AC ELECTRICAL LOAD ANALYSIS SAMPLE WITH USAGE FACTORS
Consumer
OEM P/N
Qty kW/unit
Phase
Volts
Amps
PF
Total kW
Eng. Rm Fans 1 240 DER Fans 1 240 Water Heater 1 240 Fresh Water Pmp 1 240 LP Compressor 1 240 Battery Charger 1 120 Eng. Preheater 1 120 Black Water Pmp 1 240 Defogger 1 120
Eng Rm Heater (HVAC) 1 120 Heater (HVAC) 1 120 Fan (HVAC) 1 120 Seawater Pmp (HVAC) 1 240 Condenser (HVAC) 1 240 Evaporator (HVAC) 1 240
Lighting 1 120 lighting (below deck) 1 120 lighting (weather) 1 120
Receptacle (aft dk) 1 120 Receptacle (DER) 1 120 Receptacle (cabin) 1 120 Receptacle (galley) 1 120 Receptacle (Eng Rm) 1 120 Receptacle (Monkey) 1 120 Receptacle (Laz) 1 120 Receptacle (PH) 1 120 Receptacle (240V) 1 240
Refrigerator 1 120 Microwave 1 120 Coffee Maker 1 120
240/120 Vac Totals
HPU 3 480
Receptacle (480V) 3 480 Dive Compressor 3 480 Seawater Pump 3 480 Boom Crane 3 480
480 Vac Totals
1. Tailor the first column of 'consumers' from above with details of the proposed design.
2. Input the value in the OEM/part number, Quantity and kW/unit columns.
3. Mathematically populate the remainder of the spreadsheet to perform the requisite analysis.
4. Total the load for each of the listed conditions (e.g. summer-shore, winter-transit, etc).
5. Use DDS 310-1, Rev. 1 Electrical Power Load Analysis (EPLA) for Surface Ships for AC equipment usage factors.
Summer Conditions Winter Conditions Shore Transit Dive Operations Shore Transit Dive Operations
Usage Factor
Load (kW)
Factor
Load (kW)
0.1 1 0.5 0.1 1 0.5
1 1 1 1 1 1
0.3 0.1 0.3 0.3 0.1 0.3
0.1 0.2 0.5 0.1 0.2 0.5
0.1 0 0.1 0.1 0 0.1
0.5 0 0 0.5 0 0
0.1 0 0 0.1 0 0
0.1 0.1 0.1 0.1 0.1 0.1
0 0.1 0.1 0 0.5 0.2
0 0 0 0.1 0.1 1 0 0 0 0.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1
0.7 0.7 0.7 1 1 1 1 1 1 1 1 1
0.3 1 1 0.3 1 1
0.1 1 1 0.1 1 1
0.1 0.5 0.5 0.1 0.5 0.5
0.1 0.1 0.2 0.1 0.1 0.3
0.1 0.1 0.2 0.1 0.1 0.3
0.1 0.5 0.5 0.1 0.5 0.5
0.1 0.5 0.5 0.1 0.5 0.5
0.1 0.1 0.1 0.1 0.1 0.1
0.1 0 1 0.1 0 1
0.1 0 0 0.1 0 0
0.1 0.1 0.1 0.1 0.3 0.3
0.3 0.3 0.3 0.3 0.3 0.3
0.3 0.3 0.3 0.3 0.3 0.3
0 0 0.3 0 0 0.3
0.1 0 0.1 0.1 0 0.1
0.9 0 0.9 0.9 0 0.9