N4008519B0094 DWG_Part5.pdf
PDF 8 MB Posted
- Attached to
- Construct EOTG PEB
- Solicitation number
- N4008520R4057
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A B C D E
WP
MDP-19
DOOR
2HP, 208V, 3Ø
30A-3P, FU@20A
MDP-13
DOOR
2HP, 208V, 3Ø
30A-3P, FU@20A
WP
WP
WP
E
M
WP
E
M
E
M
E
M
E
M
E
E
M
M
SHWP-1
3/4HP, 208V, 3PH
SHWP-2
3/4HP, 208V, 3PH
B-2
120V, 1PH
B-1
120V, 1PH
VAV-5
120V, 1PH
VAV-4
120V, 1PH
VAV-3
120V, 1PH
VAV-1
120V, 1PH
VAV-2
120V, 1PH
E
M
VAV-6
120V, 1PH
E
M
VAV-7
120V, 1PH
E
M
VAV-9
120V, 1PH
E
M
VAV-8
120V, 1PH
E
M
VAV-10
120V, 1PH
MDP-16
MDP-18
MDP-14
MDP-12
MDP-4
MDP-2
MDP-6
MDP-10
MDP-8
MDP-20
LA-31
MDP-25
30A-3P, NF
LA-2
LA-4
LA-6
LA-8
LA-10
LA-12
LA-16
LA-14
LA-20
LA-18
LA-17
LA-19
LA-13
LA-15
LA-24
LA-22
E
WP
GFI GFI GFI
GFI GFI
LA-41
LA-39
LA-35
LA-37
LA-33
VFD
AC-1
154MCA, 208V, 3PH
200A-3P, FU @200, 4X
MDP-38;
4 #2/0, 1 #6 GND - 2"C.
VFD
200A-3P, NF
MDP-32; 3 #10,
1 #10 GND - 3/4"C.
AHU-1
8HP, 208V, 3PH
E
E
M
M
LA-25
DAMPER
120V, 1PH
M
M
LA-23
RECIR PUMP
120V, 1PH
MDP LA
FAMN FAT
LA-26
WP
MDP-1
MDP-3
MDP-5
DDC
LA-27
DSS-2B
DSS-1B
DSS-1A
D S
S A
E
E
LA-40
LA-36
30A-2P, FU @ 15, 4X
30A-2P, FU
@ 15, 4X
E
E
LA-29
30A-3P, NF
VFD
MDP-31
E
M
LA-32
LA-34
EF-1
120V, 1PH
UH-1
120V, 1PH
VAV-8
VAV-7
VAV-6
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
TN
PN
FLOOR PLAN
SCALE: 3/16" = 1'-0"
3/16" = 1'-0"
0' 5' 10' 20'
POWER AND CONTROL CABLING TO INDOOR UNIT, COORDINATE
REQUIREMENTS WITH EQUIPMENT PROVIDED.
POWER AND CONTROL CABLING TO OUTDOOR UNIT, COORDINATE
REQUIREMENTS WITH EQUIPMENT PROVIDED.
01/24/2020
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
LED ENCLOSED AND GASKETED
LUMINAIRE REQUIREMENTS:
1. HOUSING - FIBERGLASS OR FIBERGLASS-REINFORCED POLYESTER OUTER HOUSING, WITH
ALUMINUM COMPONENT TRAY AND HEAT SINK. OPTIONAL LENGTHS OF 4FT OR 8FT.
2. LENS - IMPACT-RESISTANT ACRYLIC OR OPTIONAL POLYCARBONATE, WITH CONTINUOUS
CLOSED-CELL POLYURETHANE GASKET, SECURED WITH STAINLESS STEEL OR
POLYCARBONATE LATCHES.
3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500K CCT
UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FOR COLOR
CONSISTENCY, AND MINIMUM EFFICACY OF 100 LUMENS/WATT. INITIAL LUMEN OUTPUT AS
INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC
DISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
5. CERTIFICATION - UL 1598, WET LOCATION (IP65, IP66, IP67), DLC QUALIFIED, AND ROHS
COMPLIANT. COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN
EQUIPPED WITH EMERGENCY BATTERY BACK-UP.
6. MOUNTING - SURFACE-MOUNTED OR SUSPENDED FROM CEILING.
7. OPTIONS - POWER CORD, INTEGRAL MOTION SENSOR, EMERGENCY BACK-UP.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY
MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN
MANUFACTURER OR PREFERENCE.
REVISED:
APRIL 2016 LIGHTING PLATE:
NL-11
LUMENS INPUT WATTS VOLTAGE MOUNTINGTYPE LAMP TYPE
D
LUMINAIRE REQUIREMENTS:
16"
9"
1. FIXTURE SHALL BE DIE CAST ALUMINUM HOUSING.
2. FINISH SHALL BE SELECTED BY ARCHITECT.
3. FIXTURE SHALL HAVE TYPE IV DISTRIBUTION.
4. FIXTURE SHALL BE UL LISTED FOR WET LOCATIONS.
LUMENS INPUT WATTS VOLTAGE MOUNTINGTYPE
SURFACE, WALL, 18'-0" AFG120343958
LAMP TYPE
3500K LED
E
A B
SURFACE WALL, MOUNT 12" ABOVE DOORMVLOT213500K LED2250
REVISED: AUGUST 2004
NL-67
LIGHTING PLATE:
DECORATIVE EMERGENCY LIGHTING UNIT
MR16 HALOGEN LAMPS SHALL BE 5 WATTS, HIGH-OUTPUT OR AS INDICATED IN
HOUSING - UV STABLE, FLAME-RATED, HIGH-IMPACT THERMOPLASTIC IN WHITE OR
BLACK TEXTURED FINISH.
INTERNAL COMPONENTS - FULLY AUTOMATIC, SOLID STATE, CONSTANT VOLTAGE,
CURRENT-LIMITED BATTERY CHARGER; MAINTENANCE-FREE LEAD-ACID BATTERY;
EXTERIOR HOUSING INDICATORS - LED AC-ON INDICATOR AND INTEGRAL TEST SWITCH.
LAMP HEADS - UV STABLE, FLAME RATED POLYCARBONATE THERMOPLASTIC.
MOUNTING - DIRECTLY TO 4" OCTAGONAL OR SQUARE OUTLET BOX.
CERTIFICATION - UL LISTED AND LABELED. COMPLIES WITH UL 924 AND NFPA 101
OPTIONS - VOLTMETER, VANDAL-RESISTANT SHIELD, SELF-DIAGNOSTIC/TESTING7.
6.
REQUIREMENTS. LISTED FOR DAMP LOCATIONS.
LUMINAIRE REQUIREMENTS:
1.
3.
5.
4.
2.
AND BUILT-IN OVERLOAD AND LOW-VOLTAGE BATTERY PROTECTION.
13"
NOMINAL
NOMINAL
5"
MAX. DEPTH
4" NOMINAL
ELECTRONICS AND WIRE GUARD.
LIGHTING FIXTURE SCHEDULE.
HOUSING - DIE-CAST ALUMINUM OR HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED
LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. RED OR GREEN LETTERS
FINISH (ON CAST ALUMINUM HOUSING ONLY) - TEXTURED POWDER COAT FINISH
OPTIONS INCLUDE WHITE, WHITE WITH BRUSHED ALUMINUM FACE, BLACK, OR BLACK
EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER WITH
MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE
ILLUMINATION - PROVIDED BY RED, GREEN OR WHITE HIGH-OUTPUT LEDS INSIDE
1.
2.
3.
4.
5.
6.
LUMINAIRE REQUIREMENTS:
REVISED: AUGUST 2004
NL-63
MOUNTING.
THERMOPLASTIC. SINGLE OR DOUBLE-FACED AS INDICATED.
AS INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH
MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND
LIGHTING PLATE:
LED EXIT SIGN
13"
NOMINAL
NOMINAL
9"
WITH BRUSHED ALUMINUM FACE.
DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS REQUIRED.
TEST SWITCH.
OF FIXTURE HOUSING. PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH
FREQUENCY-MATCHED SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.
CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.7.
LED INDUSTRIAL STRIP
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR RIGIDITY AND
SPECULAR ALUMINUM OR HIGHLY-REFLECTIVE PAINTED STEEL REFLECTORS. OPTIONAL
LENGTHS OF 4FT OR 8FT.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH HIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.
3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500K CCT
UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FOR COLOR
CONSISTENCY, AND MINIMUM EFFICACY OF 100 LUMENS/WATT. INITIAL LUMEN OUTPUT AS
INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC
DISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT. COMPLIES
WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED WITH EMERGENCY
BATTERY BACK-UP.
6. MOUNTING - SURFACE ON CEILING OR SUSPENDED.
7. OPTIONS - WIRE GUARD, CHAIN, STEM OR SWIVEL STEM HANGERS.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY
MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN
MANUFACTURER OR PREFERENCE.
REVISED:
APRIL 2016 LIGHTING PLATE:
16"
9"
LUMINAIRE REQUIREMENTS:
1. FIXTURE SHALL BE DIE CAST ALUMINUM HOUSING.
2. FINISH SHALL BE SELECTED BY ARCHITECT.
3. FIXTURE SHALL HAVE TYPE IV DISTRIBUTION.
4. FIXTURE SHALL BE UL LISTED FOR WET LOCATIONS.
NL-7
REMOTE EMERGENCY LIGHTING UNITS
LAMPS AND FINISHES SHALL BE COMPATIBLE
WITH PRIMARY UNIT WITH WHICH USED.
FOR USE WITH BATTERY UNIT
1.
NOTES:
TYPE - C
REMOTE FIXTURES
TYPE - E
TYPE - D
TYPE - A TYPE - B
SKETCH DATE JUNE 2002 STYLE
NL-54
01/24/2020
PRISMATIC LENS LED TROFFER
REVISED: APRIL 2016
NL-3
LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD ROLLED STEEL, PAINTED AFTER FABRICATION.
EXTRUDED ALUMINUM DOOR WITH SPRING-LOADED CAM LATCHES. HIGH
REFLECTANCE, WHITE POLYESTER POWDER-COATED FINISH. OPTIONAL SIZES
OF 1FT x 4FT, 2FT x 2FT, AND 2FT x 4FT AVAILABLE.
2. LIGHT SOURCE - LED BOARD OR ARRAY WITH MINIMUM 50K HOURS RATED LIFE
AT L70, 3500K COLOR TEMPERATURE UON, MAXIMUM 4-STEP MCADAM ELLIPSE
BINNING TOLERANCE FOR COLOR CONSISTENCY, MINIMUM EFFICACY OF 90
LUMENS/WATT, WITH A MINIMUM CRI OF 80. INITIAL LUMEN OUTPUT AS
INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9
PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL
HARMONIC DISTORTION. STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED IN
LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS
COMPLIANT. COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL
924 WHEN EQUIPPED WITH EMERGENCY BATTERY BACK-UP. IC RATED WHEN
INDICATED.
6. MOUNTING - RECESSED IN SUSPENDED ACOUSTICAL TILE OR HARD CEILING.
7. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A
LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT
INTENDED TO INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
C
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
NO SCALE
SE RATED
PANEL
600A MCB
208/120V
3Ø, 4W
NEMA 1
22 KAIC
PANEL
150A, MLO
208/120V
3Ø, 4W
NEMA 1
22 KAIC
4 #1/0, 1 #6 GND 2"C
TWO 4"C WITH 4-350 KCMIL, IN EACH
CONDUIT TO SERVICE
TRANSFORMER AND ONE 4" C
SPARE, CONCRETE ENCASED.
SERVICE GROUND:
1 #1 - 1/2"C TO GROUND ROD
1 #1 - 1/2"C TO WATER SERVICE
1 #1 - 1/2"C TO BUILDING STEEL
1 #1 - 1/2"C TO REBAR IN SLAB
1 #1/0 - 3/4"C TO LIGHTNING PROTECTION
SPD
4 #6, 1 #10 GND 1"C
LIGHTING 3.3 KVA 100% 3.3 KVA
EXTERIOR LIGHTING 0.4 KVA 100% 0.4 KVA
RECEPTACLES 17.3 KVA NOTE - 113.6 KVA
AIR CONDITIONING 74.7 KVA 100% 74.7 KVA
HEATING 9.7 KVA 100% 9.7 KVA
MISCELLANEOUS 7.5 KVA 100% 7.5 KVA
1. 1st 10 KVA @ 100%, REMAINDER @ 50%
FIRE ALARM PANEL 3.0 20/1P 1 2 20/1P 5.8 VAV-1
FIRE ALARM TRANS 3.0 20/1P 3 4 20/1P 5.8 VAV-2
TELEPHONE SERVICE 3.0 20/1P 5 6 20/1P 5.8 VAV-3
SPARE 20/1P 7 8 20/1P 5.8 VAV-4
SPARE 20/1P 9 10 20/1P 5.8 VAV-5
SPARE 20/1P 11 12 20/1P 5.8 VAV-6
OVERHEAD DOOR 7.5 20/3P 13 14 20/1P 5.8 VAV-7
7.5 16 20/1P 5.8 VAV-8
7.5 18 20/1P 5.8 VAV-9
OVERHEAD DOOR 7.5 20/3P 19 20 20/1P 5.8 VAV-10
7.5 22 20/1P SPARE
7.5 24 20/1P SPARE
SHWP-1 3.5 15/3P 25 26 150/3P 97.3 PANEL LA
3.5 78.5
3.5 98.9
SHWP-2 3.5 15/3P 31 32 25/3P 18.0 AHU-1
3.5 19.0
3.5 19.0
SPD 60/3P 37 38 175/3P 148.0 CHILLER
148.0
184.0
25.0 25.0 25.0 286.5 262.9 319.3
EXTERIOR LTG 3.5 20/1P 1 2 20/1P 4.5 RECEPT - 102
LIGHITNG 101,108-110
5.3 20/1P 3 4 20/1P 6.0 RECEPT - 102
LIGHITNG 102 12.5 20/1P 5 6 20/1P 7.5 RECEPT - 102
LIGHTING 103-107 10.1 20/1P 7 8 20/1P 9.0 RECEPT - 102
SPARE 20/1P 9 10 20/1P 4.5 RECEPT - 102
SPARE 20/1P 11 12 20/1P 4.5 RECEPT - 102
RECEPT - 106 9.0 20/1P 13 14 20/1P 7.5 RECEPT - 101
RECEPT - 105 9.0 20/1P 15 16 20/1P 7.5 RECEPT - 101
RECEPT - 103 9.0 20/1P 17 18 20/1P 6.0 RECEPT - 101
RECEPT - 104 10.5 20/1P 19 20 20/1P 7.5 RECEPT - 101
REECPT - 108-110 6.0 20/1P 21 22 20/1P 9.0 RECEPT - 107
BOILER RECIR PUMP 12.5 20/1P 23 24 20/1P 9.0 RECEPT - 107
MOTORIZED DAMPER 5.0 20/1P 25 26 20/1P 7.5
RECEPT - 108,109,110,EXT.
DDC 1.5 20/1P 27 28 20/1P SPARE
B-1 3.5 20/1P 29 30 20/1P SPARE
B-2 3.5 20/1P 31 32 20/1P 2.5 UH-1
HEAT TRACE 10.0 20/1P 33 34 20/1P 2.5 EF-1
HEAT TRACE 10.0 20/1P 35 36 15/2P 7.2 DSS-1
HEAT TRACE 10.0 20/1P 37 7.2
HEAT TRACE 10.0 20/1P 39 40 15/2P 7.2 DSS-2
HEAT TRACE 10.0 20/1P 41 7.2
51.6 41.8 57.5 45.7 36.7 41.4
METALLIC GATE VERTICAL
FRAME
METALLIC FENCE MESH
HINGE
METALLIC FENCE MESH
ZINC COATED BOLT, TYPICAL
1"W X 1/8" THICK COPPER.
BRAID BONDING STRAP
METALLIC
FENCE MESH
#4/0 BARE COPPER GROUNDING
CONDUCTOR
EXOTHERMIC WELDED CONNECTION
GROUND ROD
FINISHED GRADE
CRIMP ON CONNECTOR
BOLT TO FENCE POST
FENCE POST (METALLIC)
±12"
±12"
NO SCALE
SEE FENCE POST
GROUNDING DETAIL THIS
SHEET.
NOTE:
PANELS MUST BE SURFACE MOUNTED.
PANEL ENCLOSURES MUST BE NEMA 1.
INV INV
TO LA-3 EMERGENCY
LIGHTS
TO LA-5 EMERGENCY
LIGHTS
INVERTER: 2000 W,
120V
INVERTER: 1500 W
120V
SHORT CIRCUIT AND VOLTAGE DROP CALCULATIONS
Name: *
Type: 120/208, 3p, 225kVA
Source N/A Impedance (%Z) 2
Voltage
208 KVA 225
Phase 3
Full Load Amps
Voltage Fluctuation:
1.05
Multiplier
50.00
Name: * Conductor Size: 350KCMIL
Source: Service Transformer "X" Material:
Copper
Voltage
Conduit Type: Non-Magnetic
Phase 3 5
Voltage Rating: Up To 5KV
Available Fault Current 32827 Constant 18868
Multiplier
0.525 Conductors/Phase: 2
Length (ft): 125
Load (Amps): 347 2.0
Name: * Conductor Size: #1/0
Source: Panel MDP Material:
Copper
Voltage
Conduit Type: Non-Magnetic
Phase 3 5
Voltage Rating: Up To 5KV
Available Fault Current 17237 Constant 7692
Multiplier
0.782 Conductors/Phase: 1
Length (ft): 15
Load (Amps): 100 0.3
MC MC MC MC MC MC MC
MC MC MC MC MC MC MC
MC MC MC MC MC MC MC
MC
MC
MC
MC
MC
MC
MC
MC
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
TN
PN
ROOF PLAN
SCALE: 3/16" = 1'-0"
3/16" = 1'-0"
0' 5' 10' 20'
NOTES THIS SHEET
PROVIDE GROUND RING AROUND BUILDING
#1/0 MINIMUM, BONDING CONNECTION TO BUILDING SERVICE GROUNDING
ELECTRODE SYSTEM.
COPPER SWIVEL ADAPTER
BRONZE STANDING SEAM POINT BASE
BARE COPPER
CONDUCTOR
CLIP WITH CABLE HOLDER @ 3'-0" 0/C
SOLID COPPER BLUNT
TIP AIR TERMINAL
AIR TERMINAL MOUNTING DETAIL
NOT TO SCALE
GROUND ROD
1" PVC CONDUIT WITH
DOWN CONDUCTOR
CONCEALED IN WALL
TO ROOF TOP LIGHTNING
PROTECTION DEVICES
ROOF
PENITRATION
12" MINIMUM
24"
MIN.
DOWN LEAD DETAIL
NOT TO SCALE
1. THE DESIGN SHOWN ON THE PLANS IS INTENDED TO SHOW BASIC SYSTEM
REQUIREMENTS. THE CONTRACTOR SHALL PROVIDE A COMPLETE LIGHTNING
PROTECTION SYSTEM DESIGN AND INSTALLATION WITH CLASS I MATERIALS.
DESIGN SHALL CONFORM TO UL 96A.
2. INSTALLER SHALL BE CERTIFIED BY A NATIONALLY RECOGNIZED TESTING
LABORATORY OR BY THE LIGHTNING PROTECTION INSTITUTE (LPI) AS A MASTER
DESIGNER/INSTALLER.
3. PROVIDE STAND-OFF MOUNTING CLIPS TO MAINTAIN SEPARATION OF LIGHTNING
PROTECTION CONDUCTORS AND METAL ROOF FLASHING.
4. INSTALLATION OF AIR TERMINALS SHALL NOT COMPROMISE THE WATER
PREVENTION INTEGRITY OF THE PARAPET COPING.
5. CABLES/CONDUCTORS/CONNECTORS/ETC. SHALL BE
ANCHORED/SECURED/SUPPORTED TO ACCOMMODATE THE ROOF WIND LOADS AS
DEFINED IN THE ROOF REPLACEMENT PORTION OF THIS PROJECT.
GENERAL LIGHTNING PROTECTION NOTES
THE LIGHTNING PROTECTION SYSTEM SHALL BE PROVIDED
SEPARATELY FROM THE PRE-ENGINEERED PANELIZED
METAL RELOCATABLE BUILDING
GENERAL NOTE:
B3
B5
LEGEND
NEW WORK NOTE SYMBOL
GROUNDGND
ABBREVIATIONS
CONDUIT C
MAIN CONDUCTOR CABLE, MINIMUM CLASS 1, #1/0 MINIMUM
MC
AIR TERMINAL, ALUMINUM 1/2"Ø SOLID, 12" HIGH MINIMUM.
GROUND ROD, COPPER CLAD, 5/8" DIA X 10'-0", TOP 30" BFG
DIAMETERDIA
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
LEGEND & ABBREVIATIONS
TELECOMMUNICATIONS
TELECOMMUNICATIONS BACKBOARD - 4'X4'X3/4" FIRE RETARDANT, TYPE AC
TELECOMMUNICATIONS MAIN GROUND BUS BARTMGB
COMBINATION TELEPHONE/DATA OUTLET, 5"x5"x2 1/8"D BOX WITH
SINGLE GANG PLASTER RING AND SINGLE GANG COVERPLATE TO
MATCH ELECTRICAL OUTLET COVERPLATE MATERIAL AND COLOR,
46" AFF, UON, WITH 1 1/4"C WITH (4) CAT6 UTP CABLE (GREEN), TO
AND TERMINATED WITH GROUNDING BUSHING.
GENERAL SPECIAL SYSTEMS
THE GENERAL CONTRACTOR SHALL PROVIDE IN-WALL REINFORCEMENT AS NECESSARY.
THE CONTRACTOR SHALL COORDINATE AND PROVIDE ALL REQUIRED RACEWAY SYSTEMS FOR ALL SPECIAL SYSTEMS INCLUDING CONDUIT WITH PULL STRING, JUNCTION BOXES, GROUNDING, BACKBOARDS, ETC. THE CONTRACTOR SHALL COORDINATE ALL ROUGH-IN, BOX SIZES AND CONFIGURATIONS, CONDUIT SIZES AND ROUTING WITH THE OWNERS
VENDOR PRIOR TO INSTALLATION OF THE RACEWAY SYSTEM.
THE CONTRACTOR SHALL PROVIDE ALL CABLING, JACKS, COVER PLATE, DEVICES, AND COMPONENT EQUIPMENT
UNLESS OTHERWISE NOTED.
FINAL DEVICE LOCATIONS AND ELEVATIONS SHALL BE COORDINATED OWNER.
TELEPHONE SYSTEMS
THE TELEPHONE SYSTEM WILL BE THROUGH THE CONTRACTOR. THE CONTRACTOR SHALL PROVIDE A COMPLETE
RACEWAY SYSTEM AS INDICATED.
ALL CONDUITS SHALL BE 1 1/4" MINIMUM, SHALL HAVE A PULL WIRE AND SHALL BE TERMINATED WITH INSULATED GROUNDING BUSHING. ALL TELEPHONE BOXES SHALL BE 5" X 5" X 2 7/8" DEEP WITH A SINGLE GANG RISE AND BLANK COVER PLATE UNLESS OTHERWISE INDICATED. COORDINATE CONDUIT QUANTITIES, SIZES AND LOCATIONS.
THE BUILDING SHALL BE PRE-WIRED BY THE CONTRACTOR DURING CONSTRUCTION PRIOR TO CLOSING THE WALL
CAVITIES.
ALL CONDUITS WITH PULL WIRE FOR COMMUNICATIONS DEVICE SHALL BE PROVIDED WITH INSULATED GROUND BUSHING. WHERE A FULL WALL SEPARATES THE CONDUIT STUB OUT FROM THE DESTINATION ROOM, PROVIDE A 1 1/2" MINIMUM SLEEVE THROUGH THE WALL TO ACCOMMODATE THE CABLING. PROVIDE ALL CONDUITS AND SLEEVES PENETRATING RATED FIRE OR SMOKE WALLS WITH APPROVED FIRE RETARDANT TO PROVIDE A UL RATED ASSEMBLY.
MAINTAIN VENDOR RECOMMENDED SEPARATION BETWEEN WIRING OF DIFFERENT SYSTEMS AND FROM INTERFERENCE PRODUCING ELECTRICAL DEVICES SUCH AS FLUORESCENT LIGHTS, BALLASTS, TRANSFORMERS, RELAYS, MOTOR
CONTROLS, ETC..
GENERAL SPECIAL SYSTEM NOTES
REQ'D REQUIRED
PNL PANEL
NATIONAL ELECTRICAL CODENEC
GROUNDGND
EXIST EXISTING
EXISTING TO REMAINETR
CONDUIT C
UNLESS OTHERWISE NOTEDUON
AREA OF REFUGE ASSISTANCEARA
ABBREVIATIONS
ABOVE FINISHED GRADEAFG
ABOVE FINISHED FLOORAFF
FAMN
BELOW FINISHED GRADEBFG
DUCTBANK TRENCH DETAIL - TYPE A
NO SCALE
" M
IN
IM
U M
6"
REMOVE EXISTING LANDSCAPE AND
PLANT LIFE AND SAVE FOR REUSE AS
APPLICABLE. AFTER BACKFILL AND
COMPACTION IS COMPLETE, PROVIDE
4" OF SCREEN TOP SOIL AND PROVIDE
LANDSCAPE AND PLANT LIFE TO MATCH
EXISTING.
SCREENED TOP SOIL,
4" MINIMUM
FINISH GRADE
12" MINIMUM
#12AWG COPPER SOLID
THW TRACER WIRE
2"C SCH 80 PVC, DIRECT BURIAL
DUCTBANK AS INDICATED
BUILDING ENTRANCE TERMINALBET
TELECOMMUNICATIONS RISER DIAGRAM
NO SCALE
FIRST FLOOR
TMGB
BET
1"C WITH (2) CAT6
UTP CABLES
CAB
PB-X QUAZITE PULL BOX, 24"X24"X36"DP
WALL
MOUNTED
CABINET
NO SCALE
PULLBOX DETAIL
SIDE VIEW
PULL SLOT
STAINLESS STEEL
HEX BOLTS
SKID RESISTANT
SURFACE
MOUSEHOLE, EACH END
NOTES:
4. STANDARD GREEN COLOR
2. CONSTRUCTED OF POLYMER CONCRETE OR REINFORCED FIBERGLASS
3. LOAD DESIGN: 8000 LB LOAD OVER A 10" SQUARE
CONDUIT (SWEEP DEEPER
6" DEEP GRAVEL AND
CRUSHED ROCK BASE
GRADE
1. NOMINAL INSIDE DIMENSIONS: (18"W X 30L") X 24"D (BOX
EXTENSIONS ARE ACCEPTABLE AS NECESSARY TO OBTAIN REQUIRED DEPTH).
" M
IN
IF SPECIFIED)
3"
STUB CONDUITS INTO BOX AND
PROVIDE INSULATED BUSHING
PROVIDE LOGO DEFINING THE SYSTEM THAT THE BOX
IS ACTUALLY SERVING (TELEPHONE, LIGHTING, FIRE
ALARM, ETC.)
PB
CAB WALL MOUNTED CABINET
COMBINATION TELEPHONE / DATA JACK
NO SCALE
1-1/4"C TO CABLE TRAY
(4) 4 PAIR 24 AWG COPPER CAT
6 UTP, GREEN CABLES
(2) DUAL MOLDED 8P8C JACKS
385 A 386
387 A 388
5" X 5" X 2 1/8" BOX
GREEN COMPUTER
ICON
GREEN
TELEPHONE
ICON
TELEPHONE OUTLET, 5"X5"X2 1/8"D BOX WITH SINGLE GANG
PLASTER RING AND SINGLE GANG COVERPLATE TO MATCH
ELECTRICAL OUTLET COVERPLATE MATERIAL AND COLOR, 46"
AFF, UON, WITH 1 1/4"C WITH (1) CAT6 UTP CABLE (GREEN VOICE),
TO AND TERMINATED WITH GROUNDING BUSHING.CAB FIRE ALARM/MASS
NOTIFICATION CONTROL
PANEL
WALL TELEPHONE OUTLET
NO SCALE
1-1/4"C
4" X 4" X 2 7/8" BOX
MOUNTING STUDS
GREEN TELEPHONE
(1) 4 PAIR 24 AWG COPPER
CAT 6 UTP
(1) GREEN CAT 6 UTP RJ45
JACKS
RP-41
(2) 4"C SCH. 80 PVC DIRECT BURIED - ONE WITH
(1) 6 PAIR, OSP RATED TELEPHONE CABLE AND
ONE EMPTY CONDUIT W/ PULL STRING
102 106
FAMN
1 1/4"C WITH (1)
CAT6 UTP CABLE
1 1/4"C WITH (4)
CAT UTP CABLES
NEW PEB
BUILDING
BLDG. 2209
(TO BE DEMOLISHED)
(1) 2"C SCH. 80 PVC DIRECT BURIED WITH (1) 6
PAIR, OSP RATED TELEPHONE CABLE.
PB
TYPICAL GROUND BUS BAR DETAIL
NO SCALE
COPPER BASED BOLTS, NUTS, & LOCK
WASHERS (TYPICAL)
STAND-OFF INSULATOR, 1KV MINIMUM
(2" MINIMUM OFFSET) (TYPICAL)
COPPER MAIN TELECOMMUNICATIONS
GROUND BUS BAR ( )
4" x 12" x 1/4" THICK (TYPICAL)
TMGB
(1) #6 CU GND IN 3/4"C. CONNECT TO
ELECTRICAL PANEL GROUND ELECTRODE
SYSTEM PER NEC ARTICLE 800
TO BUILDING STEEL
TO CABLE TRAY
TO TELECOM CABINET
MOUNTING BRACKET(S)
FACTORY DRILLED HOLES (TYPICAL)
CONTRACTOR SHALL SIZE
TELECOMMUNICATIONS GROUNDING
AND BONDING INFRASTRUCTURE
PER ANSI J-STD-607-D
TBB/TBC SIZE (AWG)TBB/TBC LENGTH M (FT)
LESS THAN 4 (13)
4 - 6 ( 14 - 20 ) 6 - 8 ( 21 - 26 ) 8 - 10 ( 27 - 33 )
10 - 13 ( 34 - 41 ) 13 - 16 ( 42 - 52 ) 16 - 20 ( 53 - 66 ) 20 - 26 ( 67 - 84 ) 26 - 32 ( 85 - 105 ) 32 - 38 ( 106 - 125 ) 38 - 46 ( 126 - 150 ) 46 - 53 ( 151 - 175 ) 53 - 76 ( 176 - 250 ) 76 - 91 ( 251 - 300 )
GREATER THAN 91 ( 301 )
TBB - TELECOMMUNICATIONS BONDING BACKBONE
TBC - TELECOMMUNICATIONS BONDING CONDUCTOR
750kcmil 600kcmil 500kcmil 350kcmil 300kcmil 250kcmil
4/0 3/0 2/0 1/0
DDC PANEL TELEPHONE OUTLET, 5"X5"X2 1/8"D BOX WITH SINGLE
GANG PLASTER RING AND SINGLE GANG COVERPLATE TO MATCH
ELECTRICAL OUTLET COVERPLATE MATERIAL AND COLOR, 46" AFF,
UON, WITH 1 1/4"C WITH (1) CAT6 UTP CABLE (GREEN VOICE), TO
AND TERMINATED WITH GROUNDING BUSHING.
CAB
DDC
DIRECT DIGITAL CONTROLDDC
/ DDC
01/24/2020
TELECOMMUNICATION JUNCTION BOX. SIZE AS REQUIRED.
4" DETECTABLE WARNING
TAPE, ORANGE
COMPACTED BACKFILL, COMPACT TO
95% WITH 12" MAXIMUM LIFTS
TRENCH WIDTH
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
TN
PN
SITE PLAN
TMGB
BET
WOMEN
BILLETING
MEN
BILLETING
RAID
STORAGE
INSTRUCTOR
GEAR LOCKER105
HRST
LOCKER
ACC
LOCKER
ROPE GEAR
MAINT. LOCKER
MECH.
(2) 4"C TO PULLBOX. REFER
TO SHEET T-002 FOR
ADDITIONAL INFORMATION.
TELECOM
ELECT.
RISER
ROOM
DDC
CAB
3"C
1 1/4"C
(TYP)
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
TN
PN
FLOOR PLAN
SCALE: 3/16" = 1'-0"
3/16" = 1'-0" 0' 5' 10' 20' 01/24/2020
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
FIRE PROTECTION SYSTEMS SHALL COMPLY WITH:
-NFPA 13 (2019)
-UNIFIED FACILITIES CRITERIA 3-600-01.(WITH CHANGE 3, 05/10/19)
-NFPA 24 (2019)
FIRE STOP ALL PENETRATIONS OF SMOKE / FIRE WALLS, CEILINGS, FLOORS, ROOFS,
ETC. THE PENETRATION SYSTEM SHALL MATCH OR EXCEED THE FIRE / SMOKE RATING
OF THE WALL OR FLOOR BEING PENETRATED.
SPRINKLERS ARE TO BE COORDINATED WITH ALL ARCHITECTURAL FEATURES,
DIFFUSERS, SPEAKERS, LIGHTING FIXTURES, CEILING SYSTEMS, AND STRUCTURAL
SYSTEMS.
PROVIDE CABINET AND STOCK OF EXTRA SPRINKLER HEADS OF ALL TYPES USED IN
ACCORDANCE WITH NFPA 13.
AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS SHALL BE
ORDINARY, UNLESS NOTED OTHERWISE.
ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S
LABORATORIES, INC. (UL) AND THE FACTORY MUTUAL LABORATORIES. VALVES SHALL
BE FACTORY MARKED "UL" AND "FM", 175 PSI WORKING PRESSURE.
ALL VALVES ON THE FIRE PROTECTION SYSTEM SHALL BE ELECTRICALLY SUPERVISED.
PROVIDE TAMPER SWITCHES. REFER TO FIRE ALARM DRAWINGS FOR MORE
INFORMATION.
PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY. THE ENTIRE PIPING
SYSTEM SHALL BE FLUSHED CLEAN. THE UNDERGROUND PIPING SHALL BE FLUSHED
BEFORE CONNECTION TO ANY ABOVE GROUND PIPING TO REMOVE ANY DEBRIS.
PROVIDE HEAD GUARDS ON SPRINKLER HEADS IN ELECTRICAL, MECHANICAL,
ELEVATOR, TELEPHONE, STORAGE ROOMS, AND GYM AREA.
PROVIDE SMOOTH BORE CORROSION RESISTANT OUTLETS FOR INSPECTOR'S TEST
VALVES GIVING FLOW EQUIVALENT TO 1 SPRINKLER.
FIRE SPRINKLER PIPING SHALL NOT BE LOCATED ABOVE ELECTRICAL PANELBOARDS
PER ARTICLE 384-4 OF NFPA 70.
PROVIDE ADDITIONAL SPRINKLERS, PIPING, FITTINGS, APPURTENANCES, AND ALL
OTHER WORK NECESSARY TO ACCOMMODATE ANY INTERIOR DESIGN LAYOUTS OR
CHANGES TO SUCH LAYOUTS WHICH ARE OR MAY BE INCLUDED IN THE WORK. THESE
SPRINKLERS AND ASSOCIATED WORK SHALL BE PROVIDED WHERE REQUIRED TO
RESOLVE ANY CONFLICTS OR OTHER LAYOUT CHANGES NEEDED TO ACCOMMODATE
ALL MISCELLANEOUS ITEMS (I.E. CEILING OFFSETS, SOFFITS, COVES, CODE
INSPECTION/INTERPRETATIONS, STRUCTURAL SYSTEM CONFLICTS, ETC.) RELATED TO
INTERIOR DESIGN CONFIGURATION CHANGES.
BUTTERFLY VALVES SHALL BE ALLOWED DOWNSTREAM OF THE DISCHARGE SIDE OF
THE BACKFLOW PREVENTER.
SHOP DRAWINGS SHALL INDICATE ALL CEILING HEIGHT CHANGES FOR CONDITIONS
SUCH AS SOFFITS, BULKHEADS, ETC.
SHOP DRAWINGS SHALL INDICATE ALL SHELVING AND HEIGHTS.
INDICATE THE TOTAL SQUARE FOOT AREA PROTECTED BY SYSTEM ON SHOP
DRAWINGS.
INDICATE THE NUMBER OF SPRINKLERS ON EACH RISER ON SHOP DRAWINGS.
FIRE SPRINKLER MAIN LINE
FIRE SPRINKLER BRANCH PIPE
BACK FLOW PREVENTOR
FIRE SPRINKLER RISER
STANDARD PENDENT HEAD
UPRIGHT PENDANT HEAD
CONCEALED PENDANT HEAD
SIDEWALL SPRINKLER HEAD
BUTTERFLY VALVE
OS&Y VALVE W/TAMPER SWITCH
CHECK VALVE
PIPE TURN UP
PIPE TURN DOWN (DN)
PIPE CAPPED
ABOVE CEILINGAC
ABOVE FINISHED FLOORAFF
ABOVE FINISHED GRADEAFG
FIRE DEPARTMENT CONNECTIONFDC
WITHW/
GALLONS PER HOURGPH
GAL GALLON
HP HORSE POWER
GPM GALLONS PER MINUTE
HEADHD
EXISTINGEXIST
ETR EXISTING TO REMAIN
NFPA NATIONAL FIRE
PROTECTION ASSOCIATION
SHEET WHERE SHOWN
SHEET WHERE CUT
DETAIL/RISER/ENLARGED PLAN
NEW WORK NOTE DESIGNATION#
COTR CONTRACTING OFFICER'S
TECHNICAL
REPRESENTATIVE
NOT IN CONTRACTNIC
FIRE ALARM CONTROL PANELFACP
ACOUSTICAL CEILING TILEACT
GYP GYPSUM BOARD CEILING
OPEN TO STRUCTUREOTS
SMOOTH CONCRETE DECKSCD
DRY PENDENT HEAD
ORDINARY
HAZARD
MODERATE TO HIGH DENSITY OF FLAMMABLES, WITH FIRES OF
MODERATE HEAT RELEASE EXPECTED
STORAGE AREAS, LAB SPACES, COMPUTER SPACES, ELECTRICAL
ROOMS, MECHANICAL ROOMS, AND UTILITY SPACES, ETC.
HAZARD HAZARD DESCRIPTION HAZARD EXAMPLES
DENSITY
GPM/SQ.FT.
DEMAND
AREA*(SQ.FT)
HOSE
ALLOWANCE
0.2 2,500 250
MIN.
K-FACTOR
8.0
*DESIGN AREA REDUCTIONS IN NFPA 13 FOR QUICK RESPONSE SPRINKLERS ARE NOT PERMITTED. EXTENDED COVERAGE SPRINKLERS ARE NOT PERMITTED.
LIGHT
HAZARD
LOW COMBUSTIBILITY AND LOW DENSITY OF COMBUSTIBLES, WHERE
FIRES WITH RELATIVELY LOW HEAT RELEASE ARE EXPECTED.
OFFICE AREAS, PUBLIC AREAS, BREAK ROOMS, BATHROOMS, AND
CORRIDORS, ETC.
0.1 1,500 250 5.6
5" STORZ CONNECTION, MOUNTED ON
WALL
CHECK VALVE
ELECTRIC ALARM BELL
FLOW SWITCH
TEE CONNECTION
WATER PRESSURE GAUGE
RISER CHECK VALVE
MAIN DRAIN VALVE
MAIN DRAIN
BACKFLOW PREVENTER - "N" PATTERN
REDUCED PRESSURE TYPE
O S & Y GATE VALVE W / SUPERVISORY
SWITCH
BACKFLOW PREVENTER TEST HEADER
TO SPRINKLER SYSTEM
ANCHOR IN ACCORDANCE
WITH NFPA 24 (TYP FOR 2)
01/24/2020
POINT OF NEW CONNECTION
THIS CONTRACTOR SHALL PROVIDE NEW SPRINKLER SYSTEM INSTALLATION AS REQUIRED
TO SUIT NEW FLOOR PLANS AND REFLECTED CEILING PLANS WITHIN THE ENTIRE BUILDING.
SPRINKLER SYSTEM DESIGN, MATERIALS AND INSTALLATION SHALL BE IN ACCORDANCE
WITH NFPA 13, STATE, AND LOCAL AUTHORITIES. SPACING AND LOCATION OF SPRINKLERS
SHALL NOT EXCEED THAT PERMITTED FOR LIGHT AND ORDINARY HAZARD OCCUPANCY.
SPRINKLER HEADS SHOWN ON PLANS INDICATE DESIGN INTENT ONLY. CONTRACTOR IS
RESPONSIBLE FOR DETERMINING QUANTITY OF MATERIALS AND FINAL DESIGN OF THE
SYSTEM TO MEET NFPA-13 REQUIREMENTS.
SPRINKLER SCHEDULE:
USE SPRINKLER TYPES BELOW FOR THE FOLLOWING APPLICATIONS:
ROOMS WITHOUT CEILINGS: UPRIGHT SPRINKLERS
ROOMS WITH SUSPENDED CEILINGS: PENDENT SPRINKLERS.
WALL MOUNTING: SIDEWALL SPRINKLERS
BELOW GRADEBG
AutoCAD SHX Text
SATISFACTORY TO: DATE
AutoCAD SHX Text
APPROVED: PWO OR OICC DATE
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
SYM
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text F
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
SCALE: NOTED
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CONST. CONTR. NO.
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
AutoCAD SHX Text
19-0094 CONSTRUCT EOTG PEB
AutoCAD SHX Text
T.H. BURTON P.E.
AutoCAD SHX Text
B.WALKER
AutoCAD SHX Text
M. DELACEY
AutoCAD SHX Text
M. FORD
AutoCAD SHX Text
C. WEISE
AutoCAD SHX Text 60025512
AutoCAD SHX Text
FX001
AutoCAD SHX Text
AutoCAD SHX Text
FIRE SPRINKLER GENERAL NOTES LEGEND AND ABBREVIATIONS
AutoCAD SHX Text
FIRE PROTECTION GENERAL NOTES
AutoCAD SHX Text
LEGEND & ABBREVIATIONS
AutoCAD SHX Text
UFC HAZARD REQUIREMENTS*:
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
WET PIPE SPRINKLER RISER DETAIL
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text V
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MARTIN H. FORD
AutoCAD SHX Text Lic. No. 048072
AutoCAD SHX Text
SPRINKLER NOTE:
ChrisLife
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
TN
PN
SITE PLAN
6" FIRE SERVICE, BG. INSTALL IN ACCORDANCE WITH NFPA 24 AND NFPA 13. REFER TO
FLOOR PLAN, SHEET FX101, FOR CONTINUATION.
5" STORZ CONNECTION, MOUNTED ON EXTERIOR WALL.
01/24/2020
AutoCAD SHX Text S
AutoCAD SHX Text
UGC
AutoCAD SHX Text
TPED
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
UGC
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
FM
AutoCAD SHX Text
FM
AutoCAD SHX Text
FM
AutoCAD SHX Text S
AutoCAD SHX Text
WM
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text
8" PVC
AutoCAD SHX Text
6" PVC
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text
FW
AutoCAD SHX Text W
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text S
AutoCAD SHX Text
UGE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text
OHE
AutoCAD SHX Text S
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text 2"
AutoCAD SHX Text
UGC
AutoCAD SHX Text
BLDG. RR281
AutoCAD SHX Text
EOTG PEB
AutoCAD SHX Text H
AutoCAD SHX Text Y
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SATISFACTORY TO: DATE
AutoCAD SHX Text
APPROVED: PWO OR OICC DATE
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
SYM
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text F
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
SCALE: NOTED
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CONST. CONTR. NO.
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
AutoCAD SHX Text
19-0094 CONSTRUCT EOTG PEB
AutoCAD SHX Text
T.H. BURTON P.E.
AutoCAD SHX Text
B.WALKER
AutoCAD SHX Text
M. DELACEY
AutoCAD SHX Text
M. FORD
AutoCAD SHX Text
C. WEISE
AutoCAD SHX Text 60025513
AutoCAD SHX Text
FX002
AutoCAD SHX Text
AutoCAD SHX Text
FIRE SPRINKLER SITE PLAN
AutoCAD SHX Text
SCALE: 1" = 10'-0"
AutoCAD SHX Text 10'
AutoCAD SHX Text 1" = 10'-0"
AutoCAD SHX Text 20'
AutoCAD SHX Text 10'
AutoCAD SHX Text 5'
AutoCAD SHX Text 0'
AutoCAD SHX Text
NEW WORK NOTES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FLOW TEST RESULTS:
AutoCAD SHX Text
RESIDUAL:
AutoCAD SHX Text
FLOW:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
TIME:
AutoCAD SHX Text
STATIC:
AutoCAD SHX Text
LOCATION:
AutoCAD SHX Text
CONDUCTED BY:
AutoCAD SHX Text
49 PSI
AutoCAD SHX Text
42 PSI
AutoCAD SHX Text
1,088 GPM
AutoCAD SHX Text
PACE COLLABORATIVE, P.C.
AutoCAD SHX Text 09/12/2019
AutoCAD SHX Text 9:17 A.M
AutoCAD SHX Text
MCB CAMP LEJEUNE
AutoCAD SHX Text
DR. G.W. CARVER STREET
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text V
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MARTIN H. FORD
AutoCAD SHX Text Lic. No. 048072
WET PIPE SPRINKLER RISER,
REFER TO DETAIL, SHEET FX001,
FOR FURTHER INFORMATION,
6" SPRINKLER SERVICE, REFER TO
SITE PLAN, SHEET FX002, FOR
CONTINUATION.
108 1
FX401
5" STORZ CONNECTION,
30° ANGLED DOWN
EXISTING FIRE HYDRANT
VEHICLE
STORAGE
2 2
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
TN
PN
FLOOR PLAN
SCALE: 3/16" = 1'-0"
3/16" = 1'-0" 0' 5' 10' 20'
NEW WORK NOTES
THIS SPACE IS DESIGNATED AS LIGHT HAZARD OCCUPANCY.
THIS SPACE IS DESIGNATED AS ORDINARY HAZARD OCCUPANCY.
01/24/2020
AutoCAD SHX Text
SATISFACTORY TO: DATE
AutoCAD SHX Text
APPROVED: PWO OR OICC DATE
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
SYM
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text F
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
SCALE: NOTED
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CONST. CONTR. NO.
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
AutoCAD SHX Text
19-0094 CONSTRUCT EOTG PEB
AutoCAD SHX Text
T.H. BURTON P.E.
AutoCAD SHX Text
B.WALKER
AutoCAD SHX Text
M. DELACEY
AutoCAD SHX Text
M. FORD
AutoCAD SHX Text
C. WEISE
AutoCAD SHX Text 60025514
AutoCAD SHX Text
FX101
AutoCAD SHX Text
AutoCAD SHX Text
FIRE SPRINKLER FLOOR PLAN
AutoCAD SHX Text
AutoCAD SHX Text
WOMENS BILLETING
AutoCAD SHX Text
ROOM SCHEDULE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ACC LOCKER
AutoCAD SHX Text
AutoCAD SHX Text
ROPE GEAR MAINTENANCE LOCKER
AutoCAD SHX Text
AutoCAD SHX Text
HRST LOCKER
AutoCAD SHX Text
AutoCAD SHX Text
INSTRUCTOR GEAR LOCKER
AutoCAD SHX Text
AutoCAD SHX Text
RAID STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
MECH.
AutoCAD SHX Text
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
AutoCAD SHX Text
TELECOM
AutoCAD SHX Text
MENS BILLETING
AutoCAD SHX Text
AutoCAD SHX Text
RISER ROOM
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text V
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MARTIN H. FORD
AutoCAD SHX Text Lic. No. 048072
WET PIPE SPRINKLER RISER,
REFER TO DETAIL, SHEET FX001,
FOR FURTHER INFORMATION,
6" SPRINKLER SERVICE,
REFER TO SITE PLAN, SHEET
FX002, FOR CONTINUATION.
108 1
FX101
5" STORZ CONNECTION, 30°
ANGLED DOWN
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
TN
PN
ENLARGED FIRE PUMP ROOM FLOOR PLAN
SCALE: 3/16" = 1'-0"
3/16" = 1'-0" 0' 5' 10' 20'
NEW WORK NOTES
THIS SPACE IS DESIGNATED AS LIGHT HAZARD OCCUPANCY.1
01/24/2020
AutoCAD SHX Text
SATISFACTORY TO: DATE
AutoCAD SHX Text
APPROVED: PWO OR OICC DATE
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
SYM
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text F
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
SCALE: NOTED
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CONST. CONTR. NO.
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
AutoCAD SHX Text
19-0094 CONSTRUCT EOTG PEB
AutoCAD SHX Text
T.H. BURTON P.E.
AutoCAD SHX Text
B.WALKER
AutoCAD SHX Text
M. DELACEY
AutoCAD SHX Text
M. FORD
AutoCAD SHX Text
C. WEISE
AutoCAD SHX Text 60025515
AutoCAD SHX Text
FX-401
AutoCAD SHX Text
AutoCAD SHX Text
FIRE SPRINKLER ENLARGED FIRE PUMP FLOOR PLAN
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text V
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MARTIN H. FORD
AutoCAD SHX Text Lic. No. 048072
Stamp
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE
FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE
PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
FIRE ALARM AND MASS NOTIFICATION LEGEND
FIRE ALARM MANUAL PULL STATION, 48" AFF TO ACTUATING ARM, UON
FIRE ALARM/MNS AUDIO/VISUAL (SPEAKER/STROBE) APPLIANCE, 80"
AFF, OR 6" BELOW FINISHED CEILING, WHICHEVER IS LOWER, UON.
SUBSCRIPT INDICATES MINIMUM CANDELA RATING OF STROBE.
F
S
REQ'D REQUIRED
PNL PANEL
NATIONAL ELECTRICAL CODENEC
GROUNDGND
EXIST EXISTING
EXISTING TO REMAINETR
CONDUIT C
UNLESS OTHERWISE NOTEDUON
FIRE ALARM/ MASS NOTIFICATION SYSTEM
AREA OF REFUGE ASSISTANCEARA
ABBREVIATIONS
ABOVE FINISHED GRADEAFG
ABOVE FINISHED FLOORAFF
FMCP
BELOW FINISHED GRADEBFG
FIRE ALARM/MASS NOTIFICATION
CONTROL PANEL
S
WP
FIRE ALARM AUDIO (SPEAKER) APPLIANCE, 80" AFG, WALL
MOUNT, SUBSCRIPT "WP" INDICATES WEATHER PROOF.
MASS NOTIFICATION SYSTEMMNS
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL
FAMN
GENERAL FIRE ALARM NOTES
GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, WORK SHOWN ON FIRE
ALARM DRAWINGS IS NEW WORK TO INCLUDE THE FIRE ALARM/MASS NOTIFICATION
PANEL, DEVICES, AND APPLIANCES ON DRAWINGS FOR A COMPLETE AND
OPERATIONAL SYSTEM.
COORDINATION: THE CONTRACTOR MUST REVIEW CONTRACT DOCUMENTS
INCLUDING FIRE ALARM DRAWINGS AND SPECIFICATIONS. CONTRACTOR MUST
COORDINATE AND ADJUST ACCORDINGLY AS DIRECTED BY THE COTR.
AS-BUILT DRAWINGS: SECURE AN EXTRA SET OF DRAWINGS TO BE KEPT ON SITE
AND MARK DAILY, THE DRAWINGS IN RED AS THE PROJECT PROGRESSES IN
ORDER TO KEEP AN ACCURATE RECORD OF ALL DEVIATIONS BETWEEN THE WORK
SHOWN ON THE DRAWINGS AND THE WORK WHICH IS ACTUALLY INSTALLED. THESE
MARKED DRAWINGS MUST REFLECT ANY AND ALL CHANGES AND REVISIONS TO
THE ORIGINAL DESIGN WHICH EXISTS IN THE COMPLETED WORK. DELIVER THE
MARKED DRAWINGS TO THE COTR AT PROJECT CLOSE-OUT. IN ADDITION, PROVIDE
CONTACT ID POINT DESCRIPTIONS FOR EACH DEVICE.
INSPECTIONS: ARRANGE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .