This solicitation is for the design and construction of a new rifle range and support facilities at the Marine Corps Recruit Depot in Parris Island, South Carolina. The project includes construction of a new target storage building, Butts control house, toilet facilities, target area berm, retaining walls, safety side walls, and earth berm structures behind the target impact area with retaining walls and equipment maintenance surfaces. Built-in equipment to be provided comprises Butt System benches, target numbers, target lifters, flag poles, and firing line benches. Responses are due in accordance with the solicitation schedule.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M D
M D
GENERAL FOUNDATION NOTES:
1. SLABS-ON-GRADE MUST BE PLACED DIRECTLY OVER PREPARED
SUBGRADE PER NOTES ON S-001.
DENOTES PROVIDE 6" CONCRETE: NORMAL-WEIGHT,
REINFORCED W/ WWR 6x6-W2.9xW2.9
` DENOTES PROVIDE 18" CONCRETE: NORMAL-WEIGHT,
REINFORCED W/ #6 @ 8" OC T&B EW OVER VAPOR BARRIER
2. DENOTES PROVIDE CONCRETE WALL. (SEE SECTION FOR
THICKNESS & REINFORCING).
3. SEE S-501 FOR TYPICAL FOUNDATION AND SLAB DETAILS.
4. SEE S-502 FOR TYPICAL CONCRETE WALL DETAILS.
5. SOG & FDN SHALL SLOPE TO DRAIN. SEE ARCH FOR DIRECTION AND
SLOPE. SOG & FDN SHALL MAINTAIN A MINIMUM DEPTH OF 1' - 4".
6. ALL DIMENSIONS ARE TO THE FACE OF WALL OR CENTERLINE OF COLUMN
UNLESS NOTED OTHERWISE.
SOG6
CS18
GENERAL ROOF FRAMING NOTES:
1. DENOTES PROVIDE LOAD-BEARING WALL BELOW.
2. SEE S-501 FOR TYPICAL CONCRETE SLAB DETAILS.
3. DENOTES PROVIDE 8" NORMAL WEIGHT CONCRETE.
4. ALL DIMENSIONS ARE TO THE FACE OF WALL OR CENTERLINE
OF COLUMN UNLESS NOTED OTHERWISE
CS8
B
S -3
TARGET BERM
RETAINING WALL
TARGET LINE
PLATFORM
CONCRETE
STAIR
D4
S-501
C4
S-301
C4
S-301
C4
S-301
A2
S-305
CONTINUOUS RETAINING
WALL FOUNDATION
CS18
CS18
D4
S-501
C1
S-302
11' - 7 1/2"11' - 8"
SLOPE
A3
S-302
TYP @
COILING
DOOR
S-502
A4
B3/ S-303
B / S
-3
TYP
EL. 9.2'
3' - 2 1/2"
B
S -3
TARGET BERM
RETAINING WALL
SLOPE
B1
S-301
B1
S-301
B1
S-301
A5
S-305
B5
S-305
SIM
SIM
CONCRETE ROOF
B5
S-305
C1
S-302
C4
S-302
#5 @ 6" OC T&B
O C
T
B
SLOPE
CS8
A3
S-302
8'-0" x 8'-0" x 1'-0"
SHEAR DROP CAP (TYP)
TYP @
COILING
DOOR
A2
S-302
EL. 19.2'
ROOF BEARING EL. 17.2'
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:5
:5
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
SF103
T A
R G
E T
S T
O R
A G
E F
R A
M
IN
G P
L A
N S
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832227
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
NTRUE
NORTH
NTRUE
NORTH
2'
SCALE : 1/4" = 1'-0"
0 4' 8'
1/4" = 1'-0"
TARGET STORAGE FOUNDATION PLAN
A1
1/4" = 1'-0"
TARGET STORAGE ROOF FRAMING PLAN
A3
1/2'
SCALE : 1" = 1'-0"
0 1' 2'
/2 /2
M
B P
A M
E N
D M
E N
T
R
E V
IS
E
D S
L A
B C
A L L O
U T
O U
T S
D
IE
O F
T A
R G
E T
S
O
R A
G
A B C D
/D1 SB101 /C1 SB101 /B1 SB101
/A1 SB101
NORTH SAFETY WALL KEY PLAN
NTRUE
NORTH
C
S
B
M A
T C
H L
IN
E
TYPICAL SEGMENT
A1
S-304
TARGET BERM
RETAINING WALL
A2
S-304
A3
S-304
CJ CJ EJCJ EJ CJ EJ CJ EJ CJ EJ CJ EJ6' - 0"
CJ
EJ
EJ CJ
T/FTG EL 5.00'
(TYP)
25' - 0"
(TYPICAL)
25' - 0"
17' - 11 5/8"
T/FTG EL 5.00'
UNBALANCED SEGMENTUNBALANCED SEGMENT
B3
S-304
REGRADE NORTH SIDE OF SIDE
SAFETY WALL FOR PLACEMENT OF
NEW FOOTING
SEGMENT 1
B3
S-304
2' - 7 3/8"
50' - 0"
7' - 4 5/8"
225' - 0"26' - 6"50' - 0"15' - 6"7' - 8 3/4"
D
S
B
B
S
B
M A
T C
H L
IN
E
M A
T C
H L
IN
E
TYPICAL SEGMENT
A3
S-304
EJ CJ EJCJ EJ CJ EJ CJ EJ CJ EJ CJ EJCJ CJ EJCJ EJ CJ EJ CJ EJCJ
T/FTG EL 5.00'
REGRADE NORTH SIDE OF SIDE
SAFETY WALL FOR PLACEMENT
OF NEW FOOTING
500' - 0"
C
S
B
A
S
B
M A
T C
H L
IN
E
M A
T C
H L
IN
E TYPICAL SEGMENT
A3
S-304
CJ EJ CJ EJ CJ EJ CJ EJCJ EJ CJ EJ CJ EJ CJ EJ CJ EJCJ CJ EJCJ EJCJ
REGRADE NORTH SIDE OF SIDE
SAFETY WALL FOR PLACEMENT
OF NEW FOOTING
500' - 0"
B
S
B
M A
T C
H L
IN
E
TYPICAL SEGMENT
A3
S-304
____________ A2
S-304
____________ A1
S-304
EJ CJ EJ CJ EJ CJ EJCJ
6' - 0"
SEGMENT 1
25' - 0"
SEGMENT 2
25' - 0"
CJ
UNO
25' - 0" TYP
17' - 8"
REGRADE NORTH SIDE OF SIDE
SAFETY WALL FOR PLACEMENT OF
NEW FOOTING
125' - 0"
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:0
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
SB101
N O
R T
H S
ID
E
S A
F E
T Y
W A
L L P
L A
N
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832229
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
1" = 20'-0"
NORTH SIDE SAFETY WALL - A
D1
1" = 20'-0"
NORTH SIDE SAFETY WALL - B
C1
1" = 20'-0"
NORTH SIDE SAFETY WALL - C
B1
1" = 20'-0"
NORTH SIDE SAFETY WALL - D
A1
SCALE : 1" = 20'-0"
0 20' 40'10'
NTRUE
NORTH
NTRUE
NORTH
NTRUE
NORTH
NTRUE
NORTH
/2 /2
M
B P
A M
E N
D M
E N
T
A
D D
E D
W A
L L L
E N
G T
H D
IM
E
N S
IO
N
S A
N D
R E
V
IS
/F T
G
A T
W A
L L B
A
A
S
B
TARGET BERM
KEY PLAN
B / A
S
B
NTRUE
NORTH
A
S
B 2C
SF102
A1
TARGET LINE
PLATFORM
CONCRETE STAIR
RETAINING WALL
FOUNDATION
MATCHLINE
/A2 SB102
C4
S-305
B
S -3
RETAINING WALL
FOUNDATION
C1
S-305
C3
S-305
EJ
T/WALL
STEP
T/FTG EL 9.20'
CJ
EJ
CJ
CJ
EJ
CJ
EJ
CJ
EJ
CJ
EJ
CJ
EJ
CJ
EJ EJ
/4
/4
CONCRETE
STAIR
TARGET LINE
PLATFORM
RETAINING WALL
FOUNDATION
MATCHLINE
/A1 SB102
C1
S-305
BUTT'S CONTROL
HOUSE
SF104
B2
SF103
A1
MATCHLINE
/A3 SB102
EJ
CJ
CJ
EJ
CJ
EJ
CJ
EJ
CJ
EJ
CJ
EJ
CJ
EJ
T/FTG EL 9.20'
T/FTG EL 9.20'
/8
/4
B3/ S-303
B / S
-3
CJCJ
EJEJ
SF101
A1
CONCRETE
STAIR
TARGET LINE
PLATFORM
A
S -3
C3
S-305
C4
S-305
T/WALL STEPMATCHLINE
/A2 SB102
NORTH SAFETY WALL
/8
/4
CJ
EJ
CJ
T/FTG EL. 5.00'
D5
SB102
T/FTG EL. 7.2'
T/FTG EL. 9.2'
EJ
EJEJ
(COORD W/ ACTUAL EQUIPMENT SELECTED)
± 3' - 0" SQUARE TRANSFORMER
FINISHED GRADE
OR PAVEMENT
GRAVEL OR CRUSHED
STONE W/ NO MORE
THAN 10 PERCENT OF
MATERIAL THAT
PASSES THROUGH NO.
4 SIEVE
CONDUIT
CONCRETE
EQUIPMENT
PAD
#4 @ 12" OC
EACH WAY
1' - 2"
OPENING
10" x24"2' - 4"
S E
E C
G
C
G
F O
R H
E
IG
H T
M A
X
M
IN
4' - 4" MAX
8" 8"
TYP
1' - 0"
TYP
1' - 0"
NOTE:
1. GC SHALL COORDINATE SIZE OF PAD WITH EQUIPMENT SELECTION.
2. GC SHALL COORDINATE LOCATION OF PAD WITH ELECTRICAL.
L E
N G
T H
D E
V E
L O
P M
E N
T
L E
N G
T H
D E
V E
L O
P M
E N
T
#4 @ 12" OC #6 @ 12" OC
#6 @ 12" OC
EACH WAY
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:0
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
SB102
T A
R G
E T
B E
R M
R E
T A
IN
IN
G W
A L L P
L A
N
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832230
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
NTRUE
NORTH
NTRUE
NORTH
1" = 20'-0"
TARGET BERM RETAINING WALL - A
A1
1" = 20'-0"
TARGET BERM RETAINING WALL - B
A2
SCALE : 1" = 20'-0"
0 20' 40'10'
1/2'
SCALE : 1" = 1'-0"
0 1' 2'
1" = 20'-0"
TARGET BERM RETAINING WALL - C
A3
NTRUE
NORTH
1" = 1'-0"
ELECTRICAL EQUIPMENT PAD
D5
/2 /2
M
B P
A M
E N
D M
E N
T
A
D D
E D
W A
L L L
E N
G
H
IM
E N
S
IO
N
A
S
B
IMPACT BERM
FRONT KEY PLAN
B
A
S
B
NTRUE
NORTH
RETAINING
WALL
FOUNDATION
MATCHLINE
/A2 SB103
C1
S-306
CJ
EJ
EJ
EJ
EJ
CJ
CJ
EJ
CJ
CJ
EJ
CJ
± 53.8°
EJ
C
S B
A
S -3
SLOPE T
/W
ALL
55' -
/8
T/FTG EL 6.00'
T/FTG EL 6.00'
/2
25' - 0"
25' - 0"
C1
S-306
EJ
CJ
EJ
EJ
EJ
CJ
CJ
EJ
CJ
CJ
EJ
CJ
A3
S-3
MATCHLINE
MATCHLINE
EJ
CJ
EJ
/A4 SB103
/A1 SB103
T/FTG EL 6.00'
T/FTG EL 6.00'
MATCHLINE
EJ
CJ
EJ
CJ
EJ
/A2 SB103
± 20.3°
T/FTG EL 6.00'
SLOPE T/WALL
T/FTG EL 6.00'
/8
/8
TOP OF GRADE
B3
S-307
M
IN
(SIM)
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:0
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
SB103
IM
P
A C
T B
E R
M F
R O
N T
R E
T A
IN
IN
G W
A L L P
L A
N
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832231
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
1" = 20'-0"
IMPACT BERM FRONT RETAINING WALL - A
A1
1" = 20'-0"
IMPACT BERM FRONT RETAINING WALL - B
A2
NTRUE
NORTH
NTRUE
NORTH
SCALE : 1" = 20'-0"
0 20' 40'10'
1" = 20'-0"
IMPACT BERM FRONT RETAINING WALL - C
A4
NTRUE
NORTH
1/8" = 1'-0"
IMPACT BERM FRONT/REAR CONNECTOR -
SLOPING WALL
C3
/2 /2
M
B P
A M
E N
D M
E N
T
A
D D
E D
W A
L L L
E N
G T
H D
IM
E
N S
IO
N
S A
N D
R E
V
IS
/F T
G A
T N
O R
T H
E N
D O
F W
A
S E
B
ID
P
IL
E T
IP
E
L E
V A
T
IO
N
IN
Z O
N E
I I
.0
B A
S E
B
ID
P
IL
E T
IP
E
L E
V A
T
IO
N
IN
Z O
N E
I
B A
S E
B
ID
P
IL
E T
IP
E
L E
V A
T
IO
N
IN
Z O
N E
I
.0
A
A
S
B
IMPACT BERM
REAR KEY PLAN
B
A
S
B
NTRUE
NORTH
C
S
B
RETAINING WALL
FOUNDATION
EL. 7.00'
CJ
EJ
CJ
EJ
CJ
EJ
CJ
EJ
CJ
RETAINING WALL
EJ
CJ
MATCHLINE
/A2 SB104
B1
S-307
B1
S-307
C
S B
BATTERED PILE
(TYP THIS SIDE)
VERTICAL PILE
(TYP THIS SIDE)
T.P. 14
T.P. 12
T.P. 13
T.P. 11
T.P. 15
C
S B
EL. 7.00'
EL. 7.00'
T.P. 16
T Y
P
41' - 6 1/2"
/8
/4
/4
30.0°
/8
RETAINING WALL
FOUNDATION
C
S B
CJ
EJ
CJ
EJ
CJ
EJ
CJ
EJ
RETAINING WALL
VERTICAL PILE
(TYP THIS SIDE)
B1
S-307
EJ
BATTER PILE
(TYP FAR SIDE)
ADDITIONAL BATTER PILE
(EVERY OTHER THIS SIDE)
CJ
EJ
CJ
EJ
CJ
EJ
B1
S-307
VERTICAL PILE
(TYP THIS SIDE)
MATCHLINE
MATCHLINE
/C4 SB104
/A1 SB104
BATTERED PILE
(TYP THIS SIDE)
BATTERED PILE
(TYP THIS SIDE)
B
S B
T.P. 10
T.P. 9
T.P. 6
T.P. 5
EL. 7.00'
T.P. 4
T.P. 7
T.P. 8
T Y
P
T R
A N
S
IT
IO
N
Z O
N E
.0
B A
S E
B
ID
P
IL
E T
IP
E
L E
V A
T
IO
N I N
GENERAL PLAN NOTES:
1. DENOTES TEST PILE (T.P.).
2. "CJ" INDICATES CONTROL JOINT (SEE )
3. "EJ" INDICATES EXPANSION JOINT (SEE )
4. COORDINATE DIMENSIONS, ORIENTATIONS, LOCATIONS, AND
ELEVATIONS WITH THE ARCHITECTURAL AND CIVIL DRAWINGS.
REPORT DIMENSIONAL DISCREPANCIES PRIOR TO
CONSTRUCTION. SITE LAYOUT, ELEVATIONS, AND GRADING ARE
GOVERNED BY THE CIVIL DRAWINGS. SEE ARCHITECTURAL
DRAWINGS FOR INTERIOR FEATURES AND EQUIPMENT.
5. PILES SHOWN HERE ARE 14 INCH SQUARE PRECAST
PRESTRESSED CONCRETE DRIVEN PILES.
6. PILE DRIVING CRITERIA AND ACTUAL PENETRATION DEPTHS
MUST BE ESTABLISHED DURING DRIVING THROUGH DYNAMIC
TESTING WITH A PILE DRIVING ANALYZER (PDA). THREE BASE
BID PILE TIP ELEVATIONS ARE SHOWN IN AN EFFORT TO
ACCOMODATE THE APPARENT VARIATION IN BEARING STRATA
DURING INITIAL TEST PILE DRIVING AND ANALYSIS.
/C1 S-502
/C1 S-502
0"
EJ
CJ
EJ
CJ
B1
S-307
RETAINING WALL
FOUNDATION
RETAINING WALL
VERTICAL PILE
(TYP THIS SIDE)
MATCHLINE
/A2 SB104
EJ
CJ
EJ
EL. 7.00'
BATTERED PILE
(TYP THIS SIDE)
A
S B
/4
5'
3/
4"
T.P. 4
T.P. 3
T.P. 1
T.P. 2
TYP3'
6"
/4
45.0°
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:0
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
SB104
IM
P
A C
T B
E R
M R
E A
R R
E T
A
IN
IN
G
W A
L L P
L A
N
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832232
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
1" = 20'-0"
IMPACT BERM REAR RETAINING WALL - A
A1
1" = 20'-0"
IMPACT BERM REAR RETAINING WALL - B
A2
SCALE : 1" = 20'-0"
0 20' 40'10'
NTRUE
NORTH
NTRUE
NORTH
NTRUE
NORTH
1" = 20'-0"
IMPACT BERM REAR RETAINING WALL - C
C4
/2 /2
M
B P
A M
E N
D M
E N
T
A
D D
E D
W A
L L L
E N
G
H
IM
E N
S
IO
C
IMPACT BERM
REAR KEY PLAN
B
NTRUE
NORTH
A
C
S
B
B
S
B
A
S
B
A
RETAINING WALL
FOUNDATION
PILE SYSTEM
SACON WALL
GIRT BY MANUF
SACON COLUMN
WRAP, TYP
34" CIP CONCRETE
W x
W x
W x
W x
W x
W x
APPROXIMATE
FINISHED GRADE
C1
S-308
B4
S-308
12" SACON WALL
SACON ON WALLS
ABOVE GRADE.
SACON WALL
SUPPLIER TO
PROVIDE STEEL
BANDING AND BOLT
CONNECTIONS OF
PANEL TO CONRETE
WALL.
W x
W X
W X
W X
W X
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
(UNO)
10' - 0"
CJ EJEJCJEJCJEJCJEJCJEJEJ CJ
RETAINING WALL
FOUNDATION PILE SYSTEM
SACON COLUMN
WRAP, TYP
C1
S-308
B4
S-308
12" SACON WALL
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
(UNO)
10' - 0"
CJEJCJEJCJEJCJEJ
W x
W X
W X
W X
RETAINING WALL
FOUNDATION PILE SYSTEM
SACON WALL
GIRT BY MANUF
SACON COLUMN
WRAP, TYP
C1
S-308
B4
S-308
12" SACON WALL
SACON ON WALLS ABOVE
GRADE. SACON WALL
SUPPLIER TO PROVIDE
STEEL BANDING AND BOLT
CONNECTIONS OF PANEL
TO CONRETE WALL.
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
(UNO)
10' - 0"
APPROXIMATE
FINISHED GRADE
34" CIP CONCRETE
CJ EJ
CJ
EJCJEJCJ
RETAINING WALL
(SEE )/C3 SB103
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:0
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
SB105
IM
P
A C
T B
E R
M W
A L L E
L E
V A
T
IO
N
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832233
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
3/32" = 1'-0"
SACON WALL ELEVATION - A
C1
3/32" = 1'-0"
SACON WALL ELEVATION - B
B1
3/32" = 1'-0"
SACON WALL ELEVATION - C
A1
8'
SCALE : 3/32" = 1'-0"
0 16' 24'
NTRUE
NORTH
NTRUE
NORTH
NTRUE
NORTH
/2 /2
M
B P
A M
E N
D M
E N
T
R
E V
IS
E
D C
O L U
M N
C A
L L O
U T
A T
E L E
V A
T
IO
N B
A N
D S
A C
O
W
L L N
O T
E A
T E
L E
V A
T
IO
N A
A N
FLOOD PLAIN
13.07'
TARGET BERM
RETAINING WALL
RETAINING WALL
OVERHANG
PAVEMENT
EXTERIOR
CONCRETE WALL
S-301
C4
VERTICAL EXTENSION
SEE
FOR MORE
INFORMATION
/C1 S-305
S-305
C3
18" MATT FOUNDATION
TRENCH DRAIN
S-302
A2 @ COILING
DOOR ONLY
SLOPE
CONCRETE SLAB-ON-
GRADE (SEE PLAN FOR
REINF AND SLOPE)
#6 VERT @ 8" OC EACH FACE
#4 HORIZ @ 8" OC
EACH FACE
VAPOR BARRIER
10"
2" CLR
2" CLR
#57 STONE
(2) #4 @ 4" OC
EACH FACE
#6 @ 8" EW
T&B
#6 @ 8" EW
T&B
CONT.
PERFORATED
DRAIN PIPE
(SEE )
WATERSTOP
/B1 S-305
T/SLAB
#6 VERT @ 8" OC
EACH FACE
(T Y
P
1' - 6"
WATERPROOFING TO
BOTTOM OF MAT SLAB
GRANULAR
BACKFILL
DOWELS TO MATCH
REINFORCING
FILTER
FABRIC
GEOCOMPOSITE
SHEET DRAIN
CONCRETE SLAB-ON-
GRADE (SEE PLAN
FOR REINF)
#5 VERT @ 12" OC
T/SLAB
VAPOR BARRIER
8" CONC WALL
#5 @ 12" OC OR
DRILL AND EPOXY
(EMBED 7")
#4 @ 12" OC
#6 @ 8" EW T&B#6 @ 8" EW T&B
#57 STONE 1
CONCRETE ROOF SLAB
(SEE PLAN FOR REINF)
10"
(2) #4 T&B @ 4" OC OVER
WALL BELOW, TYP
/8
M
IN
(1) #4 HOOK @ 8" OC
CENTERED IN WALL
CONCRETE WALL
(2) #4 @ 4" OC
EACH FACE
WATERSTOP
SLOPE
2 5/8"
1 3/8"
CONCRETE ROOF SLAB
(SEE PLAN FOR REINF)
(2) #4 T&B @ 4" OC
OVER WALL BELOW
#5 VERT @ 12" OC
CENTERED IN WALL
DOWEL TO MATCH
VERT REINF
#4 @ 12" OC
#4 @ 24" OR DRILL AND
EPOXY DOWELS (6" EMBED)
8"
6"
CAST-IN-PLACE
CONCRETE WALL
CONCRETE SLAB
PROVIDE CHAMFER
AT EXPOSED
EDGES, TYP
#4 HORIZ. &
VERT @ 12" OC
M A
X
T/SLAB
SLOPE TOP OF
CONCRETE TOWARD
BASIN
DRAINAGE BASIN WITH
STAINLESS STEEL GRATE
(REMOVEABLE) WITH ABRASIVE
WALKING SURFACE
L1-3/4x1-3/4x3/16 W/ 1/4"x2
3/4" STUDS @ 12" OC
(COORD. W/ GRATING)
#4 @ 12"
EACH WAY,
TYP.
PERIMETER FOUNDATION
SLAB BEYOND
RETAINING WALL
FOUNDATION OR SLAB
CONCRETE WALL
BEYOND
CONCRETE SLAB
14" MIN.
14" MIN.
#4 @ 12" OC
T/SLAB
1' - 6" 5' - 0" MAX 2' - 6"
GRAVEL
CONCRETE ROOF SLAB
(SEE PLAN FOR REINF)
(1) #4 HOOK @ 8" OC
CENTERED IN WALL
CONCRETE WALL
(2) #4 T&B @ 4" OC
OVER WALL BELOW
8"
#6 VERT @ 12" OC
CENTERED IN WALL
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:0
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
S-301
P
IT
H E
A D
S E
C T
IO
N
S
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832234
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
1/4" = 1'-0"
SECTION AT HEADS
C1
1" = 1'-0"
RETAINING WALL ON MATT FOUNDATION
C4
1" = 1'-0"
CIP WALL ON MATT FOUNDATION
C2
1" = 1'-0"
PIT BUILDING ROOF EDGE
B1
1" = 1'-0"
CIP WALL TO ROOF CONNECTION
B2
1" = 1'-0"
TYPICAL PRIVACY WALL
B3
3/4" = 1'-0"
DRAINAGE BASIN
A1
1/2'
SCALE : 1 1/2" = 1'-0"
0 1' 1 1/2'
1/2'
SCALE : 1" = 1'-0"
0 1' 2'
1'
SCALE : 3/4" = 1'-0"
0 2' 3'
2'
SCALE : 1/4" = 1'-0"
0 4' 8'
1" = 1'-0"
SECTION - CONC SW WALL TO CONC ROOF
B4
/2 /2
M
B P
A M
E N
D M
E N
T
A
D D
E D
W A
L L T
H
IC
K N
E S
S A
T D
E T
A
IL
FLOOD PLAIN
13.07'
AT EXTERIOR COLUMNS TURN
90 DEGREE BAR HOOKS
TOWARDS THE INTERIOR SIDE
CONCRETE COLUMN (SEE )
T/SLAB
T/FTG=T/SLAB
T
IE
S P
A C
IN
G
/2
T
Y P
(S E
E S
C H
E D
U L
E
T
IE
S
O C
HORIZONTAL CONSTRUCTION JOINT SHALL
OCCUR AT BOTTOM OF SLAB (TYP). TOLERANCE
ON TOP OF COLUMN ELEVATION SHALL BE +1/2"
AND -3/4". DEVIATION FROM TOLERANCES SHALL
BE CORRECTED PRIOR TO SLAB CONCRETE
PLACEMENT.
C L R
(S E
E S
C H
E D
U L E
L A
P S
P L
IC
E
S L A
B R
E
IN
F O
R C
IN
G
A T
C O
L U
M N
T Y
P T
IE
S
P A
C
IN
G F
R O
M
P L A
N
S E
E
C L R
COVER REQUIRMENTS
SEE S-004 FOR CLEAR
PROVIDE (1) ADDITIONAL TIE AT MID-
DEPTH OF SLAB.
18" SQUARE
CONCRETE
COLUMN
(8) #6
VERTICAL
DOWEL TO MATCH
VERTICAL REINF
B1
S-302
T Y
P
8' - 0" (TYP)
(U N
O
#6 @ 8" EW T&B
SEE B1 S-302 FOR
ADDITIONAL
INFORMATION
(3) TIES WITHIN
FOOTING
#57 STONE
VAPOR BARRIER
/B1 S-302
(8)-#6 VERTICAL 1' - 6"
EQ EQ 1 1/2" CLR
E Q
E Q
#3 TIES @ 12" OC
MATCH ROOF
HORZ REINF.
LOOP VERT.
REINF. AT TOP
OF WALL
ACI 180° HOOK
10"
CONCRETE WALL
(2) #4 @ 4" OC
EACH FACE
10"
CONCRETE ROOF
SLAB
(1) #4 HOOK @ 8" OC
CENTERED IN WALL
SLOPE
#4 HORIZ. @ 12"
OC EACH FACE
HORIZ. 180° HOOK
SLOPE 1/8"/FT
PRECAST
CONCRETE CAP
DRIP EDGE
DOWEL PIN @ 24"
OC (BY MANUF)
EL. 19.2'
S-302
C4
S-301
B1
S-301
C4
TARGET BERM
RETAINING WALL
RETAINING WALL
OVERHANG
PAVEMENT
EXTERIOR
CONCRETE WALL
VERTICAL EXTENSION
18" MATT
TRENCH DRAIN
S-302
C4 SIM @ COILING
DOOR ONLY
SLOPE
CONCRETE SLAB-ON-
GRADE
8" CONC WALL
#57 STONE
#6 VERT @ 12" OC
CENTERED IN WALL
#6 @ 8" EW T&B#6 @ 8" EW T&B
DOWEL TO MATCH
VERT REINF
#4 @ 12" OC
VAPOR BARRIER
8"
MATCH TYP. WALL
VERT. REINF.
#4 HORIZ. @ 12"
OC EACH FACE
LOOP VERT. REINF.
AT TOP OF WALL
ACI 90° HOOK
INTO WALL
ACI 180° HOOK
CONCRETE ROOF SLAB
3/8"x10"x CONT
EMBED PLATE
1/2" DIA x 6" LG
HEADED STUD @ 12"
OC STAGGERED
CONCRETE WALL
COILING DOOR
COILING DOOR
CONNECTION
(BY MANUF)
EXTERIOR FINISH
SLOPE 1/8"/FT
PRECAST
CONCRETE CAP
DRIP EDGE
DOWEL PIN @ 24" OC DRILLED AND
EPOXY GROUTED INTO WALL
(EMBED 4") (BY PRECAST MANUF)
10"
8"
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:0
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
S-302
P
IT
H E
A D
A N
D T
A R
G E
T S
T O
R A
G E
S E
C T
IO
N
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832235
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
NTS
TYPICAL CONCRETE COLUMN
REINFORCING LAYOUT - ELEVATION
A3
1" = 1'-0"
TYPICAL CONCRETE PIER REINFORCING -
DETAIL
B1
1" = 1'-0"
SECTION - TARGET STORAGE OVERHANG
C4
1/2" = 1'-0"
SECTION - OVERALL TARGET STORAGE
C1
1" = 1'-0"
SECTION - CONC SW WALL TO MATT FDN
A1
1" = 1'-0"
COILING DOOR OPENING DETAIL
A2
/2 /2
M
B P
A M
E N
D M
E N
T
A
D D
E D
W A
L L T
H
IC
K N
E S
S A
T D
E T A
IL
S
A A
N D
A A
R
V
IS
E
D C
O L S
IZ
E
A T
T/WALL
SEE C1/CG301
T/FTG
FLOOD PLAIN
13.07'
TARGET LINE PLATFORM
REINFORCED W/ #4 @ 12" OC EW
6" 6" 3' - 6"
24" LONG #4
@ 18" OC
TARGET BERM
RETAINING WALL
T/SLAB
T/FTG
4' - 6"SLOPE 1/4"
PER FOOT
"BALLISTIC
FILL"
"SELECT MATERIAL"
#57 STONE
PAVEMENT
S-305
A2
S-305
A1
BEYOND
+ 1' - 0"
DRAIN PIPE
(SEE )
TARGET LINE
PLATFORM
TARGET LINE BENCH
FLAG WALL BRACKET
CONCRETE WALL
OVERHANG
TRENCH DRAIN
/B1 S-305
CONCRETE CAP
(BEYOND)
NOTES : SEE FOR REINFORCING AND DIMENSIONS/C4 S-305
S-305
C4
GEOCOMPOSITE
SHEET DRAIN
S-305
C3 BEYOND
TARGET BERM
WALL (BEYOND)
FLAG WALL BRACKET
(1) 3/8"x3" EMBED
CONCRETE SCREW
3/8"x1-1/2" STEEL
PLATE BENCH
WALL BRACKET
CONCRETE
RETAINING WALL
TARGET LINE PLATFORM
T/SLAB
MATCH TYP. WALL
VERT. REINF.
ACI 90° HOOK INTO
WALL
#4 HORIZ. @ 12"
OC EACH FACE
STD. ACI BEND &
INCLINE TO FIT
2' - 6"
SLOPE 1/8"/FT
C3
S-305
C4
S-305
DRAINAGE PITRETAINING WALL
FOUNDATION
OVERHANG
TARGET BERM
RETAINING WALL
TYPICAL
FOOTING &
REINF
FOOTING &
REINF AT
HEADS
(2) #5 @ 4" HORIZ. & VERT., TYP.
EA. EDGE EA. FACE
WALL BEYOND
SEE FOR
ELEVATION AT
BUTTHOUSE
/B1 S-303
LOUVER OPENING
(SEE TYP. REINF
DETAIL ON S-502)
S-501
D4
4' - 9"
EXISTING SAFETY WALL
T/OVERHANG
T/SLAB
(2) 48" LG #5 @ 4"
DIAG., TYP. EA.
CORNER EA. FACE
1" EXPANSION JOINT
C1
S-301
TARGET BERM
RETAINING WALL
OVERHANG C3
S-305
RETAINING WALL
FOUNDATION
DRAINAGE PIT
C4
S-305
FOOTING &
REINF AT
HEADS
TYPICAL
FOOTING &
REINF
(2) 48" LG #5 @ 4" DIAG., TYP.
EA. CORNER EA. FACE
(2) #5 @ 4" HORIZ. & VERT.,
TYP. EA. EDGE EA. FACE
SEE FOR
ELEVATION AT
BUTTHOUSE
/B1 S-303
WALL BEYOND
NORTH SIDE
SAFETY WALL
WALL BEYOND
4' - 9"
S-501
D4
LOUVER OPENING
(SEE TYP. REINF DETAIL
ON S-502)
1" EXPANSION JOINT
C1
S-301
MATCH TYP. WALL
VERT. REINF.
#4 HORIZ. @ 12"
OC EACH FACE
LOOP VERT.
REINF. AT TOP
OF WALL
ACI 90° HOOK
INTO WALL
ACI 180° HOOK
HORIZ. 180° HOOK
DRIP EDGE
PRECAST
CONCRETE CAP
DOWEL PIN @ 24"
OC (BY MANUF)
3' - 6"
SLOPE 1/8"/FT
#4 HORIZ@ 18"
OC EACH FACE
VERT REINF VARIES
(SEE DIMENSION
STRING)#5 VERT @
12" OC
RETAINED
EARTH
L A
P SEE PLAN FOR REINF
IN FOUNDATION (TYP)(2) #4 HORIZ @
4" EACH FACE
OVERHANG
AT HEADS
S-305
A5
(2) #4 HORIZ @ 4"
EACH FACE
T/FTG
8' - 1 3/8" 10"
2" CLR
V
E R
T
O C
O C
2" CLR
TRENCH DRAIN
WATERSTOP
#4 HORIZ. @ 18"
OC EACH FACE
VERT REINF VARIES
(SEE DIMENSION
STRING)
#5 VERT. @
12" OC
RETAINED
EARTH AND
BALLISTIC FILL
L A
P
#5 TRANSV TOP @ 6" OC
#4 LONG. T&B @ 12"
OC MAX.
(2) #4 HORIZ. @
4" EACH FACE
(2) #4 HORIZ @
4" EACH FACE
TYPICAL
OVERHANG
TARGET LINE
PLATFORM
#5 TRANSV
BOTTOM @ 6" OC
S-305
B5
T/FTG
4' - 4 1/2" 4' - 0" 10"
V
E R
T
O C
TRENCH DRAIN
10' - 2"
19' - 4 1/2"
O C
RETAINING WALL
FOOTING
GEOTEXTILE
FILTER FABRIC
NOTES:
1. DRAINAGE AGGREGATE IS GRAVEL OR CRUSHED STONE W/ NO MORE
THAN 10 PERCENT OF MATERIAL THAT PASSES THROUGH NO. 4 SIEVE.
GRANDULAR BACKFILL
6" PERFORATED
DRAIN PIPE
RETAINED
EARTH
6" MIN.6"
T/FTG
GEOCOMPOSITE
SHEET DRAIN
COARSE DRAINAGE GRAVEL-
PEASTONE (SEE NOTE 1)
1/8" SLOPE
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:1
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
S-305
T A
R G
E T
B E
R M
W A
L L S
E C
T
IO
N S
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832238
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
1/2" = 1'-0"
SECTION - PLATFORM
A2
3/8" = 1'-0"
TARGET BERM RETAINING WALL
C1
3/4" = 1'-0"
PLATFORM EQUIPMENT
A1
3/4" = 1'-0"
TYPICAL OVERHANG
B5
1/8" = 1'-0"
SOUTH END ELEVATION
B3
1/8" = 1'-0"
NORTH END ELEVATION
A3
3/4" = 1'-0"
OVERHANG AT PIT BUILDINGS
A5
3/8" = 1'-0"
WALL AND FOUNDATION BEYOND HEADS
C3
3/8" = 1'-0"
TYPICAL WALL AND FOUNDATION
C4
1" = 1'-0"
TARGET BERM FOUNDATION DRAIN
B1
1/2'
SCALE : 1" = 1'-0"
0 1' 2'
1'
SCALE : 3/4" = 1'-0"
0 2' 3'
1'
SCALE : 1/2" = 1'-0"
0 2' 4'
2'
SCALE : 3/8" = 1'-0"
0 4' 6'
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
/2 /2
M
B P
A M
E N
D M
E N
T
A
D D
E D
R E
B A
R C
A L L O
U T A
T D
E T
A
IL
S C
A
N D
REF. EL. 0.0'
T/FTG
FINISHED GRADE =T/WALL
SEE C1/CG301
FLOOD PLAIN
13.07'
"BALLISTIC FILL"
"SELECT FILL"
PAVEMENT
DRAINAGE DITCH
COORDINATE TOP OF
FOOTING WITH LOW
POINT OF DITCH
S-306
C3
#57 STONE
S-306
C4
1' - 6" 11' - 6" 1' - 6"
GEOCOMPOSITE
SHEET DRAIN
C L R
V
E R
T
O C
RETAINED
EARTH
VERT REINF VARIES
(SEE DIMENSION
STRING)
#4 VERT @ 12" OC
#7 @ 12" OC T&B
#4 HORIZ @ 18" OC
EACH FACE
2" CLR
#4 @ 12" OC T&B
/8
L A
P
(2) #4 @ 4" EACH FACE
(2) #4 @ 4"
EACH FACE
/B1 S-305
6' - 8" SEE C1/S-306 FOR STONE
BASE UNDER FOUNDATION
10" 4' - 0"
11' - 6"
2" CLR
GEOCOMPOSITE
SHEET DRAIN
WEEP HOLES
STRAIGHT WALL SEGMENT
CONTINUOUS REINF
AT BASE OF WALL
CONTINUOUS REINF AT
TOP OF WALL
RETAINING WALL
FOUNDATION
RETAINING WALL
FOUNDATION
CONTINUOUS REINF
AT TOP OF WALL
CONTINUOUS REINF
AT BASE OF WALL
STRAIGHT WALL SEGMENT
NOTES:
1. USE PVC FOR WEEP HOLES AND KEEP CONCRETE REINFORCING
AT LEAST 3 INCHES CLEAR OF PVC.
RETAINING WALL
FOOTING
3" WEEP HOLE
@ 8' - 0" OC
DRAINAGE
DITCHGEOCOMPOSITE
SHEET DRAIN
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:1
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
S-306
IM
P
A C
T B
E R
M F
R O
N T
W A
L L S
E C
T
IO
N S
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832239
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
3/8" = 1'-0"
IMPACT BERM FRONT RETAINING WALL
C1
3/8" = 1'-0"
DETAIL
C3
1/2'
SCALE : 1" = 1'-0"
0 1' 2'
2'
SCALE : 3/8" = 1'-0"
0 4' 6'
3/8" = 1'-0"
SOUTH END SLOPE ELEVATION
A1
3/8" = 1'-0"
NORTH END SLOPE ELEVATION
A3
1" = 1'-0"
FRONT IMPACT BERM FOUNDATION DRAIN
C4
/2 /2
M
B P
A M
E N
D M
E N
T
R
E V
IS
E
D F
O O
T
IN
G T
H
IC
K N
E S
S A
T D
E T
A
IL
T/WALL
SEE C1/CG301
T/WALL
FINISHED GRADE
T/FTG
FLOOD PLAIN
13.07'
SACON (SHOCK-
ABSORBING CONCRETE)
WALL BY FABRICATOR
BATTERED PILES
VERTICAL PILES
ROADWAY
"SELECT FILL"
"BALLISTIC FILL"
"SELECT FILL"
#57 STONE
S-307
B4
S-308
C1
S-307
B3
WEEP HOLES
(SEE )/A1 S-307
(S E
E C
IV
IL
M
A X
M
A X
(TYP)
15.0°
1' - 6" 21' - 0"
1' - 6"
GEOCOMPOSITE
SHEET DRAIN
S-307
A1
PILE
T/FTG
PILE CUT-OFF
PRECAST
CONCRETE PILE
CAST-IN-PLACE
PILE CAP
PROVIDE 5'-0" LONG x 1-3/4"
ID (INSIDE DIA) GALV
CORRUGATED SLEEVES TO
ALLOW FOR PILE CUT-OFF
TO ELEVATION. FILL SOLID
WITH NON-SHRINK GROUT
(TYP)
A2
S-307
(4) #7 HOOKED
A615 DEFORMED
REINF BARS
EXTEND PILE
INTO PILE CAP
C L R
M A
X
M
IN
2' - 3"
#5 LONG @ 12" OC
#9 TRANSV @ 8" OC
#9 TRANSV @ 8" OC
SEE SACON
DETAILS FOR TIES
& COLUMN
ANCHORAGE
SACON
WALL
RETAINED
EARTH
#6 HORIZ. @ 12" OC
EACH FACE
#9 DOWELS @ 4" OC
#9 VERT. @ 8" OC
#6 VERT. @ 12"
OC
#6 DOWELS @
12" OC
T/GRADE
T/WALL
SEE C1/CG102
PILEPILE
L A
P
PILE
S-307
B4
33"
#6 BENT BARS @ 12"
OC (CENTER JOINT
CROSSING UNDER
WALL)
WEEP HOLES
3' - 6" 11' - 6"
6' - 9" 2' - 10"
BATTERED PILES
VERTICAL PILES
SACON ON WALLS
ABOVE GRADE (SEE
ELEVATION ON )
(NO SACON WALL AT
SIMILAR CONDITION)
SB105
(M
IN
2' - 3" 2' - 3"
TYPICAL BATTERED CONCRETE PILE
NOTES:
1. SEE GENERAL NOTES FOR DETAILED
DESIGN INFORMATION.
CHAMFER, TYP
PRECAST CONCRETE PILE
REINF PER MANUF
(DESIGN MUST SATISFY
REFERENCED STANDARDS
AND CONTRACT DOCUMENTS)1
S Q
U A
R E
4" 6" 4"
(4) 1-3/4" GALV
CORRUGATED SLEEVES
AT TOP OF PILE
TYPICAL VERTICAL CONCRETE PILE
NOTES:
1. SEE GENERAL NOTES FOR DETAILED
DESIGN INFORMATION.
CHAMFER, TYP
PRECAST CONCRETE PILE
REINF PER MANUF
(DESIGN MUST SATISFY
REFERENCED STANDARDS
AND CONTRACT DOCUMENTS)1
S Q
U A
R E
14"
(1) 1-3/4" GALV
CORRUGATED SLEEVES
AT TOP OF PILE
NOTES:
1. USE PVC FOR WEEP HOLES AND KEEP CONCRETE REINFORCING AT LEAST
3 INCHES CLEAR OF PVC.
RETAINING WALL
FOOTING
RETAINED
EARTH
3" WEEP HOLE
@ 8' - 0" OC
FINISHED GRADE
GEOCOMPOSITE
SHEET DRAIN
1/4" = 1'-0"
IMPACT BERM REAR RETAINING WALL
B1
1" = 1'-0"
DETAIL
B4
1/4" = 1'-0"
DETAIL
B3
1" = 1'-0"
SECTION
A2
1" = 1'-0"
REAR IMPACT BERM FOUNDATION DRAIN
A1
1/2'
SCALE : 1" = 1'-0"
0 1' 2'
2'
SCALE : 1/4" = 1'-0"
0 4' 8'
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:1
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
S-307
IM
P
A C
T B
E R
M R
E A
R W
A L L S
E C
T
IO
N S
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832240
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
/2 /2
M
B P
A M
E N
D M
E N
T
R
E V
IS
E
D S
A C
O N
W A
L L N
O T
E A
T D
E T
A
IL
SACON (SHOCK-
ABSORBING CONCRETE)
WALL BY FABRICATOR
HORIZONTAL GIRT
MEMBER BY SACON WALL
MANUFACTURER
W12 SACON WALL COLUMN
(SEE ELEVATIONS FOR SIZE)
T
IE
S
SACON COLUMN
WRAP BY SACON
FABRICATOR
NON-SHRINK GROUT
FILL
IMPACT BERM REAR
RETAINING WALL
S-308
D2
ALL STRUCTURAL STEEL
ITEMS MUST BE
GALVANIZED (G90 MIN)
S-308
B4
SACON COLUMN
COVER BEYOND
STEEL BANDING AND CONNECTIONS BY
SACON SUPPLIER
SACON COLUMN
COVER BY SUPPLIER
STEEL BANDING AND
CONNECTIONS BY SACON
SUPPLIER
COLUMN CONNECTIONS BY
SACON SUPPLIERSTEEL COLUMN
(SEE ELEVATION)
12" MIN.
M
IN
1' - 9"
1" 6 1/2" 1' - 0" 2 1/2"
N O
N -S
H R
IN
K
G R
O U
T
V O
ID
NON-SHRINK GROUT
2' - 6" VOID
(4) 1-3/4" DIA F1554 GR. 36
ANCHOR BOLTS @ W12x35
(4) 1-3/8" DIA. @ W12x26
2-1/2" BASEPLATE @ W12x35 2" BASEPLATE @ W12x26
5/16
/2
/2
ALL STRUCTURAL STEEL
ITEMS MUST BE
GALVANIZED (G90 MIN.)
C5
S-308
#3 CLOSED TIES AT
SPACING SHOWN HERE
COLUMN ANCHOR BOLT
(SEE )/C5 S-308
FILL VOID WITH
NON-SHRINK
GROUT
GALVANIZE COLUMN,
BASEPLATE, WELDS,
BOLTS, AND NUTS (G90 MIN)
STEEL COLUMN
(SEE ELEVATION)
(10) #7 VERT
T
IE
S
O C
2"
T/FTG
NOTES:
1.
2.
PROVIDE LEVELING NUTS & WASHERS, SHIM
STACKS, OR LEVELING PLATE TO
TEMPORARILY SUPPORT COLUMN DURING
LEVELING AND GROUTING.
PLATE WASHER W/
STANDARD HOLE (SEE
TABLE)
HEAVY HEX NUT AND
SQUARE PLATE
WASHER AT
EMBEDDED END
SEE
NOTE 1
PROVIDE ADEQUATE PROJECTION FOR
INSTALLATION OF NUT ABOVE BASE PL, 6" MIN
MININMUM PLATE
WASHER DIMENSIONS
AR DIA MIN WASHER
DIMENSION
MIN WASHER
THICKNESS
3/4"
7/8" 2 1/2" 5/16"
1" 3" 3/8"
1 1/4" 3" 1/2"
1 1/2" 3 1/2" 1/2"
1 3/4" 4" 5/8"
2" 5" 3/4"
2 1/2" 5 1/2" 7/8"
2" 1/4"
S H
R
IN
K G
R O
U T
/2
(M
IN
N
O N
L
TACK
SEE
NOTE 2
FINISHED GRADE
OR PAVEMENT
GRAVEL OR CRUSHED
STONE W/ NO MORE
THAN 10 PERCENT OF
MATERIAL THAT
PASSES THROUGH NO.
4 SIEVE
CONCRETE
EQUIPMENT
PAD
#4 @ 12"
OC EACH
WAY
3' - 10"8"1' - 6"
NOTE:
1. GC SHALL COORDINATE SIZE OF PAD AND LOCATION WITH CIVIL.
1' - 0"
M A
X
L E
N G
T H
D E
V E
L O
P M
E N
T
L E
N G
T H
D E
V E
L O
P M
E N
T
M
IN
#6 @ 12"
OC EACH
WAY
#6 @ 12" T&B
(7) #4 CONT
T&B
CLR
3"
C L R
C L R
1/8" SLOPE
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
DES DRW CHK
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
A/E INFO
SEAL
AS NOTED
DRAWFORM REVISION: 25 AUG 2020
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SATISFACTORY TO DATE
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
1 2 3 4 5
A
B
C
D
1 2 3 4 5
A
B
C
D
/2
/2
:0
:1
P M
C U s e rs \m s w e e n e y \D o c u m e n ts
\R e v it L o c a l\
-P a rr is I s la n d R a n g e
I m p ro v e m e n ts P h a s e
-R
-S T
R U
C T m s w e e n e y p e s e n g in e e rs .c o m
.r v t
L A
D J o b N o -1
-0
S-308
S A
C O
N W
A L L S
E C
T
IO
N S
P -4
C H
O S
IN
R
A N
G E
IM
P
R O
V E
M E
N
TS
M O
D E
R N
IZ
A
TI
O
N , P
H
10 TENTH STREET N.E., SUITE 200
ATLANTA, GA 30309
Tel 404.874.8333 Fax 404.874.8330
1641320
P A
R R
IS
I
S L A
N D
S
C
12832241
M
ID
LA
N
T D
C C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
V
IR
G
IN
IA
M C
R D
P A
R R
IS
I
S L A
N D
DGDG MBP
June 24, 2021
Approved by CDR A. Litteral, P.E.
PWO, MCRD Parris Island
DJD
CJC / LJM
EJA
DSN
1/4" = 1'-0"
IMPACT BERM SACON WALL
C1
1" = 1'-0"
SACON JOINT & BANDING
D2
1" = 1'-0"
SACON COLUMN COVER
C2
1" = 1'-0"
STEEL COLUMN BASEPLATE
C5
1" = 1'-0"
STEEL COLUMN WALL ANCHORAGE
B4
1" = 1'-0"
TYPICAL ANCHOR BOLT ASSEMBLY
A3
1/2'
SCALE : 1" = 1'-0"
0 1' 2'
2'
SCALE : 1/4" = 1'-0"
0 4' 8'
1" = 1'-0"
ELECTRICAL PAD DETAIL
A1
/2 /2
M
B P
A M
E N
D M
E N
T
R
E V
IS
E
D C
O L U
M N
S
IZ
E C
A L L O
U T
A T
D E
T A
IL
| Sheets |
| SF103 - TARGET STORAGE FRAMING PLANS |
| SB101 - NORTH SIDE SAFETY WALL PLAN |
| SB102 - TARGET BERM RETAINING WALL PLAN |
| SB103 - IMPACT BERM FRONT RETAINING WALL PLAN |
| SB104 - IMPACT BERM REAR RETAINING WALL PLAN |
| SB105 - IMPACT BERM WALL ELEVATION |
| S-301 - PIT HEAD SECTIONS |
| S-302 - PIT HEAD AND TARGET STORAGE SECTION |
| S-305 - TARGET BERM WALL SECTIONS |
| S-306 - IMPACT BERM FRONT WALL SECTIONS |
| S-307 - IMPACT BERM REAR WALL SECTIONS |
| S-308 - SACON WALL SECTIONS |
| 2021-09-24T10:03:21-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:03:38-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:03:38-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:03:38-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:03:39-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:03:39-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:03:56-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:03:56-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:04:09-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:04:21-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:04:22-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:04:22-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:05:53-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:10-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:10-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:11-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:11-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:12-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:12-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:12-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:13-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:13-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-09-24T10:06:14-0400 | |
| James E. Donahue, R.A. | |