Mechanical Record Set - VA Med Surge 32.pdf
PDF 467 KB Posted
- Attached to
- J041--Chiller & Condenser Maintenance - SF Federal contract opportunity
- Solicitation number
- 36C26324Q0595
About this file
This document appears to be a mechanical record drawing for a renovation project at the VA Medical Center in Sioux Falls, South Dakota. The drawing provides an overview of the mechanical piping systems, including the locations of air handling units, exhaust fans, chilled water and heating water piping, and other mechanical equipment. Key details include:
The related federal contract opportunity is a solicitation (RFQ) for HVAC Chiller and Condenser Maintenance services at the Sioux Falls VA Health Care System. This is a total set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB). The period of performance is one base year from 07/01/2024 to 06/30/2025, with four one-year option periods. Quotes are due by 04/19/2024. The NAICS code is 811310 with a $12.5 million size standard. Interested SDVOSBs must be registered in SAM.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation 36C26324Q0595 Amendment 0001.pdf | ||
| 36C26324Q0595 0001_1.docx | DOCX document | |
| Mechanical Record Set - VA Med Surge 35.pdf | ||
| Mechanical Record Set - VA Med Surge 18.pdf | ||
| Solicitation 36C26324Q0595.pdf | ||
| Mechanical Record Set - VA Med Surge 42.pdf | ||
| 36C26324Q0595_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
DN
DN
RECORD DRAWING
DATE: BY:
THE ISSUANCE OF THIS RECORD DRAWING IS A
REPRESENTATION BY THE ARCHITECT/ENGINEER THAT
THE CONSTRUCTION OR ALTERATIONS OF THE BUILDING
IS IN GENERAL, AS OPPOSED TO PRECISE, CONFORMITY
WITH THE DESIGN PREPARED AND PROVIDED BY THE
ARCHITECT/ENGINEER.
GRID
1S 2S 3S 4S
2.9
E30
E36E32 E33 E34 E35
E1 E2 E3 E4
5-AHU9
5-EF11
5-ERC5
5-UH3T
C W
R
G H
R
G
H S
/4
M P
S
1" HWR1" HWS
4" CWS
4" CWR
3/4" MPR
1 1/4" MPS
4" GHR
4" GHS
5-ET4
5-AS15-P15
5"MPS, 1 1/2"MPR, 4"CWS,
4"CWR, 4:GHR, 4"GHS DN
THRU FLOOR
1"HWS, 1"HWR DN
THRU FLOOR
5-PH37
5-PH36
C W
S
2" 2"
CWS
CWR
HWSHWR
GHS GHR 2"
2"
3" GHR
3" GHS
5-RF-37
5-CH-1
5-RF-36
5-ERC-36E
5-ERC-37E
5-PHR-37
5-PHR-36
5-AHU-36
5-AHU-37
5-PGH37
5-PGH36
5-PC37
5-PC36
3" GHS UP
3" GHR UP
4" CWS UP
4" CWR UP
4" HWR UP
5-AHU
1C
5-MH505
1F
5-MH505
7F
5-MH505
/2
M P
R
4" 4"
1 1/2" GHR
4"
1 1/2" GHS
6" 6"
C W
R
6" CWS
1S
2.9
0S 2S 3S 4S
-1S
3/4" HWS/HWR UP
BARE FINNED TUBE
@ 12'-0".
T
EXISTING
EXISTING
2 1/2" LPR DOWN
IN CHASE
5-MH401
1F
VALVE AND
CAPPED PIPES FOR
TEMPORARY
HEATING SYSTEM
VALVE AND
CAPPED PIPES FOR
TEMPORARY
COOLING SYSTEM
C1
5-MH506
F1
5-MH506
ALL WORK IN LAB AND DENTAL AREAS
TO BE PERFORMED AFTER HOURS,
BETWEEN 6PM-6AM.
CEMLINE V25CCP-3x2-D-65
STEAM CONDENSATE
RECEIVER TANK, NON-ELECTRIC
CONDENSATE PUMPS
F5
5-MH506
1. MATERIALS AND EQUIPMENT SHOWN ON PLANS SHALL BE NEW AND SHALL BE
FURNISHED BY THIS CONTRACTOR UNLESS OTHERWISE INDICATED.
2. IN GENERAL, PIPING SHALL BE RUN CONCEALED IN SUSPENDED CEILING
SPACES AND IN SHAFTS PROVIDED UNLESS NOTED OR OTHERWISE
INDICATED. CERTAIN ROOMS HAVE NO SUSPENDED CEILINGS, AND PIPING IN
THESE ROOMS SHALL BE EXPOSED.
3. PIPING IS INTENDED TO BE CONCEALED IN WALLS AND PARTITIONS UNLESS
SPECIFICALLY NOTED OTHERWISE. SOME ITEMS MAY APPEAR NOT TO BE
CONCEALED DUE TO DIGITAL REGISTRATION AND ALIGNMENT ISSUES
ASSOCIATED WITH THE DUPLICATION PROCESS.
4. COOPERATE WITH THE OTHER TRADES TO AVOID ANY CONFLICTS BETWEEN
PIPING, DUCTWORK, ELECTRICAL WORK.
5. DETAILS, SCHEMATICS, DIAGRAMS, DESIGNATE GENERAL ARRANGEMENT
ONLY.
6. FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT SHOWN ON
FLOOR PLANS, REFER TO ELEVATIONS, DETAILS, RISERS AND SCHEDULES.
7. THIS CONTRACTOR IS RESPONSIBLE FOR ALL SLEEVES AND/OR OPENINGS
WHERE REQUIRED TO RUN PIPES THROUGH FOUNDATIONS, FLOOR SLABS,
WALLS, BRIDGING AND BEAMS EXCEPT WHERE OTHERWISE INDICATED.
8. CONSULT REFLECTED CEILING PLAN FOR EXACT LOCATION OF SPRINKLER
HEADS, GRILLES, REGISTERS, AND DIFFUSERS.
9. CEILING ACCESS IS REQUIRED AT ALL REHEAT COILS, VALVES, FIRE
DAMPERS, MANUAL AND MOTORIZED DAMPERS LOCATED ABOVE CEILING.
CEILING ACCESS PANELS WILL BE PROVIDED UNDER THE GENERAL SECTION
OF CONSTRUCTION AND SHALL BE MINIMUM OF 24" X 24" UNLESS OTHERWISE
INDICATED. COORDINATE WITH GENERAL CONTRACTOR.
10. THERMOSTATS LOCATED AT OUTSIDE WALLS SHALL BE MOUNTED ON
INSULATED BACKING TO MINIMIZE WALL EFFECT.
11. THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS. NOTIFY THE A/E IMMEDIATELY OF ANY
DISCREPANCIES.
12. WHERE NEW SERVICES ARE SHOWN CONNECTING TO EXISTING, VERIFY
EXACT LOCATION AND SIZE OF EXISTING.
13. EXISTING SERVICES SHALL BE MAINTAINED UNLESS OTHERWISE INDICATED.
14. ALL PIPING, FIXTURES, ETC., WHICH ARE DASHED AND/OR INDICATED BY NOTE
ON DEMOLITION PLANS SHALL BE REMOVED.
15. PIPE RUNOUT SIZES TO REHEAT COILS SHALL BE 3/4" UNLESS OTHERWISE
NOTED.
16. RECIRCULATING HOT WATER, OXYGEN, VACUUM, AIR, AND GAS SHALL BE 1/2"
UNLESS OTHERWISE INDICATED.
17. REFER TO THE SPECIFICATIONS FOR SIZING OF CONTROL VALVES.
18. WHERE MATERIAL IS INDICATED TO BE REMOVED, IT SHALL REMAIN THE
PROPERTY OF THE OWNER. THIS CONTRACTOR SHALL DISPOSE OF
MATERIAL AS DIRECTED BY THE OWNER.
19. BALANCING OF HYDRONIC SYSTEMS SHALL BE PERFORMED BY AN NEBB OR
AABC CERTIFIED TEST AND BALANCE AGENCY.
20. PIPE PENETRATIONS OF RATED WALLS AND FLOORS SHALL BE SLEEVED AND
PROPERLY FIRE SEALED.
21. PIPE PENETRATIONS OF SMOKE PARTITION WALLS SHALL BE PROPERLY
SEALED TO RESIST THE PASSAGE OF SMOKE AS REQUIRED BY THE LOCAL
AUTHORITY.
22. THE HEATING AND/OR COOLING HYDRONIC SYSTEM SHALL BE PROVIDED AND
FILLED WITH AN ANTIFREEZE GLYCOL SOLUTION (AS INDICATED ON THE
EQUIPMENT SCHEDULES) BY THE PIPING CONTRACTOR WHO SHALL BE
RESPONSIBLE FOR DETERMINING THE AMOUNT OF GLYCOL REQUIRED.
PIPING PLAN GENERAL NOTES
NOTE: NOT ALL KEYNOTES MAY BE USED ON EACH PLAN
PIPING PLAN KEYNOTES
VALVE AND CAP EXISTING MEDICAL GAS PIPING TO EXISTING HEADWALL
UNITS
2 6" RELIEF VENT UP, COORD. WITH ARCH.
NOT ALL CHANGES DONE IN THIS AREA WERE DOCUMENTED. FIELD VERIFY
CHANGES IN THIS AREA.
4 -
5 -
6 -
7 -
8 -
9 -
10 -
KEYPLAN
N O
R T
H
BUILDING
REMODE
L
BUILDING
ADDITION EXISTING
BUILDING
10/19/2018
Copyright TSP, Inc. 2012
CONSULTANTS:
Drawing Number
Drawing Title
A
TSP, Inc.
1112 N. West Ave, Sioux Falls, SD 57104 phone: (605) 336-1160 fax: (605) 336-7926 www.teamtsp.com Date Checked Drawn
Project Number
Building Number
Project Title
Location
ARCHITECTS/ ENGINEERS:
Approved: Project Director
Office of Construction and Facilities Management
Dwg. of
Department of Veterans Affairs
C
D
E
F
B
A
C
D
E
B
F
2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
FULLY
SPRINKLERED
/1
9/
:0 4:
P
M
I:\ _T
S P
R ev it Lo ca l\0
7_
V A
_M ed
S ur g_ M
E P
_q ua m en kj
.r vt
1ST FLOOR MECHANICAL PIPING PLAN
5-MP101
100% CONSTRUCTION DOCUMENTS
VA Medical Center 2501 W. 22nd Street, PO Box 5046 Sioux Falls, SD 57117-5046
Acute Inpatient Med. Unit Add & Renovation
Sioux Falls VA Health Care System
JTC08/06/2012 BSW
04100857
82 123
1/8" = 1'-0"1F
1ST FLOOR MECHANICAL PIPING PLAN
MARK REVISION DESCRIPTION DATE
R Record Drawings 07/27/2018
RDND Record Drawings - No Documentation Changes 07/27/2018
KJQ
RDND