This document is a sources sought notice from the Naval Facilities Engineering Command, Mid-Atlantic seeking capable small businesses to perform construction services for the Dry Dock 2 Complex at the Portsmouth Naval Shipyard in Kittery, Maine. The project consists of fabricating and installing approximately 23,100 square feet of enclosures, including a 21,500 square foot permanently installed enclosure with towers, storage areas, railcar access, work areas and cranes, as well as a 1,600 square foot modular relocatable enclosure. Additional scope includes utility infrastructure and modifications, clean room finishes, and HVAC, electrical, alarm and communication systems. Responses are due by November 24, 2020. Interested small businesses should submit capabilities packages demonstrating experience on similar projects over $40 million involving structural steel fabrication, mechanical and crane systems, and construction in congested areas. Award of a contract is anticipated in June 2021 for SDVOSB, VOSB, 8(a), HUBZone, and women-owned small businesses.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
We Keep Your Power On May 15, 2019 ASCO POWER TECHNOLOGIES L.P, NORTHEAST SALES DISTRICT, 2537 ROUTE 52, SUITE 14, EAST FISHKILL NY, 12533, TEL# 508-624-0466, FAX # 508-630-1653
Bill of Materials – Automatic Transfer Switches Portsmouth Naval Shipyard DD#1
Designation
QTY
AMPS/
POLES BYPASS TRANSITION CATALOG NUMBER OPTIONAL ACC. ENCL. DRG. WIRING DRG.
BOM
NUMBER
- 2 600/3 YES OPEN J07ATB030600M5XC
6D,72EE2,99,
131,135SB
802093 806095-879
TO BE
ENGINEERED
*To be engineered BOMs does not have as built drawings. Only preliminary drawings are provided.
05/15/19
# 1
AMPS: 600
QTY: 2
Bulletin Number : 7000 Series Transfer Switches Catalog Number : J07ATB030600M5XC
Service Voltage / Hz : 460V/60 Hz Optional Accessories : 6D,72EE2,99,131,135SB
By-pass Isolation : Yes Product Description : Automatic Open Transition Transfer and Bypass-Isolation Switches
No. of Switched Poles : 3
Neutral Configuration : None [0]
Withstand Rating :
42,000 @ 480 Vac – Time Based Rating (0.05 secs) 50,000 @ 480 Vac – Specific Circuit Breaker Rating 200,000 @ 600 Vac – Current Limiting Fuse Rating (J/L)
No. of Cables & Lug : See below outline size
Enclosure : 1 (C) – UL Type 1 Enclosure Service : Three Phase, 4-wire
ACCESSORY DESCRIPTION
# Accessory Code Description
1 6D Retransfer to normal mode selector. Maintained two position selector switch permits selection of manual or automatic retransfer to normal. Manual retransfer requires a second selector switch (6B/6C) to be momentarily closed to initiate a retransfer to the normal source. While in manual retransfer mode, if an emergency source failure should occur and the normal source is still available, manual retransfer will be automatically bypassed.
2 72EE2 5170 Quad-Ethernet Module provides transfer switch dashboard screen with password protected control capabilities, email alerts and open protocol support in a single module with an integrated 4 port Ethernet switch.
3 99 Indicates that all additional signal lights are push to test type
4 131 ARRA 'Buy American' Compliant
5 135SB 5210 Power Meter mounted on the door monitoring the load side of the switch with bypass status inputs wired to a Moxa IO module. Powered from both sources.
Portsmouth Naval Shipyard DD#1 ATS Detailed Information
05/15/19
DRAWINGS FOR APPROVAL
Drawing Number Description
802093 Enclosure Outline and Mounting Diagram
806095-879 Three Phase Wiring Diagram
ASCO
NOT PROVIDED
NOT
PROVIDED
ASCO 7000 Series POWER TRANSFER SWITCH
Protecting:
• Healthcare Facilities
• Enterprise / Colocation / Cloud Data Centers
• Commercial Buildings / Industrial Buildings
• Telecom Mobile / Central Switching Centers
• Process Manufacturing
• Distributed Energy Resources (Microgrid) / Load Management
• Water Treatment Facilities
ASCO 7000 Series POWER TRANSFER SWITCHES
As society becomes increasingly dependent on the quality and reliability of electrical power, interruption or complete loss of power can result in serious hardships, significant financial losses, or dangers to life and safety.
ASCO Power Technologies (ASCO) provides industry-leading products and solutions for reliably transferring critical loads to emergency power sources. Using ASCO products can mean the difference between a minor inconvenience and a major catastrophe.
You’ll find ASCO Power Transfer Switches wherever there is a critical load to protect.
ASCO offers a variety of product solutions to meet virtually every requirement, including distributed generation applications. That’s why the 7000 SerieS is available in open, delayed, closed and soft load transition configurations. Additionally, switched or overlapping neutral options provide for more accurate operation of ground fault protection systems and reduction of voltage transients from unbalanced load switching.
• Conventional two-position transfer configuration, plus closed and delayed transition modes of operation. All configurations available with either automatic or non-automatic control.
• Listed to UL 1008 Transfer Switch Equipment for Automatic Transfer Switches and Certified to CSA 22.2, No. 178.
• Qualified and certified to IEC 60947-6-1, CE marked (optional). (Limited to certain accessories.)
• Rated up to 600 VAC, 30 through 4000 amps.
• 3 to 18-Cycle Withstand and Closing Rating (WCR) Standard, 30-Cycle WCR Optional.
• Reliable and field-proven solenoid operating mechanism.
• High WCRs including short-time withstand current rating for optimum flexibility in circuit breaker coordination (600-4000 amps).
• Solid, switched, or overlapping neutral conductor options.
• Front replaceable main and arcing contacts (800-4000 amps).
• Programmable microprocessor controller with keypad and LCD display.
• Centrally located terminal block for customer control connections (260-4000 amps).
• 16mm, industrial grade control switches and indicating lights.
• Switch position and source acceptability LED indicators.
• Standard ground conductor connections.
• Four auxiliary contacts, two contacts closed when switch is in normal position and two contacts closed when switch is in emergency position.
• Local/remote communications capability for interfacing with ASCO POWERQUEST® communication products.
• Protected by a comprehensive 2, 5, or 10 year warranty.
7000 Series
7000 SERIES POWER TRANSFER SWITCHES PRODUCT FEATURES
ASCO Power Transfer Switches are the standard of the industry. High speed transfer of loads between alternate sources of power, regardless of ampacity, is achieved using a reliable, field-proven solenoid operating mechanism. When combined with a programmable microprocessor controller with keypad and LCD display, they offer the most advanced method of transferring all types of loads, such as motors, electronic drives, UPS’s and microprocessor-based systems. 7000 SerieS Power Transfer Switches are available open or enclosed, in ampacities ranging from 30 through 4000 amps with the largest selection of optional accessories offered anywhere. All switching configurations are available with an integrally mounted bypass-isolation switch. Configurations are also available for service entrance applications.
Fig. 1: Three Pole 7000 SerieS Automatic Transfer Switch rated 1600 amps
(shown with optional front connected terminals and Power Meter).
The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World.
7000 SERIES POWER SWITCHING SOLUTIONS
Automatic & Non-Automatic Transfer Switching
ASCO Transfer Switches are available in both automatic & non-automatic initiation types. Both types are electrically operated. For automatic transfer switches, the controller initiates transfer. For non-automatic transfer switches, the user initiates switching transfer between power sources using switches mounted locally or at remote locations. Non-automatic switches have the following features:
• Sizes from 30 through 4000 amps.
• Microprocessor-based controller provides for addition of optional accessories.
• Controller prevents inadvertent operation under low voltage conditions.
• Low control circuit operating currents allow for long distances between remotely mounted manual control switches and the transfer switch.
• Source acceptability lights inform operator when sources are available to accept load.
• Standard inphase monitor can be activated for transferring motor loads.
Fig. 2: Three Pole, Non-Automatic, Electrically-Operated 400 Amp Switch in a Type 1 Enclosure.
7000 SERIES POWER SWITCHING SOLUTIONS
Open Transition Transfer Switching
ASCO Transfer Switches are available in a standard, 2-position, open transition configuration to reliably transfer loads between power sources. Loads transfer to the alternate source in less than 100ms.
In phase transfer can be activated for transferring motor loads. Open transition switches are suitable for a wide range of applications.
• Available from 30 to 4000 amps.
• Utilizes reliable, field-proven, single solenoid operating mechanisms.
• Single operator design prevents direct connection of both sources.
Delayed Transition Transfer Switching
ASCO Delayed Transition Transfer Switches are designed to provide transfer of loads between power sources with a timed load disconnect position for an adjustable period of time. Applications include older style variable frequency drives, rectifier banks, and load management applications.
• 150 through 4000 amps.
• Utilizes reliable, field-proven solenoid operating mechanisms.
• Mechanical interlocks to prevent direct connection of both sources.
• Indicator light (16mm, industrial grade type LED) for load disconnect position.
• Adjustable time delay for load disconnect position.
Closed Transition Transfer Switching
ASCO Automatic Closed Transition Transfer Switches feature main contacts that overlap, permitting the transfer of electrical loads without power interruption. The switch transfers in a make-before-break mode if both sources are within acceptable parameters. Control logic continuously monitors source conditions and automatically determines whether the load transfer should be open (conventional non-overlap mode) or closed transition.
• Available 150 through 4000 amps.
• Utilizes reliable, field proven solenoid operating mechanism.
• Closed Transition Transfer is achieved passively within 5 electrical degrees, without control of engine generator set.
• Additional control wiring not required.
• Overlap time is less than 100 milliseconds (consult your local utility on protective relay requirements).
• Failure to synchronize and extended parallel time indication.
Fig. 3: Four pole, Delayed Transition 200 Amp Transfer Switch.
Fig. 4: Four Pole, Closed Transition, 1000 Amp Transfer Switch in a Type 1 enclosure.
WITHSTANDING AND CLOSING ON SHORT CIRCUIT FAULT CURRENTS
Withstanding and closing on short circuit currents require transfer switches that can handle extremely high electromagnetic forces and thermal stresses. Circuit breakers and fuses are designed to open on short circuit currents. However, while transfer switches must withstand a short circuit current until the over-current device clears the fault.
The withstand and closing rating (WCR) indicates the highest level of current a transfer switch can close on and carry for a specific amount of time. For system coordination purposes, the time must be sufficient for the upstream over-current protective device to clear the fault. The WCR must equal or exceed the available fault current and system voltage at the power source terminals of the switch.
The purpose of a power transfer switch is to maintain power to the load, whereas an overcurrent device is designed to open under a fault condition to protect the circuit conductors and equipment. ASCO power transfer switches use a unique solenoid operator design to force and lock the main contacts closed on a high current fault, rather than allowing them to open like a circuit breaker.
Main contact material composition, contact geometry, arcing contact design, and other features all affect the ability of the power transfer switch to withstand and close-on high fault currents. ASCO employs a variety of computer modeling programs to determine the optimal combination of all these elements to create a superior transfer switch design.
ASCO power transfer switches are available with a full range of WCRs to accommodate a variety of over-current devices with fault-clearing times from 0.004 to 0.5 seconds (1/4 to 30 cycles). In fact, ASCO transfer switches provide the industry’s most comprehensive solution for all short circuit requirements. Our 7000 SERIES WCR table addresses all time-based, specific breaker, current-limiting fuse, and short-time ratings necessary for accommodating selective coordination requirements.
In order to meet NEC selective coordination requirements, short-time settings are specified on circuit breakers following a coordination study. A circuit breaker’s short-time settings require transfer switches to withstand and close-on short circuit currents for time durations of 0.1 seconds (6 cycles for a 60Hz system) or longer. The 4th Edition of UL1008 added this optional “Short-Time Rating” for transfer switches in 2002. Underwriters Laboratories does not require a specific time or specific number of cycles to qualify for this rating, but the transfer switch WCRs must coordinate with the short-time settings on the breakers.
While there are no ideal time delay breaker settings for selective coordination, many engineers have been successful with using 0.3 seconds (18 cycles) for the most upstream breaker short-time settings. However, 0.5 second (30-cycle) settings may be required for larger projects with multiple levels of distribution breakers or where transfer switches are served by ANSI switchgear with 30-cycle withstand ratings.
As with most electrical devices, higher ratings usually result in higher costs. The goal is to optimize selective coordination in the system while incorporating power transfer switches at a reasonable cost. ASCO 7000 SERIES H and G frame Power Transfer Switches include a 0.3 second (18-cycle) short-time rating as stan-dard along with a 0.05 second (3-cycle) short-circuit rating. The 18-cycle rating should be sufficient to satisfy most selective coordination requirements without adding cost to the transfer switch budget.
The ASCO P, Q, S, and U frame 7000 SERIES Power Transfer Switches are perfect for larger projects, or for systems using ANSI switchgear requiring a 0.5 second
(30-cycle) rating. These switches feature a re-designed contact assembly with more robust contact frames, heavier-duty crank arms, and a high-speed coil closing circuit. These design enhancements enable flexibility for selective coordination solutions and provide safe and reliable fault current endurance for up to 0.5 seconds.
7000 SERIES BYPASS ISOLATION SWITCHES
Automatic Transfer Bypass-Isolation Switches
Transfer Switch Drawout Features (150-4000 Amps)
ASCO Automatic Transfer & Bypass-Isolation Switches are available in open transition, closed transition, and delayed transition designs. The bypass and isolation features allow the primary automatic transfer switch to be inspected, tested, and maintained without interrupting power to the load. They also provide redundant power transfer if the ATS is disabled or removed from service.
• Available 150 to 4000 amps.
• Allows bypass-isolation without load interruption.
• Bypass switch and transfer switch have identical electrical ratings.
• Heavy-duty mechanical interlocks prevent unintended operation.
• Bypass contacts carry current only during bypass mode.
• Drawout design allows for easy transfer switch maintenance.
• Bypass and isolation handles are permanently mounted. The bypass switch has dead front quick-make, quick-break operation for transferring loads between live sources.
• Bypass switch is fully rated for use as a manual 3-position transfer switch.
• Bypass and isolation functions are simple, requiring a total of two operating handles.
• No toggle switches, push buttons, selector switches, or levers are required for bypass-isolation operation.
• Mechanical indicators show bypass and transfer switch positions.
• 800 -1200 amp models available in shallow depth, front connected or rear connected designs.
Fig. 5: J-Frame 150-600 amps
Fig. 6: H-Frame 600-1200 amps
Fig. 7: G-Frame 1000-3000 amps
Fig. 8: G-Frame 4000 amps
• Automatic secondary disconnects remove all control power as switch is withdrawn.
• Drawout carriage provides for easy transfer switch mechanism maintenance and/or removal via commercially available breaker hoists.
• Optional transfer switch lifting yoke kit available
• Optional automatic shutters that close when the transfer switch is withdrawn to provide bus isolation. Specify accessory 82C (1600-3000 Amp only).
Automatic Secondary
Disconnects
Automatic Shutters
(optional on 1600-3000amps)
Self Aligning
Jaws
Fig. 9: Bypass-Isolation Transfer Switch Secondary Disconnects and
Optional Automatic Shutters.
Fig. 10: Bypass-Isolation Transfer Switch Self-Aligning Power Jaws.
7000 SERIES BYPASS ISOLATION SWITCHES
Bypass and Isolation Handles - Simple as 1, 2, 3
1 Bypass to Normal
N
E
L
Push in bypass handle and turn it counter clockwise
Bypass handle
Isolation handle
Bypass Switch
Automatic Transfer Switch
2 Test Position
N
E
L
Turn isolation handle counter clockwise until window shows “Test”
Isolation handle
Bypass Switch
Automatic Transfer Switch
3 Isolation Position
N
E
L
Turn isolation handle counter clockwise until window shows “isolate”
Isolation handle
Bypass Switch
Automatic Transfer Switch
1 Bypass to Normal
N
E
L
Push in bypass handle and turn it counter clockwise
Bypass handle
Isolation handle
Bypass Switch
Automatic Transfer Switch
2 Test Position
N
E
L
Turn isolation handle counter clockwise until window shows “Test”
Isolation handle
Bypass Switch
Automatic Transfer Switch
3 Isolation Position
N
E
L
Turn isolation handle counter clockwise until window shows “isolate”
Isolation handle
Bypass Switch
Automatic Transfer Switch
1 Bypass to Normal
N
E
L
Push in bypass handle and turn it counter clockwise
Bypass handle
Isolation handle
Bypass Switch
Automatic Transfer Switch
2 Test Position
N
E
L
Turn isolation handle counter clockwise until window shows “Test”
Isolation handle
Bypass Switch
Automatic Transfer Switch
3 Isolation Position
N
E
L
Turn isolation handle counter clockwise until window shows “isolate”
Isolation handle
Bypass Switch
Automatic Transfer Switch
Isolation handle
Mechanical isolation handle position window (connected/test/isolate)
Bypass switch position
Transfer switch position
Source availability
Isolation handle position
Padlocking provisions
Mechanical bypass switch position flags
7000 SERIES GROUP 5 CONTROLLER
The 7000 SERIES Controller (Group 5) is used with all sizes of Power Transfer Switches from 30 through 4000 amps. It is the most reliable and field-proven transfer switch controller in the industry and includes, as standard, all of the voltage, frequency, control, timing and diagnostic functions required for most emergency and standby power applications. It can be equipped with a color Touch Display Interface that provides information to better manage your transfer and bypass switch. (See page 16 for additional information.)
Because severe voltage transients are frequently encountered in industrial distribution systems, the controller's logic board is separated and isolated from its power board. This improves electrical noise immunity performance and helps assure compliance with the rigorous transient suppression standards shown in the table below.
7000 SERIES Group 5 Controller
Emission Standard - Group 1, Class A EN 55011:1991
Generic Immunity Standard, from which: EN 50082-2:1995
Electrostatic Discharge (ESD) Immunity EN 61000-4-2:1995
Radiated Electromagnetic Field Immunity ENV 50140:1993
Electrical Fast Transient (EFT) Immunity EN 61000-4-4:1995
Surge Transient Immunity EN 61000-4-5:1995
Conducted Radio-Frequency Field Immunity EN 61000-4-6:1996
Voltage Dips, Interruptions and Variations Immunity EN 61000-4-11:1994
Group 5 Controller Standard Display
Advanced Touch Display Interface (TDI) Accessory 150 Tech. Package (see page 16)
Enter/Save SettingsEsc
Increase Value
Decrease Value
Menu Scroll
Menu Scroll
Normal OK
Load on Normal
7000 SERIES GROUP 5 CONTROLLER
Control Features
• Touch pad programming of features and settings without the need for meters or variable power supplies.
• Sixteen (16) selectable operating voltages available in a single Controller.
• On-board diagnostics provide control panel and ATS status information for analyzing system performance.
• Displays and counts down active timing functions.
• Selectable multi-language display (English, German, Portuguese, Spanish, or French. For other languages, contact ASCO).
• Password protection to prevent unauthorized tampering of settings.
• Optional Color Touch Display Interface simplifies control management and expands event log to 1,000 events. Specify Accessory 150AT (ATS) or 150BT (Bypass).
• Remote monitoring and control with ASCO POWERQUEST® communication products.
Specify Accessory 72EE2.
• Load shed option for bus optimization applications.
Specify optional accessory 30B.
• Historical event log.
• Statistical ATS systems monitoring information.
Voltage and Frequency Sensing
• 3-Phase under-voltage and over-voltage settings on normal and emergency sources.
• Under-frequency and over-frequency settings on normal and emergency.
• True RMS Voltage Sensing with +/- 1% accuracy; Frequency Sensing Accuracy is +/- 0.2%.
• Selectable settings: single or 3-phase voltage sensing on normal and emergency; 50 or 60Hz.
• Phase sequence sensing for phase-sensitive loads.
• Voltage unbalance detection between phases.
Status and Control Functions
• Output contact (N/O or N/C) for engine-start signals.
• Selection between “commit/no-commit” on transfer to emergency after engine start and normal restores before transfer.
• Advanced inphase algorithm that automatically measures the frequency difference between the two sources and initiates transfer at appropriate phase angles to minimize disturbances when transferring motor loads.
• Standard event log displays 99 logged events with the time and date of the event, event type and event reason.
• Output signals for remote indication of normal and emergency source acceptability
• Statistical ATS/System monitoring data screens that provide:
- Total number of ATS transfers.
- Number of ATS transfers caused by power source failure.
- Total number of days ATS has been in operation.
- Total number of hours that the normal and emergency sources have been available.
Time Delays
• Engine start time delay - delays engine starting signal to override momentary normal source outages - adjustable 0 to 6 seconds.
• Transfer to emergency time delay - adjustable 0 to 60 minutes.
• Emergency source stabilization time delay to ignore momentary transients during initial generator set loading - adjustable
0 to 6 seconds.
• Retransfer to normal time delay with two settings:
- Power failure mode - 0 to 60 minutes.
- Test mode - 0 to 10 hours.
• Unloaded running time delay for engine cool down - adjustable 0 to 60 minutes.
• Pre-transfer and post-transfer signal time delay for selective load disconnect with a programmable bypass on source failures -adjustable 0 to 5 minutes. This signal can be used to drive a customer-furnished relay, or for two sets of double throw contacts rated 3 amps at 480 volts AC. Specify ASCO optional accessory 31Z.
• Fully programmable engine exerciser with seven independent routines to exercise the engine generator, with or without loads, on a daily, weekly, bi-weekly or monthly frequency.
• Alarm signals, logic, and time delays for use with closed transition switches.
- In synch time delay - 0 to 3 seconds.
- Failure to synchronize - 1 to 5 minutes.
- Extended parallel - 0.1 to 1.0 seconds.
• Delayed transition load disconnect time delay - adjustable 0 to 5 minutes.
7000 SERIES POWER CONTROL CENTER
Status
Settings
Data Logging
System Status
Voltage and Frequency Settings
ATS Statistics
Time Delay Status
Engine Exerciser
Displays system status in clear, concise language.
Message shown indicates normal source is acceptable and the load is connected to the normal source.
Provides voltage and frequency setting values for normal and emergency sources. Voltage pick-up, dropout and trip settings are set in percentage of nominal voltage and are also displayed in rms voltage values.
Instant availability of statistical information on total number of ATS transfers, number of transfers caused by power failures and total days controller has been energized, plus more.
Active time delay status displays time remaining until next control event.
Seven independent programs, load/no load selection, flexible run times and daily, weekly, bi-weekly and monthly exercise routines.
Displays voltage for each phase, frequency, phase rotation and voltage unbalance for both normal and emergency sources.
Displays detailed information for last 99 events, including time of occurrence, length of event, date and reason for event.
Displays the relative phase angle between sources and frequency differential to indicate the controller is awaiting an inphase condition.
Source Status
Historical Event Log
Inphase Transfer Status
Normal OK
Load on Normal
Normal Voltage
Dropout.........85%.408V
Pickup...........90%.432V
O.V. Trip.....110%.528V
ATS Statistics
ATS Total Xfers: 46
SRC Fail Tot Xfers: 20
Days Energized: 36.5
Normal OK
TD.Engine.Cooldown:
4min15s
P1...............Engine.Exerciser
Enable:....Yes....WLoad:....Yes
Start: 19h30min. ALL MON
Run.Time:..............21h15min
Normal Source
Vab=480V.......................ABC
Vbc=480V.............Vunbal=1%
Vca=480V..................60.0Hz
Provides direct reading display for setting time delays.
Time Delay Settings
TD N>E Xfer Signal
Bypass if N Fail: No
Pre Xfer: 0 min 20s
Post Xfer: 0 min 20s
16.AUG02/95........13H10:17
ENG.START..........NORMFAIL.
15.AUG02/95........13H10:25
XFER.N>E
Emerg OK
Waiting for In-Sync
-45° 0.02Hz
Standard features can be activated with the keypad.
As an example, when enabled, the “shed load” option causes the transfer switch to transfer the load off of the specified source. If desired, the load shed transfer can be made inphase.
Feature Settings
Shed Load
Direction: From E
Inphase: No TD/0.25
7000 SERIES USER CONTROLS AND INDICATORS
Control Switches and Indicating Lights
• Switch position indicating lights (16 mm, industrial grade LEDs).
• Source acceptability indicating lights with true indication of the acceptability of each source, as determined by the voltage, frequency, voltage unbalance, and phase sequence settings of the control panel (16mm, industrial grade LEDs).
• Three position (16mm, industrial grade type) selector switch:
• Automatic: Normal maintained position.
• Test: Momentary position to simulate normal source failure for system test function.
• Reset Delay Bypass: Momentary position to bypass transfer and re-transfer time delay.
Control Switches and Indicating Lights for Closed Transition Switches
• Extended Parallel Time - Provides visual indication when the pre-set extended parallel time has been exceeded. The controls automatically open the emergency or normal main contacts. Separate contact also available to shunt trip external breaker.
• Failure To Synchronize - Visually displays a failure to synchronize alarm if the time delay settings are exceeded during closed transition transfer operation.
• TS Locked Out - Prevents transfer in either direction if the extended parallel time is exceeded.
• Alarm Reset - Resets extended parallel and failure to synchronize alarms.
• Closed Transition Bypass - Pushbutton allows transfer between sources in an open transition mode.
Fig. 16: 7000 SERIES User Controls and Indicators.
Fig. 17: 7000 SERIES User Controls and Indicators.
7000 SERIES OPTIONAL ACCESSORIES
Time Delays and Extended Control Power
Manual Controls for Automatic Transfer Switches
2C Provides an extended time delay on engine starting. The standard feature one-time delay is adjustable from 0 to 6 seconds. Accessory 2C allows this time delay to be adjustable from 0 to 60 minutes in one-second intervals; factory set at 5 minutes.
1G1 Similar to accessory 2C except using 24 volt DC external input signal. Controls, metering and communication remain remains active when both power sources are de-energized.
1GB1 Same as accessory 1G1 except using 120 volt AC external input.
1PS1 Extended control power ride-through (approx. 25 seconds) for Group 5 ATS controller and select communications and metering accessories, e.g. Acc. 72EE2, 72FC, 135L, etc.
6C Reset switch for manual retransfer to normal with automatic retransfer in the event of emergency source failure.
6D Selector switch for automatic/manual retransfer to normal. Automatic bypass if emergency fails.
NOT APPLICABLE
Extension Harness 37B Six foot (6’) extension harness to increase distance between transfer switch and control panel on open-type units.
Indicators 14A/ 14B
Additional auxiliary contact sets to indicate switch position. Two sets are standard. Specify total number of sets if more are required.
18B Two-pole, double-throw contacts operate when emergency source voltage is present at transfer switch terminals.
18G Two-pole, double-throw contacts operate when normal source voltage is present at transfer switch terminals.
99 “Push-to-Test” feature on all pilot light indicators.
Customer Control Circuits 30A Load-shedding circuit initiated by opening of a customer-supplied contact.
30B* Load-shedding circuit initiated by removal of customer-supplied control voltage. *(Specify voltage).
31Z Selective load disconnect control contacts (two provided) that operate with time delay prior to and/or after load transfer and retransfer.
43R Terminal block for all customer control connections on 30 to 150 amp models only (standard on all other sizes).
Note: For ordering information, see the ASCO 7000 Series Power Transfer Switch Dimensional Data and Shipping Weights (ASCO Publication No. 3040 DW)
Communications 107G Provides Building Monitoring Systems with transfer switch, bypass and load power metering information in
Modbus TCP/IP, BACnet IP and SNMP Protocols. Compatible with any Accessory 150 Technology Package or 72EE2.
72EE2 Offers remote Ethernet monitoring via open Mod bus and SNMP protocols, email notifications and embedded monitoring web pages. (Catalog No. 5170 for stand alone product).
Neutral Conductor Options
• Solid neutral, with fully-rated terminals. (AL-CU) UL Listed.
• Conventional neutral switching pole.
• Overlapping neutral transfer contacts. Allows for proper ground-fault sensing and avoids generator voltage transients during transfer.
Special Applications 45 Custom Alphanumeric nameplate mounted on the front of the switch
111A Generator - to - Generator for Standby Applications
111B Generator - to - Generator for Prime Power Applications
125A Seismic Certification to the requirements of the International Building Code for electrical equipment
131 Certification of compliance with the American Recovery & Reinvestment Act (Buy American Provision) - Must be specified at time of order placement
Bypass-Isolation switch Options 14A1 Auxiliary contact to close in “Bypass to Normal” position.
14B1 Auxiliary contact to close in “Bypass to Emergency” position.
14T Auxiliary contact to close when transfer switch is in “Automatic” position.
14U Auxiliary contact to close when transfer switch is in “Isolate” position.
14V Auxiliary contact to close when transfer switch is in “Test” position.
82C Automatic shutters for bus isolation when transfer switch is withdrawn. (See page 6 for details)
82E LED Bypass status indicator, optional on G frame 1600 to 4000 amps only. Standard for all other size switches.
Surge Protection ASCO 510 TVSS, rated 65KA
73AC1 Normal source protection. (3Ø, 4wire WYE)
73AC2 Emergency source protection. (3Ø, 4wire WYE)
73AC3 Load side protection. (3Ø, 4wire WYE) Note: Other distribution voltages and kA ratings available (Contact ASCO).
Name: ATS-LS1 Location: Basement
QUAD-ETHERNET MODULE ACCESSORIES
Quad-Ethernet Module Accessory 72EE2
To: John
Transferred from Emergency to Normal
Date Time: 12/23/16 09:51:55
12/23/15 9:51 PM
ASCO ATS Alert
9:52<
Monitoring
• Engine-generator, utility, and transfer switch status
• Email Notification
• Alarms and Alerts
• Statistics and Activity
• Event Log (downloadable)
• Controller Setpoints
• Power Monitoring*
• Energy Consumption*
• Historical KW Demand*
*Accessory 150A or 150B
Control
• Engine Start/Stop
• ATS Transfer/Retransfer
• Generator Test
• Bypass Timer Delays
Communicate
• Modbus
• SNMP
• SMTP Advanced Encryption
Standard
• Four Port Ethernet Switch
• RS485 Port
Ordering
Catalog Number 5170
Catalog Name Quad-Ethernet Module
Transfer Switch Accessory 72EE2
ATS Tech Package 150A for Non-Bypass
ATB Tech Package 150B for Bypass
Part Number for Kit K1106217-001
Ports
Ethernet
Number of Ports 4
Type of Ports RJ45, 10/100 BaseTX
Protocol Modbus, SMTP, SNMP
RS485
Number of Ports 1
Type of Connection 2-Wire or 4-Wire
Protocol Modbus
Ordering and Specifications Information
The Quad-Ethernet Module is the easiest way to connect, monitor and control your power transfer switch, utility power and engine-generator. Through the web app, you can monitor power conditions, start your engine-generator, and transfer between power sources.
ENERGY AND POWER METERS
5400 SERIES Power Quality Meter5210 Power Meter
Transfer Switch Bypass
Transfer Switch Transfer Switch
Bypass Transfer Switch
Transfer Switch Bypass
Transfer Switch Transfer Switch
Bypass Transfer Switch
Technology Packages 150A 150B 150A1 150B1 150A2 150B2 150A3 150B3
Meter Accessories 135L 135SB 140L 140B 140LS 140SB 140LX 140XB
Meter Catalog Number 5210 5410 5450 5490
Energy and Power Measurements
Power factor (total), Apparent power (total), Active and reactive power (total), Active and reactive power (per phase, rms), Apparent power (per phase, rms), Power factor (per phase, rms), Voltage, Current, Frequency
Power Quality Analysis Total harmonics distortion
Continuous waveform recording, harmonics, inter-harmonics, voltage sag and swell detection, unbalanced components (zero, negative, positive), flicker, fast flickering, crest factor, K-factor
Power Quality Analytics Software
No Yes (Acc. 107G) Yes (Acc. 107G) Yes (Acc. 107G)
Web-page interface Yes Yes Yes Yes
Communications Protocol Modbus TCP/IP, SNMP Modbus TCP/IP Modbus TCP/IP Modbus TCP/IP
BACnet IP Protocol Yes (Acc. 107G) Yes (Acc. 107G) Yes (Acc. 107G) Yes (Acc. 107G)
Sampling Rate (samples per cycle) 32 256 512 1024
Voltage Harmonics 15th 127th 255th 511th
Internal Memory 128KB 128MB 4GB 16GB
Transient Detection at 60/50Hz
No 65.1 / 78.1us 32.5 / 39 us 16.3 / 19.5 us
NTP Time Synchronization Yes (Acc. 107G) Yes Yes Yes
Digital Inputs / Outputs - - 8 / 4 16 / 8
Analog Inputs / Outputs - - 4 / 4 8 / 8
Form-C Relay Contacts - - 3 6
N/A
N/A www.ascopower.com www.ascoapu.com
ASCO. Innovative Solutions.
ASCO Power Technologies - Global Headquarters 160 Park Avenue
Florham Park, NJ 07932 Tel: 800 800 ASCO customercare@ascopower.com
The ASCO and ASCO Power Technologies marks are owned by Emerson Electric Co. or its affiliates and utilized herein under license. ©2017 ASCO Power Technologies. All Rights Reserved.
Publication 3040 R16 © February, 2017 Printed in the U.S.A.
Publication 3227 3-16-17
Limited Guardian Warranty
7000 Series Power Transfer Switches
This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser's business.
General:
ASCO Power Technologies, LP products and systems are in our opinion the finest available. We take pride in our products and are pleased that you have chosen them. Under certain circumstances we offer with our products the following Limited Guardian Warranty Against Defects in Material and Workmanship.
Please read your Guardian Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain performance under this Warranty.
LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP
Product Description Catalog Code Automatic Transfer Switch 7ATS, 7ADTS, 7ACTS
Automatic Transfer Bypass - Isolation Switch 7ATB, 7ADTB, 7ACTB Non Automatic Transfer Switch ( Electrically Operated) 7NTS
Manual Transfer Switch 7MTS
Service Entrance Transfer Switch (SEATS)
7AUS, 7ADUS, 7ACUS,
7AUB, 7ADUB, 7ACUB,
7APS, 7ARS, 7ASUD,
7ASUS, 7ASUB
Power Transfer Load Center (PTLC) 7000L Automatic Soft Load Transfer Switch
& Bypass-Isolation Switch
7ASLS, 7ASLD, 7ASLE
7ASLB
Terms of Warranty:
The following Limited Warranty is conditioned upon User’s compliance with the following:
1. The ASCO 7000 Power Transfer Switch is installed in accordance with ASCO specifications and state and local codes and standards by an electrician licensed in the state of installation.
2. The ASCO 7000 Power Transfer Switch is maintained in accordance with ASCO instructions and used under normal conditions for the purposes intended by ASCO.
As provided herein, the ASCO product is warranted to be free of defects in material and workmanship for a period of two, five, and ten years from date of shipment from ASCO provided that the product has been stored in a suitable environment prior to installation; except, however, for 7AUS, 7AUB, 7APS, 7ARS, 7ASLD, 7ASLE, 7ASUD, 7ASUS, 7ASUB and 7000L products, the warranty period for the circuit breaker shall be two (2) years from date of shipment from ASCO. The product shipment date will be determined only from the ASCO bill of lading. If any part or portion of the ASCO product fails to conform to the Warranty within the Warranty period, ASCO, at its option, will furnish new or factory remanufactured products for repair or replacement of that portion or part.
YEARS 1 – 2: Covers all replacement parts, labor, and travel expenses necessary to remedy the defects in material and/or workmanship. All warranty repair or replacement of said equipment will be performed at ASCO’s option at ASCO's service facility location, factory, or User’s installation site by ASCO’s certified service personnel as deemed most practical by ASCO.
YEARS 3 – 5: Following expiration of the initial two year warranty period as detailed herein, parts only determined to be defective will be provided at no charge. Customer is responsible for all other related costs (labor and travel expenses). This does not apply to circuit breakers in 7AUS, 7AUB, 7APS, 7ARS, 7ASLD, 7ASLE, 7ASUD, 7ASUS, 7ASUB and 7000L products.
YEARS 6 – 10: Following expiration of year five warranty period as detailed herein, Main Contacts only determined to be defective will be provided at no charge. Customer is responsible for all other related costs (labor and travel expenses).
Optional Available Extended Warranty:
Optional extended warranty coverage may be purchased from ASCO for a specified fee at the time of the original sale. If purchased, it shall extend the coverage conditions noted for years 1-2 above up to an additional three (3) years, to provide up to five (5) years of coverage applicable to the above referenced products. Extended warranty coverage must be purchased in one (1) year increments.
Not Provided
Publication 3227 3-16-17
The length of the optional extended coverage shall be reflected on the ASCO invoice and/or order acknowledgement document. The extended warranty coverage does not affect the standard warranty described above for years 3-10 or the 2 year circuit breaker warranty; those warranty periods will remain the same.
All warranty related repairs, replacements or adjustments must be made by ASCO Services Inc. or its duly authorized representative.
Warranty Extends to First Purchaser for Use, Non-transferable:
This Warranty is extended to the first person, firm, association or corporation for whom the ASCO product specified herein is originally installed for use (the "User") in the fifty United States or Canada. This Warranty is not transferable or assignable without the prior written permission of ASCO.
Assignment of Warranties:
ASCO assigns to User any warranties which are made by manufacturers and suppliers of components of, or accessories to, the ASCO product and which are assignable, but ASCO makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this Warranty to such components or accessories.
Drawings, Descriptions:
ASCO warrants for the period and on the terms of the Warranty set forth herein that the ASCO product will conform to the descriptions contained in the certified drawings, if any, applicable thereto, to ASCO's final invoices, and to applicable ASCO product brochures and manuals current as of the date of product shipment (“Descriptions”). ASCO does not control the use of any ASCO product. Accordingly, it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A
PARTICULAR PURPOSE.
Warranty Claims Procedure:
Within a reasonable time, but in no case to exceed thirty (30) days, after User's discovery of a defect, User shall contact ascopowerwarranty@ascopower.com . Subject to the limitations specified herein, (i) during the first two years of the warranty, an ASCO service representative will repair the non-conforming ASCO product warranted hereunder without charge for parts, labor, or travel expenses; (ii) during the remainder of the warranty, ASCO will arrange for an ASCO service representative to repair or replace the non-conforming ASCO product warranted hereunder without charge for covered parts, and User shall bear all labor, travel expenses, and shipping charges associated with repair or replacement of the product herein. Warranty coverage will apply only after ASCO’s inspection discloses the claimed defect and shows no signs of treatment or use that would void the coverage of this Warranty. All defective products and component parts replaced under this warranty become the property of ASCO.
Warranty Performance of Component Manufacturers:
It is ASCO's practice, consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible, to cooperate with and utilize the services of component manufacturers and their authorized representatives in the performance of work to correct defects in the product components. Accordingly, ASCO may utilize third parties in the performance of Warranty work, including repair or replacement hereunder, where, in ASCO's opinion, such work can be performed in less time, with less expense, or in closer proximity to the ASCO product.
Items Not Covered By Warranty:
THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or connection, negligence, inappropriate on site operating conditions, repair by non-ASCO designated personnel, accident in transit, tampering, alterations, a change in location or operating use, exposure to the elements, water, or other corrosive liquids or gases, Acts of God, theft or installation contrary to ASCO's recommendations or specifications, or in any event if the ASCO serial number has been altered, defaced, or removed.
THIS WARRANTY DOES NOT COVER shipping costs, installation costs, external circuit breaker resetting or maintenance or service items and further, except as may be provided herein, does NOT include labor costs or transportation charges arising from the replacement of the ASCO product or any part thereof or charges to remove or reinstall same at any premises of User.
REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY
PERIOD.
THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT FOR USE IN THE CONTROL AREA OR ANY REACTOR CONNECTED OR SAFETY APPLICATIONS OR WITHIN THE CONTAINMENT AREA OF A NUCLEAR FACILITY OR FOR INTEGRATION INTO
MEDICAL DEVICES.
Limitations:
THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
USER'S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE ASCO PRODUCT AS SET FORTH HEREIN.
IF USER'S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT JURISDICTION, ASCO'S RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED THE NET PRODUCT PURCHASE PRICE.
Not Provided
Publication 3227 3-16-17
IN NO EVENT SHALL ASCO ASSUME ANY LIABILITY FOR INDIRECT, SPECIAL, INCIDENTAL, CONSEQUENTIAL OR EXEMPLARY DAMAGES OF ANY KIND WHATSOEVER, INCLUDING WITHOUT LIMITATION LOST PROFITS, BUSINESS INTERRUPTION OR LOSS OF DATA, WHETHER ANY CLAIM IS BASED UPON THEORIES OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT, OR OTHERWISE.
Miscellaneous:
NO SALESPERSON, EMPLOYEE OR AGENT OF ASCO IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. Warranty terms may be modified, if at all, only in writing signed by an ASCO officer.
ASCO obligations under this Warranty are conditioned upon ASCO timely receipt of full payment of the product purchase price and any other amounts due. ASCO reserves the right to supplement or change the terms of this Warranty in any subsequent warranty offering to User or others.
In the event that any provision of this Warranty should be or becomes invalid and/or unenforceable during the warranty period, the remaining terms and provisions shall continue in full force and effect.
This Warranty shall be governed by, and construed under, the laws of the State of New Jersey, without reference to the conflict of laws principles thereof.
This Warranty represents the entire agreement between ASCO and User with respect to the subject matter herein and supersedes all prior or contemporaneous oral or written communications, representations, understandings or agreements relating to this subject.