This document is an amendment to a solicitation for the Repair of Boilers, Associated Services and Distribution Systems. The key details are:

The amendment provides answers to an RFI question regarding work orders completed over the last five years. It also requires the contractor to acknowledge receipt of the amendment prior to the offer due date. The solicitation is for a contract to provide labor, equipment, and materials for repairs and maintenance of boilers, valves, piping systems, and other power plant equipment and systems at the Naval Submarine Base New London. The contract has a performance period of 1 year. Pricing details are not provided in the amendment. The contracting activity is the Department of the Navy Naval Facilities Engineering Command.

View the file

Other files

File Type Posted
Amendment 3.pdf PDF
Wage Determination.pdf PDF
RFI Form.pdf PDF
Amendment 1.pdf PDF
Attachment 15 0100000 C Boilers.pdf PDF
Attachment 5 NEPA.pdf PDF
Attachment 1 General Contract Information.pdf PDF
Attachment 14 J150200005 Historical WOs.xls XLS spreadsheet
Attachment Sheet.xlsx XLSX spreadsheet
Attachment 9 J020000005F On site Labor Summary Report.xls XLS spreadsheet
Attachment 12 J020000009 UEM Contractor Outage Process.pdf PDF
Attachment 13 J150200004 Service Order Summary Report.xls XLS spreadsheet
Attachment 17 0200000 F Boilers.pdf PDF
Attachment 4 J020000008 Boilers ELINS.xlsx XLSX spreadsheet
Attachment 3 J150200003 Map.pdf PDF
25R2506 (1442).pdf PDF
Attachment 11 J020000007 Cont Haz Mat Inv Log.pdf PDF
Attachment 19 1502000 C Boilers.pdf PDF
Attachment 2 J150200006 BLDG 29 Boiler Specifications.pdf PDF
Attachment 18 0200000 J Boilers.pdf PDF
Attachment 21 1502000 FAP Boilers.pdf PDF
Attachment 10 J020000006 Install Spill Control Plan.pdf PDF
Attachment 20 1502000 F Boilers.pdf PDF
Attachment 16 0200000 C Boilers.pdf PDF
Attachment 6 J150200007 NLON Inventory.xlsx XLSX spreadsheet
Attachment 8 J020000005E Quality Inspec Survey report.xls XLS spreadsheet
Attachment 22 1502000 J Boilers.pdf PDF
Attachment 23 1502000 M Boilers.pdf PDF
Attachment 7 J020000005D Contractor Incident Report.pdf PDF
Attachment 24 1502000 PAP Boilers.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE OF PAGES

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

Answer RFI Question: Could you provide a summary of all work orders completed over the last five years with as much information as possible?

Summary of all work orders (scope of works) over the last five years are provided below. This amendment needs to be signed and returned with proposal.

NAVFACSYSCOM MID-ATLANTIC

PWD NEW LONDON

BOX 400.BLDG 135

NAVAL SUBMARINE BASE NEW LONDON

GROTON CT 06349-5026

See Item 6

N4008525R2506

11/08/2024

10/11/2024

Title: Power Plant Repairs of 1S Boiler Combustion Controls

Prepared by: Stacey Sangillo

Date: September 13, 2019

Performance Period: 90 calendar days eProjects #:

Attachments:

SCOPE OF WORK:

1) 1S Boiler Repairs (Thermal Production Commodity)

a) Request service technician to perform troubleshooting of combustion system on boiler 1S. Boiler 1S is constantly tripping due to low O2 and will not fire consistently above 33% firing range. Request service technician service for 2 weeks.

URGENCY: Heating season begins October 15th and this boiler is necessary to be in service for heating season. Boiler cannot currently reach full load capacity.

Title: FY2023 Power Plant Boiler #4 Repairs

Date: December 29th, 2022

Performance Period: 60 calendar days eProjects #:

Attachments: 20221229 GE Power Plant Boiler #4 Repairs

This is to be a task order on the Boiler Maintenance contract.

1) Boiler #4 Repair

a) Provide all labor, materials, and equipment for repair of Boiler #4 Throat.

b) Services include providing necessary welding and pipefitting skills to repair/replace boiler throat gasket after boiler experienced a “puff”.

c) Provide parts as necessary to support gasket replacement.

d) Provide materials for resealing of boiler including manhole gaskets, handhole gaskets, and two boxes of 1/2” rope.

f) Coordinate outage schedule with power plant staff. Due to nature of work and winter season, only one boiler can be in an outage at a time.

2) Boiler #4 Tuning

a) After repair is complete and boiler is closed, provide all labor, materials, and equipment for three days of tuning services in support of Boiler 4.

b) Services include providing monitoring equipment for exhaust gases and correcting the fuel curve of unit into environmental parameters. Tuning also to ensure proper combustion of unit.

c) Provide parts and equipment (O2 analyzer, Nox analyzer, etc) as necessary to support tuning process.

Maximo#: DNGTJR Date: 06/18/2019

Various Electrical Projects Phase I (B29 2400V Relays, Replace GE Relays)

Statement of Work (SOW) NAVFAC Mid-Atlantic Public Works Department, New London in Groton, CT

Requirements:

The contractor is responsible for the following:

a.) The work shall be phased to minimize electrical system outages and provision shall be made to provide temporary electrical service if the affected facility cannot tolerate an outage of sufficient duration to complete the work.

b.) Schedule will be based on personnel and equipment availability.

Contractor shall complete all work 45 days from award of contract contingent on work site availability. Contractor shall notify PWD/FEAD if 45 days is not feasible due to material availability.

c.) Preliminary reports are required only for equipment that has failed to meet performance standards.

d.) Final reports will be issued in both electronic (Adobe PDF, unlocked for comments, page extraction and page deletion) and hard copy form no later than 10 business days after the completion of the work. The final report will include both the failure and retest reports for any failed equipment.

e.) All computer generated models (Example: SKM) will be provided at the completion of the project.

f.) Contractor will incorporate as-built changes into existing AutoCAD drawings.

g.) Obtain all necessary permits and licenses prior to the performance of the subject work.

h.) Install all products in accordance with recognized trade practices by licensed tradesmen skilled in their fields.

i.) Install all products in accordance with existing local, state, and federal laws and guidelines.

j.) Clean up and repair of any damage to government-owned facility, equipment, or grounds as a result of contractor activity (or their representatives) and to maintain the site free of debris and clean at all times.

k.) The contractor shall ensure that its employees conduct themselves in a businesslike, professional manner at all times while on site.

l.) Provide all owners’ manuals and other original equipment manufacturer (OEM) provided documents on all installed equipment (if applicable).

m.) Provide feedback with regards to any changes, additions, and/or modifications to the SOW as necessary.

n.) Removal and proper disposition of work-related scraps, garbage, and debris.

o.) The contractor shall comply with the NEC, NFPA, OSHA life safety regulations and the Army Corps of Engineers standards while working on SUBASENLON.

p.) All testing shall be in compliance with the most recent NETA standards.

q.) Public works shall be informed of any discrepancies. If at any time during the contract unforeseen problems arise, the contractor shall stop work for that section of work and consult the PWD/FEAD engineer at once. No further or additional work shall take place until approved by the PWD/FEAD engineer.

r.) If the contractor requires storage or lay down areas for materials and or equipment arrangement shall be made with the PWD.

s.) The contractor will compile and submit a cost estimate (material and labor) for needed repairs identified beyond the scope of work.

Work Location: SUBASENLON

Hours of Operation:

All work shall be performed between the hours of 0800 to 1600 Monday through Friday.

Government Technical Point of Contact:

Christopher Manner NAVFAC PWD New London P.O. Box 400, Building 135 Groton, CT 06349-5400

(860) 694-3590 Christopher.Manner@navy.mil

Security Information:

a.) The contractor shall make arrangements with the Public Works Department (PWD) Utilities or FEAD electrical engineering technician to obtain any required base passes.

b.) All work for this project will be on the lower base and will require a base security pass and vehicle inspections. All persons working on lower base must receive radcon training.

c.) All contractor equipment, personnel and vehicles are subject to inspection and search by US government security officials (or designated representatives) upon entry to any government owned and/or operated installations and facilities.

d.) Contractor personnel shall comply with all local base/installation security procedures required to gain access to US Government ships, facilities and other assets.

e.) The contractor shall comply with all SUBASE emergency drills and training exercises that may take place while working on base.

f.) If directed by US government security officials (or designated representatives), the contractor shall remove any equipment or personnel considered a security risk.

g.) Government reserves the right to visit, inspect and travel with contractor assets that will be used in support of the requirement.

h.) The contractor shall coordinate and comply with “all security requirements” regarding each personnel assigned to this project through the assigned FEAD Engineering Technician or designated representative within 10 working days of the contract release (or effective date, whichever comes first).

Authorized Changes Only By the Contracting Officer a.) The Contractor shall not comply with any order, direction or request of Government personnel unless it is issued in writing and signed by the Contracting Officer, or is pursuant to specific authority otherwise included as a part of this contract.

b.) The Contracting Officer is the only person authorized to approve changes in any of the requirements of this contract and notwithstanding provisions contained elsewhere in this contract, the said authority remains solely the Contracting Officer's.

Applicable Documents: N/A

Scope of Work:

a.) Power Plant 2400V Relays

a. Remove all 16 of the General Electric DIACA5A, Rev B feeder protective relays currently located in in-service cells. Replace them with Basler BE1-50/51B-218 relays.

b. Supply 2 Basler BE1-50/51B-218 relays as spares

c. Remove and dispose of all six (6) of the known faulty GE DIACA5A, Rev B relays currently located in spare cubicles. Leave the empty cases and relay faces in place.

d. Ensure relays are tested against the appropriate TCC.

e. Ensure relay settings agree with any recommended protective device settings.

f. Apply voltage or current to all analog inputs and verify correct registration of the relay meter functions.

g. With breaker in the test position, verify electrical operation by protective relays.

h. Functional Operation (Perform as Applicable):

i. 50 Instantaneous Overcurrent Relay

1. Determine pickup.

2. Determine dropout.

3. Determine time delay.

ii. 51 Time Overcurrent

1. Determine minimum pickup.

2. Determine time delay at two points on the time current curve.

1.0 PROJECT DESCRIPTION

A. Background. Per Regulations of Connecticut State Agencies Section 22a-174-22 and boiler operating permit number 070-0283 boiler stack emission testing for Nitrous Oxides shall be conducted every five years from the date of the previous stack test. In order for the boilers to be emission testing ready a boiler recalibration/tuning will be necessary. Additionally boilers must be recalibrated for peak heating season and summertime light load operation. Recalibration involves balancing the fuel to air ratio to run at the highest efficiency possible while adhering to Connecticut Department of Energy and Environmental Protection (CT DEEP) emission limitations. Supplying excess air to boilers while ensuring complete combustion of fuel also has the detrimental effect of diluting combustion products and lowering their temperature. Lower temperature combustion products transfer less heat to boiler feed water increasing the amount fuel required to produce the same volume of steam created with less excess air. During the winter time (peak heating season) the excess air introduced to the boiler is cooler and less humid and the summer (low steam demand) the excess air introduced to the boiler warmer and more humid. These seasonal changes combined with changes in boiler loading necessitate recalibration (tuning) of boilers at least semi-annually. The installation of a condensate return meter is necessary to better understand and manage boiler plant operations. The amount of condensate returned for use in the boiler determines how much make-up water will need to be introduced into the system. Condensate return water is generally re-introduced to the boiler feed water system at a much higher temperature than make-up water reducing the amount of boiler heat input energy from fuel to create steam. Having a condensate return meter will assist in identifying boiler performance issues.

B. Existing Site Conditions In the past boiler calibration/tuning services have been performed by Frank I. Rounds Company under the Boiler Maintenance Contract with the latest set of boiler tuning for boiler 4 occurring in March 2022.

C. Scope of Work

1. Annual Boiler Certification Services

a. Provide all labor, materials, and equipment for 20 days of boiler fine tuning services in support of Boiler 1S and Boiler 4. One week of tuning services will be required for each boiler during their overhaul periods prior to (October/November) and following (April/May) the heating season months. Boiler 4 will need to be tuned in March 2024 and late October or early November 2024. Boiler 1S will need tuned in May 2024 and late October or early November 2024.

b. Tuning services provided shall include: the real time monitoring and analysis of boiler stack exhaust gases for adjusting each unit’s excess air to fuel ratio for compliance with Connecticut Department of Energy and Environmental Protection (CT DEEP) air emission standards while providing the highest boiler combustion efficiency possible.

c. Supply boiler replacement parts as necessary to facilitate the boiler tuning process.

d. Provide materials to reseal boilers to include manhole gaskets, hand hole gaskets, and two boxes of 1/2” rope gasket. Provide materials for the re-sealing of the front door inner-pass for each boiler as recommended by the manufacturer.

e. Provide recertification of two boiler emergency safety relief safety valves and recommend replacement if warranted.

i. Kunkle Valve (EMRN.CRN0G0787.5CL)

1. Model- 6252AMK01-AS

2. Size- 3”

3. Setting – 150 PSI

4. Capacity – 30,297 lb/hr

ii. Kunkle Valve (EMRN.CRN0G0787.5CL)

1. Model- 6252ALJ01-AS

2. Size- 2 ½”

3. Setting – 150 PSIG

4. Capacity – 24,008 lb/hr

f. Coordinate the scheduling of each required boiler outage with the power plant staff.

Due to installation steam demand, only one boiler can be out of services at a time.

g. Provide four (4) sets (8 total bottles total) of calibration gases for tuning of each boiler’s combustion gas excess oxygen sensor.

h. Provide two (2) new boiler feed water safety valves (one for each boiler).

i. Make – Kunkle Valve (EMRN.CRN0G0787.5CL)

1. Model- 9188BEDE06BJE

2. Size – ¾”

3. Setting- 300 PSIG

4. Capacity- 106 GPM

2. Install Condensate Flow Meter

a. Install Magnetic Flowmeter on discharge line of condensate pumps. Modify discharge piping to include isolation valves and a bypass loop to accommodate energized system maintenance of meter. Arrange piping in such a way to ensure that piping segment with the meter remains full of water. Pipe is 3” Schedule 80 Carbon Steel.

b. Provide a Rosemount 8750 series or equal meter with flanged connections and PTFE liner capable of enduring high temperatures and maintaining compatibility with existing boiler metering equipment. Provide a wall mounted transmitter configuration. Provide a Rosemount 775 Wireless “THUM” adapter to be connected to plant wireless system. Equip meter with submersion resistance potting with 100’ submersible cable.

c. Recommended Flow Meter Model: 8750WDMW1A1FTSA030CA1S10

d. THUM model: 775XD11NAWA3WK9

e. Coordinate Flowmeter installation with plant operation staff.

f. If the piping associated with installing the condensate meter is installed piecemeal then it will not require any special rigging. However, if the piping is prefabricated then it may require rigging to position the assembly in the fuel oil pit.

From: Sandmel, Christopher A LCDR USN SUBASE NEW LONDON CT (USA) To: Eller, David H CIV USN NAVFAC MIDLANT NOR (USA); Works-Dennis, Dawn M CIV USN NAVFAC MIDLANT NOR

(USA); Milkowski, Matthew R LCDR USN NAVFAC MIDLANT NOR (USA) Cc: Sangillo, Stacey A CIV USN NAVFAC LANT NOR VA (USA); Giangregorio, Michael A CIV USN NAVFAC MIDLANT

NOR (USA); Blackley, Joshua G LT USN NAVFAC MIDLANT NOR (USA); Papitto, John A CIV USN NAVFAC MIDLANT NOR (USA); Smith, Timothy P CIV USN NAVFAC MIDLANT NOR (USA); Buren, Aaron V LT USN NAVFAC

MIDLANT NOR (USA)

Subject: RE: Plant Gas Compressors - SOW and GE Date: Friday, January 29, 2021 20:21:06

Mike, In accordance with 15 Jan MIDLANT After Hours and Emergency Contract Guidance memo, I am providing authorization for this contract action and NTP (NTE $30k). Once particulars are arranged with CBR, please provide details so I can inform Ops chain.

V/r, PWO

Sent with BlackBerry Work (www.blackberry.com)

From: Eller, David H CIV USN NAVFAC MIDLANT NOR (USA) <david.eller@navy.mil> Date: Friday, Jan 29, 2021, 8:07 PM To: Works-Dennis, Dawn M CIV USN NAVFAC MIDLANT NOR (USA) <dawn.works-dennis@navy.mil>, Milkowski, Matthew R LCDR USN NAVFAC MIDLANT NOR (USA) <matthew.milkowski@navy.mil> Cc: Sangillo, Stacey A CIV USN NAVFAC LANT NOR VA (USA) <stacey.sangillo@navy.mil>, Giangregorio, Michael A CIV USN NAVFAC MIDLANT NOR (USA) <michael.giangregorio@navy.mil>, Sandmel, Christopher A LCDR USN SUBASE NEW LONDON CT (USA) <christopher.sandmel@navy.mil>, Blackley, Joshua G LT USN NAVFAC MIDLANT NOR (USA) <joshua.blackley@navy.mil>, Papitto, John A CIV USN NAVFAC MIDLANT NOR (USA) <john.papitto@navy.mil>, Smith, Timothy P CIV USN NAVFAC MIDLANT NOR (USA) <timothy.smith5@navy.mil>, Buren, Aaron V LT USN NAVFAC MIDLANT NOR (USA) <aaron.buren@navy.mil> Subject: RE: Plant Gas Compressors - SOW and GE

Just adding Dawn, LT Buren and LCDR Milkowski to this email.

v/r David Eller Public Works Manager PWD New London Work Phone: (860) 694-4484 Cell: (860) 772-8528 e-mail: David.Eller@navy.mil

From: Papitto, John A CIV USN NAVFAC MIDLANT NOR (USA) <john.papitto@navy.mil>

Sent: Friday, January 29, 2021 8:04 PM To: Giangregorio, Michael A CIV USN NAVFAC MIDLANT NOR (USA) <michael.giangregorio@navy.mil>; Sandmel, Christopher A LCDR USN SUBASE NEW LONDON CT (USA) <christopher.sandmel@navy.mil>; Eller, David H CIV USN NAVFAC MIDLANT NOR (USA) <david.eller@navy.mil>; Blackley, Joshua G LT USN NAVFAC MIDLANT NOR (USA) <joshua.blackley@navy.mil>; Smith, Timothy P CIV USN NAVFAC MIDLANT NOR (USA) <timothy.smith5@navy.mil> Cc: Sangillo, Stacey A CIV USN NAVFAC LANT NOR VA (USA) <stacey.sangillo@navy.mil> Subject: Plant Gas Compressors - SOW and GE

Proposed Task Order on CBR Boiler Maintenance Contract.

1) Hire Contractor Enerflex, the specialist who’s done previous work on our Gas Compressors.

2) Provide 1 day of onsite field service technician, including 2 days travel expenses. Include

$2500 of material in proposal.

3) Plant will LOTO units, and provide electrical/mechanical support to Contractor as needed.

4) Contractor shall investigate/troubleshoot/fix Lube Oil temperature faults on South Gas

Compressor and restore to full functionality.

5) Contractor shall investigate/troubleshoot/fix potential gas valve leak on North Gas

Compressor and restore to full functionality.

6) Contractor shall startup both units, including checking for proper pressures, temperatures, flows, and any leaks.

7) Contractor shall provide a report summarizing work done.

GE

1 day tech $3000 2 day travel $6000 Misc material $2500

Subtotal $11500 10% CBR markup $1150

Total $12650

V/r John Papitto, UEM

Title: Replace Induce Draft Fan and Motor on Boiler #4, B29

Date: December 20, 2019

Performance Period: 60 calendar days eProjects #:

Attachments: a) ID Fan Submittal

b) Picture fan location (within document)

c) Picture motor data (within document)

This is to be a task order on the new Boiler Maintenance contract.

SCOPE OF WORK:

1) Replace Induced Draft Fan on Boiler #4 (Thermal Production Commodity)

a) Purchase and install Induce Draft (ID) Fan with motor. See attached specification sheet. Replace in kind and replace motor with same electrical requirements.

b) Provide a lift plan to meet all safety requirements in EM-385. Plan is to be approved by PW Crane/Rigging prior to work start.

c) Upon arrival of new fan and motor, setup scaffolding and rigging to prepare to remove old induce draft fan and motor.

d) With power plant assistance, ensure lock out tag out is performed on fireside of Boiler #4 and fan electrical system to remove ID fan.

e) Power plant staff will perform electrical disconnect of fan motor.

f) Support, rig, unbolt, and lower ID fan and motor.

g) Rig, bolt, and install new ID fan and motor. Provide all necessary material to install fan and motor.

h) Plant staff will provide electrical reconnect when requested by contractor.

i) Remove scaffolding and clean up site. Discard fan and motor.

Attachment: b) Picture fan location

Fan location is difficult to work.

Located 30 ft above nearest platform.

Bearing is located within the breeching.

Attachment c) Picture motor data

Title: FY2021 Power Plant Repairs, Reverse Osmosis Unit

Date: December 1, 2020

Performance Period: 60 calendar days eProjects #:

SCOPE OF WORK:

1) Replace Motorized Valve and associated Plugs

a) Purchase and install motorized valve. Replace motor with same electrical requirements.

b) Upon arrival of valve, setup rigging to remove old valve.

c) With power plant assistance, ensure lock out tag out is performed on water system.

d) Power plant staff will perform electrical disconnect of motorized valve.

e) Support, rig, unbolt, and lower valve.

f) Rig, bolt, and install new valve. Provide all necessary material to install valve (gaskets, seals, bolts, grease, etc.)

g) Plant staff will provide electrical reconnect when requested by contractor.

h) Remove rigging and clean up site. Discard valve.

i) Replace plugs on locations needed on RO unit.

j) Test run unit for proper operations.

27 December 2021

AIR EMISSIONS TESTING OF CATERPILLAR GENERATORS

STATEMENT OF WORK (SOW)

US NAVAL SUBMARINE BASE NEW LONDON

GROTON, CONNECTICUT

PROJECT DESCRIPTION

A. Background Two non-emergency Caterpillar diesel generators (EU-448 & EU-449) in the power plant (B-29) provide electrical power on demand as well as emergency operation use. The Connecticut Title V Operating Permit requires annual air emissions testing of both units. For 2022, the required testing includes emission factors for carbon monoxide (CO) and nitrogen oxides (NOx).

B. Existing Conditions Air Emission Stack testing of the two Caterpillar diesel generators were previously completed the week of 17-21 August 2020 and the week of 5-9 July 2021. Air Emissions Stack Testing is due again on or before July 6, 2022 on both Caterpillar Diesel Generators.

The Emissions Testing needs to be scheduled and intent to test (ITT) forms submitted to Connecticut Department of Energy and Environmental Protection (CTDEEP) via Subase Environmental Division at least 60 days prior to the scheduled test dates.

C. Scope of Work The contractor shall provide labor, materials, and equipment required to perform the work described in this SOW. The contractor is responsible for providing ladders to access the established sampling locations on each catalyst inlet and stack location. The contractor shall provide the testing services according to the monitoring requirements in the Title V Operating Permit and in 40 CFR 63, Subpart ZZZZ using the applicable EPA test methods described in 40 CFR 60, Appendix A.

C.1 Air Emissions Testing The contractor shall provide a minimum of three trained personnel to perform the following:

1. Prepare and submit the Intent to Test (ITT) application to CTDEEP no later than 60 days before the scheduled tests date.

2. Perform the required emissions stack testing for CO and NOx on both diesel generators.

in accordance with the attached proposal (Appendix A) dated 11/30/2021 on the scheduled date.

3. Provide the tested emissions factor results in multiple units per the reporting instructions.

4. The contractor is responsible for submitting the results report to the CTDEEP after the tests are completed as described in Section E Reports.

5. The contractor is responsible for all for fees to the CTDEEP for the stack testing.

The Environmental Division Air Program Manager will be the sponsor for the security clearances for the access to lower base. The Air Program Manager will be present at the testing site during the tests. One CTDEEP representative will also be present to observe the tests. Utility Control Room personnel in Building 29 will work with the contractor to operate the generators at varying loads during the tests. The Subase will provide space for a 12’ long enclosed trailer adjacent to the garage door on the north side of the Power Plant (B- 29). In addition, electrical power along with access to the control room and the roof will be provided.

D. Guidance Documents Connecticut Title V Operating Permit 070-104-TV: Section III Subsection G.2(b)(i)(C) Regulations of Connecticut State Agencies (RCSA) Section 22a-174-22e Code of Federal Regulations Title 40 Part 63, Subpart ZZZZ Code of Federal Regulations Title 40 Part 60, Appendix A Test Report – July 2021 – Diesel Generator RICE MACT Compliance Test Program, Air

Tox Environmental Company, Inc.

E. Reports

The contractor shall provide a report detailing all collected data and results for the combined test scenarios within 60 days following completion of each field effort, or as soon as lab samples have been processed. If the test scenarios are completed over separate mobilizations, a separate report will be generated for each scenario. The reports will also include a description of the sampling and analytical methodologies used, process conditions and a detailed interpretation of the information gathered.

Because these test scenarios are structured to demonstrate compliance with both the CT DEEP permit requirements and with the EPA RICE MACT, the report will address both State and Federal requirements and will be suitable for submission to the EPA and CT

DEEP.

Appendix A: Air Tox Environmental Company, Inc. Proposal No. 22017 – Navy Base Caterpillar RICE 5-year Testing Program 2022

November 30,2021

James R. Norris Air Programs Manager, Environmental Division

US NAVAL SUBMARINE BASE NEWLONDON

Building 439, Room 104 Groton, CT 06349-5400

RE: Air Tox Proposal No. 22017 - Navy Base New London Caterpillar 5-Year Compliance Test

Dear Mr. Norris, Air Tox Environmental Company, Inc. (Air Tox) of Willington, Connecticut, is pleased to present this proposal to the United States Navy Submarine Base New London (SUBASENLON) for performing emissions testing at the powerhouse at the Navy Submarine Base located in Groton, Connecticut.

The Scope of Work provided below is based on Air Tox’s understanding of the units to be tested, the facility’s operating permits, and the EPA and CT DEEP testing requirements.

Table 1

List of Sources, Possible Testing Scenarios, & Respective Pollutants

Test Scenario

Unit ID

Test Condition

Pollutants Tested

Test Motivator

TS 1

Diesel Gen 1, EU-449

Firing Oil

Outlet: NO + CO

Inlet: CO

CT DEEP NSR Permit 070-0285, RCSA 22a-174-22e

RICE MACT (40CFR63 ZZZZ)

TS 2

Diesel Gen 2, EU-448

Firing Oil

Outlet: NO + CO

Inlet: CO

CT DEEP NSR Permit 070-0286, RCSA 22a-174-22e

RICE MACT (40CFR63 ZZZZ)

SCOPE OF WORK

Air Tox will provide an accurate measurement of emission rates for the pollutants listed in Table 1 respective to each test scenario.

The data collected during these test program will consist of defensible, quality assured data that will be used to demonstrate the facility’s compliance with the respective allowable emission rate limits in accordance with the U.S. Environmental Protection Agency (US EPA) and the Connecticut Department of Energy and Environmental Protection (CT

DEEP).

Air Tox Environmental Company, Inc.

Proposal No. 22017 – Navy Base Caterpillar RICE 5-Year Testing Program 2022 Page No. 1

Test Protocol & Test Notification

Upon award of contract and subsequent request to test, Air Tox will prepare a Site Specific Test Plan (Test Protocol) detailing the methodologies that will be used to perform the compliance test program. The document will contain a brief introduction, including a proposed schedule, as well as sections detailing the plant operations, sampling and analytical methodologies, and quality assurance procedures.

The protocol will be suitable for submission to the CT DEEP & EPA as applicable.

Air Tox will notify, at the client’s request, the CT DEEP in writing of the facility’s intention to conduct the performance test at least 45 calendar days prior to the test date. The notification will also include the aforementioned Site Specific Test Plan.

Test Scenario 1 – Caterpillar Diesel Generator No. 1 Compliance Test

Air Tox anticipates that this test program will take a single mobilization effort and a single day (approximately 9 hours onsite) to perform the testing in accordance with the required EPA Methods. This is contingent on full cooperation from the facility and prompt operation of the equipment.

The test program will consist of three (3) one-hour test runs for concentration and mass-rate measurements of pollutants NO and CO and concentration measurements of diluents O and CO from the exhaust stack of the source. The concentration of CO and O prior to the oxidation catalyst will also be measured simultaneously with the outlet measurements.

All testing must be performed while the unit operates at “Worst Case Conditions” as specified in the air permit greater than 90% of maximum rated capacity (MRC) as determined by heat input to satisfy the CT DEEP’s test requirement. It will be the facility’s responsibility to maintain the appropriate load for the test runs.

Table 2

Test Scenario No. 1 Test Method List & Sampling Format

Emission Parameter Reference Method Sampling Format Sample Location

Diluents (O & CO ) EPA Method 3A 3 x 60 minute runs Continuous Sampling DG-1 Stack

Volumetric Flow Rate EPA Methods 1 & 2 3 x 12 point Traverses DG-1 Stack

Exhaust Moisture (H O) EPA Method 4` 3 x 60 minute runs Integrated Sampling DG-1 Stack

Oxides of Nitrogen (NOX) EPA Method 7E 3 x 60 minute runs Continuous Sampling DG-1 Stack

Carbon Monoxide (CO) EPA Method 10 3 x 60 minute runs Continuous Sampling DG-1 Stack

CO EPA Method 10 3 x 60 minute runs Continuous Sampling DG-1 Catalyst Inlet

Diluent (O ) EPA Method 3A 3 x 60 minute runs Continuous Sampling DG-1 Catalyst Inlet

Proposal No. 22017 – Navy Base Caterpillar RICE 5-Year Testing Program 2022 Page No. 2

Also included will be a No. 2 fuel oil sample that will be analyzed by Sterling Analytical Laboratory in Springfield, MA. The analysis will determine the actual O Fuel F-Factor for determining lb/hr and lb/MMBTU emission rates while firing fuel oil.

Test Scenario 1 – Caterpillar Diesel Generator No. 2 Compliance Test

Air Tox anticipates that this test program will take a single mobilization effort and a single day (approximately 9 hours onsite) to perform the testing in accordance with the required EPA Methods. This is contingent on full cooperation from the facility and prompt operation of the equipment.

The test program will consist of three (3) one-hour test runs for concentration and mass-rate measurements of pollutants NO and CO and concentration measurements of diluents O and CO from the exhaust stack of the source. The concentration of CO and O prior to the oxidation catalyst will also be measured simultaneously with the outlet measurements.

All testing must be performed while the unit operates at “Worst Case Conditions” as specified in the air permit greater than 90% of maximum rated capacity (MRC) as determined by heat input to satisfy the CT DEEP’s test requirement. It will be the facility’s responsibility to maintain the appropriate load for the test runs.

Table 3

Test Scenario No. 2 Test Method List & Sampling Format

Emission Parameter Reference Method Sampling Format Sample Location

Diluents (O & CO ) EPA Method 3A 3 x 60 minute runs Continuous Sampling DG-2 Stack

Volumetric Flow Rate EPA Methods 1 & 2 3 x 12 point Traverses DG-2 Stack

Exhaust Moisture (H O) EPA Method 4` 3 x 60 minute runs Integrated Sampling DG-2 Stack

Oxides of Nitrogen (NOX) EPA Method 7E 3 x 60 minute runs Continuous Sampling DG-2 Stack

Carbon Monoxide (CO) EPA Method 10 3 x 60 minute runs Continuous Sampling DG-2 Stack

CO EPA Method 10 3 x 60 minute runs Continuous Sampling DG-2 Catalyst Inlet

Diluent (O ) EPA Method 3A 3 x 60 minute runs Continuous Sampling DG-2 Catalyst Inlet

If the DG-2 test program is able to be tested during the same mobilization as the DG-1 test program (Air Tox anticipates that this will be the case), only the single fuel sample will be taken and analyzed as described for Scenario 1, and this single sample will be applied to both engines, as the fuel for both units is from the same source. If DG-2 is tested during another independent mobilization, a discrete fuel sample will be taken and analyzed and used to determine the DG-2 emission rates.

Proposal No. 22017 – Navy Base Caterpillar RICE 5-Year Testing Program 2022 Page No. 3

Test Reports

Within thirty (30) days following completion of each field effort, or as soon as lab samples have been processed, a report detailing all collected data and results for the combined test scenarios will be submitted to the client for review. If the test scenarios are completed over separate mobilizations, a separate report will be generated for each scenario. This report will also include a description of the sampling and analytical methodologies used, process conditions and a detailed interpretation of the information gathered.

Because these test scenarios are structured to demonstrate compliance with both the CT DEEP permit requirements and with the EPA RICE MACT, the report will address both State and Federal requirements and will be suitable for submission to the EPA and CT DEEP.

Miscellaneous Diagnostic Sampling/Test Event

Should SUBASENLON require additional air emissions measurements for diagnostic and internal purposes for any of the sources covered in this proposal, Air Tox will bill according to the price scheme below.

For this event, Air Tox can provide real-time measurements for NO , CO, O , and CO to Navy Personnel. All sampling results will be provided to the client on the day of testing, including raw data and test summary sheets. Formal CT DEEP notification and formal report writeup are not included in this price.

For testing of parameters beyond those listed above, (e.g. NH , CH O, Particulate) additional pricing can be provided.

Proposal No. 22017 – Navy Base Caterpillar RICE 5-Year Testing Program 2022 Page No. 4

FUNDING

Air Tox proposes to perform the Scope of Work detailed above for fees as outlined below.

TS 1 – Caterpillar Generator No. 1 Compliance Test (EPA + CT DEEP) .....................................$ 4,850 TS 2 – Caterpillar Generator No. 2 Compliance Test (EPA + CT DEEP) .....................................$ 4,850 Misc. Diagnostic Testing Event ( 9 Hours On Site, 1 Day, Mobilization Included) ......................$ 3,900 Additional Testing Day Extension (i.e. Test Program Extend beyond a single day per source)...$ 2,400

Costs include all testing and documentation outlined above, including equipment and laboratory analysis fees. Cost also includes a single mobilization to and from each site.

Process upsets, unusually inclement weather, or other factors beyond the direct control of Air Tox that would require additional time may impose additional costs. No additional costs will be billed, however, without prior approval from the client.

In the event that Air Tox is unable to perform services due to problems or delays on-site beyond the control of Air Tox the following cost will be incurred:

Delayed less than 8 hours on-site $240/hour*

Delayed an entire day on-site $2,400/day**

*- No additional cost would be incurred if total time of the delays were not greater than 2-hours within a single day on-site. However, if the total time of the delay exceeds the 2-hour allotment then the- accumulated time delayed will be charged.

** - This cost would be incurred only if the entire crew remained on-site during an entire 8-hour day without performing any of the testing tasks.

Air Tox can begin work on the project immediately upon receipt of a purchase order. Once scheduled, a minimum of 10 working days notice will be required to reschedule any fieldwork without cost impact.

Proposal No. 22017 – Navy Base Caterpillar RICE 5-Year Testing Program 2022 Page No. 5

TERMS AND CONDITIONS

The client will be invoiced for the testing program in accordance with the following: 100%

Upon completion of the field effort.

All invoices are payable upon receipt. Prices quoted do not include state and local taxes, if applicable. This quotation is valid for a period of 60 days and is based on mutually acceptable terms and conditions. As part of this project, the client will be expected to provide the following:

Sampling ports & safe access thereto (scaffolding and man lifts if necessary).

240/120VAC 30amp Single Phase circuit and 4 prong receptacle. Adequate 120 VAC circuits for test equipment.

Sampling ports & safe access thereto (scaffolding & man lifts if necessary).

Pertinent process descriptions, drawings, and operational data, if required.

Personnel to record process data and coordinate the test program.

Operation of the facility at the required loads and/or conditions for a time period adequate to complete testing.

Cooperation towards successful completion of the project.

Air Tox appreciates this opportunity to be of service to SUBASENLON. If you have any questions, or require further information, feel free to contact me at your convenience.

Regards, Air Tox Environmental Company, Inc.

Will Beckwith, Project Engineer Air Tox Environmental

479 Tolland Turnpike Willington, CT 06279 Phone: 860-487-5606 x100 Mobile: 860-490-1989 will@airtoxenviro.com www.airtoxenviro.com

Proposal No. 22017 – Navy Base Caterpillar RICE 5-Year Testing Program 2022 Page No. 6

Title: FY2023 B29 Boiler Plant Repairs Prepared by: Chris Mason Date: 2023-02-07 Performance Period: 365 calendar days eProjects #: 1599821

This is to be a task order under the Boiler Maintenance contract.

SCOPE OF WORK:

1. Annual Boiler Certification Services

a. Provide all labor, materials, and equipment for ten days of tuning services in support of Boiler 1S and Boiler 4.

b. Services include providing monitoring equipment for exhaust gases and correcting the fuel curve of unit into environmental parameters.

c. Provide parts as necessary to support tuning process.

d. Provide materials for resealing of boiler including manhole gaskets, handhole gaskets, and two boxes of 1/2” rope gasket.

e. Provide recertification for two safety valves and replacement if necessary.

f. Coordinate outage schedule with power plant staff. Due to nature of work, only one boiler can be in an outage at a time.

g. Provide eight (8) sets of calibration gases for tuning boiler excess oxygen transmitter

2. Perform Air/Stack Testing on Caterpillar Generators

a. Provide 2 sets (mobilizations) air emissions testing for units to be determine by environmental requirements.

b. Emissions testing to include notification to state, testing reports, and coordination with base environmental department.

c. CO testing for Caterpillar Diesels is required to be completed by 7/5/2023 or base could receive Notice of Violation (NOV). State requires notification of testing 90 days prior to testing or NOV could be issued. Notification must occur by 4/5/2023. Contract award must be completed in April 2023.

d. Also include with price, payment of CTDEEP fee for Air inspector labor.

3. Perform Air/Stack Testing on Boiler 1S

a. Provide 2 sets (mobilizations) air emissions testing for units to be determine by environmental requirements.

b. Emissions testing to include notification to state, testing reports, and coordination with base environmental department.

c. NOx testing for Boiler 1S using Natural Gas and #2 Fuel Oil. Boiler 1S required to be completed by 7/20/2023 or base could receive NOV. State requires notification of testing 90 days prior to testing or NOV could be issued.

Notification must occur by 4/20/2023. Contract award must be completed in April 2023.

d. Also include with price, payment of CTDEEP fee for Air inspector labor.

e. Provide two days of boiler manufacturer’s representative to assist during emissions testing

4. Upgrade Existing Condensate Receiver in Lower Level

a. Goals of the replacement are to increase capacity, update strainer to basket type, re-pipe receiver vent to be full size

b. Replace existing condensate receiver in location “Lower Level 1S”

c. Existing model: Hoffman Watchman WC-12-20-B (160031)

d. Requirements of replacement tank:

i. Increase tank size to at least 23 gallons

ii. Duplex pumps

iii. Duplex pump controller

e. Recommended Replacement: Hoffman SCC3B

i. This recommended replacement has the same inlet height as the existing, eliminating a significant amount of piping re-work

f. Replace existing y-type strainer with new basket type recommended by receiver manufacturer

g. Replace all inlet piping from first valve to receiver

h. Replace all discharge piping from the receiver to the first valve off of the plant condensate header

i. Install isolation and check valves on both pump discharges

j. Install all new vent piping at full size of vent discharge of receiver

k. Scheduling: It is recommended that this replacement take place during a cold steel.

Coordinate with plant to schedule

Title: FY2022 Power Plant Repairs

Date: March 23, 2022

Performance Period: 365 calendar days eProjects #:

Attachments: 20220223GE 2022 Power Plant Repairs, US.Subase.NewLondon.ZZZZ.Letter.Final

This is to be a task order on the Boiler Maintenance contract.

1) Annual Boiler Certification Services

a) Provide all labor, materials, and equipment for ten days of tuning services in support of Boiler 1S and Boiler 4. Boiler certification expires at the end of May.

b) Services include providing monitoring equipment for exhaust gases and correcting the fuel curve of unit into environmental parameters.

c) Provide parts as necessary to support tuning process.

d) Provide materials for resealing of boiler including manhole gaskets, handhole gaskets, and two boxes of 1/2” rope.

e) Provide recertification for two safety valves and replacement if necessary.

f) Provide repair to safety valve piping connection to 1S boiler. Current connection is leaking.

g) Replace tube in Boiler 1S that was recommended by boiler inspector.

g) Coordinate outage schedule with power plant staff. Due to nature of work, only one boiler can be in an outage at a time.

2) Repair condensate lines from B29 to B318

a) Provide all labor, materials, and equipment to demolish and install new condensate lines from the fuel pit of B29 to first valve in B318. Estimated to be around 100 ft of condensate line (3” to 4” diameter). Site visit required to determine material requirements.

b) Condensate replacement work will be in tunnel and trench of SUBASE New London.

These are confine spaces.

c) Also provide and install new condensate pumps and motors. Government will provide electrical services to install motors for pumps.

d) Provide and install new condensate receiver tank. Due to the possibility of difficult access to tank area. Evaluate, design, propose and submit solution of new tank installation. - Due to location of tank, and access government will consider other options proposed by contractor.

e) If abandon hot heating piping is still in place by the time this contract is awarded, request to demolish this piping to access condensate lines. Remove and dispose of piping.

3) Air Testing

a) Request mobilization of air testing contractor to perform sampling testing for diesel generators. Testing protocol is to be submitted to environmental for approval. Test methods will be generated to meet recommended suggestions received from EPA letter addressed to Mike Brown. Re: EPA Response with Instructions for Moving Forward with Alternative Monitoring Request for Petition for Alternate Catalyst Inlet Temperature Range. Letter is provided as attachment.

Title: FY2021 Power Plant Gas Purging and Tuning

Date: January 22, 2021

Performance Period: 90 calendar days eProjects #:

Attachments: 20210122 GE Power Plant Gas Purging and Tuning

1) Gas Purging

a) Provide two mobilizations of gas purging.

b) A mobilization is considered an entire purge of 400 linear feet of natural gas lines at Building 29 stopping at Eversource’s equipment.

c) Plant manager will provide coordination between Eversource and contractor.

d) Eversource will be responsible to secure gas from main line.

e) Contractor will provide labor and materials to purge 400 linear feet of natural gas line.

f) The first mobilization for gas purging is expected to take place in April 2021. The next event will be determined in coordination with the base energy project.

2) Boiler Tuning Services

a) Provide labor for ten days of tuning services in support of Boiler 1S and Boiler 4.

b) Services include providing monitoring equipment for exhaust gases and correcting the fuel curve of unit into environmental parameters.

c) Provide parts as necessary to support tuning process.

d) Provide materials for resealing of boiler including manhole gaskets, handhole gaskets, and two boxes of 1/2” rope.

Title: FY2021 Power Plant Repairs, Boiler 1S O2 Analyzer

Prepared by: John Papitto

Date: April 9, 2021

Performance Period: 30 calendar days eProjects #: 1599821

Attachments:

SCOPE OF WORK:

1) Provide Boiler 1S O2 Analyzer

a) Purchase and provide (1) Rosemount In-Situ Flue Gas Oxygen Transmitter, Order Model # 6888A-1OXY-4-1-1HT-04-01-0-0-0-0, with all appurtenances per attached Rosemount Quote 81571-0-JP dated 4/8/21.

b) Purchase and provide (1) Rosemount General Purchase Electronics, Order Model # 6888XI-1OXY-4-1-1HT-02-00-00-00-00-00, with all appurtenances per attached Rosemount Quote 81571-0-JP dated 4/8/21.

c) Plant staff will install.

BID DOCUMENTS SUBMISSION

PREPARED BY: UTILITIES AND ENERGY MANAGEMENT BRANCH

BUILDING 135 NAVAL SUBMARINE BASE GROTON CT 06349

Non Destructive Examination of Deaerating Tanks

Prepared by: Mike Sprague, P.E.

Mechanical Engineer

Request for Proposal:

The work described in this Statement of Work involves Non Destructive Examination (NDE) of Two Deaerating (DA) Tanks in the Power Plant (B 29).

General Work Requirements:

Provide all labor, equipment, materials, testing, transportation, permits, licenses, and supervision necessary to complete the work required for the contract and to provide a complete and usable system.

All work shall be in conformance with all applicable Referenced Criteria, Construction Standards, Current Federal, State, Installation, Local Laws and Regulations, including applicable Building and Fire and Life Safety codes. The advisory provisions of all codes and standards shall be mandatory, as though the word “shall” had been substituted for “should” wherever it appears. Reference to the “authority having jurisdiction” shall be construed to mean “Contracting Officer”. Comply with current Federal, State, County, and Local Environmental Regulations. When discrepancies in the referenced standards and the contract requirements occur, the more stringent requirements shall govern. Only new materials and equipment shall be installed in the work. All materials, equipment and appliances shall be of the current manufacturers’ products. No obsolete or discontinued materials and equipment shall be used, except that construction materials containing recycled content that completely comply with all materials specifications found elsewhere may be used. (Refer to NEPA for any additional requirements)

General Specification

The Contractor shall remove all debris off Government property daily.

The Contractor or Contractor Representative shall have a valid driver’s license, valid and current registration and vehicle insurance to obtain vehicle pass.

All employees are required to be either United States citizens or documented legal residents (status verified by prime contractor). All Contractor employees shall obtain the required employee and vehicle passes. Personnel will be issued appropriate identification badges when the Contractor submits, in writing on company letterhead, a list indicating that all individuals are bona fide employees. Employees shall complete questionnaires and other forms as required by Installation order.

Workers are required to have a current and valid RADCON AWARENESS card.

RADCON Training is available directly from the RADCON Department located on Lower Base. They are located in building 76 and can be reached at the following number: 860 694 2970.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .