Q&A 1
| Q&A # 1 | ||
| The following are answers to questions received from potential offerors. The answers provide clarification only and DO NOT constitute an amendment to the solicitation. | DATE: | Monday, January 08, 2018 |
| HULLS/TITLE: | LHD-6 USS BONHOMME RICHARD | |
| SOLICITATION NO: | N0002418-R-4404 | |
| NAVSEA POCs: | Steve Galer |
Ivy Hosokawa NAVSEA POC E-MAIL: steven.galer@navy.mil ivy.e.hosokawa@navy.mil NAVSEA POC #: Steve Galer: 202-781-2873 Ivy Hosokawa: 202-781-3121
| QUESTION #/ DETAILS | QUESTION/ ANSWER | ||||||
| # | Question Area | ITEM NO: | TITLE | PARA # | PAGE # | Contractor Question | Government Response |
| 1 | Solicitation Question | 721-90-001 857-11-002 992-11-005 992-11-009 992-11-011 | Various Work Items | Draft RFP Attach J-3 contains duplicate lines for items 721-90-001, 857-11-002, 992-11-005, 992-11-009, and 992-11-011. Please correct. |
| This was corrected prior to RFP release on Nov 28 and updated J-3 posted on FBO. | ||
| 2 | Missing References | 511‐11‐005 |
512‐11‐006 512‐11‐016 512‐11‐020 513‐11‐001 533‐11‐008 581‐11‐003 588‐11‐001 634‐21‐001 631‐41‐001 665‐90‐001 665‐90‐001 665‐90‐001
| 997‐11‐001 | Various Work Items | Correct Drawing Discrepancies as noted in Sheet BQ 2 | Some items have been corrected in Errata package 1, as noted on attached Excel worksheet BQ 2, all the remaining drawings on contained on the technical data disk provided to the bidders. | |||||
| 3 | Spec Error | 512-11-034 | ||||||
| 512-11-040 | Preheater; replace | 3.1 | 1 | Equipment on 1.3.1 (PHR 01-77-2) of 512-11-040 and 1.3.2 of 512-11-034 are the same. Is this a typo? | Spec numbers listed are incorrect. Spec numbers should be 511-11-040 and 511-11-034. 1.2.6 and 1.3.2 will be deleted from 511-11-034 in Errata 2 package. | |||
| 4 | Spec Error | |||||||
| Bidder Error | 512-11-006 | Ventilation Supply System, Structure and Plating; replace | 3.6 | 14 | Vent assemblies identified as 1.3.6.19, 1.3.6.20, 1.3.6.24, 1.3.6.25 and 1.3.5.20 thru 1.3.5.26 cannot be found on Ref.2.7 (DWG. #512-6858101). Please provide the correct DWG Number for estimating and material requisition purposes. | Vent assemblies identified as 1.3.6.19, 1.3.6.20, and 1.3.5.20 thru 1.3.5.26 will be corrected to reflect vent assemblies listed on Ref.2.7 (DWG. #512-6858101) as part of Errata 2.Vent assemblies 1.3.6.24 and 1.3.6.25 are listed on ref 2.8 in accordance with the specification. | ||
| 5 | Missing Reference | 513-11-001 | Ventilation Supply System, Structure and Plating; replace | 3.1 | 11 | Vent assemblies identified as 1.3.3.32, 1.3.3.33 and 1.3.3.34 have the same assembly number. Please verify to correct. | 1.3.3.33 will be changed to 031-03-04-D and 1.3.3.34 will be changed to 032-03-05-D as part of Errata 2. | |
| 6 | Missing Reference | 513-11-001 | Ventilation Supply System, Structure and Plating; replace | 3.1 | 11 | Hinge screen assy.1.3.2.43 and 1.3.3.48 has no Ref. drawing number. Please provide. | Hinge screen assy 1.3.2.43 is FN 166 of 2.7 and 1.3.3.48 is FN 73 of 2.8. Work Item will be updated as part of Errata 2 package. |