piping (Section 33 31 23.00 10) with epoxy coatings as specified in Section 09 96 00 for ferrous surface coatings. (2) Specification 33 31 23.00 10 section
2.9.1 applies to all steel piping for the SS & OW systems, except exterior surfaces of vent piping must be coated as indicated above per Section 09 96 00.
1. Reference: Specification section 33 31 23.00 10 Sanitary Sewer force Main and Oily Waste Piping
Question: No required material type or connection type for above trench pipe and fittings regarding oily waste and sanitary sewer riser connections is included in Specification 33 31 23.00 10. Please provide material specifications for oily waste/sanitary sewer riser pipe and fittings above pier trench? 102
All Oily Waste & Sanitary Sewer piping and fittings
(risers) above trench lids shall be the same material as the carrier piping (as indicated on
Detail C1 / MW502) and fittings (of the double wall piping) below the trench lids, and the exterior surfaces of riser piping and fittings above the trench lids must be epoxy coated as specified in
Section 09 96 00 for ferrous surface coatings.
Drawings EW601, EW602 and EW603 marked Preliminary, not for construction. Are these drawings part of the project? Will the Navy issue new drawings for construction? 103
See revised EW601, EW602, and EW603. See amendment
#006.
Drawing EW602 – Note 2 says to provide MV gear per 26 05 48.00 10. However, Spec section 26 05 48.00
10 is for seismic and antiterrorism protection for Electrical Equipment. Can you please provide the correct spec section for the MV switch gear? 104 See revised EW602. See amendment #006.
Drawing EW602 describes generator and switchgear sequence of operation. Does that mean the MV gear is generator paralleling gear? If so it seems like the MV paralleling gear would come with the generator.
Please clarify if the MV switchgear is Government furnished. 105
Per the sequence of operations given on Sheet EW602, the medium voltage gear shall allow closed transition and extended operation in paralell with the utility. Refer to
Specification Section 26 32 13.00 20 for required upgrades to the existing generator to work with the new gear to allow closed transition and paralelling. MV gear is provided by contractor.
Below are supplier questions for the Hazardous Material Storage Building.
Spec reference: Section 13 34 20
1. Please provide the electrical options required for the Hazardous Materials Storage Building listed in Section 13 34 20 /
# 2.2. No electrical options were included in the specification; however, options will be required for the chemicals being stored.
2. Drawing AB101 shows separate storage bays needed, but the building electrical options and alarms typically required for the storage requirements are not included in the specification.
3. Also on Drawing AB101 the 4 bay chemical storage building will need to be moved out further from the larger building wall, because of the required clearance needed for the electrical options installed on back wall to support the separate bay storage.
4. On Drawing AB101, we recommend that Hazardous Material Storage 119 be quoted as a separate 4 hour fire-rated chemical storage building that will be installed outside next to the larger building with door access directly into the chemical storage building installed on the outside of the larger structure. 106
Furnish interior class 1 /div1 explosion proof LED luminares and switch at doors. Also note the building should be fire sprinklered by manufacturer as noted on the drawings. 2.
Power connection added to sheet EB111. 3. Electrical junction box connection point shall be located on top or side to allow access. 4. Clarification: terminology in specification intended for the prefabricated storage building
(rooms X115-118) rather than room 119.
See revised sheets EB111, EB605, and EB608. See amendment #006.
Section 3.1.b of the MMPA Monitoring and Construction Restriction Requirements states, “Hydroacoustic monitoring will be conducted for 12 piles (3 piles of each size) struck with an impact hammer.” With only three sizes of piling please confirm there will only be 9 piles required to have “Hydroacoustic Monitoring”.
See revised ESA/MMPA Document. See solicitation amendment #006.
Will some of the dock area to the south of the new pier (KB Dock) be made available for the contractor to dock small vessels? 108
Limited Mooring is available, however mooring may be at another Pier other than KB Docks. Boats will need to be removed periodically when no work is to occur. Carderock boat launch is available for small boat launching.
On drawing EW131 “T-61” is called out for a conduit note. We can not see this note on the schedule on drawing EW628.
Please advise? 109
See revised sheet EW628. See solicitation amendment
#006.
The plan dimensions for the concrete utility pads shown on page CW121 do not match the sizes shown on page CW161.
Please clarify the correct sizes. 115
See revised drawing CW161. See solicitation amendment
#006.
Where does specification 03 42 13.00 10 Precast Concrete Products for Below Grade Construction apply? The only below grade precast concrete we see on the drawings are storm water manholes, catch basins and vaults. These items are covered by section 30 40 00. 116
This refers to the Containment Tank that collects wash water from the Wash Rack. Refer to Detail C1/CU502, C1/CU201, and Key Note 21 on CU103.
New natural gas line is shown on drawing MB403. This line connects to an existing line. Will the gas utility, PSE, charge a connection fee? If so, will this fee be paid by the government? Is all work shown on MB403 to be performed by this contractor or will PSE require that their forces or designated contractor perform the work? 117
All work shown will be completed by contractor, except connection to existing main. Coordinate connection with
PSE, including associated fee.
41 22 13.13, Page 5 Section 1.2.2.3 Paragraph 1 - “Swivel bearing sheaves” should be “swivel trunnion”. You have the choice of having or not having swivel trunnion. If you want it please confirm and revise spec. 118
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 10 Section 2.3.1.1 Paragraph 1 - Spec. section states, Bridge travel limit switches are optional. But section 2.4.9.1 states, provide bridge limit switches. Please clarify 119
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 11 Section 2.3.1.2 Paragraph 1 - Spec. section states, Trolley travel limit switches are optional. But section 2.4.9.1 states, provide trolley limit switches. Please clarify. 120
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 13 Section 2.4.5.1 Paragraph 1&2 - Bridge and trolley brakes are electro-mechanical disc type. There is no electro-hydraulic bridge or trolley brakes. Delete the entire section 2.4.5.1 121
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 14 Section 2.4.5.2 Paragraph 1 - Hoist has one holding brake and a mechanical load brake. If there were two holding brakes then this section would apply. Delete the section 122
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 14 Section 2.4.5.2 Paragraph 1 - Hoist has one holding brake and a mechanical load brake. If there were two holding brakes then this section would apply. Delete the section 123
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 15 Section 2.4.7.4 Paragraph 1 - Do not see the requirement of motorized trolley for pendant in the specification. Delete the section. 124
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 17 Section 2.4.12.2 Paragraph 1 - There are no lights, heater, or accessory circuits on the crane.
Isolation transformer is not required. 125
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 18 Section 2.4.12.3 Paragraph 1 - Receptacles are required on the footwalk. But there is no footwalk on the crane. Delete the section. 126
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 18 Section 2.4.12.4 Paragraph 1 - Need detailed specification on the floodlights like level of illumination on the floor level. 127
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 18 Section 2.4.12.5 Paragraph 1 - There is no electrically driven lubrication pump on the crane. Delete the section 128
See revised specification 41 22 13. See amendment #006.
41 22 13.13, Page 19 Section 2.5.2 Paragraph 1 - Is drum grounding a requirement or optional? 129 Drum grounding is required.
On drawing EW131 “T-61” is called out for a conduit note. We can not see this note on the schedule on drawing EW628.
Please advise? 130
See revised sheet EW628. See amendment #006.
There is a Pull Box on Sheet EW131 that is unidentified, located between Grid Lines G & F. Please advise as to what size this box is to be? 131
See response to PPI 069.
Is Panel A3 on drawing EW405 and EW612 new or existing? Please advise? 132 Panel A3 is new.
On drawing EW602 do we replace the feeders between P3/T1, P3/M4, P3/M3, P3/T2 and B7136 Pad Mounted Switch?
We see (3) #500 15kv & (1) #4/0. Please advise if the conductors are existing of if we need to put new ones in? 133
The conduit and conductors between the items listed are existing. Feeder is being re-named and re-labeled per Sheet
Keynote 5.
There is a wire note (T-61) on drawing EW131 that does not show up on the conduit schedule on drawing EW628. Please advise? 134
See revised sheet EW628. See amendment #006.
The Door Schedule on drawing AB602 lists the material for the doors and frame for the main entry door, number 001-1, as steel. However, elevation F1 on AB602 shows a profile that would typically be aluminum. In addition, Hardware
Group 1 is called out for this door and it is titled Exterior Aluminum Entry. Are the main entry doors and surrounding frame to be aluminum or steel? 135
See revised sheet AB602. See amendment #006.
In the equipment list on Sheet MW511, Item I reads, "SUBMERSIBLE TURBINE PUMP WITH LEAK DETECTION & INTEGRAL
ANTI-SIPHON VALVE". An integral anti-siphon valve does exist for a submersible turbine. Please advise of an acceptable alternative anti-siphon. 136
See revised sheet MW511. See amendment #006.
The drawings show a pig launcher is to be installed for the DFM piping run between the utility enclosure and the containment vault. Because this is a one product system (diesel), is a pig launcher necessary? 137
In addition to pipeline cleaning, specialized PIGs can also be used for monitoring pipe thickenss for corrosion. Provide
PIG launcher.
The single wall stainless-steel piping is called out as 316 SS in numerous places, but in the specs in section 33 52 10 2.3.1.1, it calls out a 304 SS flange. Please advise. 139
Stainless Steel piping is Type 316L. Specification 33 52 10
2.3.1.1 should read "Stainless steel flanges shall conform to
ASTM A182/A182M". See revised specification section. See amendment #006.
Are stainless-steel press fittings acceptable for use on this project? 141
No - Stainless Steel press fit couplings are not allowed on the DFM system. Provide pipe and fitting connections as specified in 33 52 10 section 2.4.1 and flanged couplings where indicated per specification 33 52 10 section 2.3. See amendment #006
On sheet CW152, there is reference to Detail A2 / MW412. There is no detail A2 on MW412. 142 See revised sheet CW152. See amendment #006
Section 33 52 11 of the specs describes a utility enclosure with fuel ports to unload diesel from trucks to
UST's. This is not depicted in utility enclosure detail on drawing MW412/A1. 143
Fuel Utility Enclosure (housing fuel filters) does not have fuel intake ports. Fuel fill ports are located directly above each underground storage tank UST-1 & UST-2, as shown on sheet MW111, MW511, and MW611.
Please confirm that the expensive parameters of section 33 08 55 2.2 of the specs is to be adhered to for this simple marine fueling system. 144
Confirmed. Comply with specification 33 08 55 2.2.
Can 2" tank vent risers be made from galvanized steel? 147
No - DFM (DW) or single wall HDPE can be used for fuel tank vent piping. See revised specification 33 52 10 section
2.4.4 for DFM vent piping. See amendment #006.
On MW511, equipment list item S states 4" fill drop tubes are to be stainless-steel. Is aluminum acceptable? 148
No - Provide 316L Stainless Steel.
Sheet MW511 does not specify tank riser material. Is 10mil wrapped, black Sch 40 pipe acceptable? 149
No - Tank risers are 316L Stainless Steel; see Item "S" on sheet MW511.
Can 2" single-wall fiberglass pipe be used for underground tank vents? 150
No - See revised specification 33 52 10 section 2.4.4 for
DFM vent piping. See amendment #006.
Can 4" over 3" double-wall fiberglass pipe be used for underground DFM piping from utiliy enclosure to DFM containment vault? 151
No - double-wall fiberglass pipe is unacceptable.Provide
DFM (DW) pipe as specified in section 33 52 10 paragraph
2.4.3. See amendment #006.
On MW112, Note 9 states "PROVIDE 5FT X 5FT PIPE FOR SEISMIC MOVEMENT...". Neither
DW thermoplastic pipe nor SW stainless-steel pipe will do a 5ft loop. Is a single wall hose being requested? 152
Provide U-shaped exansion loop (using 90 degree double wall elbow fittings) sized as described in keynotes 8 and 9 on sheet MW112.
Please confirm that the expensive parameters of section 33 08 55 3.5 of the specs is to be adhered to.
This specification requests extreme flushing and cleaning for the DFM system. For a marine fueling system of this size, the recommended practice is to pump fuel through the system during startup, purging, and calibration, which is sufficient for flushing of the system.
We request that startup, purging, and calibration be acceptable for cleaning the system. 153
Comply with specification 33 08 55 3.5.
Master Fire Alarm Boxes are shown on drawings EW131, EW132 & EW133. Where do these Master Fire Alarm Boxes terminate at, or where is the head end equipment that they go to? 159
See revised sheet EW404.
Finished Ceiling on Drawing Ab103 in rooms 102 and 103 is showing acoustical tile ceilings, but the room finish schedule on Drawing indicates those rooms to receive drywall ceilings. Please confirm which drawing is correct.
AB103 shows room 102 to receive SATC and room 103 to receive a gypsum board ceiling, while the room finish schedule calls for 102 to receive SATC and 103 to receive gypsum board. AB603 has been updated to show 102 to receive SATC. See revised sheet AB603. See amendment
#006.
Per Drawing AB401, the metal railing at mechanical platform M01 and M02 shows only 8’-0” of guard rail being removable. In contrast, Drawing SB103 also showing the guard rail, but indicates that “all of the guard rails is to be removable”. Please confirm which drawing is correct 163
All sections of railing should be removable per SB103, see revised sheet AB401. See amendment #006.
It is not clear as to the intent of how the maintenance bay walls and ceiling are to be finished. Drawings
AB101, AB301 and AB302 does not call-out or identify how the interior maintenance bay walls are to be finished. Are the maintenance bay walls to be steel stud framed with Type X gypsum board at the full wall height (to the ceiling)? Also, can you confirm how the interior ceiling is to be finished? 164
Walls and ceiling to be exposed to structure/insulation except where walls are to receive plywood wainscot (also see PPI 62 response that addresses wainscots)
RFP Drawings - Vol. 2 (VMF)
Sheets - AB402, AB403, AB603
RFP Specification Section - 06 20 00, paragraph 2.2 Countertops
Question:
Specification Section 06 20 00, paragraph 2.2 Countertops indicate laminated plastic-faced countertops and include associated material requirements. Drawing Sheets AB402, AB403, and AB603 call out solid surface (Corian, Linen Finish) for the countertops in the VMF. Please confirm that all countertops in the VMF shall be Corian, Linen Finish as indicated on drawing sheets AB402, AB403, and AB603. If confirmed, please provide intended finish requirements (i.e. integral backsplash or loose backsplash, edge profile, side splash requirement, etc.) 165
Per AB402 and AB403, base cabinets are to be PLAM and counters solid surface with loose 3/4" thick, 4" high backsplash with 1/4 round bullnote edge (also see PPI 82 response)
RFP Drawings - Vol. 2 (VMF)
Sheets - AB103, AB301, AB603
Question:
VMF RFI: The Room Finish Schedule on Sheet AB603 indicates that Rooms 119, 120, 121, & 122 have an 'Exposed' Ceiling.
However, The Reflected Ceiling Plan on Sheet AB103 illustrates a Gypsum Ceiling Board finish for the same rooms.
Additionally, Building Section A1/AB301 appears to illustrate a suspended gypsum ceiling at Comms Room 120. Please confirm that Rooms 119, 120, 121, & 122 shall have a suspended gypsum board ceiling with painted finish. If confirmed, please also provide ceiling elevation for each room. 166
See response to PPI #88.
RFP Drawings - Vol. 2 (VMF)
Sheets - AB601
Question:
VMF RFI: Contractor requests the following clarifications regarding the Wall Types defined on Sheet AB601:
Wall Type "A" is indicated to construct in accordance with Gypsum Association # WP 1072. Per WP 1072, stud spacing shall be at 24" O.C. Wall Type "A" is shown to have studs at 16" OC Max. Please advise required stud spacing.
Wall Type "C" is indicated to construct in accordance with Gypsum Association # WP 5015. Per WP 5015 stud spacing shall be at 24" O.C. Wall Type "C" is shown to have studs at 16" OC Max. Please advise required stud spacing.
Wall Types do not indicate wall height. Please confirm non-rated walls shall be installed at height above ceiling height.
Please confirm fire rated walls shall be installed to structure above, unless continuous with a rated horizontal assembly.
Please confirm Wall Type "A" shown in notes does not exist. 167
Wall type A should have 16" OC stud spacing, the Gypsum
Association stud spacing is a maximum. 2. Wall type C should have 16" OC stud spacing, the Gypsum Association stud spacing is a maximum. 3. For Non-rated partitions keynote 15 on AB301 and keynote 11 on AB302 refers to
SB106. For rated partitions there should be either a horizontal assembly or the wall should be continuous up to the roof structure. 4. Wall type A is called out several times on AB101.
RFP Drawings - Vol. 2 (VMF)
Sheets - SB102, SB501, AB101
Question:
VMF RFI: Detail B2/SB501 provides CFS Wall Framing Schedule. Contractor requests the following clarifications regarding the information in the schedule:
WT1 is indicated to have a wall height (AFF) of 28' - 0". The location for this wall is shown to be the plan south wall of
Corridor 102, which will have a roof structure at a higher elevation than 28' - 0" AFF. On sheet AB101, this same wall is designated as a 'B1' wall and to be 1 hour fire rated. Please advise if WT1 shall extend to structure above to provide 1 hour fire rating.
WT2 does not specify wall height. On sheets SB102 and AB101, the only WT2 wall (near GL 7.5) is a fire rated wall. Please confirm WT2 shall extend to structure above to provide 1 hour fire rating. 168
1. See section C1/AB301 showing the B1 wall in question
(wall between room 102 and 114) extending to underside of roof. 2. See section A1/AB301 showing the B1 wall in question (wall between room 113 and 114) jogging and extending to underside of roof. See revised SB102 as these walls have been updated to WT3.
RFP Drawings - Vol 2 (VMF)
Drawing AB603 & AB604
Drawing AB603 shows safety glazing in door types D and F1. Similarly, Drawing AB604 shows transparent and operable windows in between the panels P1 and P2. Please provide a specification section for windows and glazing for these elements. 169
See new specifications 08 51 13 and 08 81 00. See amendment #006.
Reference: Plan Sheets EB101, EB505
Plan Sheet EB101 shows XL-03 luminaires to be installed. There are no detail callouts for XL-03 luminaire pole or base installation. Please confirm details B1/EB505 and A1/EB505 are associated with the XL-03 luminaire. 174
The pole and pole base details are for the XL-03 luminaires shown on EB101. See revised sheets EB101 and EB505. See amendment #006.
RFP Drawings - Vol. 2 (VMF)
Sheets - AB402, AB403, AB603
RFP Specification Section - 06 20 00, paragraph 2.2 Countertops
Question:
Specification Section 06 20 00, paragraph 2.2 Countertops indicate laminated plastic-faced countertops and include associated material requirements. Drawing Sheets AB402, AB403, and AB603 call out solid surface (Corian, Linen Finish) for the countertops in the VMF. Please confirm that all countertops in the VMF shall be Corian, Linen Finish as indicated on drawing sheets AB402, AB403, and AB603. If confirmed, please provide intended finish requirements (i.e. integral backsplash or loose backsplash, edge profile, side splash requirement, etc.) 175
See PPI #165 repsponse
RFP Drawings - Vol. 2 (VMF)
Sheets - AB103, AB301, AB603
Question:
VMF RFI: The Room Finish Schedule on Sheet AB603 indicates that Rooms 119, 120, 121, & 122 have an 'Exposed' Ceiling.
However, The Reflected Ceiling Plan on Sheet AB103 illustrates a Gypsum Ceiling Board finish for the same rooms.
Additionally, Building Section A1/AB301 appears to illustrate a suspended gypsum ceiling at Comms Room 120. Please confirm that Rooms 119, 120, 121, & 122 shall have a suspended gypsum board ceiling with painted finish. If confirmed, please also provide ceiling elevation for each room. 176
Refer to sim previous PPI #88
RFP Drawings - Vol. 2 (VMF)
Sheets - AB601
Question:
VMF RFI: Contractor requests the following clarifications regarding the Wall Types defined on Sheet AB601:
Wall Type "A" is indicated to construct in accordance with Gypsum Association # WP 1072. Per WP 1072, stud spacing shall be at 24" O.C. Wall Type "A" is shown to have studs at 16" OC Max. Please advise required stud spacing.
Wall Type "C" is indicated to construct in accordance with Gypsum Association # WP 5015. Per WP 5015 stud spacing shall be at 24" O.C. Wall Type "C" is shown to have studs at 16" OC Max. Please advise required stud spacing.
Wall Types do not indicate wall height. Please confirm non-rated walls shall be installed at height above ceiling height.
Please confirm fire rated walls shall be installed to structure above, unless continuous with a rated horizontal assembly.
Please confirm Wall Type "A" shown in notes does not exist. 177
Refer to PPI #167 response
RFP Drawings - Vol. 2 (VMF)
Sheets - SB102, SB501, AB101
Question:
VMF RFI: Detail B2/SB501 provides CFS Wall Framing Schedule. Contractor requests the following clarifications regarding the information in the schedule:
WT1 is indicated to have a wall height (AFF) of 28' - 0". The location for this wall is shown to be the plan south wall of
Corridor 102, which will have a roof structure at a higher elevation than 28' - 0" AFF. On sheet AB101, this same wall is designated as a 'B1' wall and to be 1 hour fire rated. Please advise if WT1 shall extend to structure above to provide 1 hour fire rating.
WT2 does not specify wall height. On sheets SB102 and AB101, the only WT2 wall (near GL 7.5) is a fire rated wall. Please confirm WT2 shall extend to structure above to provide 1 hour fire rating. 178
Refer to PPI #168 response
Ref
SB102
C1SB301
AB103
C1 /AB301
A3 and A4/ AB501
Section C1 on SB 301 gives foundation detail occurring at metal building column ad the window panel through grid line E.
According to SB 02 this footing is 6 ft wide and 2’-6” deep carrying a 5 inch slab on grade per C1/ SB301.
A cut, C1 /AB301 , through the same area on drawing AB103, shows details at building perimeter of A3 and A4 on AB501.
In these details the metal building wall appears to sit on a curb out board of the slab with rigid insulations sandwiched between this curb and the foundation.
Please confirm there is no curb on top of the 5 inch SOG and that rigid insulation would be placed to the exterior of the
SOG and of the footing. 182
Provide curb per revised structural drawing C1/SB302, exterior insulation is acceptable. See amendment #006.
What are the charge weights and stand-off distances for the project? Translucent Panel Spec 086045, paragraph 1.1 (last sentence) states, “Systems must meet requirements of UFC 4-010-01”. Then in paragraph 1.2, the last line item, it references the 2012 edition of the UFC 4-010-01/DOD Minimum
Antiterrorism standards for Buildings. I cannot get pricing on the translucent panels until I have this information. The blast requirements could change the bay spacing, could require stronger mullions and potentially double walled perimeter I beams. 183
The government established the VMF to be located more than 50 feet on the interior side of a controlled perimeter during the design phase; therefore, construction standoff distances do not apply per Interim Technical Guidance (ITG
2018-02), Implementation of NAVADMIN 026/18 Policy and
Exemptions to Minimum Antiterrorism UFC Standards for
Navy Projects— 12 March 2018. This ITG exemption has been incorporated into subsequent releases of UFC 4-010-
01 FYSA.
This PPI is regarding HV-1, HV-2, and HV-3.
Spec section 23 54 16 paragraph 2.3.1 requires maximum air temperature rise of 7 deg F during minimum operation.
Modulating gas burners carry a 40% turndown ratio, which correlates to a 32 degree max temperature rise at minimum airflow.
Please confirm a temperature rise of 32 degrees is acceptable. 185
See revised specification 23 54 16. See amendment #006.
Specification 03 31 29, paragraphs 1.8.6.4 discusses options for Supplemental Corrosion Protection (SCP) in the event concrete mixes don’t meet service life in durability modeling, options include premium rebar use and corrosion inhibitor admixture.