This document summarizes a hazardous materials survey report for a proposed shoot house project at Marine Corps Base Camp Lejeune in Jacksonville, North Carolina. The report identifies building materials tested for asbestos, lead-based paint, polychlorinated biphenyls, and other hazardous materials. No asbestos was found in samples of duct mastic or concrete masonry unit sealant. Paint samples contained lead, cadmium, chromium, arsenic, barium, selenium and silver above detection limits. Lead wipe samples and soil samples around the building identified varying levels of lead. Fluorescent light fixtures contained mercury-containing lamps. Recommendations are provided for regulatory compliance during renovation and demolition.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-1514 Shoot House Building RR249
Marine Corps Base Camp Lejeune Jacksonville, NC
Clark Nexsen #9893
GER 130-8061
Prepared for
Dana Cook Clark Nexsen
Prepared by H. Nelson Adcock
NC Asbestos Inspector # 13140
REPORT OF
HAZARDOUS MATERIALS
CONSULTING SERVICES
Southern Professional Center 1 2712 Southern Boulevard, Suite 101 Virginia Beach, Virginia 23452
(757) 463-3200 Fax (757) 463-3080 E-mail germail@geronline.com
January 10, 2023
Clark Nexsen 4525 Main Street, Suite 1400 Virginia Beach, Virginia 23462
Attention: Dana Cook, Project Manager
Subject: Hazardous Materials Consulting Services P-1514 Shoot House Building RR249 Marine Corps Base Camp Lejeune Jacksonville, NC CN Project #9893
GER 130-8061
GeoEnvironmental Resources, Inc. has completed our hazardous materials sampling of the subject facility. This work was completed in accordance with the scope of work and fee outlined in our proposal P22-130-7716 dated May 3, 2022 as accepted by Clark Nexsen. This report is relevant to the date of our field work and should not be relied upon for later dates.
We appreciate the opportunity of completing this work for Clark Nexsen (CN). If there are any questions concerning this report, please contact us.
Sincerely, GeoEnvironmental Resources, Inc.
Wyatt S. Pine H. Nelson Adcock, Jr.
Hazardous Materials Specialist President VA Asbestos Inspector (#3303004643) NC Asbestos Inspector (#13140)
Attachments: (1) Report
(2) Laboratory Results
(3) Sample Location Plan
(4) Photographs
(5) Licenses
Southern Professional Center I 2712 Southern Boulevard, Suite 101 Virginia Beach, Virginia 23452
(757) 463-3200 Fax (757) 463-3080 E-mail germail@geronline.com
TABLE OF CONTENTS
Section 2 Laboratory Results
Section 1 Report
Section 3 Sample Location Maps
Section 4 Photos
Section 5 Licenses
ACRONYMS
AAS Atomic absorption spectroscopy ACBM Asbestos-containing building materials ACM Asbestos-containing materials ACT Acoustical ceiling tile ADA Americans with Disability Act AHERA Asbestos Hazard Emergency Response Act ASHARA Asbestos Schools Hazard Abatement Reauthorization Act ASTM American Society of Testing and Materials CMU Cement masonry unit CFC Chlorofluoro carbons CHMM Certified Hazardous Materials Manager CFR Code of Federal Regulation CSP Certified Safety Professional DEHP Di (2-ethylhexyl) phthalate DRO Diesel Range Organics ECD Electron capture detectors EA Each EPA U.S. Environmental Protection Agency GC Gas chromatography GRO Gasoline Range Organics GWB Gypsum wall board HBM Hazardous building material HID High intensity discharge HM Homogeneous material HUD U.S. Housing and Urban Development LBP Lead-based paint LF Linear feet LS Lump sum MDL Minimum detection limit mg/cm2 Milligrams per square centimeter mg/kg Milligrams per kilogram mg/L Milligrams per Liter ND none detected NVLAP National Voluntary Laboratory Accreditation Program OSHA Occupational Safety and Health Administration PCB Polychlorinated biphenyl PLM Polarized light microscopy ppm Parts per million RCRA Resource Conservation and Recovery Act SAP Sample and Analysis Plan SF Square Feet TCLP Toxicity characteristic leaching procedure TLV Threshold Limit Value TPH Total Petroleum Hydrocarbons TSI Thermal System Insulation VAC Virginia Administration Code VOC Volatile Organic Compound XRF X-Ray Fluorescence
P-1514 Shoot House Building RR249 GER 130-8061 Page 1
PROJECT DESCRIPTION
Project information is per the Statement of Architect-Engineer Services (SAES) Revision 18 dated April 2021, provided by Clark Nexsen (CN).
This project is titled “FY 23 MILCON Project P-1514, Shoot House.” The project is described in the SAES, and Attachment 16 as follows:
SAES - D2. Development of the Design: The project(s) covered by this T.O. require(s) the preparation of a DBB construction contract package (i.e. drawings, specifications, basis of design (BOD), design analysis, engineering calculations, cost estimate, studies, and investigations, etc.).
Design submittals will be due at the Design Development (35-50%), 65% Over The Shoulder Review, Pre-Final (100%) and Final Corrected Design stages. The DBB Design must be developed in accordance with the Basic IDIQ Contract SAES, FC 1-300-09N, and as described in this SAES.
Attachment 16 - The objective of this Statement of Work (SOW) is to provide the organizational framework necessary to obtain an Environmental and Hazardous Materials (HAZMAT) Survey related to the planned demolition of building RR249 and associated utilities as part of the project to construct a new Shoot House at Stone Bay, Marine Corps Base Camp Lejeune, NC on an adjacent site.
Our scope of work was to perform an inspection of the building and collect bulk samples of suspect asbestos-containing materials (ACM) and paint chip samples to determine RCRA metal concentrations.
We also inspected existing lighting fixtures for PCB-containing ballasts collected wipe samples for lead and collected surface soil samples for lead analysis around the perimeter of the Building
RR249.
BUILDING DESCRIPTION
According to SAES Attachment 16 Building RR249, was constructed in 1998. The building contains approximately 4,800 square feet. The Building is a high bay 1-story structure which serves as a practice shooting facility.
The building consists of a pre-engineered metal building. The exterior of the building, including the walls and roof are covered with metal panels. The interior of the building includes a concrete floor and various timber frames partition walls. Many of the partition walls are covered with a product named “Armorcore.”
There is a catwalk located below the roof in the building. This catwalk is used by instructors during training activities.
The building is ventilated using three ventilation fans and associated metal ductwork. The ventilation fans are mounted on the metal roof.
SAMPLING METHODOLOGIES
SUSPECT ASBESTOS-CONTAINING MATERIALS
(ACM)
The AHERA regulation, 40 Code of Federal Regulations (CFR) 763, is the primary governing regulation when performing asbestos surveys. This regulation was originally enacted for school buildings, but has since been applied to public and commercial buildings by the Asbestos School Hazard Abatement Reauthorization Act (ASHARA) in 1994 and by the Occupational Safety and Health Administration’s (OSHA) worker protection regulations in 1995, specifically 29 CFR 1926.1101(k). The demolition of structures is also subject to 40 CFR Part 61 “National Emission Standards for Hazardous Air Pollutants” (NESHAPs).
ACM is specifically addressed in 40 CFR 61 Subpart M “National Emission Standard for Asbestos.”
ACM is generally divided into three primary classifications as follows: (a) Surfacing material, (b) Thermal System Insulation, and (c) Miscellaneous
P-1514 Shoot House Building RR249 GER 130-8061 Page 2
GER
Report of Hazardous Materials Study P-1514 Shoot House
Building RR249, Marine Corps Base Camp Lejeune Jacksonville, NC
GER 130-8061
material. These classifications are defined in 40 CFR 763.83 as provided below.
Miscellaneous material means interior building on structural components, structural members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.
Surfacing material means material in a school building that is sprayed-on, troweled-on, or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.
Thermal system insulation means material in a school building applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.
The sampling methodologies employed to address the ACM categories described above are as follows:
Surfacing material – An accredited inspector shall collect, in a statistically random manner that is representative of the homogeneous are, bulk samples from each homogeneous area of friable surfacing material that is not assumed to be ACM, and shall collect the samples as follows:
(1) At least three bulk samples shall be collected from each homogeneous area that is 1,000 SF or less.
(2) At least five bulk samples shall be collected from each homogeneous area that is greater than 1,000 SF but less than or equal to 5,000 SF.
(3) At least seven bulk samples shall be collected from each homogeneous area that is greater than 5,000 SF.
Thermal system insulation - An accredited inspector shall collect the samples as follows:
(1) At least three bulk samples, in a random distributed manner from each homogeneous area of thermal system insulation that is not assumed to be ACM.
(2) Collect at least one bulk sample from each homogeneous are of patched thermal system insulation that is not assumed to be ACM if the patched section is less than 6 linear or square feet.
(3) In a manner sufficient to determine whether the material is ACM or not ACM, collect bulk samples from each insulated mechanical system that is not assumed to be ACM where cement or plaster is used on fittings such as tees, elbows, or valves.
(4) Bulk samples are not required to be collected from any homogeneous area where the accredited inspector has determined that the thermal system insulation is fiberglass, foam glass, rubber, or other non-ACBM.
Miscellaneous material - An accredited inspector shall collect the samples as follows:
(1) In a manner sufficient to determine whether material is ACM or not ACM from each homogeneous area of friable miscellaneous material that is not assumed to be ACM.
Non friable suspected ACBM - An accredited inspector shall collect the samples as follows:
If any homogeneous area of non friable suspected ACBM is not assumed to be ACM, then an accredited inspector shall collect, in a manner sufficient to determine whether the material is ACM or not ACM, bulk samples from the homogeneous are of non friable suspected ACBM that is not assumed to be ACM.
LEAD BASED PAINT (LBP)
Testing of painted surfaces for lead, cadmium and chromium was conducted by collecting bulk paint chip samples from various painted surfaces. It is important to note that this inspection was not intended to meet the requirements of HUD sampling protocols for lead paint and was not a comprehensive, surface-by-surface evaluation, but rather a screening inspection of major painted components, which may contain LBP.
WIPE SAMPLING
Wipe sampling was performed using a gauze provided by Eurofins Laboratory. A 100cm2 template was placed on the surface area to be sampled. The gauze was removed from the paper package and wetted with distilled water. The area inside the template was wiped with firm pressure using “S” stokes covering the entire surface (edge to edge). The exposed side of the gauze was folded inward. The area was again wiped with the gauze
P-1514 Shoot House Building RR249 GER 130-8061 Page 3
GER
using S-strokes, starting at right angles to the first wipe. The exposed side of the gauze was again folded inward. The area was again wiped with the twice folded gauze using S-strokes in the original direction. The sample gauze was placed inside the laboratory provided plastic container, sealed and labeled and preserved on ice and forwarded to the laboratory using chain of custody controls.
SOIL SAMPLING
Soil samples were collected using a stainless steel trowel. The soil samples were collected from the upper 6-inches of soil. The soil was placed in clean, 4-ounce glass containers provided by Eurofins Laboratory. The containers were sealed, labeled preserved on ice and forwarded to the laboratory using chain of custody controls.
TCLP SAMPLING
Subsamples of various building materials were collected to form a composite sample for TCLP analysis. The composite sample consisted of a minimum of 105 grams of various building materials. The subsamples we placed into plastic bags, sealed, labeled preserved on ice and forwarded to the laboratory using chain of custody controls.
ANALYTICAL METHODS
SUSPECT ASBESTOS-CONTAINING MATERIALS
(ACM)
Suspect bulk ACM samples were analyzed using polarized light microscopy (PLM) and dispersion staining techniques. The analytical method was conducted in accordance with Method EPA-600/M4-82-020 and/or EPA 600/R-93/116.
Analysis was performed by EMSL Analytical, Inc., Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA-LAP, LLC-IHLAP Lab 100194, NYS ELAP
10872, NJ DEP 03036.
LEAD BASED PAINT (LBP)
Paint chip samples were analyzed for 8 RCRA metals using inductively coupled plasma (ICP) emission spectroscopy (SW-846, 6010C). Analysis was performed by EMSL Analytical, Inc.
Cinnaminson, NJ NELAP Certifications: 10896, PA
68-00367, AIHA-LAP, LLC ELLAP 100194, A2LA
2845.01.
WIPE SAMPLES
Wipe samples were analyzed for Lead using inductively coupled plasma (ICP) emission spectroscopy (SW-846, 6010B). Analysis was performed by Eurofins Laboratory. Eurofins Canton, OH NELAP Certification: 460175, VA.
TCLP SAMPLES
TCLP samples were analyzed using protocol (SW 846), method 1311/6010D/7470A. Analysis was performed by EMSL Analytical, Inc.
SOIL SAMPLES
Soil samples were analyzed for Lead using inductively coupled plasma (ICP) emission spectroscopy (SW-846, 6010C). Analysis was performed by EMSL Analytical, Inc. Cinnaminson, NJ NELAP Certifications: 10896, PA 68-00367, AIHA-LAP, LLC ELLAP 100194, A2LA 2845.01.
PREVIOUS REPORTS
The Government did not provide a previous hazardous materials report for Building RR249.
FIELD INVESTIGATION
BUILDING INSPECTION
We performed an inspection of Building RR249 at MCB Camp Lejeune on August 30, 2022. The purpose of the inspection was to identify and sample, as required, suspect ACM, paint containing RCRA metals, and lighting containing PCB electrical ballasts and mercury lamps. Additional we performed an assessment of the building and soils around the building for residual lead.
ASBESTOS INSPECTION
A visual inspection of the building was performed and identified the following building materials:
1. Painted wood walls and ceilings,
2. Rubber sheets on the inside of the exterior walls,
3. Painted CMU walls, P-1514 Shoot House Building RR249 GER 130-8061 Page 4
4. Unpainted timber framing,
5. Unpainted concrete floor,
6. Painted structural steel,
7. Metal exterior panel walls and roof,
8. Metal exterior doors,
9. Hollow wood interior doors,
10. Three ventilation fans mounted on the roof of the building along with metal ductwork,
11. Fiberglass wallboard.
We did not readily observe miscellaneous sealants, plumbing, thermal system insulation, floor tile and mastic or acoustical ceilings in the building.
Four (4) bulk samples of suspect asbestos-containing materials (ACM) were collected. The suspect ACM samples included: tan duct mastic on metal ventilation ductwork, and CMU block filler. The attached Table 1, in Section 2 lists the sample materials, sample location, and laboratory results. Drawings showing the approximate sample locations are provided in Section 3.
As the sample results indicate no samples were determined to contain asbestos.
ASBESTOS DISCUSSION
The EPA defines ACM as any material which contains greater than 1% asbestos by weight.
Laboratory analysis of bulk samples collected during the field investigation did not identify ACM.
If asbestos abatement work is necessary due to unforeseen conditions, it must be performed in accordance with local, state and Federal regulations including but not limited to:
29CFR1926.1101 - Asbestos 40CFR61 - National Emission Standards for Hazardous Air Pollutants 10A NCAC 412C.0600 - North Carolina Asbestos Hazard Program 15A NCAC 13A - North Carolina Hazardous Waste Management 15A NCAC 13B - North Carolina Solid Waste Management
Marine Corps Base Camp Lejeune Environmental Affairs Division regulations.
PAINT SAMPLING
Two (2) paint chip samples were collected by GER.
The purpose of our sampling was to obtain representative data on the concentrations of the 8 RCRA metals (Arsenic, Barium, Cadmium, Chromium, Lead, Mercury, Selenium and Silver) in the existing painted surfaces scheduled to be disturbed by the work. Paint was collected from building materials which may be disturbed during the demolition.
Our inspection services were not intended to meet the requirements of HUD sampling protocols for lead paint.
The attached Table 2, in Section 2 lists the sample materials, sample location, and laboratory results.
Drawings showing the approximate sample locations are provided in Section 3.
LEAD, CADMIUM, & CHROMIUM PAINT
DISCUSSION
There are two frequently used standards to define lead-based paint, the Consumer Product and Safety Commission (CPSC) and the Department of Housing and Urban Development (HUD). In 1978, the CPSC, acting under the authority of the Consumer Product Safety Act, banned the sale of paint containing more than 0.06% lead by weight to consumers. The Department of Housing and Urban Development (HUD) defines lead-based paint as any paint, varnish, shellac, or other coating that contains lead equal to or greater than
1.0 mg/cm2 as measured by x-ray fluorescence (XRF) analyzer or laboratory analysis, or 0.5% by weight as measured by laboratory analysis.
The Occupational Safety and Health Administration (OSHA) Lead in Construction Standard (29 CFR 1926.62) does not define lead-based paint.
Compliance with this standard is required even for paints with less than 0.5% or 0.06% lead by weight. Therefore, painted surfaces exceeding the MDL should not be disturbed without taking the appropriate precautions when performing certain high risk tasks. Activities such as scraping, sanding, welding/torching and disturbance of painted surfaces could potentially release leaded
P-1514 Shoot House Building RR249 GER 130-8061 Page 5 dust. OSHA has categorized the following high risks tasks into three groups:
Group 1: manual demolition manual scraping heat-gun applications power tool cleaning with dust collection system spray paint with lead-based paints
Group 2: lead burning using lead-containing mortar power tool cleaning without dust collection system rivet blasting cleanup activities where dry expendable abrasives are used movement and removal of abrasive blasting enclosures
Group 3: abrasive blasting welding, cutting and burning on steel structures
Sampling results for lead paint indicate that both samples collected and analyzed were found to have lead concentrations above the laboratory's reporting limit. The samples were not determined to be LBP. Therefore, all existing painted surfaces scheduled for renovation/demolition should be considered lead containing for the purposes of complying with 29 CFR 1926.62 in order to protect workers and the environment.
Paints containing cadmium and chromium are often found as protective coatings on structural steel or exterior coatings on metal surfaces. These paints tend to be red, yellow or orange and are typically the first layer. The bulk paint chip sample was also tested for cadmium and chromium. Both samples collected and analyzed indicated concentrations above the reporting limit for cadmium and chromium. The National Institute for Occupational Safety and Health (NIOSH) identifies chromium and cadmium as a confirmed carcinogen. Construction Standards established by OSHA for cadmium and lead are:
Chromium 29 CFR 1926.1126 Cadmium 29 CFR 1926.1127 Lead 29 CFR 1926.62
The permissible exposure limits (PEL) established by OSHA are 5 ug/m3 for cadmium, 5 ug/m3 for chromium (chromates) and 50 ug/m3 for lead. If the PEL is exceeded, appropriate measures must be taken to reduce the hazard and provide training and personal protective equipment.
The PEL is an airborne measurement to address worker exposure. There is no direct correlation between lead, cadmium, and chromium concentrations in paint and worker exposure. Only when these concentrations are below the laboratory’s MDL, is worker exposure not an issue.
Therefore, all existing painted surfaces scheduled for renovation/demolition should be considered lead, cadmium, and chromium containing for the purposes of complying with 29 CFR 1926.62 and 29 CFR 1926.1126, and in order to protect workers and the environment.
Additionally, the paint samples were analyzed for Arsenic, Barium, Mercury, Selenium and Silver.
Both paint samples contained concentrations above the laboratory reporting limit for Arsenic, Barium, Selenium and Silver. Mercury was not detected at a concentration above the laboratory reporting limit.
Appropriate precautions should be taken during the disturbance of all painted surfaces to ensure protection of workers and the environment.
All paint disturbance work shall be performed in accordance with all local, state and Federal regulations to protect workers and the environment, including but not limited to:
29CFR 1926.62 - Lead 29CFR 1926.1126 - Chromium 29CFR 1926.1127 - Cadmium 15A NCAC 13A - North Carolina Hazardous Waste Management 15A NCAC 13B - North Carolina Solid Waste Management
Marine Corps Base Camp Lejeune Environmental Affairs Division regulations.
WASTE CLASSIFICATION FOR PAINTED
BUILDING COMPONENTS
Building components and demolition waste streams which are painted must be properly characterized prior to disposal. The EPA Resource Conservation and Recovery Act (RCRA) regulations establish the
P-1514 Shoot House Building RR249 GER 130-8061 Page 6 limits for RCRA leachable metals (lead, cadmium, chromium, etc.). Leachable metals means the amount of metals likely to leach from the waste into the surrounding soil/groundwater system of a landfill. The leachable concentration of chemicals in a waste stream is determined by an analytical method called the toxicity characteristic leaching procedure (TCLP). Waste stream TCLP concentrations that equal or exceed the RCRA limits must be transported to a hazardous waste treatment, storage, or disposal facility. Precautions should be implemented to prevent the storage of any hazardous waste for more the 90 days. Specific permits are necessary to store hazardous waste in excess of 90 days
LEAD WIPE SAMPLES
Lead dust wipe samples were collected from various surfaces inside Building RR249. Five lead dust wipe samples designated as W1 through W5 were collected. The samples were collected from both horizontal and vertical surfaces as follows:
W1: Concrete floor wipe sample, horizontal surface, lead concentration 80 ug/100 cm2 (743.2 ug/ft2).
W2: Concrete floor wipe sample, horizontal surface, lead concentration 660 ug/100 cm2 (6,131.4 ug/ft2).
W3: On top of a partition wall, horizontal surface, lead concentration 710 ug/100 cm2 (6,595.9 ug/ft2).
W4: Rubber coated exterior wall, vertical surface, lead concentration 2.9 ug/100 cm2 (23.94 ug/ft2).
W5: Rubber coated exterior wall, vertical surface, lead concentration 1.7 ug/100 cm2 (15.79 ug/ft2).
Lead dust wipe concentrations ranged from 1.7 ug/100 cm2 (15.79 ug/ft2) to 710 ug/100 cm2
(6,595.90 ug/ft2).
The attached Table 3, in Section 2 lists the sample materials, sample location, and laboratory results.
Drawings showing the approximate sample locations are provided in Section 3.
LEAD WIPE SAMPLES DISCUSSION
Typical bullets use lead styphnate and lead peroxide among other materials in the bullet primer. In some cases the bullet may also contain lead. We do not know anything about the weapons or ammunition used in the building. The source for the lead dust is likely to be the primer associated with the ammunition used in the weapons.
There are two regulatory protocols to use with regards to evaluating lead wipe sample concentrations.
One protocol is 40 C.F.R. Part 745 - Lead-Based Paint Poisoning Prevention in Certain Residential Structures. This protocol describes the lead dust clearance level for lead in dust as 10 ug/ft2 for floors, 200 ug/ft2 for interior window sills and 400 ug/ft2 for window troughs.
The second protocol is based on the OSHA Technical Manual. The surface contamination calculations described in the OSHA Technical Manual assumes the area of a workers hand is 100 cm2. This area is the same as the surface wipe sample area. Thus, the amount of contaminant in a 100cm2 sample could all be transferred to a worker’s hand upon contact. The OSHA Technical Manual describes a method to calculate an acceptable surface limit. The calculation requires the TLV for lead inhalation exposure which is 50 ug/m3 based on 29 CFR 1926.62. In this case the TLV is the same as the PEL for lead. The TLV is multiplied by the volume of air inhaled by an average worker in an eight-hour workday, which is 10m3. Multiplying 50 ug/m3 times 10m3 yields 500 ug as an acceptable lead dose. Dividing the acceptable lead dose by the approximate surface area of a worker’s hand results in an acceptable surface limit of 5 ug/cm2.
The lead concentration in each of the lead wipe samples exceeded the HUD clearance level of 10 ug/ft2.
The lead concentration in lead wipe samples W1, W2, and W3 exceeded the calculated OSHA acceptable surface limit of 5 ug/cm2.
Prior to the demolition of the building it should be properly deconned to collect the residual lead dust and to prevent it from spreading to the surrounding soil. The decon work should be monitored to ensure the workers are not exposed to airborne lead concentrations greater than the those specified in 29CFR 1926.62 - Lead.
P-1514 Shoot House Building RR249 GER 130-8061 Page 7
All lead dust cleanup work shall be performed in accordance with all local, state and Federal regulations to protect workers and the environment, including but not limited to:
29CFR 1926.62 - Lead 15A NCAC 13A - North Carolina Hazardous Waste Management 15A NCAC 13B - North Carolina Solid Waste Management
Marine Corps Base Camp Lejeune Environmental Affairs Division regulations.
LEAD SOIL SAMPLES
To assess the soil around the perimeter of the building for lead exterior soil sampling was conducted. The soil surrounding the building generally consisted of gravel and dirt. One soil sample was collected on each side of the building.
The attached Table 4, in Section 2 lists the sample materials, sample location, and laboratory results.
Drawings showing the approximate sample locations are provided in Section 3.
EPA defines a soil lead hazard as bare soil on residential real property or on the property of a child-occupied facility that contains total lead equal to or exceeding 400 parts per million (ppm) in a play area, or an average of 1,200 parts per million of bare soil in the rest of the yard based on soil samples.
LEAD SOIL SAMPLES DISCUSSION
Lead is a naturally occurring element found in soil.
The lead concentration can vary depending on location and historical use of the property.
Lead was detected in each of the four soil samples collected and analyzed around Building RR249. The lead concentrations ranged from 13 mg/Kg to 390 mg/Kg.
EPA defines a soil lead hazard as bare soil on residential real property or on the property of a child-occupied facility that contains total lead equal to or exceeding 400 parts per million (ppm) in a play area, or an average of 1,200 parts per million of bare soil in the rest of the yard based on soil samples.
The lead concentrations in the soil samples did not exceed 400 ppm. The lead in soil should not present an issue; however, if the soil is to be disturbed and removed from the site additional soil characterization will be required.
All lead soil disturbance work shall be performed in accordance with all local, state and Federal regulations to protect workers and the environment, including but not limited to:
29CFR 1926.62 - Lead 15A NCAC 13A - North Carolina Hazardous Waste Management 15A NCAC 13B - North Carolina Solid Waste Management
Marine Corps Base Camp Lejeune Environmental Affairs Division regulations.
TCLP SAMPLE
One composite TCLP sample was obtained from the various building materials in Building RR249.
Subsamples were collected from painted CMU, painted wood inside the building and a painted wooden door inside the building.
The sample was analyzed for TCLP RCRA 8 metals (Arsenic, Barium, Cadmium, Chromium, Lead, Mercury, Selenium and Silver). Laboratory analysis did not identify any RCRA metal concentrations above the laboratory reporting limit.
The attached Table 5, in Section 2 lists the sample materials, sample location, and laboratory results.
Based on the TCLP sample analysis the building materials do not appear to be hazardous.
POLYCHLORINATED BIPHENYLS (PCBS)
On January 1, 1979, the Environmental Protection Agency (EPA) banned the manufacturing of light ballasts which contain PCB’s and phased out most PCB uses. Therefore, all light ballasts manufactured prior to January 1, 1979 without “Non-PCB” markings must be considered PCB containing. The EPA’s actions subjects all substances containing over 50 ppm PCBs to regulatory control (with the exception of PCB-contaminated waste oil which is prohibited at any level).
P-1514 Shoot House Building RR249 GER 130-8061 Page 8
Our field investigation of existing light fixtures indicated the fixtures inside the building were T-8 fluorescent lamps. There were a total of forty-four
(44) fluorescent light fixtures in the building. T-8 fixtures generally contain electronic ballasts which are not PCB containing.
The exterior lighting on the building appeared to be LEDs.
Any non-electronic ballast not marked “No PCB’s” must be considered to contain PCB’s.
All PCB work shall be performed in accordance with all local, state and Federal regulations to protect workers and the environment, including but not limited to:
40CFR761 - Polychlorinated Biphenyls (PCBs) Manufacturing, Processing, Distribution In Commerce, and Use Prohibitions 15A NCAC 13A - North Carolina Hazardous Waste Management 15A NCAC 13B - North Carolina Solid Waste Management
Marine Corps Base Camp Lejeune Environmental Affairs Division regulations.
MERCURY CONTAINING LAMPS
The fluorescent light fixtures in the building contained T8 fluorescent lamps. The lamps contain mercury and should be recycled. The building contains a total of 176 fluorescent lamps.
All mercury containing lamp recycling shall be performed in accordance with all local, state and Federal regulations to protect workers and the environment, including but not limited to:
15A NCAC 13A - North Carolina Hazardous Waste Management 15A NCAC 13B - North Carolina Solid Waste Management
Marine Corps Base Camp Lejeune Environmental Affairs Division regulations.
PCB SEALANTS
In recent years, EPA has learned that caulk containing potentially harmful PCBs was used in many buildings, including schools, in the 1950s through the 1970s. Since the building was constructed in 1998 PCB containing sealants are not likely to be present.
We performed a visual inspection of the building and did not observe suspect PCB containing sealants associated with the building.
LIMITATIONS
This report has been prepared for the exclusive use of Clark Nexsen and/or their agents. This service was performed in accordance with generally accepted environmental practices. No other warranty, expressed or implied, is made. Our conclusions and recommendations are based, in part, upon information provided to us by others and our site observations. We have not verified the completeness or accuracy of the information provided by others, unless otherwise noted. Our observations and recommendations are based upon conditions readily visible at the time of our site visit and upon current industry standards. During our inspection, accessible areas were visually inspected for the presence of asbestos and lead based paints.
The findings at these locations area assumed to be representative throughout the impacted areas of the building. Inaccessible areas were not visually inspected. Areas inspected for the above-referenced materials were limited to those designated by the client.
Under this scope of services, GER assumes no responsibility regarding response actions (e.g. O&M Plans, Remediation, Notifications, etc.) initiated as a result of these findings. GER assumes no liability for the duties and responsibilities of the Client with respect to compliance with local, state and Federal regulations. Compliance with regulations and response actions are the sole responsibility of the Client and should be conducted in accordance with local, state and Federal regulations and should be performed by appropriately licensed personnel, as warranted.
P-1514 Shoot House Building RR249 GER 130-8061 Page 9
SECTION 2
Laboratory Results
Table 1 - Asbestos Sample Results
Table 2 - Paint Sample Results
Table 3 - Lead Wipe Sample Results
Table 4 - Lead Soil Sample Results
Table 5 - TCLP Sample Results
Laboratory Analytical Results
P-1514 Shoot House GER 130-8061
NO. SAMPLE LOCATION SAMPLE MATERIAL % & TYPE OF ASBESTOS
1 Shoothouse HVAC Tan Duct Mastic None Detected
2 Shoothouse HVAC Tan Duct Mastic None Detected
3 Shoothouse Electrical Room CMU Block Sealant None Detected
4 Shoothouse Electrical Room CMU Block Sealant None Detected
Table 1 - Asbestos Bulk Sample Results
P1 P2
Arsenic, % by wt P1: Composite - Structural steel and metal door P1: Tan paint 0.00040 0.00036 ND 0.00060
Barium, % by wt P2: Catwalk handrail and wooden door frame P2: Black and Tan paint 0.0020 0.0018 0.0046 0.00540
Cadmium, % by wt 0.0020 0.0018 0.0083 0.0025
Chromium, % by wt 0.00020 0.00018 0.0042 0.0051
Lead, % by wt 0.00020 0.00018 0.013 0.0029
Mercury, mg/Kg 0.12 0.12 ND ND
Selemium, % by wt 0.00040 0.00036 0.00092 0.00044
Silver, % by wt 0.00020 0.00018 0.00020 0.00020
NOTES:
BOLD results indicate the sample is Lead Based Paint (LBP).
All YELLOW HIGHLIGHTED samples exceed the laboratory reporting limit (RL).
ND - Not detected at the reporting limit.
Table 2 - Paint Sample Results
Metal SAMPLE LOCATION SAMPLE MATERIAL P2
REPORTING LIMIT
SAMPLE ID & RESULTS
P1
REPORTING LIMIT
NO. SAMPLE LOCATION SAMPLE MATERIAL RESULTS (ug/100 cm2) RESULTS (ug/ft2)
W1 Shoothouse floor Lead Dust Wipe 80 743.2
W2 Shoothouse floor Lead Dust Wipe 660 6,131.40
W3 Shoothouse top of lower wall Lead Dust Wipe 710 6,595.90
W4 Shoothouse Rubber Coated exterior wall Lead Dust Wipe 2.9 26.94
W5 Shoothouse Rubber Coated exterior wall Lead Dust Wipe 1.7 15.79
NOTES:
BOLD results indicate the sample exceeds the EPA HUD threshold of 10 ug/ft2 for floors.
Table 3 - Lead Wipe Sample Results
NO. SAMPLE LOCATION SAMPLE MATERIAL RESULTS (mg/Kg)
S1 West side of building Soil (0-6") 15
S2 South side of building Soil (0-6") 13
S3 East side of building Soil (0-6") 390
S4 North side of building Soil (0-6") 38
NOTES:
BOLD results indicate the sample exceeds 400 mg/Kg.
Table 4 - Lead Soil Sample Results
NO.
SAMPLE
LOCATION
Arsenic
(RL=0.10
Barium
(RL=0.10
Cadmium
(RL=0.10
Chromium
(RL=0.10
Lead
(RL=0.10
Mercury
(RL=0.0020
Selenium
(RL=0.10
Silver
(RL=0.10
TCLP-1
Composite sample from CMU, painted wood and door
ND ND ND ND ND ND ND ND
NOTES:
BOLD results indicate the sample is HAZARDOUS.
ND - Not detected at the reporting limit.
Table 5 - TCLP Sample Results (mg/L)
SECTION 2.1
Asbestos - Analytical Results
EMSL Analytical, Inc.
10801 Southern Loop Blvd Pineville, NC 28134
Tel/Fax: (704) 525-2205 / (704) 525-2382 http://www.EMSL.com / charlottelab@emsl.com
412208791EMSL Order:
Customer ID: GEOE25
Customer PO: 130-8061
Project ID:
Attention: Phone:Wyatt Pine (757) 463-3200
Fax:GeoEnvironmental Resources (757) 463-3080
Received Date:2712 Southern Blvd. 09/01/2022 9:00 AM
Analysis Date:Suite 101 09/06/2022 - 09/07/2022
Collected Date:Virginia Beach, VA 23452 08/30/2022
Project: P-1514 Shoothouse 130-8061
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
412208791-0001
None DetectedNon-fibrous (Other)100%Brown/Tan
Non-Fibrous
Homogeneous
Tan HVAC Duct
Mastic
412208791-0002
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Tan HVAC Duct
Mastic
412208791-0003
None DetectedQuartz
Non-fibrous (Other)
15%
85%
Gray/White
Non-Fibrous
Homogeneous
CMU Block Sealant
412208791-0004
None DetectedQuartz
Non-fibrous (Other)
20%
80%
Gray/White
Non-Fibrous
Homogeneous
CMU Block Sealant
Analyst(s)
Ashley Hill (2)
Brant Alyea (2)
Lee Plumley, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Pineville, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from: 09/07/2022 14:10:36
Page 1 of 1ASB_PLM_0008_0001 - 1.78 Printed: 9/7/2022 2:10 PM
OrderID: 412208791
OrderID: 412208791
SECTION 2.2
Paint - Analytical Results
Lee Plumley, Laboratory Manager
Approved By:
Fax: (757) 463-3080 Phone: (757) 463-3200
The following analytical report covers the analysis performed on samples submitted to EMSL Analytical, Inc. on 9/1/2022. The results are tabulated on the attached data pages for the following client designated project:
130-8061 Shoothouse P1514
The reference number for these samples is EMSL Order #412208779. Please use this reference when calling about these samples. If you have any questions, please do not hesitate to contact me at (704) 525-2205.
9/7/2022Attn: Wyatt Pine GeoEnvironmental Resources 2712 Southern Blvd.
Suite 101 Virginia Beach, VA 23452
The samples associated with this report were received in good condition unless otherwise noted. This report relates only to those items tested as received by the laboratory. The QC data associated with the sample results meet the recovery and precision requirements established by the NELAP, unless specifically indicated. All results for soil samples are reported on a dry weight basis, unless otherwise noted. This report may not be reproduced except in full and without written approval by EMSL Analytical, Inc.
EMSL Analytical, Inc.
10801 Southern Loop Blvd, Pineville, NC 28134 Phone: (704) 525-2205 Fax: (704) 525-2382 Email: charlottelab@emsl.com
Barium and Silver Matrix Spike Percent Recovery and Duplicate RPD Outside Acceptance Limits mailto:charlottelab@emsl.com
10801 Southern Loop Blvd, Pineville, NC 28134 Phone/Fax: (704) 525-2205 / (704) 525-2382 http://www.EMSL.com charlottelab@emsl.com
412208779 CustomerID: GEOE25 CustomerPO: 130-8061 ProjectID:
EMSL Order:
Analytical Results
Attn: Wyatt Pine GeoEnvironmental Resources 2712 Southern Blvd.
Suite 101 Virginia Beach, VA 23452
Received: 9/1/2022 09:00 AM
130-8061 Shoothouse P1514
Fax: (757) 463-3080 Phone: (757) 463-3200
Project:
8/30/2022Collected:
Client Sample Description Lab ID:P1 412208779-0001 Composite Paint Sample Tan S.S. Tan Door
Collected: 8/30/2022
Method Parameter Result Units Analysis
Date & AnalystRL Prep
Date & Analyst
METALS
Mercury by CVAA, SW- 846-7471B
Mercury AHND mg/Kg 9/6/2022 00:000.12 9/6/2022 AH
3050B/6010D Arsenic LPND % wt 9/6/2022 19:590.00040 9/6/2022 LPD
3050B/6010D Barium LP0.0046 % wt 9/6/2022 19:590.0020 9/6/2022 LPD
3050B/6010D Cadmium LP0.0083 % wt 9/6/2022 19:590.0020 9/6/2022 LPD
3050B/6010D Chromium LP0.0042 % wt 9/6/2022 19:590.00020 9/6/2022 LPD
3050B/6010D Lead LP0.013 % wt 9/6/2022 19:590.00020 9/6/2022 LPD
3050B/6010D Selenium LP0.00092 % wt 9/6/2022 19:590.00040 9/6/2022 LPD
3050B/6010D Silver LP0.00020 % wt 9/6/2022 19:590.00020 9/6/2022 LPD
Client Sample Description Lab ID:P2 412208779-0002 Composite Paint Sample Tan Catwalk Handrail Blk Door Frame
Collected: 8/30/2022
Method Parameter Result Units Analysis
Date & AnalystRL Prep
Date & Analyst
METALS
Mercury by CVAA, SW- 846-7471B
Mercury AHND mg/Kg 9/6/2022 00:000.12 9/6/2022 AH
3050B/6010D Arsenic LP0.00060 % wt 9/6/2022 20:060.00036 9/6/2022 LPD
3050B/6010D Barium LP0.0054 % wt 9/6/2022 20:060.0018 9/6/2022 LPD
3050B/6010D Cadmium LP0.0025 % wt 9/6/2022 20:060.0018 9/6/2022 LPD
3050B/6010D Chromium LP0.0051 % wt 9/6/2022 20:060.00018 9/6/2022 LPD
3050B/6010D Lead LP0.0029 % wt 9/6/2022 20:060.00018 9/6/2022 LPD
3050B/6010D Selenium LP0.00044 % wt 9/6/2022 20:060.00036 9/6/2022 LPD
3050B/6010D Silver LP0.00020 % wt 9/6/2022 20:060.00018 9/6/2022 LPD
MDL - method detection limit J - Result was below the reporting limit, but at or above the MDL ND - indicates that the analyte was not detected at the reporting limit RL - Reporting Limit (Analytical) D - Dilution Sample required a dilution which was used to calculate final results
Definitions:
Page 2 of 2ChemSmplw/RDL/NELAC-2.19.0.0 Printed: 9/7/2022 4:23:09 PM http://www.EMSL.com
OrderID: 412208779
OrderID: 412208779
SECTION 2.3
Lead Wipe - Analytical Results
ANALYTICAL REPORT
Eurofins Canton 180 S. Van Buren Avenue Barberton, OH 44203 Tel: (330)497-9396
Laboratory Job ID: 240-172530-1 Client Project/Site: MCBCL Bldg RR249 - Shoot House
For:
GeoEnvironmental Resources Inc GER 2712 Southern Blvd Suite 101 Virginia Beach, Virginia 23452
Attn: Mr. H. Nelson Adcock, Jr.
Authorized for release by:
9/12/2022 3:50:37 PM
Leslie Howell, Project Manager I (330)966-9266 Leslie.Howell@et.eurofinsus.com
This report has been electronically signed and authorized by the signatory. Electronic signature is intended to be the legally binding equivalent of a traditionally handwritten signature.
Results relate only to the items tested and the sample(s) as received by the laboratory.
https://eol.et.eurofinsus.com/myEOL/ https://www.eurofinsus.com/environment-testing/ask-the-expert/ http://www.eurofinsus.com/Env mailto:Leslie.Howell@et.eurofinsus.com
Table of Contents
Client: GeoEnvironmental Resources Inc GER Project/Site: MCBCL Bldg RR249 - Shoot House
Laboratory Job ID: 240-172530-1
Eurofins Canton
9/12/2022
Cover Page
Table of Contents
Definitions/Glossary
Case Narrative
Method Summary
Sample Summary
Detection Summary
Client Sample Results
QC Sample Results
QC Association Summary
Lab Chronicle
Certification Summary
Chain of Custody
Definitions/Glossary Job ID: 240-172530-1Client: GeoEnvironmental Resources Inc GER
Project/Site: MCBCL Bldg RR249 - Shoot House
Glossary
These commonly used abbreviations may or may not be present in this report.
¤ Listed under the "D" column to designate that the result is reported on a dry weight basis
Abbreviation
%R Percent Recovery
CFL Contains Free Liquid
CFU Colony Forming Unit
CNF Contains No Free Liquid
DER Duplicate Error Ratio (normalized absolute difference)
Dil Fac Dilution Factor
DL Detection Limit (DoD/DOE)
DL, RA, RE, IN Indicates a Dilution, Re-analysis, Re-extraction, or additional Initial metals/anion analysis of the sample
DLC Decision Level Concentration (Radiochemistry)
EDL Estimated Detection Limit (Dioxin)
LOD Limit of Detection (DoD/DOE)
LOQ Limit of Quantitation (DoD/DOE)
MCL EPA recommended "Maximum Contaminant Level"
MDA Minimum Detectable Activity (Radiochemistry)
MDC Minimum Detectable Concentration (Radiochemistry)
MDL Method Detection Limit
ML Minimum Level (Dioxin)
MPN Most Probable Number
MQL Method Quantitation Limit
NC Not Calculated
ND Not Detected at the reporting limit (or MDL or EDL if shown)
NEG Negative / Absent
POS Positive / Present
PQL Practical Quantitation Limit
PRES Presumptive
QC Quality Control
RER Relative Error Ratio (Radiochemistry)
RL Reporting Limit or Requested Limit (Radiochemistry)
RPD Relative Percent Difference, a measure of the relative difference between two points
TEF Toxicity Equivalent Factor (Dioxin)
TEQ Toxicity Equivalent Quotient (Dioxin)
TNTC Too Numerous To Count
Eurofins Canton
Page 3 of 18 9/12/2022
Case Narrative Client: GeoEnvironmental Resources Inc GER Job ID: 240-172530-1 Project/Site: MCBCL Bldg RR249 - Shoot House
Job ID: 240-172530-1
Laboratory: Eurofins Canton
Narrative
Job Narrative 240-172530-1
Comments
No additional comments.
Receipt
The samples were received on 9/1/2022 9:30 AM. Unless otherwise noted below, the samples arrived in good condition, and where required, properly preserved and on ice. The temperature of the cooler at receipt was 3.5º C.
Metals Method 3050B: Insufficient sample volume was available to perform a matrix spike/matrix spike duplicate/sample duplicate
(MS/MSD/DUP) associated with preparation batch 240-541473 and 240-541480.
No additional analytical or quality issues were noted, other than those described above or in the Definitions/Glossary page.
Eurofins Canton Page 4 of 18 9/12/2022
Method Summary
Project/Site: MCBCL Bldg RR249 - Shoot House
Method Method Description LaboratoryProtocol
SW8466010B Metals (ICP) EET CAN
SW8463050B Preparation, Metals EET CAN
NoneWipe_Area Wipe_Area - Metals EET CAN
Protocol References:
None = None
SW846 = "Test Methods For Evaluating Solid Waste, Physical/Chemical Methods", Third Edition, November 1986 And Its Updates.
Laboratory References:
EET CAN = Eurofins Canton, 180 S. Van Buren Avenue, Barberton, OH 44203, TEL (330)497-9396
Eurofins Canton
Page 5 of 18 9/12/2022
Sample Summary
Project/Site: MCBCL Bldg RR249 - Shoot House
Lab Sample ID Client Sample ID Matrix Collected Received
240-172530-1 W1 Wipe 08/30/22 09:20 09/01/22 09:30
240-172530-2 W2 Wipe 08/30/22 09:23 09/01/22 09:30
240-172530-3 W3 Wipe 08/30/22 09:28 09/01/22 09:30
240-172530-4 W4 Wipe 08/30/22 09:30 09/01/22 09:30
240-172530-5 W5 Wipe 08/30/22 09:33 09/01/22 09:30
Eurofins CantonPage 6 of 18 9/12/2022
Detection Summary
Project/Site: MCBCL Bldg RR249 - Shoot House
Client Sample ID: W1 Lab Sample ID: 240-172530-1
Lead
RL
0.30 ug/100 cm2
MDL
0.20
Analyte Result Qualifier Unit Dil Fac D Method Prep Type
Total/NA180 6010B
Client Sample ID: W2 Lab Sample ID: 240-172530-2
Lead
RL
1.5 ug/100 cm2
MDL
1.0
Analyte Result Qualifier Unit Dil Fac D Method Prep Type
Total/NA5660 6010B
Client Sample ID: W3 Lab Sample ID: 240-172530-3
Lead
RL
1.5 ug/100 cm2
MDL
1.0
Analyte Result Qualifier Unit Dil Fac D Method Prep Type
Total/NA5710 6010B
Client Sample ID: W4 Lab Sample ID: 240-172530-4
Lead
RL
0.30 ug/100 cm2
MDL
0.20
Analyte Result Qualifier Unit Dil Fac D Method Prep Type
Total/NA12.9 6010B
Client Sample ID: W5 Lab Sample ID: 240-172530-5
Lead
RL
0.30 ug/100 cm2
MDL
0.20
Analyte Result Qualifier Unit Dil Fac D Method Prep Type
Total/NA11.7 6010B
Eurofins Canton
This Detection Summary does not include radiochemical test results.
Page 7 of 18 9/12/2022
Client Sample Results
Project/Site: MCBCL Bldg RR249 - Shoot House
Lab Sample ID: 240-172530-1Client Sample ID: W1 Matrix: WipeDate Collected: 08/30/22 09:20
Date Received: 09/01/22 09:30
Method: 6010B - Metals (ICP)
RL MDL
Lead 80 0.30 0.20 ug/100 cm2 09/07/22 07:30 09/08/22 13:34 1
Analyte Dil FacAnalyzedPreparedUnit DResult Qualifier
Eurofins Canton
Page 8 of 18 9/12/2022
Project/Site: MCBCL Bldg RR249 - Shoot House
Lab Sample ID: 240-172530-2Client Sample ID: W2 Matrix: WipeDate Collected: 08/30/22 09:23
Date Received: 09/01/22 09:30
Method: 6010B - Metals (ICP)
RL MDL
Lead 660 1.5 1.0 ug/100 cm2 09/07/22 07:30 09/08/22 16:22 5
Analyte Dil FacAnalyzedPreparedUnit DResult Qualifier
Eurofins Canton
Page 9 of 18 9/12/2022
Project/Site: MCBCL Bldg RR249 - Shoot House
Lab Sample ID: 240-172530-3Client Sample ID: W3 Matrix: WipeDate Collected: 08/30/22 09:28
Date Received: 09/01/22 09:30
Method: 6010B - Metals (ICP)
RL MDL
Lead 710 1.5 1.0 ug/100 cm2 09/07/22 07:30 09/08/22 16:26 5
Analyte Dil FacAnalyzedPreparedUnit DResult Qualifier
Eurofins Canton
Page 10 of 18 9/12/2022
Project/Site: MCBCL Bldg RR249 - Shoot House
Lab Sample ID: 240-172530-4Client Sample ID: W4 Matrix: WipeDate Collected: 08/30/22 09:30
Date Received: 09/01/22 09:30
Method: 6010B - Metals (ICP)
RL MDL
Lead 2.9 0.30 0.20 ug/100 cm2 09/07/22 07:30 09/08/22 13:52 1
Analyte Dil FacAnalyzedPreparedUnit DResult Qualifier
Eurofins Canton
Page 11 of 18 9/12/2022
Project/Site: MCBCL Bldg RR249 - Shoot House
Lab Sample ID: 240-172530-5Client Sample ID: W5 Matrix: WipeDate Collected: 08/30/22 09:33
Date Received: 09/01/22 09:30
Method: 6010B - Metals (ICP)
RL MDL
Lead 1.7 0.30 0.20 ug/100 cm2 09/07/22 07:30 09/08/22 14:04 1
Analyte Dil FacAnalyzedPreparedUnit DResult Qualifier
Eurofins Canton
Page 12 of 18 9/12/2022
QC Sample Results
Project/Site: MCBCL Bldg RR249 - Shoot House
Method: 6010B - Metals (ICP)
Client Sample ID: Method BlankLab Sample ID: MB 240-541473/1-B Matrix: Wipe Prep Type: Total/NA Analysis Batch: 541983 Prep Batch: 541480
RL MDL
Lead <0.20 0.30 0.20 ug/100 cm2 09/07/22 07:30 09/08/22 13:26 1
MB MB
Analyte Dil FacAnalyzedPreparedDUnitResult Qualifier
Client Sample ID: Lab Control SampleLab Sample ID: LCS 240-541473/2-B Matrix: Wipe Prep Type: Total/NA Analysis Batch: 541983 Prep Batch: 541480
Lead 100 92.8 ug/100 cm2 93 80 - 120
Analyte
LCS LCS
DUnitResult Qualifier %Rec
Spike
Added
%Rec
Limits
Eurofins Canton
Page 13 of 18 9/12/2022
QC Association Summary
Project/Site: MCBCL Bldg RR249 - Shoot House
Metals
Pre Prep Batch: 541473
Lab Sample ID Client Sample ID Prep Type Matrix Method Prep Batch
Wipe Wipe_Area240-172530-1 W1 Total/NA
Wipe Wipe_Area240-172530-2 W2 Total/NA
Wipe Wipe_Area240-172530-3 W3 Total/NA
Wipe Wipe_Area240-172530-4 W4 Total/NA
Wipe Wipe_Area240-172530-5 W5 Total/NA
Wipe Wipe_AreaMB 240-541473/1-B Method Blank Total/NA
Wipe Wipe_AreaLCS 240-541473/2-B Lab Control Sample Total/NA
Prep Batch: 541480
Lab Sample ID Client Sample ID Prep Type Matrix Method Prep Batch
Wipe 3050B 541473240-172530-1 W1 Total/NA
Wipe 3050B 541473240-172530-2 W2 Total/NA
Wipe 3050B 541473240-172530-3 W3 Total/NA
Wipe 3050B 541473240-172530-4 W4 Total/NA
Wipe 3050B 541473240-172530-5 W5 Total/NA
Wipe…
This is the start of the file's text. The full file is on GovTribe.