MINI SPLIT_drawings_2024-12-05.pdf

PDF 2 MB Posted

Attached to
Ductless Mini-Split Heating & Cooling System for DCR Room at Joint Base Cape Cod Bldg #2410
Solicitation number
6913G625Q300009
Issued by

About this file

This file contains architectural and mechanical drawings dated December 5, 2024, for the installation of a mini-split HVAC system in Room #4 of Building #2410 at Joint Base Cape Cod in Sandwich, MA. The drawings include detailed floor plans, general notes, demolition requirements, and specifications for a new ductless mini-split heating/cooling system with wall-mounted blower unit for Zone 4 and a free-standing condenser unit.

The drawings consist of six sheets covering architectural, mechanical, and electrical details including cover sheet, general notes and abbreviations, demolition notes, HVAC floor plan, electrical floor plan, and power panel schedules. The mechanical plans show the installation location in a 112 SF shower room with 14-foot ceiling height and uninsulated exterior CMU walls. The drawings specify requirements for control systems, thermostats, ductwork modifications, and electrical connections, including panel load specifications showing connected loads and demand factors. The building is governed by 2018 IBC code requirements and is classified as Business Group B occupancy.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDOT/VOLPE CENTER

DEPARTMENT OF TRANSPORTATION

Room #4 MINI-SPLIT INSTALLATION

BUILDING #2410

JOINT BASE CAPE COD

SOUTH INNER ROAD

SANDWICH, MA 02542

December 5, 2024

OWNER/LESSOR:

Commonwealth of Massachusetts

Executive Office of Public Safety & Security

Military Division

2 Randolph Road

Hanscom AFB Bedford, MA 01731

PROJECT LOCATION

REGIONAL MAP SITE MAP

I SHEET I DRAWING NUMBER I SHEET NAME

GENERAL

SHEET 01 MINI-SPLIT G-000 COVER SHEET

SHEET02 MINI-SPLIT G-001 ARCH GENERAL NOTES, SYMBOLS, & ABBREVIATIONS

SHEET 03 MINI-SPLIT G-002 DEMOLITION, ELECTRICAL, MECHANICAL GENERAL NOTES, SYMBOLS, & ABBREVIATIONS

MECHANICAL

SHEET 04 MINI-SPLIT M-101 HVAC FLOOR PLAN

ELECTRICAL

SHEET 05 MINI-SPLIT E-101 ELECTRICAL FLOOR PLAN

SHEET 06 MINI-SPLIT E-201 POWER PANEL SCHEDULES

SHEET 01 MINI-SPLIT G-000

ARCHITECTURAL ABBREVIATIONS LIST:

A A

ACT ACOUSTIC CEILING TILE

ADA AMERICANS WITH DISABILITIES ACT

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

AL ALUMINUM

ALT ALTERNATE

AP ACCESS PANEL

ARCH ARCHITECTURAL

AUTO AUTOMATIC

B B

BO BOARD

BIT BITUMINOUS

BLDG BUILDING

BL BLOCKING

BM BEAM

BR BRICK

BSMT BASEMENT

BTW BETWEEN

C C

CAB CABINET

CPT CARPET

GER CERAMIC

CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CFOI CONTRACTOR FURNISHED OWNER INSTALLED

CG CORNER GUARD

CJ CONTROL JOINT

CLO CLOSET

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

COMB COMBUSTIBLE

CON CONDITION

CONG CONCRETE

COND CONDUIT

CONF CONFERENCE

CONN CONNECTION

CONT CONTINUOUS

CONST CONSTRUCTION

GOOD COORDINATE

CORR CORRIDOR

cw COLD WATER

D D

DBL DOUBLE

DEG DEGREE

DEMO DEMOLISH

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIFF DIFFUSER

DIM DIMENSION

DIR DIRECTOR

DN DOWN

DR DOOR

DS DOWNSPOUT

DTFPEPE DESIGN TEAM FIRE PROTECTION ENGINEER

PROFESSIONAL ENGINEER

DW DISH WASHER

DWG DRAWING

E E

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC

ELEV ELEVATOR

EMG EMERGENCY

EMP EMERGENCY POWER

ENCL ENCLOSED

EOAE EQUIVALENT OR APPROVED EQUAL

ES EACH SIDE

ETR EXISTING TO REMAIN

EQ EQUAL

EQUIP EQUIPMENT

EXH EXHAUST

EX EXISTING

EXT EXTERIOR

! STORAGE MECHANICAL RM

F F M

FA FIRE ALARM MFR

FON FOUNDATION MIN

FE FIRE EXTINGUISHER MIR

FEC FIRE EXTINGUISHER CABINET MISC

FF FINISH FLOOR MLDG

FHC FIRE HOSE CABINET MLWK

FIN FINISHED MO

FLASH FLASHING MOD

FLEX FLEXIBLE MT

FLR FLOOR MTD

FLOUR FLUORESCENT MTL

FP FIRE PROOFING MUL

FRZ FREEZER

FT FEET,FOOT N

FURR FURRING N

NIC

G G NO

GALV GALVANIZED NTS

GB GRAB BAR

GC GENERAL CONTRACTOR 0

GL GLASS OA

GRND GROUND OAE

GWB GYPSUM WALLBOARD oc

GYP GYPSUM OD

OFCI

H H OFF

HG HANDICAP OFOI

HCWD HOLLOW CORE WOOD OH

HDWD HARDWOOD OPP

HDWR HARDWARE

HDR HEADER p

HM HOLLOW METAL PBD

HORZ HORIZONTAL PCC

HR HOUR PED

HT HEIGHT PERF

HTR HEATER PER

HVAC HEATING, VENTILATION, AIR CONDITIONING PERM

HW HOT WATER PERP

PG

I I PH

isc iNTERNATIONAL BUILDING CODE PL

ID INSIDE DIAMETER P-LAM

IN INCH PLWD

INCD INCANDESCENT PNL

INCL INCLUDED POL

INFO INFORMATION PORT

INSUL INSULATION PRNT

INT INTERIOR PROJ

PROP

J J PT

JAN JANITOR PTD

PTW

K K PAV

KD KNOCK DOWN PWR

KO KNOCK OUT

KP KICK PLATE Q

QT

L L QTR

LAB LABORATORY QUAN

LAUN LAUNDRY

LAV LAVATORY R

LF LINEAR FEET R

LIN LINEAR RB

LT LIGHT RCP

RECP

M M RECT

MAS MASONRY RECV

MAT MATERIAL REQ

MAX MAXIMUM RES

MDF MEDIUM DENSITY FIBERBOARD RET

MDO MEDIUM DENSITY OVERLAY REV

MDX MEDIUM DENSITY OVERLAY EXTERIOR GRADE RFPE

MECH MECHANICAL RM

RND

RO

RTU

EQUIPMENT RM

cp 45•.,73•

I I

I I

I I

M s

MANUFACTURER SAN

MINIMUM SB

MIRROR SC

MISCELLANEOUS SCHED

MOULDING SD

MILLWORK SOT

MASONRY OPENING SECT

MODULAR SF

MOUNT SGPL

MOUNTED SHEA

METAL SHT

MULLION SI

SIM

N SPEC

NORTH SPK

NOT IN CONTRACT SPC

NUMBER SQ

NOT TO SCALE ss

STD

0 STL

OVERALL STOR

OR APPROVED EQUAL STR

ON CENTER STRUC

OUTSIDE DIAMETER SUP

OWNER FURNISHED CONTRACTOR INSTALLED SURF

OFFICE sv

OWNER FURNISHED OWNER INSTALLED SYM

OPPOSITE HAND SYN

OPPOSITE

T p 'i'1

PARTICLEBOARD T2

PRECAST CONCRETE TF

PEDESTAL TBD

PERFORATED TEL

PERIMETER TEMP

PERMANENT T&G

PERPENDICULAR TO

PLATE GLASS TOIL

PHASE TOL

PLATE TRD

PLASTIC LAMINATE TWS

PLYWOOD TYP

PANEL

POLISHED u

PORTABLE UBC

PRINTER UON

PROJECT U.S.

PROPERTIES

PRESSURE TREATED V

PAINTED VP

PRESSURE TREATED WOOD VAR

PAVEMENT VB

POWER VCT

VERT

Q VEST

QUARRY TILE VIF

QUARTER

QUANTITY w

WI

R W/0

RADIUS WD

RUBBER BASE WDC

REFLECTED CEILING PLAN W/D

RECEPTION WIN

RECTANGULAR WG

RECEIVING WH

REQUIRED WK

RESILIENT

RETURN

REVISION

REGIONAL FIRE PROTECTION ENGINEER

ROOM

ROUND

ROUGH OPENING

ROOF TOP UNIT

OFFICE

I 2 I l

SANITARY

BACKPAINTED SPANDREL INSULATING GLASS

SOLID CORE

SCHEDULE

SOAP DISPENSER

STATIC DISSIPATIVE TILE

SECTION

SQUARE FEET

STRUCTURAL GRADE PLASTIC LUMBER

SHEATHING

SHEET

SPANDREL INSULATING GLASS

SIMILAR

SPECIFICATION

SPEAKER

SPECIAL

SQUARE

STAINLESS STEEL

STANDARD

STEEL

STORAGE

STRAIGHT

STRUCTURAL

SUPPORT

SURFACE

SHEET VINYL

SYMMETRICAL

SYNTHETIC

T

TEMPERED GLASS

TEMPERED INSULATING GLASS

TEMPERED INSULATING W/ APPLIED FILM

TO BE DETERMINED

TELEPHONE

TEMPORARY

TONGUE AND GROOVE

TOP OF

TOILET

TOLERANCE

TREAD

TEACHER WORK STATION

TYPICAL

u

UNIFORM BUILDING CODE

UNLESS OTHERWISE NOTED

UNDERSIDE OF STRUCTURE

V

VAPOR

VARIABLE

VINYL BASE

VINYL COMPOSITE TILE

VERTICAL

VESTIBULE

VERIFY IN FIELD

w

WITH

WITHOUT

WOOD

WOOD W/ COPPER CLADDING

WASHER/DRYER

WINDOW

WIRE GLASS

WATER HEATER

WORK

SYMBOL LEGEND

X'-X"

,r ,r X'-X"

1v k l X'-X" k

OFFICE

[filJ

XXSF

0-

EB

® SYMBOLS LEGEND

1/8" = 1'-0"

LIFE SAFETY CODE SUMMARY:

2018 IBC - ICC INTERNATIONAL CODE

(CONSTRUCTION TYPE - 28)

DIMENSION LINE

ROOM DESIGNATION

ROOM NUMBER

SQUARE FOOTAGE (IF USED)

DOOR AND DOOR

TAG

PARTITION TAG

BREAK MARK

NORTH ARROW

ADAAG - ADA ACCESSIBILITY GUIDELINES

NFPA 101, 2015, NFPA 72- 2015, NFPA 13-2015

BUILDING OCCUPANCY PER IBC BUSINESS GROUP B

SCOPE OF WORK FLOOR AREA

BUSINESS

REQUIRED RATING

OCCUPANT LOAD FACTOR

BUSINESS

2,730 SF

ELECTRICAL RM L------------..J I

I r

100 SF/PERSON

FLOOR AREA

[I]

11\ LIFE SAFETY PLAN

'-V 1/8" = 1'-0"

BATHROOM

[I]

I t

X X X X X X X )lL:: .JX X X X X X X X

I I

I ------------- �------_j XXXX'. XXXXXXXXXXXX L=:x x

LIFE SAFETY PLAN LEGEND:

� ILLUMINATED CEILING MOUNTED EXIT SIGN

• -- ► PATH OF EGRESS

OCCUPANT LOAD

BUSINESS

EXITS REQUIRED

BUSINESS

MAX. ALLOWABLE TRAVEL DISTANCE SHALL

NOT EXCEED 200' (WITHOUT SPRINKLER SYSTEM)

MAXIMUM ALLOWABLE DEAD END

MAXIMUM ALLOWABLE COMMON

PATH OF TRAVEL

MAXIMUM ALLOWABLE TRAVEL DISTANCE

100 GROSS =

MINIMUM

50'

MAXIMUM

100'

250'

OCCUPANT

ACTUAL

ACTUAL

33'

84' r?

f l l J

LJ!:XXX

C7"scALE:

GENERAL NOTES:

PLAN DETAIL TAG

SECTION CUT TAG

ELEVATION/DETAIL

TITLE REFERENCE

ELEVATION DESIGNATION

COLUMN DESIGNATION

GRID LINE

AS USED IN THESE CONTRACT DOCUMENTS:

"FURNISH" MEANS TO PURCHASE AND DELIVER

TO THE PROJECT SITE COMPLETE WITH

NECESSARY APPURTENANCE,

"INSTALL" MEANS TO UNLOAD AT THE DELIVERY

POINT AT THE SITE AND PERFORM EVERY

OPERATION NECESSARY TO ESTABLISH SECURE

MOUNTING AND CORRECT OPERATION AT THE

PROPER LOCATION IN THE PROJECT.

"PROVIDE" MEANS TO "FURNISH" AND "INSTALL."

No.

USDOT/VOLPE

CENTER

55 BROADWAY CENTER

CAMBRIDGE, MA 02142-1001

Description Date

DOT REDESIGN OF

BUILDING #2410

JOINT BASE CAPE COD

SANDWICH, MA

ARCH GENERAL

NOTES, SYMBOLS, &

ABBRV.

SHEET 02

Submission 100% WORKING DOCUMENTS Project number

Date December 5, 2024 Drawn by

Checked by

MINI-SPLIT G-001

Scale As indicated

I

GENERAL DEMOLITION NOTES:

IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ADHERE TO THE FOLLOWING:

1. DO NOT CLOSE OR OBSTRUCT THE PATH OF EGRESS, CORRIDORS, OR OTHER OCCUPIED OR USED SPACES OR FACILITIES WITHOUT THE WRITTEN PERMISSION OF THE OWNER IF NECESSARY PROVIDE TEMPORARY UTILITIES. PRIOR TO OBSTRUCTION OF EGRESS PATHS OR IMPAIRMENT OF FIRE/LIFE SAFETY COMPONENTS, THE NFPA 241 AND IMPAIRMENTS PLANS MUST BE SUBMITTED FOR APPROVAL BY DESIGN TEAM FIRE PROTECTION ENGINEER WHO IS LICENSED PROFESSIONAL ENGINEER (IN FIRE

PROTECTION ENGINEERING) (DTFPEPE).

2. CEASE OPERATION IF PUBLIC SAFETY OR REMAINING STRUCTURES ARE ENDANGERED. PERFORM TEMPORARY CORRECTIVE MEASURES UNTIL OPERATIONS CAN BE

CONTINUED PROPERLY.

3. IN COMPANY OF THE ARCHITECT AND OWNER, THE CONTRACTOR WILL VISIT THE SITE AND VERIFY THE EXTENT AND LOCATION OF SELECTIVE DEMOLITION REQUIRED PRIOR TO STARTING THE WORK. CAREFULLY IDENTIFY THE LIMITS OF SELECTIVE DEMOLITION. MARK INTERFACE SURFACES AS REQUIRED TO ENABLE THE WORKMEN TO ALSO IDENTIFY THE ITEMS TO BE REMOVED AND STORED, AS WELL AS THE ITEMS TO BE LEFT IN PLACE INTACT.

4. USE MEANS NECESSARY TO PREVENT DUST FROM BECOMING A NUISANCE TO THE PUBLIC, NEIGHBORING BUILDINGS, AND TO ANY OTHER WORK BEING PERFORMED.

5. EXECUTE DEMOLITION WORK TO ENSURE THE SAFETY OF PERSONS AND ADJACENT PROPERTY AGAINST DAMAGE BY DEBRIS. CONTRACTOR WILL TAKE PROTECTIVE

MEASURES TO PREVENT DUST FROM GETTING INTO DUCTS.

6. IN THE EVENT OF DEMOLITION OF ITEMS NOT SCHEDULED TO BE DEMOLISHED, PROMPTLY REPLACE SUCH ITEMS TO THE APPROVAL OF THE ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REPAIR ANY DAMAGE DONE TO EXISTING FEATURES AS A RESULT OF THIS WORK.

DAMAGED ITEMS SHALL BE REPLACED IN KIND AND AT NO ADDITIONAL COST TO THE OWNER.

7. SHORE, BRACE AND SUPPORT EXISTING CONDITIONS AS REQUIRED FOR REMOVAL OF EXISTING CONSTRUCTION OR INSTALLATION OF THE NEW WORK.

8. COORDINATE THE REMOVAL, RELOCATION, REPLACEMENT, RE-USE, SHUT-OFF, STUB-OFF, CAPPING-OFF OR UPGRADING OF ALL EXISTING PLUMBING, HVAC, ELECTRICAL SYSTEMS, AND TELECOM SYSTEMS EQUIPMENT, AND APPURTENANCES - INCLUDING, BUT NOT LIMITED TO , UTILITY LINES, DUCTS, CONNECTIONS, PANELS, VENTS, FANS, ELECTRICAL BASEBOARD HEAT, PIPING, DEVICES, CONTROLS, SWITCHES, OUTLETS, AND CONDUIT DURING THE CONSTRUCTION AS REQUIRED, AS SCHEDULED OR AS

SPECIFIED IN ACCORDANCE WITH ALL LOCAL, MUNICIPAL, STATE CODES.

9. THE CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE OF ANY HAZARDOUS MATERIALS AND IN DOING SO SHALL COMPLY WITH ALL APPLICABLE OSHA REGULATIONS AND ALL OTHER FEDERAL, STATE AND LOCAL GUIDELINES REGARDING ASBESTOS-CONTAINING MATERIAL REMOVAL AND DISPOSAL.

10. OWNER AND ARCHITECT SHALL NOT BE HELD RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES FOR SAFETY PRECAUTIONS OR FOR THE CONTRACTORS FAILURE TO CARRY OUT THE WORK IN STRICT ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS. OWNER SHALL NOT BE RESPONSIBLE FOR ERRORS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS OR THEIR AGENTS OR EMPLOYEES OR ANY OTHER PERSONS PERFORMING ANY OF

THE WORK.

11. THE CONTRACTOR SHALL COORDINATE ALL ABOVE CEILING MEP AND STRUCTURAL ELEMENTS PRIOR TO DEMOLITION OF WALLS AND/OR CEILING. CONTRACTOR IS ULTIMATELY RESPONSIBLE FOR FIRE SAFETY DURING PROJECT BEING IN COMPLIANCE WITH IBC, IFC AND NFPA 241.

12. COORDINATE, TERMINATE, AND RELOCATE ALL WALL & CEILING ELECTRICAL (TELECOM/POWER OUTLETS, SWITCHING, THERMOSTAT, ETC.) DEVICES THAT ARE LOCATED ON WALLS & CEILINGS SCHEDULED FOR REMOVAL. GC TO V.I.F. PRIOR TO THE COMMENCEMENT OF WORK. DISCONNECT AND MAKE SAFE EXISTING ELECTRICAL

COMPONENTS TO BE REMOVED.

13. REPAIR, AND LEVEL FLOORING TO MEET MANUFACTURER'S REQUIREMENTS OF THE NEW FLOORING AND WALL MATERIALS AS SPECIFIED. IT IS THE RESPONSIBILITY OF THE GC TO FINISH ALL UNEVEN SURFACES OR PATCH ALL CONCAVE FLOORING TO A LEVEL SURFACE REGARDLESS OF FLOORING UNEVENNESS.

14. PATCH ALL EXISTING WALLS ADJACENT TO ALL WALLS SCHEDULED FOR REMOVAL. PATCHWORK WILL BE CONSISTENT WITH THE WALL RATING.

15. SUBMIT DEMOLITION SCHEDULE FOR APPROVAL INCLUDING SCHEDULE AND METHODS OF CAPPING AND CONTINUING UTILITY SERVICE.

16. THE CONTRACTOR SHALL COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS AND 29 CFR 1910.34, COVERAGE AND DEFINITIONS, 29 CFR 1910-35, COMPLIANCE WITH NFPA 101, LIFE SAFETY CODE, 29 CFR 1910-36, DESIGN AND CONSTRUCTION REQUIREMENTS FOR EXIT ROUTES, 29 CFR 1910-37, MAINTENANCE, SAFEGUARDS, AND OPERATIONAL FEATURES FOR EXIT ROUTES.

18. ALL FIRE ALARM NOTIFICATION DEVICES, EXIT SIGNAGE, HEAT DETECTORS, AND EMERGENCY LIGHTING TO REMAIN OPERATIONAL DURING DEMOLITION AND CONSTRUCTION UNTIL WHICH POINT THAT NEW FIRE ALARM SPEAKER STROBE DEVICES ARE READY TO BE INSTALLED AND ACTIVATED.

19. PROTECT ALL EXISTING BUILDING FINISHES AS WORK IS ONGOING.

GENERAL DUST CONTROL

PROVISIONS:

THE GC SHALL PROVIDE DAILY REMOVAL OF ALL DEMOLITION DEBRIS. DO NOT STORE ANY DEMOLITION DEBRIS ON THE FLOOR

OVERNIGHT.

THE GC SHALL MAINTAIN A CLEAN AND SAFE WORK AREA THROUGHOUT THE PERIOD OF DEMOLITION. THE GC SHALL, AT THE END OF EACH WORK DAY, REMOVE ALL DEMOLITION DEBRIS AND HAZARDOUS AND POTENTIALLY DANGEROUS MATERIALS USED IN THE

WORK.

THE GC SHALL CLEAN THE EXTERIOR AREAS IMPACTED BY CONSTRUCTION DUST, DIRT AND DEBRIS ON A DAILY BASIS. THE GC SHALL

BE RESPONSIBLE FOR ALL FEES, PERMITS, ETC., REQUIRED FOR WASTE DISPOSAL

GENERAL NOTES:

AS USED IN THESE CONTRACT DOCUMENTS:

"FURNISH" MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY APPURTENANCE, ftlNSTALL" MEANS TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING AND CORRECT

OPERATION AT THE PROPER LOCATION IN THE PROJECT.

ftPROVIDE" MEANS TO "FURNISH" AND "INSTALL."

MECHANICAL GRAPHIC SYMBOLS

EQUIPMENT DESIGNATION

SECTION REFERENCES

0 KEYED NOTE SYMBOL

EB INDICATES POINT OF CONNECTION

BETWEEN NEW AND EXISTING

�AIR DEVICE TAG

(SEE SCHEDULE)

I

CFM

@) THERMOSTAT/HUMIDISTAT ,

NOTE: NOT ALL SYMBOLS ARE

USED IN THIS PROJECT

SUPPLY DUCT

RETURN OR OUTSIDE AIR DUCT

� EXHAUST DUCT

[filJ I CEILING AIR DEVICE t SIDEWALL AIR DEVICE = I f f DUCTWORK tlRST FIGURE IS SIDE SHOWN)

I [ f

MANUAL VOLUME DAMPER 12X6 (RECTA GULAR DUCTWORK)

12X6 12"0 (ROUND DUCTWORK) (BO = BACKDRAFT DAMPER)

DUCT DIMENSIONS ARE INSIDE CLEAR

rn

--------------- FLEXIBLE DUCTWORK

I f f f

MOTORIZED DAMPER

11111 FLEXIBLE DUCT CONNECTION r-

I

I ♦so

FD FIRE DAMPER

SD SMOKE DAMPER

I FS COMBINATION FIRE & SMOKE DAMPER

ELECTRICAL GENERAL NOTES:

1. IN GENERAL, CONDUIT ROUTING SHOWN ON THE DRAWINGS IS DIAGRAMMATIC. ACTUAL CONDUIT ROUTING

SHALL BE DETERMINED IN THE FIELD.

2. PENETRATIONS OF CONDUITS, RACEWAYS AND WIRING THROUGH FIRE RATED WALLS AND CEILING SHALL BE FIRE STOPPED USING A FIRE STOPPING U.L. LISTED ASSEMBLY BY A CERTIFIED INSTALLER SO AS TO MAINTAIN THE

UL RATING OF THE ASSEMBLY.

AS USED IN THESE CONTRACT DOCUMENTS:

"FURNISH" MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY

APPURTENANCE,

3. AS USED IN THESE CONTRACT DOCUMENTS:

"FURNISH" MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY

APPURTENANCE,

"INSTALL" MEANS TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING AND CORRECT OPERATION AT THE PROPER LOCATION IN THE PROJECT.

"PROVIDE� MEANS TO "FURNISH" AND �INSTALL."

g

GFI

8c

[] 30/3

15AF

0-i cp

IT]

DUPLEX RECEPTACLE - 15" TO CENTER AFF UNLESS OTHERWISE NOTED

GFI = GROUND FAULT CIRCUIT INTERRUPTING

D = DEDICATED CIRCUIT

EWC = GFI FOR ELECTRIC WATER COOLER

TV = TELEVISION, 80" TO CENTER AFF

COUNTERTOP DUPLEX RECEPTACLE - OR MOUNTED AT 44" AFF WHERE NO

COUNTER EXISTS

DOUBLE DUPLEX RECEPTACLE - 15" AFF UNLESS OTHERWISE NOTED

SPECIAL PURPOSE OUTLET - 18" AFF UNLESS OTHERWISE NOTED

MOTOR

DISCONNECT SWITCH - 30/3 = SWITCH AMPS/POLES,

15AF = 15 AMP FUSE

JUNCTION BOX - # INDICATES CIRCUIT

BRANCH CIRCUIT PANELBOARD

DISTRIBUTION PANELBOARD

FUSIBLE COMBINATION FVNR MOTOR STARTER

GROUND BAR WITH INSULATED SPACERS. GROUND BAR SHALL BE 1/4"X2"X12"

COPPER MINIMUM WITH NEMA TWO HOLE LUG SPACING. INSTALL AT 24" ABOVE

FLOOR. SEE DETAIL ON SHEET E-501.

SINGLE RECEPTACLE UNDER SINK FOR GARBAGE DISPOSAL

DRY TYPE TRANSFORMER

CONDUIT

� CONDUIT AND WIRING HOMERUN.

� SHORT STROKE INDICATES PHASE CONDUCTOR.

� LONG STROKE INDICATES NEUTRAL CONDUCTOR.

LONG STROKE WITH DOT INDICATES EQUIPMENT GROUND CONDUCTOR.

MISCELLANEOUS

�1u '\J7

EQUIPMENT DESIGNATION

0--- KEYED NOTE

OFFICE --

ROOM NAME

DI]..______ ROOM NUMBER

AFF

FMCP

FVNR

TV

ABBREVIATIONS

ABOVE FINISHED FLOOR

FIRE ALARM MASS NOTIFICATION CONTROL PANEL

FULL VOLTAGE NON-REVERSING

TELEVISION

No.

US DOT/VOLPE

CENTER

55 BROADWAY CENTER

CAMBRIDGE, MA 02142-1001

Description Date

DOT REDESIGN OF

BUILDING #2410

JOINT BASE CAPE COD

SANDWICH, MA

DEMOLITION,

ELECTRICAL, &

MECHANICAL NOTES,

SYMBOLS, & ABBREV

SHEET 03

Submission 100% WORKING DOCUMENTS Project number

Date December 5, 2024 Drawn by

Checked by

MINI-SPLIT G-002

Scale 1/8" = 1'-0"

I i i I i i I i i i i i i i

STORAGE MECHANICAL RM (130SF x 14ft high to roof deck= 1820CF)

SHOWER ROOM dimensions 112SF x 14ft high to roof deck = 1568 CF -uninsulated e�terior CMU walls v1

-roofhas5"ofrigidinsulation

II

rs.=z==:sz 1z::c��===q1

ELECTRICAL RM

[I]

130SF

, " . SHOWER ROOM �

� G

FURNISH WALL

MOUNTED&

HARDWIRED

ZONE4

THERMOSTAT

112SF

EXISITING

� ����JosTAT i BATHROOM i

EQUIPMENT RM

3 JX X

HVAC

ZONE1

1266 SF

X X

OFFICE

500 SF

' [I] ! ----------------------------------------------------------------------------------------------------------------------------------------------------------------------

CD CONTROL SYSTEM: NEW HVAC THERMOSTATS & HVAC ZONES PLAN 1 1/8" = 1'-0"

FURNISH MINI-SPLIT

DUCTLESS BLOWER UNIT

FOR ZONE 4

(WALL MOUNTED) / 1

/ II

II

fiF��=z;;z==;==rzs,���r=r==r=��r==tu7===r���r=lkl I I,,, � b b'

J

_;--=- 1 I\

I

1 r

II i\ J ._,,. '-LJ ,,i "'\__ EXISTING DUCTWORK & RTU-1.

FURNISH MINI-SPLIT DUCTLESS

CONDENSER UNIT "A"

(FREE STANDING)

@ NEW MECHANICAL FLOOR PLAN

1/8" = 1'-0"

0 WEST SIDE 4 1/8" = 1'-0"

® EAST SIDE5 1/8" = 1'-0"

NEW MECHANICAL LEGEND:

= NEW DUCT

..,_ FLEX DUCT

� SUPPLY

[Z] RETURN

� EXHAUST

Q COMBINATION THERMOSTAT/

V HUMIDISTAT

� AIR DEVICE TAG

'--01/� (SEE SCHEDULE)

CFM

ETR = EXISTING TO REMAIN

CT= CURRENT TRANSDUCER

SD = SMOKE DAMPER

M = MOTOR

VFD = VARIABLE FREQUENCY DRIVE

DX= DIRECT EXPANSION

RTU = ROOFTOP UNIT

ADJ = ADUST ABLE

DEMO= DEMOLITION

AFF = ABOVE FINISHED FLOOR

LT = LOW TEMPERATURE ALARM

@) EXISTING OVERHEAD DUCTWORK FROM ROOFTOP UNIT (RTU-1)

3 SCALE: NTS

LEAD PROFESSIONAL FIRM

102 SOUTH STREET

SUITE 3

BOSTON MA 02111

P: 617-951-2700 F: 617-951-2705

No.

USDOT/VOLPE

CENTER

55 BROADWAY CENTER

CAMBRIDGE, MA 02142-1001

Description Date

DOT REDESIGN OF

BUILDING #2410

JOINT BASE CAPE COD

SANDWICH, MA

HVAC FLOOR PLAN

SHEET 04

Submission

Project number

Date

100% WORKING DOCUMENTS

147001.00

December 5, 2024 Drawn by

Checked by

MINI-SPLIT M-101

Scale As indicated

EXISTING SINK FOR CONDENSATE DRAIN

Brian Hanley Line

Brian Hanley Line

Brian Hanley Rectangle

Brian Hanley Oval

Brian Hanley Rectangle

Brian Hanley Rectangle

Brian Hanley Rectangle

Brian Hanley Rectangle

Brian Hanley Line

Brian Hanley Rectangle

Brian Hanley Rectangle

Brian Hanley Rectangle

/ 71

/ II

�J

PANEL -MOP --,_ ::C

'-4

PANEL-RP

GENERAL NOTES:

1. SEE THE MECHANICAL SHEETS FOR EXACT EQUIPMENT LOCATIONS

GENERAL NOTES:

AS USED IN THESE CONTRACT DOCUMENTS:

"FURNISH" MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY APPURTENANCE, ft w

"INSTALL" MEANS TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING AND CORRECT

OPERATION AT THE PROPER LOCATION IN THE PROJECT.

"PROVIDE" MEANS TO "FURNISH" AND "INSTALL."

,r I�

Q) i::-.=-..=i -7

I

J :::_.-;_-=i

USDOT/VOLPE

CENTER

55 BROADWAY CENTER

CAMBRIDGE, MA 02142-1001

���0 No. Description Date

DOT REDESIGN OF

BUILDING #2410

JOINT BASE CAPE COD

SANDWICH, MA

ELECTRICAL FLOOR

PLAN

SHEET 05

Submission

Project number

Date

100% WORKING DOCUMENTS

147001.00

December 5, 2024

Drawn by

Checked by

MINI-SPLIT E-101

Scale

MDP

Connected Loads By Phase (VA) Total Connected Loads By Type (VA) Demand Factors Total Demand Loads By Type (VA)

Total 55,597 Subtotal 50,773

Total Demand Load 63,466

Total Demand Amps 176

RP

Connected Loads By Phase (VA) Total Connected Loads By Type (VA) Demand Factors Total Demand Loads By Type (VA)

Total 27,813 Subtotal 24,539

Total Demand Load 30,674

Total Demand Amps 85

5, 4

No. Description Date