The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

01/24/2020

System 600

POWERS POWERS

System 600

HEATING PLANT

CONTROLLER

POWERS

System 600

COOLING PLANT

CONTROLLER

POWERS

System 600

FIELD PANEL

AHU-1

MECHANICAL ROOM

FIRST FLOOR

FIELD PLUG-IN

PORTABLE

OPERATOR'S

WORKSTATION

CWP-2

AC-1

· ENABLE/DISABLE

· SPEED

BOILER

RP-2

BACNET MSTP BUS (TYP)

· ON/OFF

· STATUS

BOILER

RP-1

POWERS

System 600

PUMP

CONTROLLER

VAV

ASC

CHILLED WATER SYSTEM :

GENERAL: THE FACILITY SHALL BE SUPPLIED WITH CHILLED WATER FROM AIR-COOLED CHILLER, AC-1. THE DESIGN CHILLED WATER SUPPLY TEMPERATURE IS 45°F.

COOLING: A CALL FOR COOLING IS DETERMINED BY ANY COOLING COIL VALVE BEING 30 PERCENT OPEN FOR A PERIOD OF MORE THAN 3 MINUTES. UPON A CALL FOR COOLING, THE CHILLER AND INTEGRAL PUMPING

PACKAGE SHALL BE ENERGIZED AND RUN FOR A MINIMUM OF 30 MINUTES. THE CHILLER MANUFACTURER'S CONTROL PANEL SHALL MAINTAIN CHILLED WATER SETPOINT (45°F). AN ANTI-CYCLE TIMER SHALL PREVENT THE CHILLER FROM BEING STARTED FOR A PERIOD OF 15 MINUTES AFTER IT SHUTS DOWN DUE TO LOW BUILDING COOLING DEMAND. THE CHILLER MANUFACTURER'S MINIMUM ON AND OFF TIMES MUST BE OBSERVED. THE

ABOVE SEQUENCE SHALL BE ACCOMPLISHED THROUGH THE BUILDING DDC SYSTEM AND CHILLER MANUFACTURER'S CONTROL PANEL. ALL ALARMS AND POINT INFORMATION RESIDING IN THE CHILLER CONTROL PANEL, SHALL BE AVAILABLE THROUGH THE BUILDING DDC SYSTEM.

CHILLER SHALL UTILIZE AN INTEGRAL PUMPING PACKAGE. PUMPS SHALL BE EQUIPPED WITH VARIABLE FREQUENCY DRIVES BUT SHALL OPERATE AT CONSTANT SPEED. PUMPS SHALL OPERATE IN A LEAD/STANDBY

CONFIGURATION, AND THE LEAD PUMP DESIGNATION SHALL ALTERNATE ON A WEEKLY BASIS. IN THE EVENT THE PRIMARY PUMP FAILS TO START DURING OPERATION, IF THE LEAD PUMP PROOF SWITCH DOES NOT DETECT

FLOW WITHIN 30 SECONDS FROM START SIGNAL, THE DDC CONTROLLER SHALL DE-ENERGIZE THE FAILED PUMP, START THE STANDBY PUMP, AND TRANSMIT A PUMP FAILURE ALARM. A PROGRAMMED ANTI-RECYCLE TIMER

SHALL PREVENT PUMP SHORT CYCLING. THE DDC CONTROLLER SHALL AUTOMATICALLY ATTEMPT A RESTART OF THE CIRCULATING PUMPS ON A PERIODIC BASIS TO ACCOMMODATE SERVICE SHUTDOWNS AND EXTENDED

POWER OUTAGES.

SEQUENCE OF OPERATION

ALARMS: ALARM IF CWS TEMPERATURE RISES ABOVE 48°F.

DDC/EMCS SIGNAL/FUNCTION:

CWS TEMPERATURE - STATUS, ALARM

CWR TEMPERATURE - STATUS

CWR TEMPERATURE

INTEGRAL CHILLED WATER PUMP CWP-1 - STATUS, ALARM

INTEGRAL CHILLED WATER PUMP CWP-2 - STATUS, ALARM

CHILLED WATER FLOWMETER - COOLING LOAD (TONS), STATUS

CWS

CWR

CWS

CWR

TO AHU-1

CWP-1

CWP-2

DPS

DI1

DPS

DI2

FMAI3

TS AI2

TS

AI1

CHILLED WATER SYSTEM

LOCAL DDC CONTROLLER

A N

A L

O G

INPUTS

CWS TEMPERATURE

D I G

I T

A L

PUMP CWP-1 STATUS (ON/OFF)

CWR TEMPERATURE

A N

A L

O G

OUTPUTS

AI1

AI2

AI3

DI1

AO1

PUMP CWP-2 STATUS (ON/OFF)DI2

AO2

CHILLED WATER FLOWMETER

MODULATING BYPASS VALVE CONTROL (V-1)

AIR-COOLED CHILLER AC-1

FS DI3

AC-1 FLOW SWITCH

DI3

REPRESENTS COMPONENTS

WHICH ARE INTEGRAL TO

CHILLER PACKAGE

DI4

DDC

DO1

AO2

AI4

CONTROL

PANEL

AC-1 STATUS (ON/OFF)DI4

D I G

I T

A L

AC-1 ENABLE/DISABLEDO1

CWS SETPOINT

AC-1 PERCENTAGE OF LOADAI4

C W

R

2"

PRESSURE GAUGE

(0-100 PSIG TYP.)

COMPOUND

PRIOR TO TAB WORK (TYP.)

REMOVE START-UP STRAINER

FLEX CONNECTION

(TYP. BOTH SIDES)

CWP-1

CWP-2

1/4"

1/4"

2"

2"

2"

CW

S

(4 5°

F)

CWR (59.2°F)

2"

2-1/2"

1"

TANGENTIAL AIR

SEPARATOR

HIGH CAPACITY

AIR VENT

DIAPHRAGM EXPANSION TANK,

PRECHARGE TO 15 PSIG

3/4"

ET

3/4" DRAIN WITH

THREADED HOSE BIBB

PRESSURE GAUGE

(O-100 PSIG)

VENTURI BALANCE

VALVE, 38.2 GPM

PROVIDE 8 WATT/SF SELF

REGULATING HEAT TAPE ON

EXTERIOR PIPING

WELLS FOR PRESSURE /

TEMPERATURE TAP

CONNECTIONS (TYP FOR 4)

AC-1

INTEGRAL TO AIR-COOLED

CHILLER AC-1

C W

S

STRAINER W/

BLOWDOWN VALVE

UNION

CHECK VALVE

TEST WELL

FLOW SWITCH

1" DRAIN LINE AND BALL VALVE

AT LOW POINT IN PIPING (TYP.)

VALVE-SET AT 15 PSIG

PRESSURE REGULATION

SET AT 50 PSIG

RELIEF VALVE

3/4" BYPASS

GLOBE VALVE TO FD

1" MAKE-UP WATER, REFER TO

PLUMBING DRAWINGS FOR

BACKFLOW PREVENTER AND

CONTINUATION

1" TO CHILLER

THERMOMETER

1" COLD WATER

MAKE-UP

C W

R

C W

S

SHOT FEEDER IN

MECHANICAL ROOM

CHILLED WATER SYSTEM FLOW DIAGRAM

SCALE: NO SCALE M-702

A

CHILLED WATER SYSTEM CONTROL DIAGRAM (DDC)

SCALE: NO SCALE M-702

B

BUILDING GLOBAL POINT (DDC)

NO SCALE

SUNSHIELD

OUTSIDE AIR

AI2 H

TAI1

OA TEMPERATURE

OA HUMIDITY

BUILDING DDC CONTROLLER

A N

A L

O G

AI2

AI1

INPUTS

LOCATE ON

NORTH WALL.

2" TEMPORARY

CHILLER

CONNECTION

SUPERVISORY BUILDING

CONTROLLER

SHWP-2

SHWP-1

NOTE: MULTIPLE UNITS

SEQUENCE OF OPERATION

EXHAUST FAN WITH THERMOSTAT (NON-DDC)

EXHAUST FAN SHALL BE CONTROLLED BY A WALL MOUNTED THERMOSTAT AND

INTERLOCKED WITH MOTORIZED DAMPER. UPON A RISE IN SPACE TEMPERATURE

ABOVE 85°F, MOTORIZED DAMPER SHALL OPEN AND FAN SHALL BE ENERGIZED.

UPON FALL IN SPACE TEMPERATURE BELOW 85°F, THE OPPOSITE SHALL OCCUR.

NO SCALE

LINE

VOLTAGE

THERMOSTAT

FAN

MOTOR

T

LINE

VOLTAGE

M MOTORIZED DAMPER

VFD

VFD

VAV

ASC

CWP-1

· ON/OFF

· STATUS

DO2

DO3

CWP-1 ENABLE/DISABLEDO2

CWP-2 ENABLE/DISABLEDO3

DSS CONDENSING UNIT

DSS EVAPORATOR

COOLING: UNIT SHALL BE CONTROLLED BY THE MANUFACTURER'S INTEGRAL THERMOSTAT.

WHEN THE SPACE TEMPERATURE RISES ABOVE THE COOLING SETPOINT (75°F), THE

THERMOSTAT SHALL ENERGIZE THE DSS UNITS AND ENERGIZE THE INDOOR UNIT SUPPLY

FAN. WHEN THE SPACE TEMPERATURE DROPS BELOW THE THERMOSTAT SETPOINT, THE

OPPOSITE SHALL OCCUR.

HEATING: UPON A FALL IN SPACE TEMPERATURE BELOW HEATING SETPOINT (68°F), THE

THERMOSTAT SHALL ENERGIZE THE INDOOR UNIT SUPPLY FAN AND OUTDOOR

COMPRESSORS. UPON A FURTHER DROP IN TEMPERATURE, THE UNITS ELECTRIC HEATING

COIL SHALL BE ENERGIZED. UPON A RISE IN SPACE TEMPERATURE ABOVE HEATING

SETPOINT, THE OPPOSITE SHALL OCCUR.

ALARM: SPACE TEMPERATURE SHALL BE MONITORED BY A SEPARATE TEMPERATURE

SENSOR. ALARM IF TEMPERATURE IS 78° F (ADJ.). UNIT CONTROL BY MANUFACTURER.

NO SCALE

DSS, CONTROL DIAGRAM (DDC)

SEQUENCE OF OPERATION

MANUFACTURER'S INTEGRAL

THERMOSTAT

RS/RLT

DUCTLESS SPLIT SYSTEM

LOCAL DDC CONTROLLER

A N

A L

O G

INPUTS

SPACE TEMPERATURE

AI1

AI1

TS

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

01/24/2020

HEATING HOT WATER SYSTEM

GENERAL: THE HOT WATER SYSTEM SHALL BE CONTROLLED BY THE BOILER MANAGEMENT SYSTEM. CONTROLLER SHALL MONITOR BOILERS'

STATUS AND HOT WATER SUPPLY TEMPERATURES. BOILERS SHALL OPERATE IN LEAD/LAG CONFIGURATION AND THE PUMPS SHALL

OPERATE IN A LEAD/STAND-BY CONFIGURATION ALTERNATING LEAD BOILERS/PUMPS STATUS WEEKLY BY SELECTING BOILER/PUMP WITH THE

LEAST TOTAL ACCUMULATED RUN TIME (HOURS). SECONDARY PUMPS ARE SIZED FOR CONNECTED LOAD AND ARE FULLY REDUNDANT.

IF THERE IS AN ALARM IN ANY BOILER OR IF A FAULT OCCURS IN THE BOILER MANAGEMENT SYSTEM, (AS DETERMINED FROM THE BINARY

FAULT OUTPUT OF THE CONTROLLER), THE ASSOCIATED BOILER WILL BE COMMANDED OFF, AND AN ALARM SHALL BE GENERATED.

ON DETECTION OF A HIGH DISCHARGE BOILER TEMPERATURE, AS DETERMINED BY THE BOILER HIGH LIMIT ALARM, THE BOILER SHALL BE

DISABLED, AND AN ALARM SHALL BE GENERATED.

BOILER (B-1, B-2 ) AND PRIMARY HOT WATER PUMP CONTROL (RP-1, RP-2 ): ON A CALL FOR HEATING AT ANY AHU OR VAV TERMINAL FOR MORE

THAN THREE (3) MINUTES, THE DDC CONTROLLER SHALL SEND A SIGNAL TO THE BOILER MANAGEMENT SYSTEM THAT HEATING IS REQUIRED.

WHEN THE DDC CONTROL SYSTEM RECEIVES A CALL FOR HEATING, THE BOILER MANAGEMENT SYSTEM SHALL BE ENGAGED AND SHALL

ENABLE THE LEAD BOILER. THE LEAD BOILER AND ASSOCIATED PRIMARY HOT WATER PUMP SHALL BE ENERGIZED. UPON A DROP IN MAIN HW

LOOP TEMPERATURE BELOW SETPOINT, THE LAG BOILER AND ASSOCIATED PRIMARY HOT WATER PUMP SHALL BE ENERGIZED.

SECONDARY HOT WATER PUMPS, SHWP-1 AND SHWP-2: THE CONTROL STRATEGY INCLUDES OPERATING VARIABLE SPEED PUMPS IN ORDER

TO MINIMIZE PUMPING POWER REQUIREMENTS. THE SPEED DRIVE OF THE VARIABLE SPEED PUMP(S) IS CONTROLLED TO MAINTAIN A

DIFFERENTIAL PRESSURE SETPOINT. THE DDC CONTROLLER SHALL BE DESIGNED TO START AND STOP THE PUMPS AND MODULATE THEIR

SPEEDS AS REQUIRED TO MEET THE SYSTEM DEMANDS. THE SYSTEM SHALL BE DESIGNED TO MAINTAIN A DIFFERENTIAL PRESSURE

SETPOINT AT A REMOTE LOCATION.

SECONDARY HOT WATER PUMPS SHALL BE CONTROLLED BY THE DDC SYSTEM. PUMPS SHALL BE ENERGIZED AND RUN ON A CALL FOR

HEATING AT ANY AHU OR VAV TERMINAL FOR MORE THAN THREE (3) MINUTES. THE DDC CONTROLLER SHALL ALTERNATE PUMP LEAD

STATUS WEEKLY BY SELECTING THE PUMP WITH THE LEAST TOTAL ACCUMULATED RUN TIME AS CALCULATED AND STORED AT THE DDC

CONTROLLER. IF EITHER SELECTED LEAD PUMP'S PROOF SWITCH DOES NOT DETECT FLOW WITHIN 30 SECONDS FROM THE START SIGNAL, THE DDC CONTROLLER SHALL DE-ENERGIZE THE FAILED PUMP, START THE STANDBY PUMP, AND TRANSMIT A PUMP FAILURE ALARM. A

PROGRAMMED ANTI-RECYCLE TIMER SHALL PREVENT PUMP SHORT CYCLING. THE DDC CONTROLLER SHALL AUTOMATICALLY ATTEMPT A

RESTART OF THE CIRCULATING PUMPS ON A PERIODIC BASIS TO ACCOMMODATE SERVICE SHUTDOWNS AND EXTENDED POWER OUTAGES.

HOT WATER RESET CONTROL: THE SECONDARY HOT WATER SUPPLY TEMPERATURE SETPOINT SHALL BE DETERMINED BY THE OUTSIDE AIR TEMPERATURE. THE HOT WATER SUPPLY TEMPERATURE SETPOINT SHALL BE RESET PROPORTIONALLY AS FOLLOWS: AS AIR TEMPERATURE RISES

FROM 20°F TO 60°F, RESET SECONDARY HWS FROM 120°F DOWN TO 100°F.

BOILER EMERGENCY SHUT-OFF CONTROL: PROVIDE TWO POSITION "ON-OFF" SWITCHES LABELED "BOILER EMERGENCY SHUT-OFF" LOCATED

AS INDICATED WHICH SHALL BE HARDWIRE INTERLOCKED WITH THE BOILERS' CONTROL PANEL. WHEN INDEXED TO THE "ON" POSITION, THE

BOILERS SHALL OPERATE UNDER NORMAL CONTROL OF THE DDC CONTROL SYSTEM. WHEN INDEXED TO THE "OFF" POSITION, THE BOILERS

SHALL BE DISABLED, AND THE GAS BURNERS TO EACH BOILER SHALL BE SHUTDOWN. MANUAL RESET SHALL BE REQUIRED.

ALARMS: IF THERE IS AN ALARM IN ANY BOILER OR IF A FAULT OCCURS IN THE BOILER MANAGEMENT SYSTEM, (AS DETERMINED FROM THE

BINARY FAULT OUTPUT OF THE CONTROLLER), THE ASSOCIATED BOILER ISOLATION VALVE SHALL CLOSE, AND AN ALARM SHALL BE

GENERATED. ON DETECTION OF A HIGH DISCHARGE BOILER TEMPERATURE, AS DETERMINED BY THE BOILER HIGH LIMIT ALARM, THE BOILER

MANAGEMENT SYSTEM SHALL BE DISABLED AND AN ALARM SHALL BE GENERATED. ALARM FOR LEAVING WATER TEMPERATURE EXCEEDING

140°F OR FALLING 10°F BELOW THE SCHEDULED HWS TEMPERATURE SETPOINT. ALARM IF ANY BOILER OR PUMP FAILS TO START OR FAILS

DURING OPERATION.

DDC/EMCS SIGNAL-FUNCTION:

RETURN WATER TEMPERATURE - STATUS

LEAVING WATER TEMPERATURE - STATUS

PUMP RP-1 - START/STOP, STATUS, ALARM

PUMP RP-2 - START/STOP, STATUS, ALARM

PUMP SHWP-1 MOTOR - START/STOP, STATUS, RUNTIME, ALARM

PUMP SHWP-2 MOTOR - START/STOP, STATUS, RUNTIME, ALARM

DIFFERENTIAL PRESSURE SENSOR - PUMP SHWP-1 AND SHWP-2 VFD CONTROL

BOILER MANAGEMENT SYSTEM - ALARM, STATUS, START/STOP

EMERGENCY GAS SHUT OFF SWITCH - BOILER B - 1, 2, START/STOP, ALARM

BOILER CONDENSATE PUMP - ALARM

PHWS

BOILER

CONTROL

PANEL

PHWS

BOILER

B-1

AN

AL

OG

HWS TEMPERATURE

DIFFERENTIAL PRESSURE

DI

GI

TA

L

AN

AL

OG

OUTPUTS

DI

GI

TA

L

SHWP-1 SPEED CONTROL

SHWP-2 SPEED CONTROL

SHWP-1 VFD, ENABLE/DISABLE

BOILER, ENABLE/DISABLE

SHWP-2 VFD, ENABLE/DISABLE

BOILER ALARM

SHWP-2

SHWR HWR TEMPERATURE

INPUTS

LOCAL DDC CONTROLLER

HEATING HOT WATER SYSTEM

RP-1 - STATUS

RP-2 - STATUS

SHWP-1 - STATUS

SHWP-2 - STATUS

EMERGENCY SWITCH

BOILER MANAGEMENT SYSTEM

BOILER LOOP SUPPLY TEMPERATURE

B-1 SUPPLY TEMPERATURE

RP-1, ENABLE/DISABLE

BRIDGE

BOILER

B-2

B-2 SUPPLY TEMPERATURE

EMERGENCY GAS

SHUTOFF SWITCH

SHWP-1

HW FLOWRATE

SHWP-1 VFD SPEED (Hz)

SHWP-2 VFD SPEED (Hz)

RP-2, ENABLE/DISABLE

GAS, ON/OFF

AI1

AI2

AI3

AI4

AI5

AI6

AI8

AI9

AI10

DI1

DI2

DI3

DI5

DI6

AO1

AO2

DO1

DO2

DO3

DO4

DO5

DO1DI1

AI5

AI4

DI6

AI3 DPS

VFD

VFD

DPS

DPS

AI2 AI8

DI4

DI5

AI1

AO2DO3

DO2 AO1 SHWSSHWS

PH

W

R

AI9

AI10

AI7

DI4

DO6

TS

TS

TS FM

TS

ES

SEQUENCE OF OPERATION

SEE SHEET M-101 FOR LOCATION

LP

D06

M

DPS

DI2

DO4

RP-1

DPS

DI3

DO5

AI6TS

BOILER LOOP RETURN TEMPERATUREAI7 TS

RP-2

HEATING HOT WATER SYSTEM CONTROL DIAGRAM

SCALE: NO SCALE M-703A

3/4" COLD WATER, SEE PLUMBING

M-703 FOR CONTROLS SCHEMATIC (TYP.)

TEMPERATURE SENSOR AND WELL. SEE SHEET

ROOM WALL (TYP. FOR 2)

VALVE AT EQUIPMENT

TO BUILDING HW SYSTEM

SEE SHEET M-101 FOR CONTINUATION

ET-1

HWR

HWS

TANGENTIAL AIR

SEPARATOR

FLOOR DRAIN

1" TO

NEAREST

3/4"

PRESSURE REGULATION

RELIEF VALVE-

AIR VENT

SET AT 50 PSIG

VALVE-SET AT 26 PSIG

1" BYPASS

HWS

3/4"

SHWP-2

3/4"

(0-100 PSIG TYP.)

PRESSURE GAUGE

SHWP-1

2"

HIGH CAPACITY

2" 2"

2"

2"

LINE SIZE

REMOVE START-UP STRAINER

PRIOR TO TAB WORK (TYP.)

1/4"

1/4"

SHEETS FOR BACKFLOW PREVENTER,

AND CONTINUATION

4" CONCRETE

EQUIPMENT PAD (TYP.)

PH

W

S

PH

W

R

2"

RP-1

INLINE PUMP, SEE

DETAIL FOR VALVE

WORK REQUIRED

PH

W

R

PH

W

S

2"

2"

30 PSIG RELIEF VALVE BY

MANUFACTURER (TYP)

FULL SIZE OF OUTLET,

PIPE TO FLOOR DRAIN

(TYP)

B-2

3/4" DRAIN AND BALL

VALVE (TYP)

B-1

HWS

SHOT FEEDER

5 GALLON

HOT WATER FLOW DIAGRAM

SCALE: NO SCALE M-703B

1" 3/4"

CONDENSATE

NEUTRALIZATION KIT

BRIDGE

RP-2

TO FLOOR DRAIN

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

LIGHTING FIXTURE

EXIT LIGHTING FIXTURE, WITH DIRECTIONAL ARROWS AS INDICATED WITH BATTERY

PACK - CONNECT AHEAD OF LOCAL SWITCH.

EMERGENCY BATTERY LIGHTING UNIT, CONNECT AHEAD OF LOCAL SWITCH.

LIGHTING FIXTURE TYPE SYMBOL. SEE LIGHTING FIXTURE DETAILS.

SINGLE POLE SWITCH, 20A, 120/277V, 46" AFF UON

EQUIPMENT CONNECTION

MOTOR CONNECTION

SAFETY SWITCH, 60A-3P, FU @ 30A, 3R

MAGNETIC MOTOR STARTER, MOUNT WITHIN SIGHT OF MOTOR 5'-0" AFF MAX,

UON.

ELECTRICAL PANELBOARD; 208/120V, 3Ø, 4W

ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN TO PANELBOARD

(PANEL AND CIRCUIT DESIGNATION AS INDICATED). AS A MINIMUM CONDITION, EACH

SINGLE PHASE CIRCUIT MUST HAVE 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL

CONDUCTOR AND 1 #12 GROUNDING CONDUCTOR IN 1/2" CONDUIT. PROVIDE

ADDITIONAL PHASE CONDUCTORS AS REQUIRED FOR "MULTIPLE PHASED"

ELECTRICAL LOADS. PROVIDE NEUTRAL CONDUCTOR TO ALL WALL SWITCH OUTLET

BOXES WHETHER REQUIRED OR NOT. PROVIDE ADDITIONAL "SWITCH LEG"

CONDUCTORS TO PROVIDE THE LIGHT FIXTURE CONTROL INDICATED. MULTIPLE

SINGLE PHASE CONDUCTORS MAY BE GROUPED TOGETHER IN A COMMON CONDUIT

IN ACCORDANCE WITH THE NEC AND AT THE CONTRACTOR'S DISCRETION.

GROUNDING CONDUCTORS MAY BE SHARED AS ALLOWED BY THE NEC. NEUTRAL

CONDUCTORS MUST NOT BE SHARED. MULTI-POLE BREAKERS MUST BE PROVIDED IN

ACCORDANCE WITH THE NEC WHERE MULTI-WIRE BRANCH CIRCUITS ARE REQUIRED.

CONDUIT LARGER THAN 1/2" AND CONDUCTORS LARGER THAN #12 MUST BE AS

INDICATED.

LIGHTING

POWER

GENERAL

WALL MOUNTED LIGHTING FIXTURE

NEW WORK NOTE SYMBOL

MOTOR RATED SWITCH WITH THERMAL OVERLOADS 20A, 120V, UON, MOUNTED

WITHIN SIGHT OF MOTOR.

PHOTOCELL, 1500W, 120V SPST, MOUNT ON ROOF, AIM NORTH

PAD MOUNTED TRANSFORMER

INDICATES FRONT

SURGE PROTECTIVE DEVICE

GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN ON

ELECTRICAL DRAWINGS IS NEW WORK TO BE PROVIDED UNDER THIS CONTRACT.

COORDINATION: COORDINATE AND COOPERATE WITH ALL TRADES ON THE

PROJECT. THE CONTRACTOR MUST REVIEW ALL CONTRACT DOCUMENTS

INCLUDING CIVIL, STRUCTURAL, ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS. CONTRACTOR MUST COORDINATE AND ADJUST ACCORDINGLY

AS DIRECTED BY THE CONTRACTING OFFICER.

AS-BUILT DRAWINGS: SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE

KEPT ON SITE AND MARK, DAILY, THE DRAWINGS IN RED AS THE PROJECT

PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF ALL DEVIATIONS

BETWEEN THE WORK SHOWN ON THE DRAWINGS AND THE WORK WHICH IS

ACTUALLY INSTALLED. THESE MARKED DRAWINGS MUST REFLECT ANY AND ALL

CHANGES AND REVISIONS TO THE ORIGINAL DESIGN WHICH EXISTS IN THE

COMPLETED WORK. DELIVER THE MARKED DRAWINGS TO THE ENGINEER AT

PROJECT CLOSE-OUT.

TESTS: TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE CONNECTING

ANY FIXTURES OR DEVICES. PERFORM INSULATION RESISTANCE TESTS ON ALL

WIRING #6 OR LARGER TO ENSURE THAT ALL PORTIONS ARE FREE FROM

SHORT-CIRCUITS AND GROUNDS.

INSPECTIONS: ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL REQUIRED

INSPECTION CERTIFICATES TO THE CONTRACTING OFFICER.

ELECTRICAL SERVICE: PROVIDE THE ELECTRICAL SERVICE. COMMUNICATE WITH

THE CONTRACTING OFFICER, VERIFY ALL REQUIREMENTS, AND COORDINATE ALL

EFFORTS.

GROUNDING: PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE

ENTIRE ELECTRICAL SYSTEM INCLUDING EQUIPMENT FRAMES CONDUITS,

SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS, AND OTHER

EQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL POWER CONDUITS.

LABELS: PROVIDE LABELS FOR ALL PANELBOARDS, SAFETY SWITCHES,

MOTOR-DISCONNECT SWITCHES, AND MOTOR CONTROLLERS. LABELS MUST BE

MACHINE ENGRAVED, LAMINATED PLASTIC, PERMANENTLY ATTACHED WITH

SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF-ADHESIVE LABELS. LABEL

MUST INDICATE EQUIPMENT DESIGNATION AND ASSOCIATED PANEL AND CIRCUIT

THAT SERVES IT.

J-BOX LABELING: LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER

IDENTIFYING CIRCUIT NUMBER AND PANELBOARD OF CIRCUITS WITHIN.

WIRING DEVICES: LABEL ALL WIRING DEVICES WITH PANELBOARD AND CIRCUIT

DESIGNATION PERMANENTLY ATTACHED WITH BLACK TYPED DESIGNATION ON

CLEAR TAPE.

PANEL DIRECTORY: PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN

EACH PANELBOARD WITH CIRCUIT LOAD INFORMATION AND ROOM NUMBER

CLEARLY IDENTIFIED. USE ACTUAL ROOM NUMBERS IN THE BUILDING, NOT THE

ROOM NUMBERS SHOWN ON THE CONTRACT DRAWINGS, AS THEY ARE OFTEN

DIFFERENT.

CONDUCTORS AND MATCHING LUGS: IN SITUATIONS WHERE CONDUCTOR SIZES

AND/OR QUANTITIES OF PARALLEL SETS HAVE BEEN INCREASED DUE TO

VOLTAGE DROP OR FOR OTHER REASONS, CONTRACTOR MUST PROVIDE THE

APPROPRIATE LUG SIZES/QUANTITIES WITHIN THE EQUIPMENT CONNECTED

(SWITCHBOARD, PANELBOARD, DISCONNECT SWITCH, TRANSFER SWITCH ETC.)

TO PERMIT SATISFACTORY CONNECTION OF THE INDICATED CONDUCTORS.

WHERE SUFFICIENT LUG SIZES AND/OR QUANTITIES CANNOT BE PROVIDED TO

ACCOMMODATE THE CONDUCTORS INDICATED, THEN PROVIDE REDUCING

ADAPTERS, PIN TERMINALS, OR A JUNCTION BOX TO SPLICE LARGER

CONDUCTORS TO APPROPRIATELY SIZED SMALLER CONDUCTORS TO FIT INTO

THE LUGS PROVIDED. ALL CONDUCTORS MUST BE SIZED IN ACCORDANCE WITH

THE NEC.

MOTOR COORDINATION: MOTORS, MOTOR STARTERS, CONTROLLERS, INTEGRAL

DISCONNECT SWITCHES, AND CONTACTORS MUST BE PROVIDED WITH THEIR

RESPECTIVE PIECES OF EQUIPMENT BY THE EQUIPMENT SUPPLIER.

COMMUNICATE WITH THE TRADES PROVIDING THE EQUIPMENT, VERIFYING ALL

REQUIREMENTS, PROVIDE ALL ELECTRICAL CONNECTIONS REQUIRED THEREIN,

AND INSTALL MOTOR STARTERS.

MOTOR DISCONNECTS: ALL MOTORS MUST HAVE DISCONNECTING MEANS.

MOTOR CONTROLLERS: ALL 3-PHASE MOTORS MUST HAVE MAGNETIC MOTOR

CONTROLLERS WITH SOLID STATE OVERLOAD RELAY PROTECTION. THE SOLID

STATE OVERLOAD RELAY MUST HAVE PHASE LOSS AND PHASE OVERCURRENT

PROTECTION WITH AUTOMATIC RESET UPON RETURN OF NORMAL POWER.

MOTOR FUSE PROTECTION: WHERE FUSE PROTECTION IS SPECIFICALLY

REQUIRED BY THE EQUIPMENT MANUFACTURER, PROVIDE FUSED SWITCHES IN

LIEU OF NON-FUSED SWITCHES OR IN LIEU OF ENCLOSED CIRCUIT BREAKERS, OR

OTHER DEVICES INDICATED.

CONNECTION DETAILS: SECURE APPROVED SHOP DRAWINGS SHOWING WIRING

DIAGRAMS, ROUGH-IN AND HOOK UP DETAILS FROM OTHER INVOLVED

CONTRACTORS FOR EQUIPMENT WHICH MUST BE CONNECTED ELECTRICALLY.

COORDINATION DETAILS: MECHANICAL EQUIPMENT WILL BE FURNISHED AND

INSTALLED BY THE MECHANICAL CONTRACTOR. THE LOCATIONS SHOWN ON THE

ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE WITH THE

MECHANICAL CONTRACTOR TO DETERMINE THE EXACT LOCATION OF EACH

PIECE OF EQUIPMENT AND DETERMINE THE EXACT ROUGH-IN AND CONNECTION

REQUIREMENTS.

WORKING CLEARANCE: COORDINATE FINAL LOCATIONS OF ELECTRICAL

EQUIPMENT WITH MECHANICAL DUCTWORK, PIPING ETC. AND ASSURE WORKING

CLEARANCE REQUIRED BY NEC WILL BE MET. SUFFICIENT ACCESS AND WORKING

SPACE MUST BE PROVIDED AND MAINTAINED AROUND ELECTRICAL EQUIPMENT

AS REQUIRED BY THE NATIONAL ELECTRICAL CODE. CONTRACTOR MUST

COORDINATE FINAL LOCATION OF EQUIPMENT PROVIDED AND INSTALLED BY

OTHER TRADES.

STARTER MOUNTING: WHERE AN INDIVIDUALLY MOUNTED SAFETY SWITCH,

STARTER OR CIRCUIT BREAKER IS SHOWN ADJACENT TO ITS RESPECTIVE LOAD

AND NOT MOUNTED ON A WALL, PROVIDE ALL SUPPORTS, BRACKETS,

ANCHORING, ETC. NECESSARY TO PROPERLY SUPPORT THE DEVICE.

LIGHTING ARRANGEMENT: ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH

THE ARCHITECTURAL REFLECTED CEILING PLANS.

LIGHTING COORDINATION: COORDINATE LIGHTING FIXTURES WITH GRILLES,

DIFFUSERS, SPRINKLER HEADS, AND ACCESS PANELS, ETC. PROVIDE FIXTURE

MOUNTING BRACKETS, ACCESSORIES, PLASTER FRAMES, ETC.. SUITABLE FOR

THE CEILING TYPES INDICATED ON THE ARCHITECTURAL PLANS.

LIGHTING CONTROL TESTING: UPON COMPLETION OF THE INSTALLATION OF ALL

LIGHTING SYSTEMS AND CONTROL DEVICES, CONTRACTOR MUST CONFIRM

PROPER OPERATION OF ALL LIGHTING CONTROLS, AND DEMONSTRATE PROPER

OPERATION TO THE CONTRACTING OFFICER.

MATERIAL COORDINATION: VERIFY CEILING AND WALL CONSTRUCTION AND

MATERIAL PRIOR TO ORDERING LIGHT FIXTURES OR OTHER DEVICES TO INSURE

PROPER FIXTURE OR DEVICE IS FURNISHED TO MATCH CONSTRUCTION.

MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED

FLOOR TO THE CENTERLINE OF THE WIRING DEVICE UNLESS OTHERWISE NOTED.

MOUNTING HEIGHTS OF LIGHTING FIXTURES ARE TO THE BOTTOM OF THE

FIXTURE UNLESS OTHERWISE NOTED.

DEVICE LOCATIONS: COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES,

AND TELE/DATA OUTLETS WITH OTHER WALL MOUNTED DEVICES SUCH AS

THERMOSTATS AND CONTROL STATIONS.

MULTI-GANG JUNCTION BOXES: WHERE OUTLETS AND SWITCHES ARE SHOWN

ON PLAN TO BE INSTALLED ADJACENT TO EACH OTHER AND AT THE SAME

MOUNTING HEIGHT, THE DEVICES MUST BE INSTALLED IN A MULTI-GANG

OUTLET BOX, UON. THE SIZE OF THE OUTLET BOX MUST BE DETERMINED BY

THE NUMBER OF DEVICES AND CONDUCTORS THAT MUST BE INSTALLED IN

THE MULTI-GANG OUTLET BOX.

FIRE STOPPING: FOR ANY WALL PENETRATIONS THROUGH FIRE-RATED

STRUCTURES PROVIDE FIRE-STOPPING TO SEAL ALL THE PENETRATIONS AFTER

THE CONDUIT HAS BEEN INSTALLED. FIRE STOPPING FOR PENETRATIONS MUST

BE UL APPROVED PER THE PENETRATION MADE IN ORDER TO MAINTAIN

FIRE-RATED INTEGRITY OF THE STRUCTURE.

CLEAN UP: ON PROJECT CLOSE-OUT CLEAN ALL ELECTRICAL DEVICES, LIGHTING

FIXTURES, LENSES, AND REMOVE ALL PAINT SPATTERS FROM DEVICES,

FIXTURES AND PLATES. REPAIR ALL INOPERATIVE LIGHTING FIXTURES.

GROUND FAULT PROTECTION: RECEPTACLES LOCATED WITHIN 6'-0" OF THE

EDGE OF SINKS MUST BE PROVIDED WITH GROUND FAULT PROTECTION

WHETHER SHOWN OR NOT.

HVAC DAMPERS, ETC: CONTRACTORS MUST COORDINATE WITH THE EQUIPMENT

AND SYSTEM BEING PROVIDED AND PROVIDE POWER CONNECTIONS

ACCORDINGLY. THESE CONNECTIONS MUST BE FOR FIRE/SMOKE DAMPERS, DDC

CONTROL DEVICES, ETC. CONTRACTOR MUST COORDINATE THE VOLTAGE

REQUIREMENTS AND PROVIDE ALL NECESSARY CONNECTIONS, COMPONENTS,

ETC. THIS INCLUDES TRANSFORMERS, BOXES, ETC.

THE FOLLOWING SUBSCRIPTS MUST APPLY TO RECEPTACLES WHERE USED:

CONTRACTOR MUST PROVIDE AN APPROPRIATE LISTED THROUGH-PENETRATION FIRE STOPPING ASSEMBLY AT EACH PENETRATION OF FIRE RATED CONSTRUCTION (I.E. WALLS AND SLABS, ETC.). SLEEVES MUST ONLY BE PERMITTED WHERE INDICATED IN THE CONTRACTOR SELECTED THROUGH-PENETRATION FIRE STOPPING ASSEMBLY. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION OF ALL RATED ASSEMBLIES AND ASSOCIATED UL DESIGNATIONS. DEVICES INSTALLED RECESSED WITHIN FIRE RATED CONSTRUCTION (I.E. LIGHT SWITCHES, RECEPTACLES, ETC.) ARE ONLY PERMITTED WHEN AN APPROVED LISTED FIRE STOPPING SYSTEM EXISTS FOR THE APPLICATION. IF AN APPROVED LISTED FIRE STOPPING SYSTEM IS UNAVAILABLE, THE CONTRACTOR MUST BRING THE CONDITION TO THE ATTENTION OF THE A/E FOR RESOLUTION PRIOR TO PROCEEDING WITH WORK.

FIRE STOPPING NOTE:

AND

SWITCH RATING

NUMBER OF POLES

FUSE RATING (NF INDICATES NON-FUSED)

NEMA ENCLOSURE IF OTHER THAN NEMA 1

SPD

T

A

P

E

M

DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 18" AFF, UON

TWO DUPLEX RECEPTACLES IN COMMON BOX, EACH 20A, 120V, 46" AFF, UON

DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 46" AFF, UON (OR 6" ABOVE

COUNTER AS APPLICABLE)

· GFI: GROUND FAULT INTERRUPTING TYPE RECEPTACLE

· +XX": DEVICE MOUNTING HEIGHT DESIGNATION ABOVE FINISHED FLOOR IF OTHER

THAN 18" OR 46".

· WP: WEATHER RESISTANT GFI RECEPTACLE WITH WEATHERPROOF WHILE-IN-USE

COVER.

ABBREVIATIONS

A AMPERE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPERE INTERRUPTING CAPACITY

BFG BELOW FINISHED GRADE

C CONDUIT

CKT CIRCUIT

CB CIRCUIT BREAKER

DDC DIRECT DIGITAL CONTROL

EBU EMERGENCY BATTERY UNIT

EC EMPTY CONDUIT

EF EXHAUST FAN

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EWH ELECTRIC WATER HEATER

EXIST EXISTING

FLA FULL LOAD AMPS

GFI GROUND FAULT INTERRUPTER

GND GROUND

HP HORSE POWER/HEAT PUMP

KAIC THOUSAND AMPERE

INTERRUPTING CAPACITY

KVA KILO-VOLT-AMPERES

KW KILO-WATTS

LTG LIGHTING

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MIN MINIMUM

MLO MAIN LUGS ONLY

MTD MOUNTED

NEC NATIONAL ELECTRICAL CODE

NF NON-FUSED

NTS NOT TO SCALE

P POLE

PNL PANEL

PNLBD PANELBOARD

Ø PHASE

PRI PRIMARY

RECEPT RECEPTACLE

SE SERVICE ENTRANCE

SEC SECONDARY

SPD SURGE PROTECTION DEVICE

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLT

W WATTS/WIRE

WP WEATHERPROOF

REMOTE EMERGENCY BATTERY LIGHTS

WATTHOUR DEMAND METER: TO CONFORM TO BASE

STANDARDS. ITRON V&I CS3 SERIES METER.

METER NOTE:

FIRE ALARM/MASS NOTIFICATION CONTROL PANELFAMN

OVERHEAD DOOR CONTROL STATION (UP/STOP/DOWN), MOUNT 46" AFF.

VFD

FIRE ALARM TRANSMITTERFAT

THREE-WAY SWITCH, 20A, 120/277V, 46" AFF UON3

VACANCY SWITCH, 20A, 120/277V, 46" AFF UONV

DIMMER SWITCH, 0-10VDC, 46" AFF UOND

THREE-WAY DIMMER SWITCH, 0-10VDC, 46" AFF UOND3

01/24/2020

ChrisLife

E

O

P

EOP 7.2

EOP 7.2

E

O

H

S

EO

P 1

2.4

E O

P

E O

P

E

O P

E O

P

E O

P

.2

E O

P

.2

EOP 7.2

EOP 7.2

EXISTING POLE

UG TERM (15KV)

CONDUIT RISER (6" PVC)

GROUND

U S

T

U S

X

X

X

X

X

X

X

X

MDP

UP

UP

UP

UP

SPARE

PRIMARY IN DUCT

SPARE

SECONDARY

IN DUCT

HH

The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

TN

PN

SITE PLAN

SCALE: 1" = 10'-0"

10'

1" = 10'-0"

20'10'5'0'

US

UP

UNDERGROUND SECONDARY CIRCUIT

UNDERGROUND PRIMARY CIRCUIT

E12.47 EXISTING OVERHEAD PRIMARY CIRCUIT; 12.47 KV

ALUMINUM, BARE, 6201 ALLOY, 19 STRAND, 394.5 KCMIL, CODE

NAME CANTON

PAD MOUNTED TRANSFORMER

FRONT

T

TAP EXISTING OVERHEAD PRIMARY LINE, PROVIDE OVERHEAD TO

UNDERGROUND TRANSITION AND EXTEND PRIMARY TO PAD MOUNTED

TRANSFORMER. SEE POLE PHOTO THIS SHEET.

CUT AND PATCH ROAD AS REQUIRED FOR UNDERGROUND, CONCRETE

ENCASED DUCT.

EXISTING POLE

EOP 7.2 EXISTING OVERHEAD PRIMARY, 7.2 KV, SINGLE PHASE TO REMAIN

PANELBOARD - 208/120V, 3 PHASE, 4 WIRE

NOT TO SCALE

PAD MOUNTED

TRANSFORMER: 225 KVA,

12.47 KV TO 208/120 V, 3

PHASE, 4 WIRE

E12.47

U P

3 #2 EPR 15KV & 1 #2 COPPER NEUTRAL IN 5" PVC

CONDUIT AND ONE 5" PVC SPARE CONDUIT

CONCRETE ENCASED. SEE CONCRETE ENCASED

DUCTBANK - DETAIL 'A' SHEET ES502.

FUSED CUTOUTS: 100A

REMOVE EXISTING POLE MOUNTED TRANSFORMER, GUY AND

OVERHEAD SECONDARY TO EXISTING BUILDING BEING

DEMOLISHED. SEE POLE PHOTO THIS SHEET.

REMOVE EXISTING DIRECT BURIED, WOOD POLE.

REMOVE EXISTING DIRECT BURIED, WOOD POLE AND OVERHEAD

SERVICE DROP TO BUILDING BEING DEMOLISHED.

NOT TO SCALE

EOP 7.2 REMOVE EXISTING OVERHEAD PRIMARY, 7.2 KV, SINGLE PHASEX X

EXISTING POLE MOUNTED TRANSFORMER

EXISTING POLE GUY

POLE MOUNTED SURGE ARRESTOR WITH GROUND.

EXISTING STREET LIGHT

TO REMAIN

EOHS EXISTING OVERHEAD SECONDARY TO REMAIN

HANDHOLE, TYPE 1.

HH

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

POLE LINE MATERIAL LIST

FLAT STEEL BRACE (TWO PIECES)

MACHINE BOLT, 3/8" X LENGTH NEEDED WITH WASHER, NUT AND LOCKWASHER

8' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 3 1/2" X 4 1/2"

MACHINE BOLT, 5/8" X LENGTH NEEDED WITH WASHER, NUT AND LOCKWASHER

TIMBER CONNECTOR

LAGSCREW, 1/2" X 4"

ANGLE STEEL BRACE (TWO PIECES)

MACHINE BOLT, 1/2" X LENGTH NEEDED, WITH WASHER, NUT & LOCKWASHER

DEADEND BOX

STEEL PIN

PIN INSULATOR

GRID GAIN, USED ONLY WHEN THERE IS NO POLE GAIN

ANGLE STEEL BRACE (ONE PIECE)

10' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 3 1/2" X 4 1/2"

5/8" EYE NUT

5/8" EYE BOLT, LENGTH AS NEEDED, WITH WASHER, NUT & LOCKWASHER

EXTENSION LINK

BELL TYPE SUSPENSION INSULATOR WITH CONNECTING HARDWARE

STRAIN CLAMP

STEEL ANGLE PIN

CLUSTER MOUNTING BRACKET, STEEL

TRANSFORMER GROUNDING CONNECTION

STIRRUP

SECONDARY LEAD SUPPORT BRACKET

ADAPTER PLATE FOR CLUSTER MOUNTING

CLEVIS BRACKET FOR SPOOL INSULATOR

SPOOL INSULATOR

U BOLT CLAMP

PREFORMED GUY GRIP

GUY HOOK

GUY STRAIN INSULATOR

GUY WIRE, SIZE AS SPECIFIED

#4 WP CU. SOFT DRAWN GROUND WIRE

GROUND CLAMP

CONDUIT COUPLING

CONDUIT BEND

INSULATED BUSHING

PERFORATED STRAPPING, 1-1/2" WIDE

HOT LINE CLAMP

FUSED CUTOUT, AS SPECIFIED

SURGE ARRESTER, AS SPECIFIED

POLE TOP PIN (RIDGE PIN) - 24 INCHES LONG

CROSSARM ANGLE PIN

ANGLE POLE TOP PIN

WEATHERPROOF SOFT DRAWN WIRE-SIZE

T0 MATCH OR EXCEED AMPACITY OF CONNECTING

CABLE, OR

AT 125% OF TRANSFORMER FULL LOAD

CURRENT, BUT NOT LESS THAN NO. 4 AWG

(a)

(b)

OH-1.5

JUNE 2002SKETCH DATE STYLE

POLE LINE MATERIAL LIST

UNDERBUILD CIRCUIT

POSITION OF COMMON NEUTRAL

OR MULTIPLEX SECONDARY

CONDUCTOR

CIRCUIT

COMM.

PROVIDE 60" CLEARANCE WHEN OPERATING VOLTAGE OF UNDERBUILD

CIRCUIT IS GREATER THAN 15KV.

NOTE

FOR HORIZONTAL SPACING REQUIREMENTS FOR CONDUCTORS ON SAME SUPPORT,

REFER TO THE NATIONAL ELECTRICAL SAFETY CODE, IEEE C2.

1.

Ø-Ø VOLTAGE 0-15KV 15-50KV

SPACING A"

SPACING B"

40"

40"

48"

40"

OH-1.4

JUNE 2002SKETCH DATE STYLE

BASIC VERTICAL SPACING REQUIREMENTS

"B"

"A"

40" MIN.

DEDICATED

CLEAR SPACE

POSITION OF LOWEST POWER (SUPPLY)

ATTACHMENT SHALL BE NO LESS THAN

24'-4" ABOVE GRADE.

DEDICATED CLEAR SPACE BETWEEN

POWER (SUPPLY) AND COMMUNICATION

CIRCUITS.

POSITION OF HIGHEST

COMMUNICATION ATTACHMENT

SHALL BE NO HIGHER THAN

21'-0" ABOVE GRADE.

EXPLANATION OF SYMBOLS LISTED FOR POLE ON SKETCH OH-1.3

EXPLANATORY NOTES - METHOD OF SHOWING SYMBOLS

SYMBOLS ARE SHOWN IN THE BASIC ORDER AS THEY APPEAR ON THE

POLE, BY STARTING AT THE TOP AND WORKING DOWN.

NUMERALS PRECEDING THE SYMBOL INDICATE THE MINIMUM REQUIRED

VOLTAGE (KV) RATING (5,15,35) OF THE ASSEMBLY, IF APPLICABLE.

NUMERAL FOLLOWING THE SYMBOL INDICATES THE NUMBER OF CON-

DUCTORS ASSOCIATED WITH THE ASSEMBLY, IF APPLICABLE.

NUMERAL IN PARENTHESIS FOLLOWING THE SYMBOL DENOTES THE

NUMBER OF ASSEMBLIES REQUIRED, IF MORE THAN ONE.

DATA IN PARENTHESIS FOLLOWING THE SYMBOL PROVIDES

INFORMATION RELATIVE TO THE SYMBOL.

1.

2.

3.

4.

5.

PROVIDE 45 FOOT LONG, CLASS 3 POLE CONTAINING:

TF -

S1 -

SDE2 -

GROUND -

X-FB -

35FR3 -

X-FB -

15F3 -

8' CROSSARM WITH FLAT BRACE

35KV INSULATORS, FLAT (MOUNTED HORIZONTAL ON CROSS-

ARM), RIDGE PIN (CENTER PHASE ON POLE TOP PIN), THREE

CONDUCTORS

8' CROSSARM WITH FLAT BRACE

15KV INSULATORS, FLAT (MOUNTED HORIZONTAL ON CROSSARM),

THREE CONDUCTORS. NOTE: THIS SYMBOL CALLS FOR THREE

CROSSARM MOUNTED PINS IN LIEU OF RIDGE PIN ON CENTER

PHASE.

TRANSFORMER ON FLAT (HORIZONTAL) CONSTRUCTION. DATA

IN PARENTHESIS DESCRIBES THE TRANSFORMER CHARACTERISTICS.

GUY (5/16") -

SECONDARY, ONE CONDUCTOR, TANGENT CONSTRUCTION (COMMON

NEUTRAL).

SECONDARY DEADEND, TWO CONDUCTORS, OPEN WIRE

DOWN GUY - WIRE SIZE 5/16"

10" SCREW TYPE ANCHOR WITH 12 FT. GUY LEAD.

NOTE: NO PLATE IS INCLUDED FOR THE ANCHOR SYMBOL.

NO EXPLANATION NECESSARY

ANCHOR -

(10" SCREW)

OH-1.3A

JUNE 2002SKETCH DATE STYLE

EXPLANATION OF NOTES/SYMBOLS

13.2

34.5

S

N

13.2

N

34.5

PLAN VIEW

POLE # (45'-3)

X-FB, 35FR3

X-FB, 15F3

TF (25KVA, 13.2 GRD. Y/7.6 KV - 120/240 V.)

S1, SDE2

GUY (5/16")

ANCHOR (10" SCREW) (12' GUY LEAD)

GROUND

NOTES

THE SYMBOLS LISTED ABOVE

INCLUDE MATERIALS (DESCRIBED

BY OVERHEAD SKETCHES) WHICH

ARE GRAPHICALLY ILLUSTRATED

BY THIS PICTURE. SEE

SKETCH OH-1.3A FOR

EXPLANATORY NOTES.

EACH SKETCH CONTAINS

MATERIAL ITEMS WHICH COMPRISE

A PART OF EACH INDIVIDUAL

SYMBOL REFERENCED BY THAT

SKETCH, THESE ITEMS ARE

INDICATED BY CIRCLED

NUMERALS WHICH ARE IDENTIFIED

BY SKETCHES OH-1.5

AND OH-1.5A.

SPACING REQUIREMENTS RELATED

TO INDIVIDUAL COMPONENTS OF

A SYMBOL ARE INDICATED ON

THE APPROPRIATE SKETCH.

VERTICAL SPACING

REQUIREMENTS BETWEEN

CIRCUITS AND/OR SYSTEMS

ARE INDICATED ON SKETCH

OH-1.4. ALL OTHER

SEPARATIONS BETWEEN

CIRCUITS, EQUIPMENT, ETC.,

SHALL CONFORM TO THE

NATIONAL ELECTRICAL

SAFETY CODE, IEEE C2.

1.

2.

3.

OH-1.3

JUNE 2002SKETCH DATE STYLE

METHOD OF SHOWING SYMBOLS

POLE LINE MATERIAL LIST

TRI-MOUNT BRACKET

TERMINATOR

MOUNTING BRACKET

CABLE GRIP HANGER

HOSE CLAMP

STUD, 3/4" X 1-3/4"

LINE POST INSULATOR

TRIPLE INSULATOR BRACKET

ANGLE CLAMP

INSULATOR, LINE POST CLAMP

4' CROSSARM

CROSSARM GAIN BRACKET

PULLEY BRACKET

WEDGE CLAMP

MIDSPAN SERVICE CLAMP

STUD, 7"

SADDLE, ANGLE

SADDLE CROSSARM

FITTING, POLE TOP

CONNECTOR

SUSPENSION CLAMP

TIE, SERVICE CABLE

54" FIBERGLASS STRAIN INSULATOR

69 PVC RISER SHIELD

PVC EXTENSION SHIELD

PVC BACK PLATE

8' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 4 3/4" X 5 3/4"

10' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 4 3/4" X 5 3/4"

OH-1.5A

JUNE 2002SKETCH DATE STYLE

POLE LINE MATERIAL LIST

BACK-UP CURRENT LIMITING FUSE

ATTACHMENT

POSITION OF GUY

SEE NOTE 3

SIDE VIEW

FRONT VIEW

THIS POLE.

CONTINUES ON BEYOND

NEUTRAL LEVEL, IF

POLE

DEADENDS ON THE

NEUTRAL LEVEL, IF

NOTES

1.

2.

3.

23 39

41 48

41 48

16"

2"

4"

40"

21"

24"

19"

36"

OH-31

JUNE 2002

(0-25KV)

U.G. TERMINAL

SKETCH DATE STYLE

MODIFY POSITION OF TERMINAL ON DEADENDS TO BE UNDER THE CONDUCTORS AND THE CUTOUTS ON THE BACKSIDE OF

CROSSARM. POLE RISER MUST BE OFFSET TO CLEAR NEUTRAL CLEVIS BRACKET.

CONNECT BOTTOM LEAD OF ARRESTER DIRECTLY TO POLE GROUND. INTERCONNECT CABLE INSULATION SHIELD

DRAIN WIRES AND CONDUIT RISER GROUND TO MULTI- GROUNDED NEUTRAL (IF EXISTING) AND POLE GROUND.

CUTOUT PROVIDES A FUSE OR A SOLID BLADE (NON-FUSED) OPTION. COORDINATE

WITH SPECIFIC DESIGN REQUIREMENTS PROVIDED.

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

ROAD SIDE

DIRECTION

OF TRAFFIC

ADDITIONAL

GROUND RODS

(WHEN REQUIRED)

PLAN

ALWAYS CONNECT THE POLE GROUND

LEAD(S) DIRECTLY TO THE NEUTRAL-

ENSURE THAT THE COPPER CONDUCTOR

WILL ALWAYS BE BELOW THE ALUMINUM.

CONNECTOR

NEUTRAL

COPPERWELD STAPLES (TYP.)

GROUND

WIRE

POLE

ELEVATION

GROUND ROD

PLASTIC OR FIBER MOLDING

GALVANIZED STAPLES (TYPICAL)

FINISHED

GRADE

#4 BARE

COPPER

POLE

OH-41

JUNE 2002SKETCH DATE STYLE

GROUND

24"

MIN.

10'-0"

MIN.

10'-0"

MIN.

24"

12"

8'-0"

MIN.

18"

MAX.

8'-0 MIN.

(FROM 24'-4"

TO 16'-4"

ABOVE GRADE)

ALTERNATE GROUND WIRE

POSITION. (USE WHEN

MULTIPLE GROUNDING

SYSTEMS ARE REQUIRED.)

(SEE NOTE 4)

1.

2.

3.

NOTES

USE ADDITIONAL GROUND RODS, WHEN REQUIRED,

TO OBTAIN RESISTANCE VALUE, AS REQUIRED BY

IEEE C2.

MAKE GROUNDING CONNECTIONS TO ALL EQUIPMENT

ON POLE AS REQUIRED BY IEEE C2.

FOR SYSTEMS OTHER THAN 4 WIRE, MULTI-

GROUNDED, USE SEPARATE GROUNDING

CONDUCTORS AND ELECTRODES FOR PRIMARY

AND SECONDARY SYSTEM DEVICE CONNECTIONS.

#4 600V INSULATED COPPER GROUNDING

CONDUCTOR REQUIRED ON PRIMARY SYSTEM

WHEN SEPARATE SYSTEMS ARE REQUIRED.

4.

AF-1

APRIL 2015

GENERAL ARC FLASH WARNING LABEL

SKETCH DATE STYLE

NOTES:

1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARC

FLASH HAZARDS.

2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.

3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIED

PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE

EQUIPMENT.

4. THE SIZE OF THE LABEL SHALL BE MINIMUM:

EQUIPMENT TYPE HEIGHT WIDTH

INDOOR 2" 3"

OUTDOOR 3" 4.5"

5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING DESIGN GUIDE

WEBSITE (WWW.WDBG.ORG) FOR USE IN A LABEL MAKING MACHINE.

A. THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO NAVIGATE TO THIS

LOCATION, FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY >

NAVFAC CADD RESOURCES > NAVFAC CADD DETAILS.

B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER:

HTTP://WWW.WBDG.ORG/CCB/BROWSE_CAT.PHP?C=232

WIDTH

HEIGHT

(SEE NOTE 1)

SERVICE CAP

CLAMP TYPE

S E

C O

N D

A R

Y

C

O N

D U

C T

O R

N E

U T

R A

L

O

R

T

O P

GRADE

FINISHED

GALVANIZED STEEL CONDUIT-SIZE AS INDICATED

SEE NOTE 3

SEE NOTE 2

CONDUIT LOCATION

OF TRAFFIC

DIRECTION

ROAD SIDE

POSITION

RISER

ALTERNATE

POSITION

RISER

POLE

1.

2.

3.

DIRECT BURIED

CABLE

DIRECT BURIED

CONDUIT

TYPE C

OH-35

JUNE 2002

(SIZE & TYPE AS INDICATED)

CONDUIT RISER

SKETCH DATE STYLE

TYPE A

CONCRETE ENCASED

CONDUIT

TYPE B

18" MIN.

2"

MIN.

NOTES

ON CONDUIT RISER FOR PRIMARY CIRCUITS, ELIMINATE SERVICE CAP

AND PROVIDE GROUNDING TYPE INSULATING BUSHING.

BOND CONDUIT TO POLE GROUND AND SYSTEM NEUTRAL (IF EXISTING).

SEE GROUNDING NOTES ON SKETCH OH-41.

SPACE STRAPS AT MAXIMUM OF 4' INTERVALS.

1'-6" O.C.

3" MINIMUM

FINISHED GRADE

DUCTBANK MARKING TAPE

3000 P.S.I. CONCRETE

P.V.C. CONDUIT SIZE

AS INDICATED

LEVELING BLOCKS

AT BASE SPACERS

M

I N

EQUAL

EQUAL

3" MINIMUM

SEPARATION

(TYP.)

BASE SPACERS

(TYP.)

NOTE: # OF DUCTS SHALL BE AS INDICATED ON PLANS.

3"

SECONDARY

TRANSFORMER BOX, SEE DETAIL A THIS SHEET

GRADE

TERMINATIONS

LOW VOLTAGE CABLE

CURRENT TRANSFORMERS (800/5)

3-POLE FUSE BLOCK

SECONDARY CIRCUIT

WHD

#4/0 BARE

MIN

2'-0"

GRADE.

PAD. MIN 18" BELOW FINISHED

ENCIRCLING ENTIRE CONCRETE

#4/0 BARE COPPER GROUND LOOP

600V INSULATION

CORNER OF PAD.

OF 4, 1 AT EACH

GROUND ROD, TYP

GROUND PAD (TYP OF 2)

#4/0, 600V

INSULATION

PRIMARY CIRCUIT

CONNECTOR

LOAD BREAK

PRIMARY NEUTRAL

BUSHING INSERT

BREAK OIL SWITCH

2 POSITION LOAD

CURRENT-LIMITING

OIL-IMMERSED

PRIMARY COMPARTMENT

ARRESTERS

SURGE

TRANSFORMER

BUSHING WELL

X0

BAYONET OIL-IMMERSED

EXPULSION FUSES

FUSES

CABLE WELL

TRANSFORMER BOX, SEE DETAIL THIS SHEET.

G

G

G

G

GROUND ROD - 3/4" x 10' CONNECT

TO CONDUCTORS BY EXOTHERMIC

WELD (TYP)

PAD MOUNTED COMPARTMENTAL TYPE

TRANSFORMER (SECURE TO TRANSFORMER

BOX PER MANUFACTURER'S

RECOMMENDATION).

SECONDARY NEUTRAL GROUND NO.

4/0 AWG CU MINIMUM

TRANSFORMER

SECTION

EXOTHERMIC WELD (TYP)

EQUIPMENT GROUND

OUTGOING SECONDARY CONDUIT(S)

(NUMBER AS NOTED ON PLANS)

PRIMARY CONDUIT

NUMBER AS NOTED ON

PLANS

EXTEND GRAVEL FILL A

MINIMUM OF ONE FOOT

BEYOND PAD ON ALL SIDES.

WELL COMPACTED GRAVEL

SUBSURFACE SHALL BE 6

INCHES THICK

EXTEND PAD A MINIMUM OF 8

INCHES BEYOND UNIT ON ALL

SIDES

PAD MOUNTED TRANSFORMER DETAIL

NOT TO SCALE

TYPICAL PAD MOUNTED COMPARTMENTAL TRANSFORMER DETAIL

NOT TO SCALE

COMPARTMENT

X10" 10"

6"

9"

18"

2-1/2"

18"

29"

29"

5"

18"

TRANSFORMER BOX DETAIL

(DETAIL BASED ON PARKER BUMPER COMAPNY STANDARD DETAILS)

A

CONCRETE ENCASED DUCTBANK - DETAIL 'A'

NOT TO SCALE

CONNECTOR

LOOP FEED

WATTHOUR DEMAND METER: TO

CONFORM TO BASE

STANDARDS. ITRON V&I CS3

SERIES METER.

EW, SIDES

#4 @ 12"

ANGLE FRAME

WELDED TO

5/8" Ø ANCHOR ROD

A

A

A

(COVER NOT SHOWN)

ANCHORS

A

6"

6"

DUCT ENTRANCE

PLAN

PULLING-IN IRON

7/8" Ø

A

A

6"

& CLAMP

GROUND ROD

TO SUMP

SLOPE 1:40

6"

DUCT ENTRANCE

SECTION A-A

A

COVER

ANCHOR

HANDLE

SECTION B-B

SECTION OF FRAME

1/8"

1 3/4"

3/4"

5" X 5" HINGE

RAISED PATTERN

1/2" FLOOR PL.

L 2 1/2 X 2 1/2 X 3/8

1/2"Ø PLUG WELD

1 3/4" X 1 1/2" X 1/2"

AS SHOWN

CUT HINGE PLATE

1/8"

1 1/4"

SEAL DETAIL

SIDE OF THE DOOR

WELDED TO ONE

2 1/2" X 3/8" SEAL

1/2" PLUG WELD

5"

PLAN OF COVER

B

& COVER

HINGE-WELDED TO FRAME

B

PATTERN

1/2" FLOOR PLATE RAISED

HANDHOLE DIMENSIONS

TYPE

A

3'-0"

1/2" PLUG WELDS

@ 8" O.C. MAX.

12" X 12" X 12"

DEEP SUMP

7/8" Ø

PULLING-

IN IRONS

SEAL, SEE

DETAIL ABOVE

6"

6"

6"

2 4'-0"

(3 PER SIDE)

AND BOTTOM

NOTES:

FOR DETAILS OF CABLE RACKS,

DUCT ENTRANCE AND PULLING-IN

IRONS, SEE PLATE UG-7.

MINIMUM CONCRETE COMPRESSIVE

STRENGTH SHALL BE 3000 PSI.

1.

2.

FLAT PLATE

WATERSTOP AT ALL

CONSTR. JTS. (TYP.)

UG-4

JUNE 2002

TYPES 1 & 2

STANDARD ELECTRICAL HANDHOLE (NONTRAFFIC)

SKETCH DATE STYLE

WALL OF MANHOLE

TYPICAL CABLE RACK

TYPICAL DUCT ENTRANCE

DUCT

INSIDE FACE

OF MANHOLE

45°

3"

DETAIL OF PULLING-IN IRON

7" MIN.

7" MIN.

8 3/8"

7/8"Ø

9"

CAST IN PLACE

3"

1 1/2"

CONCRETE WALL

LOCKWASHER

FILLET WELD

2 1/2"Ø WASHER

6 1/2" X 2 1/2" X 3/16" PLATE

ALTERNATE METHOD

C

L

(MIN)

2 1/2" RAD

1"Ø U-BOLT

1"Ø NUT

1 1/4"Ø SLEEVE

13/16"

3/16"

4"

NOTE

ALL METAL PARTS SHALL

BE HOT DIP GALVANIZED

UG-7

JUNE 2002

(PULLING-IN IRONS, CABLE RACK AND DUCT ENTRANCE)

DETAILS

SKETCH DATE STYLE

A B C D E

LA-7

D3

D3 D3 D3a

Da

V

V

D

D3a

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

C

C

C

C

B

C

C

C

E

D

E

EE

E

E

E

E

E

E

E

E

D

D

D

E

E

D

D

D

D

D

LA-3

MDP LA

LA-3

LA-5 1

LA-1, 2 #10, 1

#10GND - 3/4"C.

P

TC INV

INV

a a a a a a aa a a

V

V

V

V

V

V

The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

TN

PN

FLOOR PLAN

SCALE: 3/16" = 1'-0"

3/16" = 1'-0"

0' 5' 10' 20'

STYLE NO. & TYPE VOLTAGE MOUNTING

NOTES

FIXTURE

SYMBOL

TYPE

OF LAMPS

LED UNIVERSAL

SURFACE; CEILING

PENDANT; 2'-0" BELOW ROOF DECK

LEDNL-11, 4', 4000 LUMENS, 3500K, 29W UNIVERSAL

LED UNIVERSAL

LIGHTING FIXTURE SCHEDULE

NL-67 WALL MOUNTED, 12'-0" A.F.F.

PROVIDE FIXTURE WITH WHITE HOUSING. PROVIDE SINGLE FACE, BACK MOUNTED, RED LETTERING PROVIDE

BATTERY COMPATIBLE WITH REMOTE HEADS.

PROVIDE FIXTURE WITH WHITE HOUSING AND VOLTMETER.

PROVIDE TWO HEADS, VOLTAGE SHALL MATCH EBU, WHITE POLYCARBONATE HOUSING.

DOOR LIGHT

LED UNIVERSAL

WALL, 7'-6" AFF

BUILDING LIGHT

LED UNIVERSAL

WALL; 18' AFF

NL-63

LED UNIVERSAL

WALL MOUNTED, 18" ABOVE DOOR.

A

B

D

E

NL-7, 4', 4504 LUMENS, 3500K, 32W

SEE DETAIL E501

SEE DETAIL E501

LED UNIVERSALNL-54, TYPE E WALL MOUNTED, 9" ABOVE DOOR 3

ROUTE CIRCUIT THROUGH LIGHTING INVERTER, WHEN IN EMERGENCY MODE

ALL LIGHT FIXTURES IN ROOM SHALL BE AT 100% LIGHTING LEVEL.

ROUTE CIRCUIT THROUGH PHOTOCELL AND TIME CLOCK. CONTROL SHALL

BE PHOTOCELL ON/TIME CLOCK OFF.

NOTES THIS SHEET

01/24/2020

RECESSED; CEILINGLEDNL-3, 2X4, 4000 LUMENS, 3500K, 32W UNIVERSAL

C

60025498
60025499
60025500