N4008519B0094 DWG_Part3.pdf

PDF 8 MB Posted

Attached to
Construct EOTG PEB
Solicitation number
N4008520R4057
Issued by

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2"

AC-1

1"

(TYP.)

The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

TN

PN

SITE PLAN

SCALE: 1" = 10'-0"

10' 1" = 10'-0"

20'10'5'0' 01/24/2020

NEW WORK NOTES

PROVIDE 1000 GALLON PROPANE TANK, CONCRETE PAD, AND BOLLARDS COMPLETE.

SEE CIVIL DRAWINGS FOR BOLLARD REQUIREMENTS.

PROVIDE AIR COOLED CHILLER AND CONCRETE PAD WITHIN FENCED ENCLOSURE

COMPLETE. SEE CIVIL DRAWINGS FOR CONTINUATION.

PROVIDE UNDERGROUND CHILLED WATER PIPING, INSULATION, AND SUPPORTS

COMPLETE. PROVIDE HEAT TRACING FOR EXPOSED PIPING.

PROVIDE 2" TAP WITH BUTTERFLY VALVE AND BLIND FLANGE FOR EMERGENCY

CHILLER CONNECTION.

PROVIDE 1" MAKEUP WATER PIPING. PROVIDE HEAT TRACING FOR EXPOSED PIPING.

CONNECT TO AIR SEPARATOR AT CHILLER.

REFER TO EXTERIOR PIPE SUPPORT DETAIL.

A B C D E

AHU-1

VAV-1VAV-2

VAV-4

VAV-5

VAV-10

VAV-8

VAV-7

VAV-9

VAV-6

B-2

B-1

1 (TYP.)

SHWP-2

SHWP-1

VAV-3

B

B

B

A

A

A

A

A

A

A

A

A

A 200A

A

A

A

A

A

24x22 20"Ø 12"Ø

8"Ø

6"Ø

8"Ø

8"Ø

12x10

10"Ø14"Ø

"Ø

"Ø

8"Ø

"Ø

"Ø

10"Ø

14"Ø

"Ø

HWR

HWS

HWR

HWS

HWR

HWS

HW

R HW

S

HW

R HW

S

HW

R HW

S

1-1/2"

1" 1" 3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

7 (TYP.)

7 (TYP.)

3 (TYP.)

3 (TYP.)

26x26

20x18

Z

X

U

U

V

YY

L-1

P

TO INCOMING

LP SERVICE

HW

S HW

R

CW

S

CW

R

1"

2"

ET-1

DSS-2B

DSS-1B

DSS-1A

CHEMICAL FEED TANK

EB

EB

7 (TYP.)

T

TTT

VAV-10

VAV-1/2/3/4/5

TT

T

VAV-8

T VAV-9

T

VAV-7

T

VAV-6

T

DDC

VFD

VFD

AS-1

6 8

S

5(TYP.)

8"Ø

3/4"

10x10

XDSS-2A

T

A

A

10"Ø10"Ø

A

A

A

A

10"Ø14"Ø

A

A

A

A

10"Ø14"Ø

"Ø

WW

M

30x30

RS

/R

L

RS

/R L

D

C

C

EB

S

LP

EF-114

L-2

2"

UH-115

T T

UH-1

EF-1

L-316

D

M

M

EB

EB

B

B

B

8x10

B

B

B

6x10

8"Ø

T

T

T

T

TN

PN

FLOOR PLAN

SCALE: 3/16" = 1'-0"

3/16" = 1'-0" 0' 5' 10' 20'

NEW WORK NOTES

PROVIDE VAV TERMINAL UNIT, THERMOSTAT, CONTROL WIRING, HANGERS, AND SUPPORTS

COMPLETE.

PROVIDE AIR HANDLING UNIT AND 4" CONCRETE HOUSEKEEPING PAD SUITABLE FOR UNIT

DIMENSIONS COMPLETE.

PROVIDE HWS/HWR PIPING, INSULATION, JACKETING, HANGERS, AND SUPPORTS COMPLETE.

ROUTE PIPE AS HIGH AS POSSIBLE.

PROVIDE BOILER COMPLETE.

PROVIDE DUCT MOUNTED GRILLE COMPLETE.

PROVIDE FIRE DAMPER COMPLETE. REFER TO DETAIL ON SHEET M-502.

PROVIDE DUCTWORK, INSULATION, HANGERS, AND SUPPORTS COMPLETE. ROUTE DUCT AT 12'

AFF. COORDINATE COLOR OF EXPOSED DUCTWORK WITH COTR.

PROVIDE ACCESS DOOR IN DUCTWORK FOR FIRE DAMPER AT INDICATED LOCATION.

PROVIDE CWS/CWR PIPING, INSULATION, JACKETING, HANGERS, AND SUPPORTS COMPLETE.

ROUTE PIPE AS HIGH AS POSSIBLE INSIDE MECHANICAL ROOM. SEE SHEET MS101 FOR

CONTINUATION.

PROVIDE SLEEVES AT PIPING THROUGH EXTERIOR WALL. REFER TO DETAIL ON SHEET M-502.

PROVIDE GAS PIPING, HANGERS, AND SUPPORTS COMPLETE. ROUTE PIPE AT 9' AFF.

PROVIDE 3" CONCENTRIC VENT UP THROUGH ROOF, HANGERS, AND SUPPORTS COMPLETE.

PRESSURE REGULATOR PROVIDED BY PROPANE PROVIDER.

PROVIDE WALL EXHAUST FAN, THERMOSTAT, CONTROL WIRING, HANGERS, AND SUPPORTS

COMPLETE.

PROVIDE GAS FIRED UNIT HEATER, THERMOSTAT, CONTROL WIRING, HANGERS, SUPPORTS, AND

3" CONCENTRIC VENT KIT COMPLETE.

MOUNT LOUVER AT 10' ABOVE FINISHED FLOOR. PROVIDE BAROMETRIC RELIEF DAMPER SET TO

OPEN AT 0.05" W.G. INTERNAL BUILDING PRESSURE.

PROVIDE DIFFERENTIAL PRESSURE SENSOR FOR HEATING WATER FLOW CONTROL. PROVIDE

ISOLATION VALVES AND P/T PORTS ON EACH SIDE OF SENSOR.

MOUNT TRANSFER GRILLE ABOVE CEILING AT 12' ABOVE FINISHED FLOOR.

The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

01/24/2020

The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

01/24/2020

TURNING VANES,

SINGLE THICKNESS

ELBOW

TEE

MAIN DUCT

45°

45°

W

SA/OA

RA/EA

L = 1/4W

L (4" MIN.)

BRANCH DUCT

BALANCING DAMPER (B.D.)

W

USE ONLY WHERE RECTANGULAR RUN-OUTS ARE INDICATED ON DRAWINGS

SA/OA

RA/EA

MAIN DUCT

BRANCH DUCT

BALANCING DAMPER (B.D.)

USE ONLY WHERE ROUND RUN-OUTS ARE INDICATED ON DRAWINGS

ROUND

RECTANGULAR

L (4" MIN.)

L = 1/4W

DRAIN PAN TRAPPING FOR SECTION UNDER

NEGATIVE PRESSURE:

L = H + J + PIPE DIAMETER WHERE:

H = 1 INCH FOR EACH INCH OF NEGATIVE

PRESSURE PLUS 1 INCH

J = 1/2 H

DRAIN PAN TRAPPING FOR SECTION UNDER

POSITIVE PRESSURE:

L = H + J + PIPE DIAMETER WHERE:

H = 1/2 INCH (MINIMUM)

J = 1/2 INCH PLUS THE UNIT POSITIVE

STATIC PRESSURE AT COIL DISCHARGE

(LOADED FILTERS)

CLEANOUT (TYP. FOR 2)

DRAIN LINE SHALL BE AT LEAST

THE SAME SIZE AS THE NIPPLE

ON THE DRAIN PAN

PITCH DOWN TOWARD

DRAIN, ROUTE AS

INDICATED ON PLAN

DRAIN PANL

J

H

PROVIDE (3) 1/4"Ø VENT HOLES

PRESSURE GAUGE -

0 - 30 PSIG RANGE

CHILLER

MANUAL

AIR VENT

FLOW SWITCH

2" CWR

2" CWS

SUPPORT FROM STRUCTURE

ABOVE

THREADED ROD (TYPICAL)

STEEL ANGLE

NUT WITH LOCK WASHER

(TYPICAL)

METAL HANGER STRAP

SECURE TO BOTTOM AND

SIDES OF DUCT WITH SHEET

METAL SCREWS

NOTE: FOR ANGLE SIZE AND HANGER STRAP GAUGE, SEE SMACNA

LOW PRESSURE DUCT CONSTRUCTION STANDARDS.

SUPPORT FROM

FLOOR OR ROOF

STRUCTURE ABOVE3/8" THREADED

ROD

CLEVIS HANGER (SIZE

AS REQUIRED)

SUPPORT FROM

FLOOR OR ROOF

STRUCTURE ABOVE

BOLT AND CLAMPING

NUT (TYP.)

STEEL PIPE

STRAP

1-5/8" x 1-5/8" x 12

GAUGE STEEL CHANNEL

INSULATION SADDLE

3/8" THREADED ROD

LENGTH AS REQUIRED

INSULATION SADDLE (TYP)MULTIPLE PIPE RUNS

SINGLE PIPE RUN

6"

SECTION

PLAN

EDGE OF CHILLER

6"

6"6"

GRADE

45° CHAMFER

WWF 6 X 6 - W 2.9 X 2.9

TOP SHALL BE LEVEL

8"

2" M

IN

1' -6

STRAIGHT LENGTHS OF UNOBSTRUCTED PIPE

WITHOUT INLINE APPURTENANCES SHALL BE

INSTALLED UP AND DOWNSTREAM OF FLOW

CONTROL BALANCING VALVES PER

MANUFACTURER'S INSTALLATION

INSTRUCTIONS.

THERMOMETER 0 - 200°

F (TYP. OF 2)

3/4" DRAIN VALVE WITH

HOSE CONNECTION

FLOW CONTROL

BALANCING VALVE

PRESSURE GAGE TAP WITH CAP

AND PET COCK (TYP.)

COIL

MANUAL AIR VENT

PROVIDE VIBRATION

ISOLATING FLEXIBLE PIPING

CONNECTOR (TYP. FOR 2)

SUPPLY MAIN

RETURN MAIN

MANUAL BALANCING

VALVE W/TAPS

CONDENSATE DRAIN

TRAP. SEE DETAIL3/4" DRAIN VALVE W/

HOSE CONNECTION

DRAIN

DRAIN PAN

MANUAL AIR VENT

THERMOMETER, 30°- 75°F

RANGE (TYP)

PRESSURE GAGE TAP W/

CAP & PET COCK (TYP)

PROVIDE VIBRATION

ISOLATING FLEXIBLE PIPING

CONNECTOR (TYP. FOR 2)

NOTES:

1. ARRANGE PIPING TO PERMIT REMOVAL OF COIL.

2. MANUAL BALANCING VALVES SHALL BE INSTALLED IN

CONFORMANCE WITH VALVE MANUFACTURER'S RECOMMENDED

SPACING UP AND DOWNSTREAM FROM PIPE CHANGES IN

DIRECTION AND/OR OTHER VALVES AND COMPONENTS IN THE PIPING SYSTEM.

APPROX.

46"

THERMOSTAT/

TEMPERATURE SENSOR,

MOUNTED CENTERLINE WITH

ADJACENT WALL SWITCHES

FINISHED FLOOR

WALL SWITCH

T

WALL FRAMING (TYP.)

2" CWS/CWR

AC-1

THERMOMETER

0°-100°F RANGE (TYP.

FOR 2)

NC

2" OUTDOOR

TEMPORARY CHILLER

CONNECTION

NC

2" CWS/CWR

FLOW SWITCH

UNDERGROUND

FLEXIBLE CONNECTOR (TYP.)

3-WAY CONTROL VALVE

3-WAY CONTROL VALVE

BY-PASS SQUARE HEAD

COCK

4" ALL AROUND UNIT

45° CHAMFER

FINISHED

FLOOR 6/6 WIRE

MESH

EQUIPMENT

4"

3/4"

UNDERGROUND POLYETHYLENE PIPING

FLOORGRADE

NOTES:

1. PROVIDE PRESSURE REGULATOR FOR ALL UNITS.

2. TOTAL LOAD = 340 MBH.

3. GAS PIPING SIZED PER TABLE 402.4(4) OF THE 2015

INTERNATIONAL FUEL GAS CODE FOR SCHEDULE 40

PIPE. TOTAL DEVELOPED LENGTH: 100 FEET.

3/4"(TYP.)

(340 MBH)

PLUG VALVE (TYP.)

APPROX. 1000 GALLON PROPANE TANK

(BY PROPANE SUPPLIER) AND

CONCRETE PAD (BY CONTRACTOR).

TANK SHALL BE LOCATED MINIMUM 25'

FROM THE BUILDING AND 10' FROM

TRANSFORMER.

WALL SLEEVE

PAINTED STEEL PIPING

2ND STAGE REGULATOR, 2 PSIG,

SHUTOFF VALVE AND FLEXIBLE

PIPE CONNECTOR

1ST STAGE REGULATOR, 10-20

PSIG, SHUTOFF VALVE AND

FLEXIBLE PIPE CONNECTOR

PROPANE VENDOR SHALL FURNISH AND INSTALL L.P. GAS TANK, FIRST AND SECOND STAGE

REGULATORS, PIPING AND ASSOCIATED APPURTENANCES UP TO AND INCLUDING GAS COCK AT

BUILDING ENTRANCE. CONTRACTOR SHALL FURNISH CONCRETE PAD SIZED IN ACCORDANCE WITH ACTUAL PROPANE TANK PROVIDED, AND INSTALL GAS PIPING AND NECESSARY CONNECTIONS FROM

GAS COCK TO INDOOR EQUIPMENT. SEE PROPANE FLOW DIAGRAM, THIS SHEET.

PROPANE NOTE:

MECHANICAL 108

EXTERIOR WALL

B-1

(155 CFH)

B-2

(155 CFH)

APPLY CAULKING OR METAL-FAB MST

TAPE WHERE VENT PASSES THRU

FLASHING

APPLY THICK RING OF CAULKING OR

METAL-FAB MST TAPE AROUND VENT

AS SHOWN

MAINTAIN CLEARANCE THRU

COMBUSTIBLE JOIST AREA

PITCHED ROOF

FLASHING

CONCENTRIC VENT

MIN 2'-0"

ABOVE ROOF

OR ANY PART

OF BUILDING

WITHIN 10'

10'

REGULATOR (TYP.)

CHECK VALVE

MANUAL FLOW

CONTROL

BALANCING VALVE

NEEDLE VALVE - N.O.

(CLOSE FOR PUMP

SUCTION PRESSURE)

PRESSURE GAUGE 0 - 120

PSIG RANGE

IF PUMP SUCTION AND

DISCHARGE FLANGES

ARE TAPPED, USE

THESE POINTS FOR

PRESSURE GAUGE

CONNECTIONS

BALL VALVE - N.C.

(OPEN FOR PUMP

SUCTION)

STRAIGHT LENGTHS OF UNOBSTRUCTED PIPE WITHOUT INLINE APPURTENANCES

SHALL BE INSTALLED UP / DOWNSTREAM OF FLOW CONTROL BALANCING VALVE

PER MANUFACTURER'S INSTALLATION INSTRUCTIONS

BALL VALVE

UNION

CONCENTRIC REDUCER

MOTOR

PUMP

CONCENTRIC REDUCER

UNION

BALL VALVE

PIPE SUPPORT DETAILS

SCALE: NO SCALE M-501E CONDENSATE DRAIN TRAP DETAIL

SCALE: NO SCALE M-501F CHILLER PAD TYPICAL DETAIL

SCALE: NO SCALE M-501G

PROPANE FLOW DIAGRAM

SCALE: NO SCALE M-501A INLINE CENTRIFUGAL PUMP DETAIL

SCALE: NO SCALE M-501B CHILLED WATER COIL PIPING DETAIL

SCALE: NO SCALE M-501C AIR HANDLER UNIT HOT WATER COIL PIPING DETAIL

SCALE: NO SCALE M-501D

CHILLER PIPING DIAGRAM

SCALE: NO SCALE M-501H CONCRETE PAD DETAIL - INTERIOR

SCALE: NO SCALE M-501I

CONCENTRIC VENT DETAIL

SCALE: NO SCALE M-501L TYPICAL BRANCH CONNECTION

SCALE: NO SCALE M-501M DUCT SUPPORT DETAIL

SCALE: NO SCALE M-501N DUCTWORK FITTING DETAIL

SCALE: NO SCALE M-501O

CHILLER PIPING DIAGRAM #2

SCALE: NO SCALE M-501J SWITCH/THERMOSTAT MOUNTING HEIGHT DETAIL

SCALE: NO SCALE M-501K

VENTILATION AIR COMBUSTION

AIR

UH-1

(30 CFH)

BY-PASS SQUARE HEAD

COCK

M

PROVIDE 120 VAC

MOTORIZED GAS VALVE.

INTERLOCK WITH

EMERGENCY GAS

SHUTOFF SWITCH.

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

01/24/2020

CONTINUE UP TO

STRUCTURAL ROOF

SUPPORT. PROVIDE

INTERMEDIATE

SUPPORTS AS REQUIRED

SPRING VIBRATION

ISOLATOR (TYP.)

NUT & LOCK WASHER

TOP AND BOTTOM

SUPPORT LUGS

(IF PROVIDED)

EQUIPMENT

CHANNEL

C3x6

NUT & LOCK

WASHER TOP

AND BOTTOM

1/2" THREADED

ROD (TYP.)

THERE IS A 36 INCH CLEARANCE RESTRICTION ON SIDE OF VAV BOX

FOR SERVICE ACCESSIBILITY. THERE SHALL BE NO SPRINKLER PIPE,

LIGHTS, WALLS, ETC. WITHIN THAT AREA.

ALLOW 48 INCH OF STRAIGHT DUCT DOWNSTREAM OF UNIT BEFORE

FIRST RUNOUT.

PROVIDE THREE-WAY VALVE FOR VAV-8 AND VAV-10.

MIN. LENGTH OF STRAIGHT DUCT BETWEEN VAV BOX INLET AND 1st

UPSTREAM ELBOW OR REDUCER NOT LESS THAN 4 DUCT DIAMETERS

PRIMARY

AIR FLOW

PRIMARY AIR DUCT

AIR VALVE/DAMPER

SIZE AS INDICATED

REDUCER

NOTES:

2.

1.

DDC CONTROL BOX

36" SERVICE CLEARANCE

SIZE AS INDICATED

TRANSITION AS REQUIRED

3/4" DRAIN VALVE WITH HOSE

CONNECTION ON LOWEST PIPE

AUTOMATIC AIR VENT WITH SHUTOFF COCK

HWS

HWR

SET SLEEVE IN WALL AND

ANCHOR DURING WALL

CONSTRUCTION

ESCUTCHEON PLATES

(BOTH SIDES WHERE

EXPOSED)

INSULATION

PIPE

PACK WITH FIBERGLASS

AND SEAL BOTH SIDES

PIPE SLEEVE

WALLSET SLEEVE IN WALL

AND ANCHOR DURING

WALL CONSTRUCTION

ESCUTCHEON PLATE

(WHERE EXPOSED)

WATERPROOF

SEALANT

BACK-UP

MATERIAL

EXTERIOR INTERIOR

ANCHOR

PIPE

PIPE SLEEVE

WALL

INSULATION

PIPE WITH HEAT

TAPE

INSULATION AND

METAL JACKET (TYP)

GALVANIZED PIPE EXTENSION

-LENGTH AS REQUIRED (TYP)

3/8"Øx4" LONG GALVANIZED

BOLT SET IN CONCRETE (TYP)

1/4" THICK GALVANIZED

PLATE (TYP)

24"x12"x4" THICK CONCRETE

SUPPORT PAD

PIPE STANCHION SADDLE

(MSS-SP-69 TYPE 37) (TYP)

GRADE

ELECTRICAL POWER

CONNECTION, 120 VOLTS

HEATING CABLE

TEMPERATURE

CONTROLLER PIPING

WRAP WITH ELECTRIC HEATING CABLE

TO PROVIDE 8 WATTS/FOOT

PROVIDE MANUFACTURER'S

RECOMMENDED

ATTACHMENTS AT 6" O.C.

PIPE INSULATIONALUMINUM

JACKET

STAINLESS STEEL

HOSE CLAMP

4" THICK CONCRETE

PAD (16" x 16")

APPROX. 15"

APPROX. 10"

5 GALLON MINIMUM

CAPACITY

HOSE BIBB

BALL VALVE

3/4" TO PUMP SUCTION

3-1/2" MIN. OPENING

3/4" TO PUMP DISCHARGE

BALL VALVE

PLUGGED CROSSES (TYP.)

TWIST OFF PRESSURE CAP

TWO-WAY VALVE (UON)

NOTE: VERTICAL FIRE DAMPER INSTALLATION SHOWN.

HORIZONTAL FIRE DAMPER INSTALLATION SIMILAR EXCEPT

FIRE DAMPER SHALL INCLUDE NEGATOR SPRING CLOSURE

MECHANISM.

IF DUCTWORK IS LINED,

INTERRUPT LINER AT

FIRE DAMPER AND

PROVIDE EXTERIOR

INSULATION

EXTERIOR

INSULATION (TYP)

6" EACH SIDE (MAX.)

WHERE THE WALL IS NON-

SOLID METAL OR WOOD

STUD, OPENING TO BE

LINED WITH FIRE RESISTIVE

MATERIAL OF RATING EQUAL

TO THAT OF THE WALL

RETAINING ANGLES - MIN. 1 1/2" x 1 1/2" x 16 GA. ALL 4

SIDES. OVERLAP STRUCTURAL OPENING A MIN. OF 1" AND

COVER CORNERS OF OPENINGS

PLAIN "S" SLIP CONNECTION OR OTHER APPROVED

CONNECTION TO BE USED FOR DAMPER / DUCT

BREAKAWAY CONNECTION. (TYP) CONNECTION

SHALL BE CONSISTENT WITH DUCT PRESSURE

CLASSIFICATION

CLEARANCE - 1/8" PER LINEAR FOOT - BOTH DIMENSIONS

PROVIDE ACCESS DOOR LARGE ENOUGH TO PERMIT

MAINTENANCE AND RESETTING OF FIRE DAMPER

U.L. APPROVED FIRE DAMPER, 1 1/2 HOUR RATING,

STYLE B, 165 °F FUSIBLE LINK (REPLACEABLE)

STEEL SLEEVE

CLEARANCE - 1/8" PER LINEAR FOOT - BOTH DIMENSIONS

WHERE WALL IS CONCRETE, MASONRY OR SOLID

METAL STUD FRAMING, NO LINING IS REQUIRED

SECURE RETAINING ANGLES TO SLEEVE ONLY ON 8"

CENTERS WITH 1/4" BOLTS AND NUTS, OR No 10 STEEL

SCREWS OR MIN. 3/16" STEEL RIVETS, OR 1/2" LONG

WELDS

NOTCHED PIECE

BENT DOWN

A-A

CEILING

RUNNER

METAL STUD

FRAMING SHOWN

FLOOR

RUNNER

DETAIL A-A

24"

O.C. MAX

CEILING

RUNNER

FLOOR

RUNNER

24"

O.C. MAX

12" 1. FRAME WALL OPENINGS AS SHOWN IN FIGURE 1 OR

2.

2. DOUBLE VERTICAL STUDS ARE NOT REQUIRED FOR

OPENINGS 36"W x 36"H OR SMALLER.

3. ALL CONSTRUCTION AND FASTENERS MUST MEET

THE REQUIREMENTS OF THE APPROPRIATE WALL

DESIGN AND/OR LOCAL CODES.

4. IN WOOD CONSTRUCTION, FIRE RATED GYPSUM

WALL BOARD MUST COVER ALL WOOD STUD

SURFACES.

24" O.C. MAX

(METAL STUD)

2"

FIGURE 1

FIGURE 2

MASTIC ALL

AROUND

PREMOLDED ONE

PIECE PVC INSULATED

FITTING COVER

INSULATION

WHERE REQUIRED

TAPE FITTING COVER

TO INSULATION

BARRIER AS REQUIRED FIRE WALL (SEE

ARCHITECTURAL)

U.L. LISTED FILL, VOID OR

CAVITY MATERIAL FOR USE IN

THROUGH PENETRATION FIRE

STOPS.

PIPE DIMENSIONS VARY

AS SHOWN ON PLANS

METAL SLEEVE GROUTED

TIGHTLY IN CMU WALL

1 OR 2 HOUR WALL PENETRATION PIPING DETAIL

SCALE: NO SCALE M-502B

FIRE DAMPER INSTALLATION DETAIL (VERTICAL) FRAMING FOR OPENINGS IN WOOD AND METAL STUD WALL

SCALE: NO SCALE M-502C

SUSPENDED EQUIPMENT SUPPORT DETAIL

SCALE: NO SCALE M-502D

CHEMICAL FEED TANK DETAIL

SCALE: NO SCALE M-502E

PIPE SLEEVE THRU EXTERIOR WALL DETAIL

SCALE: NO SCALE M-502F PIPE SLEEVE THRU INTERIOR WALL DETAIL

SCALE: NO SCALE M-502G SHUT-OFF VAV TERMINAL UNIT - HOT WATER REHEAT DETAIL

SCALE: NO SCALE M-502H

HEATING CABLE DETAIL

SCALE: NO SCALE M-502J EXTERIOR PIPE SUPPORT DETAIL

SCALE: NO SCALE M-502K

3.

CAULK ALL AROUND

TO MAKE WATER

TIGHT

WALL LOUVER

PRE-ENGINEERED

METAL WALL

SHEET METAL SLEEVE

AIR FLOW

INSECT OR BIRD

SCREEN U.O.N. SEE

SCHEDULE FOR

REQUIREMENTS

6" MAXIMUM

WALL LOUVER DETAIL

SCALE: NO SCALE M-502A

CAULK ALL AROUND TO

MAKE WATER - TIGHT

AUTOMATIC GRAVITY

OPERATED

SHUTTERS

SECURE

SLEEVE TO

BUILDING W/

SCREWS ON 10"

CENTERS

EXTERIOR WALL

WALL

SLEEVE

EXHAUST

FAN

WIRE

GUARD

SECURE FAN TO WALL SLEEVE

W/ SCREWS ON 8" CENTERS

PROVIDE 4 x 4 x 1/8 STEEL

ANGLE AT TOP AND AT

FIBERGLASS PANEL ON SIDES

EXTERIOR WALL

BIRDSCREEN

EXHAUST

WALL EXHAUST FAN DETAIL

SCALE: NO SCALE M-502I

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

01/24/2020

GRILLE, REGISTER & DIFFUSER SCHEDULE

C.F.M. NECK MAX.

TAG TYPE SERVICE RANGE SIZE P.D. REMARKS

A GRILLE SUPPLY 0 - 235 12x4 0.1 14x6 PANEL, DUCT MOUNTED, DRUM LOUVER, 3" BLADE SPACING B DIFFUSER SUPPLY 115 - 230 8" 0.1 LAY-IN, 24x24 PANEL, 4-WAY BLOW PATTERN T GRILLE RETURN - 22x22 - LAY-IN, 24x24 PANEL, 35° DEFLECTION, 3/4" BLADE SPACING U REGISTER TRANSFER - 10x6 0.1 SINGLE DEFLECTION, 35° DEFLECTION, 3/4" BLADE SPACING V REGISTER TRANSFER - 10x10 0.1 SINGLE DEFLECTION, 35° DEFLECTION, 3/4" BLADE SPACING W REGISTER TRANSFER - 12x12 0.1 SINGLE DEFLECTION, 35° DEFLECTION, 3/4" BLADE SPACING X REGISTER TRANSFER - 26x14 0.1 SINGLE DEFLECTION, 35° DEFLECTION, 3/4" BLADE SPACING Y REGISTER TRANSFER - 14x12 0.1 SINGLE DEFLECTION, 35° DEFLECTION, 3/4" BLADE SPACING Z REGISTER RETURN 4900 42x36 0.1 44x36 PANEL, HEAVY DUTY, 30° DEFLECTION, 1/2" BLADE SPACING

THE FOLLOWING NOTES ARE TYPICAL UNLESS OTHERWISE NOTED:

1. PROVIDE ALUMINUM DIFFUSERS AND REGISTERS WITH OPPOSED BLADE VOLUME DAMPERS, BAKED STANDARD WHITE ENAMEL FINISH (INCLUDING HEAD OF SCREWS), MAXIMUM NC=25 AT HIGHEST CFM AND PROVIDE SQUARE TO ROUND TRANSITION AS REQUIRED.

2. MAXIMUM PRESSURE DROP SHALL INCLUDE VOLUME DAMPER WHERE DAMPER IS PROVIDED.

PUMP SCHEDULE

HEAD ELECTRICAL DATA

TAG SERVICE TYPE CONTROL G.P.M. (FT.) H.P. VOLTS PHASE R.P.M. REMARKS

SHWP-1 SECONDARY HOT WATER INLINE VFD 28.0 25.0 0.5 208 3 1800 SEE NOTES

SHWP-2 SECONDARY HOT WATER INLINE VFD 28.0 25.0 0.5 208 3 1800 SEE NOTES

NOTES:

1. PROVIDE NON-OVERLOADING MOTOR SELECTION.

2. PROVIDE INVERTER DUTY RATED MOTOR SUITABLE FOR USE WITH A VFD.

SHUT OFF V.A.V. TERMINAL BOX SCHEDULE (HOT WATER)

VOL. REG. C.F.M. MAX INLET HEATING COIL

INLET S.P. W.P.D. A.P.D.

TAG SIZE (IN.) MIN. MAX. (IN. WG.) M.B.H. G.P.M. E.W.T. L.W.T. (FT. WG.) (IN. WG.) REMARKS

VAV-1 10" 270 900 0.5 24.7 3.0 120 103.4 0.40 0.66 SEE NOTES

VAV-2 10" 270 900 0.5 24.7 3.0 120 103.4 0.40 0.66 SEE NOTES

VAV-3 10" 270 900 0.5 24.7 3.0 120 103.4 0.40 0.66 SEE NOTES

VAV-4 10" 270 900 0.5 24.7 3.0 120 103.4 0.40 0.66 SEE NOTES

VAV-5 10" 275 910 0.5 24.0 2.7 120 102.1 0.32 0.67 SEE NOTES

VAV-6 8" 170 560 0.5 14.4 1.5 120 100.7 0.12 0.56 SEE NOTES

VAV-7 4" 40 130 0.5 3.5 0.3 120 93.9 0.01 0.08 SEE NOTES

VAV-8 4" 50 165 0.5 4.3 0.4 120 95.2 0.01 0.12 SEE NOTES

VAV-9 6" 115 370 0.5 9.9 1.2 120 103.8 0.08 0.45 SEE NOTES

VAV-10 12" 365 1215 0.5 32.2 3.0 120 98.4 0.42 0.64 SEE NOTES

NOTES:

1. HEATING COIL SELECTION BASED ON 55ºF E.A.T. AT 80% OF MAX. AIRFLOW.

2. SELECT UNITS FOR MAXIMUM NOISE CRITERIA OF 35.

DUCTLESS SPLIT SYSTEM HEAT PUMP SCHEDULE

COIL E.A.T. FAN DATA HEATING DATA ELECTRIC DATA INDOOR UNIT ELECTRIC DATA OUTDOOR UNIT

TOTAL COOLING SUPPLY TOTAL E.A.T.

TAG LOCATION CAPACITY M.B.H. ºF D.B.ºF W.B.AIR C.F.M. M.B.H (ºF) M.C.A. M.O.C.P. VOLTS PHASE TAG M.C.A. M.O.C.P. VOLTS PHASE REMARKS

DSS-1A ELECTRICAL 9.0 80.0 67.0 265 12.0 70.0 INDOOR UNIT POWERED BY OUTDOOR UNITDSS-1B 9.0 15.0 208 1 SEE NOTES DSS-2A TELECOM 9.0 80.0 67.0 265 12.0 70.0 INDOOR UNIT POWERED BY OUTDOOR UNITDSS-2B 9.0 15.0 208 1 SEE NOTES

NOTES:

1. COOLING CAPACITY BASED ON 96º F AMBIENT, HEATING CAPACITY BASED ON 17° F.

2. PROVIDE INDOOR UNIT WITH COIL FREEZE PROTECTION, REMOTE MOUNTED THERMOSTAT, INTEGRAL CONDENSATE PUMP (5FT HEAD), HIGH SIDE WALL CASSETTE CONFIGURATION.

3. PROVIDE OUTDOOR UNIT WITH LOW AMBIENT CONTROL.

AIR CONTROL SCHEDULE

AIR SEPARATOR EXPANSION TANK

MAX. CAPACITY ACCEPTED APPROX. APPROX.

SYSTEM TAG G.P.M. P.D. FT. SIZE TAG (GAL.) CAPACITY (GAL.) DIAMETER HEIGHT REMARKS

HOT WATER AS-1 28.0 0.04 3 ET-1 7.6 2.5 11 17 SEE NOTES

NOTES:

1. PROVIDE CENTRIFUGAL TYPE AIR SEPARATOR WITH HIGH CAPACITY AIR VENT.

2. PROVIDE VERTICAL BLADDER TYPE EXPANSION TANK WITH FLOOR SKIRT, PRE-CHARGE TO 12 PSIG.

FAN SCHEDULE

E.S.P. ELECTRICAL DATA

TAG FAN TYPE C.F.M. (IN. WG.) DRIVE H.P. VOLTS PHASE REMARKS

EF-1 EXHAUST 500 0.35 DIRECT 1/15 120 1 SEE NOTES

NOTES:

1. PROVIDE DIRECT DRIVE FANS WITH ELECTRONIC SPEED CONTROLLER.

2. PROVIDE SIDEWALL FAN WITH WALL MOUNTING SLEEVE, INTEGRAL DISCONNECT, MOTORSIDE GUARD, AND BACKDRAFT DAMPER.

GAS FIRED UNIT HEATER SCHEDULE

INPUT CAPACITY M.B.H. OUTPUT APPROX. MOTOR ELECTRICAL DATA

TAG (C.F.H.) CAPACITY C.F.M. H.P. VOLTS PHASE REMARKS

UH-1 30 24.0 505 1/15 120 1 SEE NOTES

NOTES:

1. PROVIDE WITH SINGLE STAGE COMBINATION GAS VALVE AND HORIZONTAL CONCENTRIC VENT OUTLET.

2. PROVIDE WITH REMOTE WIRED THERMOSTAT, ADJUSTABLE HORIZONTAL LOUVERS AND PROPELLER FAN.

AIR HANDLING UNIT SCHEDULE

SUPPLY FAN DATA CHILLED WATER COOLING COIL DATA HOT WATER PRE-HEAT COIL DATA

S.A. O.A. ELECTRICAL DATA TOTAL SENS. MAX. TOTAL MAX.

C.F.M. C.F.M. E.S.P. FAN

M.C.A. M.O.C.P.

CAPACITY CAPACITY E.D.B. E.W.B. E.W.T. L.W.T. W.P.D. CAPACITY E.D.B. E.W.T. L.W.T. W.P.D.

TAG (MIN. / MAX.) (MIN. / MAX.) (IN. WG.) QTY H.P. TYPE VOLTS PHASE M.B.H. M.B.H. (ºF)(ºF)(ºF)(ºF)G.P.M. (FT. WG.) M.B.H. (ºF)(ºF)G.P.M. (ºF)(FT. WG.) REMARKS AHU-1 6950 / 2050 2050 / 450 2.00 2.00 4 DIRECT 208 19 25 3 272.6 191.5 79.7 67 45 59.2 38.2 3.24 86.8 26.0 120 6.6 93 0.6 SEE NOTES

NOTES:

1. LEAVING AIR TEMPERATURE IS TO BE PROVIDED AT THE UNIT DISCHARGE, TOTAL & SENSIBLE CAPACITIES ARE "NET" VALUES TO BE PROVIDED DOWNSTREAM OF THE SUPPLY AIR FAN.

2. PROVIDE INVERTER DUTY RATED MOTOR SUITABLE FOR USE WITH A VFD.

3. PROVIDE WITH THE FOLLOWING SECTIONS: MERV 8 FILTER, PREHEAT COIL, COOLING COIL, COIL ACCESS PANEL, FAN, AND FAN ACCESS PANEL.

4. PROVIDE AIR HANDLER UNIT WITH MAXIMUM DIMENSIONS OF 58"x58"x96".

HOT WATER BOILER SCHEDULE

INPUT OUTPUT L.W.T. E.W.T. ELECTRICAL DATA

TAG FUEL (M.B.H.) (M.B.H.) G.P.M. (ºF) (ºF) M.C.A. F.L.A. VOLTS PHASE REMARKS

B-1 PROPANE 155.0 147.3 14.0 120 100 2.8 2.2 120 1 SEE NOTES

B-2 PROPANE 155.0 147.3 14.0 120 100 2.8 2.2 120 1 SEE NOTES

NOTES:

1. PROVIDE SUITABLE FOR 2 PSIG GAS PRESSURE.

2. PROVIDE SUITABLE FOR 80 PSI WORKING PRESSURE.

3. PROVIDE ALL TRIM AND APPURTENANCES RECOMMENDED FOR INDICATED APPLICATION.

4. PROVIDE BOILERS WITH INLINE PRIMARY HOT WATER PUMP RATED FOR 15.0 GPM AND 10 FT OF HEAD

5. PROVIDE CONDENSING BOILERS WITH BACNET MS/TP INTERFACE.

LOUVER SCHEDULE

MIN. FREE AREA

TAG SERVICE SIZE (IN.) WxH (SF) C.F.M. SERVES REMARKS L-1 INTAKE 44x32 5.3 2050 AHU-1 SEE NOTES L-2 INTAKE 20x20 1.1 500 EF-1 SEE NOTES L-3 RELIEF 36x36 4.4 2050 AHU-1 SEE NOTES

NOTES:

1. PROVIDE INSECT SCREEN FOR INTAKE SERVICE, BIRDSCREEN FOR RELIEF SERVICE.

2. PROVIDE ALUMINUM STORMPROOF CONSTRUCTION.

3. PROVIDE COLOR CHART FOR FINISH SELECTION BY COTR.

4. LOUVER SHALL BE LISTED FOR AMCA 500L FOR AIRFLOW RESISTANCE AND WATER PENETRATION.

5. INTAKE LOUVERS SHALL BE AT MINIMUM 10 FEET ABOVE FINISHED FLOOR.

AIR COOLED CHILLER SCHEDULE

CAPACITY EVAPORATOR CONDENSER FAN COMPRESSOR ELECTRICAL DATA

TAG (TONS) G.P.M. P.D. (FT.) E.W.T. (°F)L.W.T. (°F)QUANTITY F.L.A. TYPE QUANTITY R.L.A. M.C.A. M.O.C.P. VOLTS PHASE REMARKS

AC-1 26 38.2 6.6 59.2 45.0 2 6.8 SCROLL 2 50.6 148 175 208 3 SEE NOTES

NOTES:

1. PROVIDE MANUFACTURER'S PUMPING PACKAGE WITH DUAL 5 HP (SIZED FOR 25 FT. HEAD) PUMPS WITH INVERTER DUTY RATED MOTORS SUITABLE FOR USE WITH VARIABLE FREQUENCY DRIVES, STRAINERS, CHECK VALVES, EXPANSION TANK, AIR SEPARATOR, AND 143 GAL. BUFFER TANK. PUMPS SHALL BE CONSTRUCTED OF MANUFACTURER'S STANDARD MATERIALS SUITABLE FOR CHILLED WATER, AND PROVIDED WITH MECHANICAL SEALS, DRIP PROOF ELECTRIC MOTOR, AND NON-OVERLOADING SELECTION.

PUMP MOTORS SHALL BE EQUIPPED WITH VARIABLE FREQUENCY DRIVES BUT SHALL OPERATE AT CONSTANT SPEED.

2. PROVIDE INTEGRAL CIRCUIT BREAKER, CONTROL VOLTAGE TRANSFORMERS, PUMPS, AND SEPARATE 120V CIRCUITS FOR EVAPORATOR PIPING HEAT TAPE AND BUFFER TANK HEAT TAPE.

3. PROVIDE WITH 4 STAGES OF UNLOADING. MINIMUM EFFICIENCY AT AHRI CONDITIONS: 9.89 EER / 14.27 IPLV.

4. PROVIDE WITH BACNET MS/TP INTERFACE, CONDENSER COIL GUARDS, WIDE AMBIENT CONDENSER CONTROL, AND 410A REFRIGERANT.

5. PROVIDE PHASE MONITORS FOR ALL 3 PHASE EQUIPMENT: PHASE UNBALANCE PROTECTION, OVER/UNDER VOLTAGE PROTECTION, PHASE LOSS PROTECTION, DELAY OF BREAK TIMER TO DELAY AUTOMATIC RESTARTS, NON-CRITICAL FAULT DELAY, PROGRAMMABLE AUTO/MANUAL RESTART, AND LOAD AND LINE SLIDE MONITORING.

6. CONDENSER COILS SHALL MEET 3000 HOUR SALT SPRAY TEST IN ACCORDANCE WITH ASTM B117-90.

7. EACH CIRCUIT SHALL BE PROVIDED WITH LIQUID AND SUCTION LINE SERVICE VALVES AND CORE FILTER DRIER ON THE LIQUID LINE.

8. CAPACITY BASED ON 96°F AMBIENT TEMPERATURE.

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO

THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE

FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE

PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

01/24/2020

VAV SHUT-OFF TERMINAL UNITS

GENERAL: AN OVERRIDE SWITCH INTEGRAL TO EACH ZONE TEMPERATURE SENSOR SHALL RETURN THE RESPECTIVE AHU FROM UNOCCUPIED TO OCCUPIED BUT ONLY THE ZONE OVERRIDDEN SHALL RETURN TO OCCUPIED MODE. WHEN ANY OVERRIDE SWITCH IS ENERGIZED, AHU AND ALL VAV BOXES ASSOCIATED WITH THE ZONE OVERRIDDEN SHALL BE ENERGIZED THROUGH DDC CONTROL BUT ONLY THE ZONE OVERRIDDEN SHALL RETURN TO OCCUPIED MODE TEMPERATURE SETPOINTS. AFTER TWO HOURS, THE ZONE SHALL RETURN TO UNOCCUPIED MODE. ENERGIZED AHU AND ALL ASSOCIATED VAV BOXES SHALL BE DE-ENERGIZED UNLESS AHU IS UNDER CONTROL OF ANOTHER ZONE IN OVERRIDE POSITION. REFER TO GLOBAL

TEMPERATURE SETPOINT NOTE THIS SHEET.

COOLING-OCCUPIED: THE ZONE TEMPERATURE SENSOR THROUGH DDC CONTROL SHALL MODULATE THE PRIMARY AIR VALVE IN THE VAV BOX TO MAINTAIN GLOBAL ZONE TEMPERATURE SETPOINT, OPENING THE AIR VALVE ON A RISE IN SPACE TEMPERATURE, OR CLOSING IT ON A FALL IN SPACE

TEMPERATURE, (NOT TO FALL BELOW MINIMUM SCHEDULED PRIMARY AIR QUANTITY).

HEATING-OCCUPIED: THE PRIMARY AIR VALVE SHALL START IN ITS MINIMUM SCHEDULED POSITION THRU DDC CONTROL. THE ZONE TEMPERATURE SENSOR THROUGH DDC CONTROL SHALL MODULATE THE HOT WATER CONTROL VALVE TO MAINTAIN GLOBAL ZONE TEMPERATURE SETPOINT. ON A RISE IN ZONE TEMPERATURE, THE OPPOSITE SHALL OCCUR. IF SPACE TEMPERATURE IS SLOW TO RESPOND, CONTROLLER SHALL MODULATE PRIMARY AIR VALVE OPEN TO A MAX OF 80%. ON A RISE IN ZONE TEMPERATURE, THE OPPOSITE SHALL OCCUR.

COOLING-UNOCCUPIED: THE VAV BOX PRIMARY AIR VALVE SHALL BE FULLY CLOSED UNLESS THE ASSOCIATED AHU SUPPLY FAN IS ENERGIZED. ON A RISE IN ZONE TEMPERATURE ABOVE SETBACK SETPOINT (85°F, ADJ.) THE VAV BOX PRIMARY AIR VALVE SHALL MODULATE TO MAINTAIN SETPOINT. DDC CONTROLLER SHALL MAINTAIN 55°F SUPPLY AIR TEMPERATURE. AHU SHALL REMAIN ENERGIZED UNTIL ZONE SETBACK TEMPERATURE SETPOINT IS ACHIEVED. IF ZONE TEMPERATURE FALLS BELOW SETBACK SETPOINT, VAV BOX SHALL CLOSE AIR VALVE TO MIN. POSITION.

HEATING-UNOCCUPIED: THE VAV BOX PRIMARY AIR VALVE SHALL BE FULLY CLOSED UNLESS THE ASSOCIATED AHU SUPPLY FAN IS ENERGIZED. ON A FALL IN ZONE TEMPERATURE BELOW SETBACK SETPOINT (60°F, ADJ.) THE PRIMARY AIR VALVE SHALL OPEN TO 80%. DDC CONTROLLER SHALL MODULATE VAV BOX HOT WATER CONTROL VALVE TO MAINTAIN ZONE SETBACK TEMPERATURE SETPOINT. IF ZONE TEMPERATURE RISES ABOVE SETBACK

SETPOINT, THE OPPOSITE SHALL OCCUR.

DDC/EMCS SIGNAL-FUNCTION:

ZONE TEMPERATURE SENSOR - AIR VALVE CONTROL, HOT WATER VALVE CONTROL, STATUS, ALARM

OVERRIDE SWITCH - OCCUPIED CONTROL, STATUS

HOT WATER CONTROL VALVE - ZONE TEMPERATURE CONTROL, STATUS

AIR VALVE - ZONE TEMPERATURE CONTROL, STATUS (AIRFLOW)

SUPPLY

TO SPACE

AIR FLOW

TS

OVER-RIDE

PUSH-BUTTON

SENSOR W/

SPACE TEMPERATURE

AIR SUPPLY

PRIMARY

VAV BOX

AIR VALVE

HW VALVE CONTROL

AIR VALVE CONTROL

A N

A L

O G

SHUT-OFF VAV TERMINAL UNIT

LOCAL DDC CONTROLLER

SPACE TEMP.

AIRFLOW QUANTITY

DISCHARGE AIR TEMP.

SPACE TEMP. SETPOINT

HWS

HWR

OVERRIDE

A N

A L

O G

D I G

I T

A L

OUTPUTS

INPUTS

2-WAY CONTROL VALVE. PROVIDE 3-WAY

CONTROL VALVE FOR VAV-8 AND VAV-10.

AO2

AO1

DI1

AI4

AI3

AI2

AI1

AO2

TS

AI3

DI1

AI2AI1

AO1

AI4

GENERAL: AHU SUPPLY FAN SPEED SHALL BE DETERMINED BY DISCHARGE AIR PRESSURE AND

POLLING OF VAV BOX DAMPER POSITIONS. AIR PRESSURE SETPOINT SHALL BE 1.5" W.G.,

ADJUSTABLE.

COOLING-OCCUPIED/OVERRIDE: AHU SUPPLY FAN SHALL BE ENERGIZED AND RUN CONTINUOUSLY.

OUTSIDE AND RETURN AIR DAMPERS SHALL MODULATE TO MAINTAIN MIN. O.A. FLOW AS MEASURED BY THE OUTSIDE AIR AIRFLOW MEASUREMENT STATION. THE O.A. DAMPER SHALL FULLY STROKE

BEFORE THE R.A. DAMPER STARTS MODULATING. DISCHARGE AIR TEMPERATURE CONTROLLER

SHALL MODULATE THE CHILLED WATER VALVE TO MAINTAIN 53°F (ADJ.) LEAVING AIR TEMPERATURE.

HOT WATER CONTROL VALVE SHALL BE FULLY CLOSED TO COIL. A SUPPLY AIR TEMPERATURE RESET

STRATEGY SHALL BE EMPLOYED. SUPPLY AIR TEMPERATURE SHALL BE RAISED IN ONE DEGREE

INCREMENTS UNTIL ONE ZONE DAMPER IS 90% OPEN. IF OA DRY BULB TEMPERATURE IS 65°F (ADJ.)

OR LOWER, THE SUPPLY AIR TEMPERATURE RESET SHALL BE NO HIGHER THAN 58°F (ADJ.). IF ANY

ZONE DAMPER IS 100% OPEN AND ZONE TEMPERATURE RISES ABOVE SETPOINT, SUPPLY AIR

TEMPERATURE SHALL BEGIN TO RESET LOWER.

COOLING-UNOCCUPIED: UNIT SHALL BE DE-ENERGIZED UNLESS THE AVERAGE OF THE ZONE

TEMPERATURES RISES ABOVE THE SETBACK TEMPERATURE SETPOINT. THE OA DAMPER SHALL BE

CLOSED.

HEATING-OCCUPIED: AHU SUPPLY FAN SHALL BE ENERGIZED AND RUN CONTINUOUSLY. O.A. FLOW

SHALL BE MAINTAINED AS DESCRIBED IN COOLING-OCCUPIED MODE ABOVE. WHEN MIXED AIR

TEMPERATURE DROPS TO 52°F, DISCHARGE AIR TEMPERATURE CONTROLLER THRU DDC CONTROL

SHALL MODULATE THE HOT WATER VALVE TO MAINTAIN 55°F LEAVING AIR TEMPERATURE. THE

CHILLED WATER VALVE SHALL BE FULLY CLOSED TO THE COIL.

HEATING-UNOCCUPIED: IF THE AVERAGE OF THE ASSOCIATED ZONE TEMPERATURES FALLS BELOW

THE HEATING NIGHT SETBACK TEMPERATURE THE AHU SHALL BE ENERGIZED. THE OA DAMPER

SHALL BE FULLY CLOSED. THE SUPPLY FAN SHALL MODULATE TO MAINTAIN DUCT STATIC PRESSURE WHILE THE VAV BOXES ARE INITIALLY AT MAXIMUM AIRFLOW. THE HOT WATER CONTROL VALVE SHALL REMAIN CLOSED UNLESS DISCHARGE AIR TEMPERATURE FALLS BELOW 55°F. ZONE HEATING SHALL BE MAINTAINED AT VAV BOXES. AS VAV BOX ZONES REACH SETPOINT, AIR VALVES SHALL

MODULATE TO MAINTAIN SETPOINT.

TRANSITION FROM OCCUPIED TO UNOCCUPIED: AUTOMATICALLY THRU DDC CONTROL AND PRESET

TIME SCHEDULE. SYSTEM SHALL ALSO BE ABLE TO BE RETURNED TO OCCUPIED MODE FROM

UNOCCUPIED MODE BY THE OPERATOR WORKSTATION. TRANSITION FROM COOLING TO HEATING

SHALL OCCUR WHEN CHILLED WATER CONTROL VALVE IS CLOSED AND MIXED AIR TEMP. FALLS

BELOW 52°F.

PRESSURE PROTECTION: A HIGH PRESSURE TRANSMITTER LOCATED AT THE SUPPLY FAN

DISCHARGE SHALL DE-ENERGIZE THE SUPPLY AIR FAN IF ITS SETPOINT, 5" WG, IS REACHED.

SEQUENCE OF OPERATION

COIL

HOT WATER

FROM VARIABLE

FREQUENCY DRIVE

FREEZESTAT

AIR

OPPOSED

DAMPER

BLADE

FILTER

OUTSIDE

NC

OPPOSED

DAMPER

BLADE

C W

R

NO

H W

R

H W

S

C W

S

NC

SET AT

5" WG

CHILLED WATER

SUPPLY FAN

M

COIL

PRIMARY

AIR

SAFETY CONTROL: SMOKE DETECTOR SHALL BE PROVIDED BY FIRE ALARM

CONTRACTOR. THROUGH DDC CONTROL IT SHALL DE-ENERGIZE THE ASSOCIATED AHU,

SIGNAL FIRE ALARM PANEL AND CLOSE THE OUTSIDE AIR DAMPER UPON THE

DETECTION OF THE PRODUCTS OF COMBUSTION.

FREEZE PROTECTION: IF HOT WATER COIL DISCHARGE AIR TEMPERATURE FALLS

BELOW 40°F DURING HEATING MODE, THE FREEZESTAT SHALL CLOSE THE OUTSIDE AIR

DAMPER, DE-ENERGIZE THE AHU SUPPLY FAN AND FULLY OPEN THE HOT WATER AND

CHILLED WATER VALVES TO COIL.

CONDENSATE HIGH LEVEL PROTECTION: IF CONDENSATE HIGH LEVEL SWITCH IS

ACTIVATED, UNIT SHALL BE DE-ACTIVATED AND AN ALARM INITIATED.

MORNING WARM-UP: AHU SHALL EMPLOY OPTIMUM START PRIOR TO OCCUPIED

STATUS. THE OA DAMPER SHALL BE FULLY CLOSED. THE SUPPLY FAN SHALL MODULATE

TO MAINTAIN DUCT STATIC PRESSURE WHILE VAV BOXES ARE INITIALLY AT MAXIMUM

AIRFLOW. HOT WATER COIL VALVE SHALL BE FULLY OPEN. AS VAV BOX ZONES REACH

SETPOINT, PRIMARY AIR VALVES SHALL MODULATE TO MINIMUM AIRFLOW.

MORNING COOL-DOWN: THE UNIT SHALL EMPLOY OPTIMUM START PRIOR TO OCCUPIED

STATUS, THE UNIT SHALL GO INTO MORNING COOL-DOWN. THE OA DAMPER SHALL

FULLY CLOSE, THE SUPPLY FAN SHALL MODULATE TO MAINTAIN DUCT STATIC

PRESSURE, THE CW VALVE SHALL MODULATE TO MAINTAIN A 53°F (ADJ.) LEAVING AIR

TEMPERATURE AND THE HOT WATER VALVE SHALL BE FULLY CLOSED TO THE COIL.

ASSOCIATED VAV BOX AIR VALVES SHALL INITIALLY BE FULLY OPEN AND THEN

MODULATE TO MAINTAIN SPACE OCCUPIED TEMPERATURE SETPOINT, VAV BOX HW

VALVES SHALL BE FULLY CLOSED TO THE COIL.

ALARMS: ALARM IF LEAVING AIR TEMPERATURE EXCEEDS 60°F IN COOLING MODE OR

DROPS BELOW 50°F IN HEATING MODE. ALARM IF AHU SUPPLY FAN FAILS TO START OR

FAILS DURING OPERATION. ALARM IF UNIT DISCHARGE STATIC PRESSURE EXCEEDS 5"

W.G. ALARM IF CONDENSATE REACHES HIGH LEVEL. ALARM UPON SMOKE DETECTOR

ACTIVATION.

DEMAND CONTROL VENTILATION: IF ANY SPACE CARBON DIOXIDE LEVEL FALLS BELOW

SETPOINT (1,000 PPM, ADJ.), THE OUTSIDE AIRFLOW RATE SHALL BE AT THE MINIMUM

SCHEDULED VALUE AS INDICATED IN THE EQUIPMENT SCHEDULE. AS LEVEL INCREASES

ABOVE SETPOINT, THE OUTSIDE AIR DAMPER SHALL PROPORTIONALLY MODULATE

OPEN TO GENERATE THE SCHEDULED MAX OUTSIDE AIRFLOW RATE OVER A 1 HOUR

(ADJ.) TIME PERIOD UNTIL THE LEVEL FALLS BELOW THE SETPOINT, AFTER WHICH THE

DAMPER POSITION SHALL RETURN TO MINIMUM.

INPUTS

D I G

I T

A L

HW VALVE CONTROL

CW VALVE CONTROL

A02

AO1

OUTPUTS

A03

A N

A L

O G

SUPPLY AIR FAN STATUS

SMOKE DETECTOR

FREEZESTAT

MIXED AIR TEMPERATURE

SUPPLY AIR TEMPERATURE

HW COIL DISCHARGE AVERAGE

UNIT DISCHARGE STATIC PRESSURE

SA DOWN DUCT PRESSURE TRANSMITTER

AI4

AI5

DI1

DI3

DI2

AI2

AI1

AI3

A N

A L

O G

LOCAL DDC CONTROLLER

AHU

OA AIRFLOW MEASURE MOUNT STATION

AI6

A04

OUTSIDE AIR DAMPER CONTROL

AO1

AO4

DM

DM

AMSAI6

AI1

TS

FS

DI3

AO2

TS

AI3

AO3

AI2

VFD TS SPS

AI4 AI5

SPS

DI1

DPS

NO

LOCATE AT 2/3 DOWN

DUCT FROM AHU

AI7

CONDENSATE HI-LEVEL

DI4

DI4

LS

RA TEMPERATURE

AI8

AI8 TS

AI7 HS

PROVIDE 3-WAY CONTROL VALVE.

PROVIDE 3-WAY CONTROL VALVE

SEE VFD CONTROL DIAGRAM

AIR

RETURN

DI2

SD

RA HUMIDITY

RETURN AIR DAMPER CONTROL

E

M

E

R

G

E

N

C

Y

H

V

A

C

S

H

U

T

D

O

W

N

P

U

L

L

T

O

R

E

S

E

T

NOTES:

1. EMERGENCY AIR DISTRIBUTION (LOCATION AS SHOWN ON PLAN

AND AS DETERMINED BY THE CONTRACTING OFFICER).

2. UPON ACTIVATION OF EMERGENCY PUSHBUTTON, ALL AIR

HANDLING UNITS SHALL BE DISABLED AND REMAIN

OFF UNTIL A MANUAL RESET HAS OCCURRED.

3. UPON ACTIVATION OF EMERGENCY PUSHBUTTON,

OUTSIDE AIR DAMPER FOR AHU-1 SHALL CLOSE FULLY.

4. SHUTOFF SWITCH SHALL BE MUSHROOM BUTTON WITH CLEAR

HINGED, PULL TO RESET, LABELED "EMERGENCY HVAC

SHUTDOWN".

ZONE TEMPERATURE SET POINTS SHALL BE DETERMINED BY A GLOBAL

TEMPERATURE SET POINT. THE ZONE TEMPERATURE SET POINT SHALL BE

MADE ADJUSTABLE BY BUILDING OCCUPANTS +/- 3°F FROM THE GLOBAL SET

POINT. IF AMBIENT TEMPERATURE IS LESS THAN 50°F, THE GLOBAL ZONE

TEMPERATURE SET POINT SHALL BE 70°F. IF AMBIENT TEMPERATURE IS

GREATER THAN 80°F, THE ZONE TEMPERATURE SHALL BE 76°F. IF AMBIENT

TEMPERATURE IS BETWEEN 50°F AND 80°F, THE GLOBAL SET POINT

TEMPERATURE SHALL BE RESET LINEARLY OR IN NO FEWER THAN 3 STEPS.

ZONE TEMPERATURE SET POINT SHALL BE +/- 1°F FROM GLOBAL SET POINT.

GLOBAL TEMPERATURE SETPOINT NOTE:

INPUTS

D I G

I T

A L

AO1

OUTPUTS

A N

A L

O G

SPEED, %

KWH CONSUMPTION

CURRENT, AMPS

DRIVE STATUS

DRIVE FAULT

DI1

DI2

AI2

AI1

AI3

A N

A L

O G

LOCAL DDC CONTROLLER

VFD

SPEED CONTROL

VFD

AO1 DO1

DI1

DI2

AI1

AI2

AI3

DO1

D I G

I T

A L

ENABLE/DISABLE

EMERGENCY AIR DISTRIBUTION SYSTEM SHUTOFF SWITCH

SEQUENCE OF OPERATION

PER THE REQUIREMENTS OF UFC 4-010-01, SECTION B-4.3, THE FACILITY SHALL BE OUTFITTED WITH AN EMERGENCY AIR DISTRIBUTION SYSTEM SHUTOFF SWITCH WHICH SHALL, THROUGH THE DDC SYSTEM, IMMEDIATELY SHUT DOWN ALL AIR DISTRIBUTION SYSTEM COMPONENTS ASSOCIATED WITH AHU-1 AND CLOSE ASSOCIATED ISOLATION DAMPERS. THE EMERGENCY SWITCH SHALL ALSO INITIATE AN AUDIBLE ALARM NOTIFICATION. SWITCH SHALL BE ACTIVATED IF BUILDING OCCUPANTS SUSPECT AIRBORNE CONTAMINANTS MAY BE PRESENT IN THE VICINITY OF THE FACILITY. LOCATE THE SHUTOFF SWITCH (OR SWITCHES) SUCH THAT THEY ARE EASILY ACCESSIBLE BY BUILDING OCCUPANTS BY LOCATING THEM ADJACENT TO MANUAL FIRE ALARM PULL STATIONS. A MINIMUM OF ONE SWITCH SHALL BE PROVIDED PER FLOOR. ADDITIONAL SWITCHES SHALL BE PROVIDED AS REQUIRED TO ENSURE THAT THE TRAVEL DISTANCE TO THE NEAREST SHUTOFF SWITCH IS NOT IN EXCESS OF 200 FEET.

SHUTOFF SWITCHES SHALL BE WELL LABELED AND BE OF A DIFFERENT COLOR THAN THE FIRE ALARM PULL STATIONS. COORDINATE COLOR AND APPEARANCE REQUIREMENTS OF THE SHUTOFF SWITCHES WITH THE GOVERNMENT PRIOR TO ORDERING.

EMERGENCY AIR DISTRIBUTION SHUT OFF LOCAL DDC CONTROLLER:

1) SHUT-OFF SWITCH STATUS (DI)

2) AUDIBLE ALARM (DO)

3) ENABLE/DISABLE (DO)

VAV AHU CONTROL DIAGRAM (DDC)

SCALE: NO SCALE M-701

A

VFD CONTROL DIAGRAM (DDC)

SCALE: NO SCALE M-701

B

HVAC EMERGENCY SHUTOFF SWITCH

SCALE: NO SCALE M-701

C

VAV SHUT-OFF TERMINAL UNIT CONTROL DIAGRAM (DDC)

SCALE: NO SCALE M-701

D

AI9

CO2

CO2 SENSOR

AI9

REPEAT POINT FOR

EACH SENSOR

60025492
60025493
Sheets and Views
M-101 MECHANICAL FLOOR PLAN
60025494
60025495
60025496
Sheets and Views
M-601 MECHANICAL SCHEDULES
60025497
60025498