LOCS Structured Cabling App B - ADD 1.pdf

PDF 6 MB Posted

Attached to
Structured Cabling RFP
Solicitation number
RFP LOC 210000000352 6
Issued by
Macomb County, Michigan

About this file

This file comprises structured cabling application drawings and technology plans for multiple school construction projects within the Lake Orion Community Schools district in Michigan, prepared by Plante Moran and GMB architectural firms. The projects include additions and renovations at Carpenter Elementary, Webber Elementary, Early Childhood Center, Orion Oaks Elementary, Paint Creek Elementary, and Stadium Drive Elementary. The drawings detail comprehensive technology infrastructure including network cabling systems, communications pathways, fire alarm systems, audio-visual cabling, distributed clock systems, access control systems, video surveillance systems, and intercom/paging systems across multiple building units. Project numbers reference specific initiatives (5-4744 for Carpenter, 5-4740 for Webber, 5-4742 for Early Childhood Center, 5-4743 for Orion Oaks, 5-5063 for Paint Creek, and 5-5064 for Stadium Drive). The drawings span multiple phases of construction documented through various bulletins and addenda issued between December 2019 and November 2020, with design development and bid documentation stages noted throughout.

The structured cabling plans specify extensive conduit routing, cable tray systems, penetration devices with fire ratings, floor boxes, and connectivity infrastructure distributed across classroom units, administrative spaces, and mechanical areas. Multiple panelboards, transformers, and distribution points are identified for electrical and communications systems. The drawings emphasize coordination between the electrical contractor (Division 26), communications contractors (Division 27), and safety/security contractors (Division 28) operating under separate bid packages. Installation requirements include underground conduits, surface raceway systems, automatic door operators, and specialized provisions for kitchen hood fire protection systems where applicable. Drawings include keynotes addressing firestopping requirements, smoke damper installations, fixture relocation procedures, and accessibility standards in accordance with NEC and local code requirements. The technology infrastructure supports interactive flat panels, wireless access points, digital clocks, PA systems, and audio-visual systems throughout each facility.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Legend:

Interactive Flat Panel

General Data (1 drop per triangle unless noted)

PA – PA Buttons

Wireless AP

AV Cabling (IFP or Audio Ehancement Box)

Clock

PA Speaker

Digital Clock (see note below)

Dual-sided Digital Clock (see note below)

Audio Enhancement/PA (4 equally spaced speakers)

Teacher location

S

D

D2

T

Lake Orion Community Schools Carpenter Elementary - Technology

Prepared by Plante Moran

D

P

W

A

C

B F

B F

B F

B F

B F

BF BF

BFBF

B F

B F

B F

B F

B F

AV

A V

A V

A V

A V

F F

A V

A V

AV

AV

A

AV

A

A V

FAA

FACP IDS

A C

S

FB1

R

C R

CR

D

M

S S

D

D

D D

CRD IC

SC

SC

S

S

S

S S S

ID

ID A

V

TS FS

S

C R

CR

1/10

1/6

C R

A V

A V

AV

AV

ID

N

R

D

AV

D

F

RELOC. PANEL 'AD'

EX. PANEL 'MSP'

EX. METER C/T

CABINET EX. UTILITY ELEC.

METER

EX. 208V UTILITY

XFMR

EX. PANEL 'A4'

EX. PANEL 'B4'

PANEL 'C'

WG/PC

WG/PC

PCPC

44"

44"

44"

44"

GFCI

44"

GFCI

44"

44"

44" 44" 44"

44"

M

M

WB1

48"

LIMITED-AREA FIRE

PROTECTION, THIS

ROOM ONLY

RTU-20.1

ON ROOF

EX. PANEL

'DP2'

WB1

64"

80"

AUTO DOOR OPER

CLASSROOM

B102

ELECTRICAL

B133

STORAGE

B132

CLOSET

A119

GIRLS

A120

BOYS

A121

STORAGE

A123

STORAGE

A122

CLASSROOM

A124

TOILET

A110

CORRIDOR

A125

CLASSROOM

A118

CORRIDOR

A117

PRINCIPAL

A104

CONFERENCE

A106

OFFICE

A107

VEST

A101

RECORDS

A112

WAITING

A102

HEALTH

A109

STOR. (TOILET ALT. G-1)

A111

CLOSET

A114

OFFICE

A115

OFFICE

A116

GYM

A133

JAN

A132

OFFICE

A134

STORAGE

A135

WOMEN

A131

MEN

A130

STORAGE

A129

CORRIDOR

A128

CORRIDOR

A113

RECEPTION

A103

HALLWAY

A105

WORK

A108

GREEN

B131

CORRIDOR

A136

RAMP

A126

STAIR

A127

M

PLUMB. FIXTURE PSU

ABOVE CLG.

PLUMB. FIXTURE PSU

ABOVE CLG.

EF-20.2

ON ROOF

EF-20.1

ON ROOF

E7.01

TYP.

E7.01 8 E7.01 8

IM

E7.01 8

P03

P02

P08

P08

P08

E7.01

8 SIM

E7.01

8 SIM

AC-23

A4-18

C-27 C-28

C-29

EX. PANEL

'DP2'

P11

P05

P03

C-26

C-24

C-25

AD-15

AD-18

AD-17

C-23

AD-25

AD-23

AD-20

AD-19

AD-24

AD-22 AD-21

P12

C02 C02

P16

P10

AD-35

C02

A4-19

ENABLES/DISABLES

"EVENT" SEQUENCE

1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.01.

2. REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

3. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF SMOKE DAMPERS AND

COMBINATION FIRE/SMOKE DAMPERS. E.C. SHALL PROVIDE 120VAC POWER

FROM DEDICATED 20A/1P BRANCH CIRCUIT (WITH BREAKER LOCKING

MECHANISM) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA (DAMPERS

MAY BE GROUPED ON EACH CIRCUIT), TERMINATED W/ BOX-COVER FUSIBLE

SWITCH AT EACH DAMPER. ALSO PROVIDE FIRE ALARM DUCT SMOKE

DETECTOR WITHIN 5 FEET OF EACH DAMPER (UNLESS COVERED BY ANOTHER

DUCT DETECTOR WITHIN 5 FEET) AND A FIRE ALARM ADDRESSABLE RELAY FOR

INTERLOCKING DAMPER W/ CORRESPONDING HVAC UNIT PER CODE

REQUIREMENTS.

4. PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN

ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR

PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS

CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES

INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST

FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.

5. COORDINATE THE INSTALLATION AND ROUGH-IN REQUIREMENTS (BOXES,

CONDUIT, ETC. IN WALLS AND CEILINGS) FOR THE FOLLOWING SYSTEMS WITH

COMMUNICATIONS AND ELECTRONIC SAFETY/SECURITY CONTRACTORS

ENGAGED VIA SEPARATE BID PACKAGE(S) (NOT IN THIS CONTRACT), INCLUDING

BUT NOT LIMITED TO:

A. NETWORK CABLING SYSTEMS

B. NETWORK ELECTRONICS (SWITCHES, ACCESS POINTS, ETC.)

C. TELEPHONE SYSTEMS

D. INSTRUCTIONAL TECHNOLOGY EQUIPMENT

E. AUDIO-VIDEO SYSTEMS AND EQUIPMENT

F. INTERIOR DIGITAL SIGNAGE SYSTEM AND DISPLAYS

G. INTERCOM/PAGING SYSTEM

H. DISTRIBUTED CLOCK SYSTEM

I. ACCESS CONTROL SYSTEM

J. VIDEO SURVEILLANCE SYSTEM

6. REVIEW ALL OTHER DISCIPLINE PLANS FOR AREAS WHERE REMOVAL AND

REINSTALLATION OF EXISTING CEILINGS WILL BE REQUIRED TO ACCOMMODATE

THE DEMOLITION AND INSTALLATION OF DUCTWORK, PIPING, AND STRUCTURE.

A. PROVIDE TEMPORARY SUPPORT, RELOCATION, OR REMOVAL OF ALL

EXISTING ELECTRICAL AND ELECTRONIC SAFETY/SECURITY ITEMS

MOUNTED ON OR IN CEILINGS. REINSTALL THE SAME ITEMS TO MATCH

EXISTING CONDITIONS WHEN CEILING IS REINSTALLED.

B. COORDINATE WITH OTHER TRADES TO MODIFY ANY ITEMS ABOVE CEILINGS

AS REQUIRED TO ACCOMMODATE INSTALLATIONS, INCLUDING BUT NOT

LIMITED TO CONDUIT, JUNCTION BOXES, CABLE PATHWAYS, ETC.

C. FIELD-VERIFY EXTENT OF WORK REQUIRED; NOT ALL ITEMS ARE SHOWN

ON DRAWINGS.

D. COORDINATE WITH CONSTRUCTION MANAGER'S DIRECTIVES.

POWER GENERAL NOTES

MECH. PLATFORM

A201

UNIT A

UNIT C

UNIT B

PROJECT NO.

DRAWN

REVIEWED

No part of this drawing may be used or reproduced in any form or by any means, or stored in a database or retrieval system, without prior written permission of

GMB Copyright 2019 All Rights Reserved c

N O

R T

H

KEYPLAN

ISSUANCES

616.796.0200 www.gmb.com

B

IM

/5 -4

L

A K

E O

R

IO

N C

A R

P E

N T

E R

E L

E M

E N

T A

R Y

A D

D

IT

IO

N

S A

N D

R E

N O

V A

T

IO

N S

/5 -4

E

.r v t

/2

/2

:5

:5

A M

E2.1A

5-4744

UNIT 'A' POWER PLAN

MCK

JB / AAB / BJH

C A

R P

E N

T E

R S

IT

E

B

U

IL

D

IN

G I

M P

R O

V E

M E

N T

S

L A

K E

O R

IO

N

C O

M M

U N

IT

Y

S C

H O

O L

S

L A

K E

O R

IO

N

M

IC

H

IG

N

O

R

1/8" = 1'-0"

UNIT 'A' POWER PLAN

ELECTRICAL KEYNOTES

C02 (1) 4" CONDUIT SLEEVE FOR DIV. 27 COMMUNICATIONS

CABLING WITH FIRESTOPPING FITTINGS

P02 BARRIER-FREE AUTOMATIC DOOR OPERATOR, FURNISHED

AND INSTALLED BY ARCH. TRADES, WIRED BY DIV. 26 PER

MANUFACTURER'S INSTALLATION INSTRUCTIONS. INTERFACE

AS REQUIRED WITH ACCESS CONTROL SYSTEM PER SECTION

28 13 00.

P03 INSTALL ALL DEVICES UNDER MILLWORK DESK ON

DUAL-CHANNEL (POWER & COMMUNICATIONS) SURFACE

RACEWAY SYSTEM PER SECTION 26 05 35. COORDINATE

CUTOUTS IN VERTICAL WORKSURFACE SUPPORTS WITH

MILLWORK CONTRACTOR TO PERMIT INSTALLATION AND

REMOVAL OF RACEWAY COVER SECTIONS. FEED RACEWAY

FROM FIXED WALL WITH AT LEAST (2) 1-1/4" OR (3) 1" COMM.

CONDUITS CONCEALED IN WALL AND COUPLED TO RACEWAY

WITH WALL BOX TRANSITION FITTING. ROUTE CONDUITS UP

ADJACENT WALL AND STUB OUT ABOVE ACCESSIBLE CEILING.

CONFIRM EXACT DEVICE LOCATIONS WITH OWNER PRIOR TO

INSTALLATION ONCE FURNITURE PLANS HAVE BEEN

DEVELOPED.

P05 UNDERGROUND CONDUITS FOR FLOOR BOX(ES), ROUTED

OVER TO AND UP NEW WALL TO ABOVE ACCESSIBLE

SUSPENDED CEILING SPACE. COORDINATE CONCRETE

FLOOR CUTTING AND PATCHING W/ ARCH. TRADES.

P08 RECONNECT NEW RECEPTACLE TO EXISTING BRANCH

CIRCUIT AS EXTENDED FROM FORMER TELEVISION OR VIDEO

PROJECTOR LOCATION (REFER TO DEMOLITION PLAN).

MODIFY CONDUIT/RACEWAYS AND CONDUCTORS AS REQ'D.

P10 CONNECT RECEPTACLE TO NEAREST EXISTING 20A

RECEPTACLE BRANCH CIRCUIT WITH AVAILABLE CAPACITY.

IDENTIFY CIRCUIT ON AS-BUILT DOCUMENTS.

P11 INSTALL RECEPTACLE INSIDE BACK OF NEW WALL-MOUNTED

EQUIPMENT RACK FOR GYMNASIUM AUDIO SYSTEM;

COORDINATE EXACT LOCATION WITH AUDIO-VIDEO SYSTEMS

CONTRACTOR (SEPARATE BID PACKAGE).

P12 COORDINATE COMMUNICATIONS CONNECTIONS REQUIRED

FOR MONITORING AND NETWORK ADMINISTRATION OF

ELECTRONIC SAFETY/SECURITY EQUIPMENT WITH OWNER,

OWNER'S MONITORING SERVICE PROVIDER(S), AND OWNER'S

COMMUNICATIONS CONTRACTOR. ALL CONNECTIONS SHALL

BE PROTECTED FROM TAMPERING AND ACCIDENTAL

DISCONNECTION.

P16 ALTERNATE G-1 (TOILET) LAYOUT IS SHOWN FOR THIS ROOM.

FOR BASE BID, DELETE FIRE ALARM NOTIFICATION APPLIANCE

AND PLUMBING FIXTURE PSU CONNECTION, PLACE STANDARD

DUPLEX RECEPTACLE ADJACENT TO STRIKE SIDE OF DOOR.

N O

R

MECH. PLATFORM POWER PLAN

12.12.2019BIDS &

CONSTRUCTION

04.14.2020BULLETIN 002

07.01.2020BULLETIN 008

07.24.2020BULLETIN 010

IDF

General Data (1 drop per triangle unless noted)

PA – PA Buttons

Wireless AP

AV Cabling (IFP or Audio Ehancement Box)

Clock

PA Speaker

Digital Clock (see note below)

Dual-sided Digital Clock (see note below)

Audio Enhancement/PA (4 equally spaced speakers)

Teacher location

S

D

D2

T

Lake Orion Community Schools Carpenter Elementary - Technology

Prepared by Plante Moran

D

P

W

A

C

A V

A V

A V

F

AV

A V

AVAV

A V

AV

A V

A

VA

V

A V

V V

A V

A V

AV AV

FACP IDS

D D

CRD IC

SC

FS

15 15

1/2

M

KP

D

A

E

1/12

C R

1/2

D

EX. 480V UTILITY

XFMR

EX. PANEL 'DP2'

EX. METER C/T

CABINET

EX. UTILITY ELEC.

METER

EX. PANEL 'BH'

EX. PANEL 'BF'

EX. PANEL 'AE'

PANEL 'A1'

B-20.1B-20.2 P-20.2 P-20.1

EX. CHWP

EX. PANEL

'DP2'

BH-11

RTU-20.2 SUPPLY

ON ROOF

CLOSET

B103

CLASSROOM

B102

GIRLS

B104

BOYS

B105

TOILET

B106

CLOSET

B109

GIRLS

B110

BOYS

B111

TOILET

B112

CLASSROOM

B108

CLASSROOM

B107

CLASSROOM

B113

TOILET

B123

TOILET

B124

STORAGE

B126

JAN

B125

FOOD SERVICE

B127

ELECTRICAL

B133

STORAGE

B132

STORAGE

B120

CONFERENCE

B122

MECH

B121

CLOSET

B114

TOILETS

B116

CLASSROOM

B115

CLOSET

B119

TOILETS

B118

CLASSROOM

B117

CORRIDOR

B101

PLATFORM

B130

GREEN

B131

STORAGE

B129

CAFETERIA

B128

RTU-20.2 EXHAUST

ON ROOF

RELOC. EX. HWRP

44"

TO SOUTH/EAST SITE LIGHTING

POLES; REFER TO SHEET ES2.01

BH-15

BH-4BH-2

E7.01

E7.01

E7.01 8

P08

P08

P08

P08 P08

P08 C-27 C-28

C-29

DOM. HW HEATER

BH-8

BH-6

GFT-20.1

BH-3

EX. PANEL

'DP2'

P12

L05

P10

L03

RTU LTS &

RECEPTS

EX. KITCHEN EXH. HOOD

FIRE PROTECTION

INSTALL ON EX. MAU

DUCTS BELOW ROOF

P10

1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.01.

2. REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

3. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF SMOKE DAMPERS AND

COMBINATION FIRE/SMOKE DAMPERS. E.C. SHALL PROVIDE 120VAC POWER

FROM DEDICATED 20A/1P BRANCH CIRCUIT (WITH BREAKER LOCKING

MECHANISM) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA (DAMPERS

MAY BE GROUPED ON EACH CIRCUIT), TERMINATED W/ BOX-COVER FUSIBLE

SWITCH AT EACH DAMPER. ALSO PROVIDE FIRE ALARM DUCT SMOKE

DETECTOR WITHIN 5 FEET OF EACH DAMPER (UNLESS COVERED BY ANOTHER

DUCT DETECTOR WITHIN 5 FEET) AND A FIRE ALARM ADDRESSABLE RELAY FOR

INTERLOCKING DAMPER W/ CORRESPONDING HVAC UNIT PER CODE

REQUIREMENTS.

4. PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN

ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR

PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS

CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES

INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST

FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.

5. COORDINATE THE INSTALLATION AND ROUGH-IN REQUIREMENTS (BOXES,

CONDUIT, ETC. IN WALLS AND CEILINGS) FOR THE FOLLOWING SYSTEMS WITH

COMMUNICATIONS AND ELECTRONIC SAFETY/SECURITY CONTRACTORS

ENGAGED VIA SEPARATE BID PACKAGE(S) (NOT IN THIS CONTRACT), INCLUDING

BUT NOT LIMITED TO:

A. NETWORK CABLING SYSTEMS

B. NETWORK ELECTRONICS (SWITCHES, ACCESS POINTS, ETC.)

C. TELEPHONE SYSTEMS

D. INSTRUCTIONAL TECHNOLOGY EQUIPMENT

E. AUDIO-VIDEO SYSTEMS AND EQUIPMENT

F. INTERIOR DIGITAL SIGNAGE SYSTEM AND DISPLAYS

G. INTERCOM/PAGING SYSTEM

H. DISTRIBUTED CLOCK SYSTEM

I. ACCESS CONTROL SYSTEM

J. VIDEO SURVEILLANCE SYSTEM

6. REVIEW ALL OTHER DISCIPLINE PLANS FOR AREAS WHERE REMOVAL AND

REINSTALLATION OF EXISTING CEILINGS WILL BE REQUIRED TO ACCOMMODATE

THE DEMOLITION AND INSTALLATION OF DUCTWORK, PIPING, AND STRUCTURE.

A. PROVIDE TEMPORARY SUPPORT, RELOCATION, OR REMOVAL OF ALL

EXISTING ELECTRICAL AND ELECTRONIC SAFETY/SECURITY ITEMS

MOUNTED ON OR IN CEILINGS. REINSTALL THE SAME ITEMS TO MATCH

EXISTING CONDITIONS WHEN CEILING IS REINSTALLED.

B. COORDINATE WITH OTHER TRADES TO MODIFY ANY ITEMS ABOVE CEILINGS

AS REQUIRED TO ACCOMMODATE INSTALLATIONS, INCLUDING BUT NOT

LIMITED TO CONDUIT, JUNCTION BOXES, CABLE PATHWAYS, ETC.

C. FIELD-VERIFY EXTENT OF WORK REQUIRED; NOT ALL ITEMS ARE SHOWN

ON DRAWINGS.

D. COORDINATE WITH CONSTRUCTION MANAGER'S DIRECTIVES.

POWER GENERAL NOTES

UNIT A

UNIT C

UNIT B

PROJECT NO.

DRAWN

REVIEWED

No part of this drawing may be used or reproduced in any form or by any means, or stored in a database or retrieval system, without prior written permission of

GMB Copyright 2019 All Rights Reserved c

N O

R

616.796.0200 www.gmb.com

C

L o ca l

P ro je ct s\

-4

E

C E

N T

R A

L m at tk al

.r v t

/1

/2

:0

:2

A M

E2.1B

5-4744

UNIT 'B' POWER PLAN

MCK

JB / AAB / BJH

C A

R P

E N

T E

R S

IT

E

B

U

IL

D

IN

G I

M P

R O

V E

M E

N T

S

L A

K E

O R

IO

N

C O

M M

U N

IT

Y

S C

H O

O L

S

L A

K E

O R

IO

N

M

IC

H

IG

R

UNIT 'B' POWER PLAN

ELECTRICAL KEYNOTES

L03 NEW BMS/ATC CONTROL RELAYS FURNISHED AND INSTALLED

BY SEPARATE BID PACKAGE FOR PILOT CONTROL OF NEW

EXTERIOR LIGHTING CONTROL CONTACTOR(S) BY SECTION 26

09 19. BMS/ATC CONTRACTOR SHALL PROVIDE CONTROL

WIRING, INTEGRATION INTO SYSTEM, AND APPLY AN

ASTRONOMIC TIME SCHEDULE IN PROGRAMMING FOR

EXTERIOR LIGHTING ZONES PER ENERGY CODE

REQUIREMENTS.

L05 RELOCATE EXISTING LIGHT FIXTURES IN ROOM AS

NECESSARY TO ACCOMMODATE MECHANICAL EQUIPMENT,

DUCTWORK, AND PIPING MODIFICATIONS. ARRANGE LIGHT

FIXTURES FOR OPTIMAL ILLUMINATION OF ALL WORKING

AREAS.

P08 RECONNECT NEW RECEPTACLE TO EXISTING BRANCH

CIRCUIT AS EXTENDED FROM FORMER TELEVISION OR VIDEO

PROJECTOR LOCATION (REFER TO DEMOLITION PLAN).

MODIFY CONDUIT/RACEWAYS AND CONDUCTORS AS REQ'D.

P10 CONNECT RECEPTACLE TO NEAREST EXISTING 20A

RECEPTACLE BRANCH CIRCUIT WITH AVAILABLE CAPACITY.

IDENTIFY CIRCUIT ON AS-BUILT DOCUMENTS.

P12 COORDINATE COMMUNICATIONS CONNECTIONS REQUIRED

FOR MONITORING AND NETWORK ADMINISTRATION OF

ELECTRONIC SAFETY/SECURITY EQUIPMENT WITH OWNER,

OWNER'S MONITORING SERVICE PROVIDER(S), AND OWNER'S

COMMUNICATIONS CONTRACTOR. ALL CONNECTIONS SHALL

BE PROTECTED FROM TAMPERING AND ACCIDENTAL

DISCONNECTION.

12.12.2019BIDS &

CONSTRUCTION

07.01.2020BULLETIN 008

General Data (1 drop per triangle unless noted)

PA – PA Buttons

Wireless AP

AV Cabling (IFP or Audio Ehancement Box)

Clock

PA Speaker

Digital Clock (see note below)

Dual-sided Digital Clock (see note below)

Audio Enhancement/PA (4 equally spaced speakers)

Teacher location

S

D

D2

T

Lake Orion Community Schools Carpenter Elementary - Technology

Prepared by Plante Moran

D

P

W

A

C

B F

BF BF

BF BF

B F

B F

B F B

F

BF

BFBF

BF

BF

BF BF

BF

BF

BF

B F

AV

A V

A V

A V

A V

A V

A V

AV

A V

A V

AV

AV

A V

AV

AV

AV

AV

AV

AV

A V

A V

AV

A V

A V

AV

A

V

AV

AV

A V

A

AV

M

S S

S S

1/8

1/8

1/6

C C

S S S

V

CR

1/12

S

N

PANEL 'D'

EX. PANEL 'AA'

EX. PANEL 'AB'

EX. PANEL 'AC'

PANEL 'A2'

PANEL 'B2'

PANEL 'A3'

20"

20"

20"

20" 20"

44" 44"

CUH-20.2

CUH-20.1

EF-20.3

ON ROOF

RTU-20.3

ON ROOF

VUV-20.3

VUV-20.1 VUV-20.2

GFCI

44"

GFCI

44" 44"

GFCI

44"

CORD REEL

CLG

CLG

CLG CLG

CLG

CLG

CORD REEL

CORD REEL

CORD REEL

CORD REEL

CORD REEL

WB1

48"

WL

GFCI

WL

GFCI

WL

GFCI

GFCI

44"

WB1

48"

44"

WB1

48"

WB1

48"

EX. PANEL

'DP2'

CLOSET

C164

CLASSROOM

C163

STORAGE

C167

GIRLS

C165

BOYS

C166

STORAGE

C168

CLASSROOM

C169

CLOSET

C157

CLASSROOM

C162

STORAGE

C161

STORAGE

C160

GIRLS

C158

BOYS

C159

CLOSET

C171

CLASSROOM

C170

STORAGE

C174

GIRLS

C172

BOYS

C173

STORAGE

C175

CLOSET

C150

CLASSROOM

C155

STORAGE

C154

STORAGE

C153

GIRLS

C151

BOYS

C152

CLASSROOM

C176

CLASSROOM

C149

CLASSROOM

C147

CLASSROOM

C140

JAN

C146

STORAGE

C141 CLOSET

C142

STORAGE

C143

GIRLS

C144

BOYS

C145

KILN

C125

CLASSROOM

C124

CLASSROOM

C127

CLOSET

C129

LOUNGE

C128

CLOSET

C130

MUSIC

C131

OFFICE

C121

OFFICE

C122

STORAGE

C123

WOMEN

C132

MEN

C133

GIRLS

C134

JAN

C135

BOYS

C136

CLOSET

C138

LRC

C137

MEDIA CENTER

C120

OFFICE

C107

STOR

C115

OFFICE

C104

OFFICE

C106

OFFICE

C117

VEST

C108

OFFICE

C103

OFFICE

C105

ELEC

C113

CORRIDOR

C109

OFFICE

C102

STOR

C111

CLASSROOM

C116

CLASSROOM

C114

CLASSROOM

C110

JAN

C112

CORRIDOR

C101

CORRIDOR

C119

CORRIDOR

C148

CLASSROOM

C156

MEDIA PROD

C126A

TELECOMM

C122A

CORRIDOR

C139

FLOOR

EX. DWH

WB1

48"

20"

D-1

D-8

D-9

D-12

D-3 D-7

D-22

D-5 D-10

D-20

D-21

D-25

D-23

D-19 D-2

D-17

D-18

D-16 D-15

D-6

D-13

D-4

D-11

D-14

E7.01 8

E7.01

8 SIM

E7.01

TYP.

P05

P06

P07

44"

EX. UVEX. UV

GFCI

40"

A3-20

A3-19

A3-31

A3-16

A3-30

A3-28

REPLACE RECEPT.

IN EX. FLOOR BOX

AB-24

AB-22

P08

P08

P08

P08 P08

P08

P08

P08

P08

P08

P08

P08 P08

P08

EX. BMS/ATC PANEL(S)

A3-39,41

A3-37

PP-1

A3-18

P14

P13

P13

P15

C04

C08

C01

C01

D-31

CUA-20.1

ON ROOF

ACU-20.1

AB-34,36

WL GFCI

ON ROOF

1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.01.

2. REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

3. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF SMOKE DAMPERS AND

COMBINATION FIRE/SMOKE DAMPERS. E.C. SHALL PROVIDE 120VAC POWER

FROM DEDICATED 20A/1P BRANCH CIRCUIT (WITH BREAKER LOCKING

MECHANISM) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA (DAMPERS

MAY BE GROUPED ON EACH CIRCUIT), TERMINATED W/ BOX-COVER FUSIBLE

SWITCH AT EACH DAMPER. ALSO PROVIDE FIRE ALARM DUCT SMOKE

DETECTOR WITHIN 5 FEET OF EACH DAMPER (UNLESS COVERED BY ANOTHER

DUCT DETECTOR WITHIN 5 FEET) AND A FIRE ALARM ADDRESSABLE RELAY FOR

INTERLOCKING DAMPER W/ CORRESPONDING HVAC UNIT PER CODE

REQUIREMENTS.

4. PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN

ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR

PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS

CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES

INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST

FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.

5. COORDINATE THE INSTALLATION AND ROUGH-IN REQUIREMENTS (BOXES,

CONDUIT, ETC. IN WALLS AND CEILINGS) FOR THE FOLLOWING SYSTEMS WITH

COMMUNICATIONS AND ELECTRONIC SAFETY/SECURITY CONTRACTORS

ENGAGED VIA SEPARATE BID PACKAGE(S) (NOT IN THIS CONTRACT), INCLUDING

BUT NOT LIMITED TO:

A. NETWORK CABLING SYSTEMS

B. NETWORK ELECTRONICS (SWITCHES, ACCESS POINTS, ETC.)

C. TELEPHONE SYSTEMS

D. INSTRUCTIONAL TECHNOLOGY EQUIPMENT

E. AUDIO-VIDEO SYSTEMS AND EQUIPMENT

F. INTERIOR DIGITAL SIGNAGE SYSTEM AND DISPLAYS

G. INTERCOM/PAGING SYSTEM

H. DISTRIBUTED CLOCK SYSTEM

I. ACCESS CONTROL SYSTEM

J. VIDEO SURVEILLANCE SYSTEM

6. REVIEW ALL OTHER DISCIPLINE PLANS FOR AREAS WHERE REMOVAL AND

REINSTALLATION OF EXISTING CEILINGS WILL BE REQUIRED TO ACCOMMODATE

THE DEMOLITION AND INSTALLATION OF DUCTWORK, PIPING, AND STRUCTURE.

A. PROVIDE TEMPORARY SUPPORT, RELOCATION, OR REMOVAL OF ALL

EXISTING ELECTRICAL AND ELECTRONIC SAFETY/SECURITY ITEMS

MOUNTED ON OR IN CEILINGS. REINSTALL THE SAME ITEMS TO MATCH

EXISTING CONDITIONS WHEN CEILING IS REINSTALLED.

B. COORDINATE WITH OTHER TRADES TO MODIFY ANY ITEMS ABOVE CEILINGS

AS REQUIRED TO ACCOMMODATE INSTALLATIONS, INCLUDING BUT NOT

LIMITED TO CONDUIT, JUNCTION BOXES, CABLE PATHWAYS, ETC.

C. FIELD-VERIFY EXTENT OF WORK REQUIRED; NOT ALL ITEMS ARE SHOWN

ON DRAWINGS.

D. COORDINATE WITH CONSTRUCTION MANAGER'S DIRECTIVES.

POWER GENERAL NOTES

UNIT A

UNIT C

UNIT B

PROJECT NO.

DRAWN

REVIEWED

No part of this drawing may be used or reproduced in any form or by any means, or stored in a database or retrieval system, without prior written permission of

GMB Copyright 2019 All Rights Reserved c

N O

R

616.796.0200 www.gmb.com

B

IM

/5 -4

L

A K

E O

R

IO

N C

A R

P E

N T

E R

E L

E M

E N

T A

R Y

A D

D

IT

IO

N

S A

N D

R E

N O

V A

T

IO

N S

/5 -4

E

.r v t

/1

/2

:0

:2

P

E2.1C

5-4744

UNIT 'C' POWER PLAN

MCK

JB / AAB / BJH

C A

R P

E N

T E

R S

IT

E

B

U

IL

D

IN

G I

M P

R O

V E

M E

N T

S

L A

K E

O R

IO

N

C O

M M

U N

IT

Y

S C

H O

O L

S

L A

K E

O R

IO

N

M

IC

H

IG

R

UNIT 'C' POWER PLAN

ELECTRICAL KEYNOTES

C01 (1) 4" CONDUIT SLEEVE FOR DIV. 27 COMMUNICATIONS

CABLING

C04 (2) 4" CONDUIT SLEEVES FOR DIV. 27 COMMUNICATIONS

CABLING WITH FIRESTOPPING FITTINGS

C08 PROTECT EX. COMMUNICATIONS EQUIPMENT, RACKS, AND

ASSOCIATED CABLING FROM THE INGRESS OF DUST AND

DEBRIS DURING CONSTRUCTION PERIOD. COORDINATE ANY

REQUIRED TEMPORARY DISCONNECTION OF POWER OR

COMMUNICATIONS CABLING WITH THE OWNER AND

CONSTRUCTION MANAGER.

P05 UNDERGROUND CONDUITS FOR FLOOR BOX(ES), ROUTED

OVER TO AND UP NEW WALL TO ABOVE ACCESSIBLE

SUSPENDED CEILING SPACE. COORDINATE CONCRETE

FLOOR CUTTING AND PATCHING W/ ARCH. TRADES.

P06 ESTABLISH NEW CONCRETE-ENCASED GROUNDING

ELECTRODE IN FOOTING OF NEW ADDITION, INTERCONNECT

WITH GROUNDING ELECTRODE SYSTEM AT SERVICE

ENTRANCE OR NEAREST SEPARATELY-DERIVED SYSTEM PER

NEC AND SPECIFICATION REQUIREMENTS.

P07 BOND METAL STRUCTURE OF ADDITION TO METAL

STRUCTURE OF EXISTING BUILDING PER NEC REQUIREMENTS.

P08 RECONNECT NEW RECEPTACLE TO EXISTING BRANCH

CIRCUIT AS EXTENDED FROM FORMER TELEVISION OR VIDEO

PROJECTOR LOCATION (REFER TO DEMOLITION PLAN).

MODIFY CONDUIT/RACEWAYS AND CONDUCTORS AS REQ'D.

P13 COORDINATE CUTOUTS IN ANY NEW FIXED CASEWORK OR

FURNITURE ALONG WALLS OR COLUMNS WITH

ARCHITECTURAL TRADES TO ENSURE THAT EXISTING

RECEPTACLES AND JUNCTION BOXES REMAIN ACCESSIBLE

PER NEC REQUIREMENTS; FIELD-VERIFY EXACT LOCATIONS

AND QUANTITIES.

P14 REINSTALL EX. RECESSED PAGING SPEAKER, BACKBOX

ENCLOSURE, AND GRILLE SALVAGED FROM BUILDING

EXTERIOR; STUB CONDUIT FROM ENCLOSURE TO INTERIOR

OF BUILDING ABOVE SUSPENDED CEILING, COORDINATE

SPLICING, EXTENSION, AND RECONNECTION OF PAGING

SYSTEM CABLING TO SPEAKER WITH COMMUNICATIONS

CONTRACTOR (SEPARATE BID PACKAGE).

P15 MOUNT CORD REELS TO STRUCTURE ABOVE SUSPENDED

CEILING SUCH THAT REELS ARE ACCESSIBLE AND CORDS

DROP DOWN THROUGH AND ARE CENTERED IN THE GAP

BETWEEN CEILING ELEMENTS. ADJUST CORD STOP SUCH

THAT RETRACTED HEIGHT OF BOX IS 8'-0" AFF.

12.12.2019BIDS &

CONSTRUCTION

07.01.2020BULLETIN 008

07.13.2020BULLETIN 009

MDF

Lake Orion Community Schools Webber Elementary - Technology

Prepared by Plante Moran Legend:

Interactive Flat Panel

General Data (1 drop per triangle unless noted)

PA – PA Buttons

Wireless AP

AV Cabling (IFP or Audio Ehancement Box)

Clock

PA Speaker

Digital Clock (see note below)

Dual-sided Digital Clock (see note below)

Audio Enhancement/PA (4 equally spaced speakers)

Teacher location

S

D

D2

T

D

P

W

A

C

BF

BF

BF

BF

BF

ID

S

A C

S

T

T

FAA

X

X

IC

KP

C R

CR CR

CR

CR CR

C R

D D D

M

M

M

S S

TS

TS

V

AV

AV

AV

AVAV

F B

A V

A V

A V

A V

A

S S

AV

AV

AV

AV

AV

F F

A V

AV

A V

A V

A V

AV

VF

VF

A

AV

C

ID

1/8

1/8

CRCR

AV

1/20

FS

C S C

ID

1/10

D

D

1/15

AV

D

D

1/8

1/20

1/2

TS

FS

A V

AV

AV

S

CR

1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.01.

2. REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

3. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF SMOKE DAMPERS AND

COMBINATION FIRE/SMOKE DAMPERS. E.C. SHALL PROVIDE 120VAC POWER

FROM DEDICATED 20A/1P BRANCH CIRCUIT (WITH BREAKER LOCKING

MECHANISM) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA (DAMPERS

MAY BE GROUPED ON EACH CIRCUIT), TERMINATED W/ BOX-COVER FUSIBLE

SWITCH AT EACH DAMPER. ALSO PROVIDE FIRE ALARM DUCT SMOKE

DETECTOR WITHIN 5 FEET OF EACH DAMPER (UNLESS COVERED BY ANOTHER

DUCT DETECTOR WITHIN 5 FEET) AND A FIRE ALARM ADDRESSABLE RELAY FOR

INTERLOCKING DAMPER W/ CORRESPONDING HVAC UNIT PER CODE

REQUIREMENTS.

4. PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN

ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR

PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS

CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES

INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST

FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.

5. COORDINATE THE INSTALLATION AND ROUGH-IN REQUIREMENTS (BOXES,

CONDUIT, ETC. IN WALLS AND CEILINGS) FOR THE FOLLOWING SYSTEMS WITH

COMMUNICATIONS AND ELECTRONIC SAFETY/SECURITY CONTRACTORS

ENGAGED VIA SEPARATE BID PACKAGE(S) (NOT IN THIS CONTRACT), INCLUDING

BUT NOT LIMITED TO:

A. NETWORK CABLING SYSTEMS

B. NETWORK ELECTRONICS (SWITCHES, ACCESS POINTS, ETC.)

C. TELEPHONE SYSTEMS

D. INSTRUCTIONAL TECHNOLOGY EQUIPMENT

E. AUDIO-VIDEO SYSTEMS AND EQUIPMENT

F. INTERIOR DIGITAL SIGNAGE SYSTEM AND DISPLAYS

G. INTERCOM/PAGING SYSTEM

H. DISTRIBUTED CLOCK SYSTEM

I. ACCESS CONTROL SYSTEM

J. VIDEO SURVEILLANCE SYSTEM

6. REVIEW ALL OTHER DISCIPLINE PLANS FOR AREAS WHERE REMOVAL AND

REINSTALLATION OF EXISTING CEILINGS WILL BE REQUIRED TO ACCOMMODATE

THE DEMOLITION AND INSTALLATION OF DUCTWORK, PIPING, AND STRUCTURE.

A. PROVIDE TEMPORARY SUPPORT, RELOCATION, OR REMOVAL OF ALL

EXISTING ELECTRICAL AND ELECTRONIC SAFETY/SECURITY ITEMS

MOUNTED ON OR IN CEILINGS. REINSTALL THE SAME ITEMS TO MATCH

EXISTING CONDITIONS WHEN CEILING IS REINSTALLED.

B. COORDINATE WITH OTHER TRADES TO MODIFY ANY ITEMS ABOVE CEILINGS

AS REQUIRED TO ACCOMMODATE INSTALLATIONS, INCLUDING BUT NOT

LIMITED TO CONDUIT, JUNCTION BOXES, CABLE PATHWAYS, ETC.

C. FIELD-VERIFY EXTENT OF WORK REQUIRED; NOT ALL ITEMS ARE SHOWN

ON DRAWINGS.

D. COORDINATE WITH CONSTRUCTION MANAGER'S DIRECTIVES.

POWER GENERAL NOTES

EX. PANEL 'AC'

PANEL 'BD'

EX. PANEL 'L1A'

PANEL 'BC'

SWBD. 'MSB'

XFMR 'T-C1'

PANEL 'DPC'

PANEL 'BE'

PANEL 'DPB'

EX. PANEL 'AD'

XFMR 'T-B1'

RTU-20.2

EXHAUST

ON ROOF

RTU-20.1

ON ROOF

MECHANICAL

B132

WOMENS TOILET

A130

MENS TOILET

A131

MECHANICAL

A138

OFFICE

A133

STORAGE

A141

JAN.

A134

STORAGE

A135

STORAGE

A136

CLASSROOM

A116

CLASSROOM

A115

OFFICE

B133

OFFICE

A129

OFFICE

A128

OFFICE

A105

MECHANICAL

A144

LRC

A126

OFFICE

A122

OFFICE

A123

OFFICE

A110

OFFICE

A111

OFFICE

B139

VESTIBULE

A118

MEDIA PRODUCTIONS

C102

ELECTRICAL

C127

OFFICE

A143

CORRIDOR

A127

CONFERENCE

A109

OFFICE

A108

TOILET

A106

KITCHEN

A140

CAFETERIA

A137

STORAGE

A142

CORRIDOR

A112

LRC

A125

CORRIDOR

A117

MECHANICAL

A119

WORK AREA

A107

CLASSROOM

A120

VESTIBULE

A101

RECEPTION

A103

CLINIC

A104

VESTIBULE

A113

OFFICE

B138

OFFICE

A132

CORRIDOR

A114

CORRIDOR

A121

CLASSROOM

A124

WAITING

A102

VUV-20.02 VUV-20.01

VUV-20.04

VUV-20.03

EHD EHD

EHD EHD

WB1

48"

WB1

48"

WB1

48"

WB1

64"

E7.01

E7.01 8

E7.01

8 SIM

WL

CUH-20.2

CUH-20.1

UH-20.2

GFCI

U.G. COMM. CONDUITS TO ORION ART

CENTER (MOOSE TREE) BLDG. AND

POWER / COMM. CONDUITS TO FUTURE

SITE SIGN, ROUTED UP IN CHASE AND

STUBBED OUT ABOVE SUSPENDED

CEILING; REFER TO SITE ELECTRICAL

PLAN, SHEET E2.01 FOR CONTINUATION

WL

GFCI

WL

GFCI

WL

GFCI

44"

44" 44"

44"

8"x2" CABLE TRAY

B-20.1

AC-14

P08

P08

P08

P08

C07

44"

44"

44" 44"

44"

44"

44"

44"

44"

P05

P02 P02

P03 P03

EX. EXH. HOOD

FIRE PROTECTION

E7.01

TYP.

C09

PANEL 'DP2'

EX. PANEL

'DP1'

AHU-20.1 EXHAUSTAHU-20.1 SUPPLY

EF-20.1

ON ROOF

PANEL 'DP2'

E7.01

8 SIM

CUH-20.3

UH-20.1

BCU-20.1

44"

44" 44"

CLG

CLG

CLG

CLG

CLG

CLG

GFCI

44"

BE-29

BMS/ATC PANEL(S)

E7.01

44"

BE-35 BE-37

BE-39 BE-41

L1A-4

L1A-3

L1A-1

L1A-19

L1A-2

L1A-9

L1A-7

L1A-6 L1A-12

L1A-14L1A-11

L1A-23

L1A-13

L1A-17

L1A-16

L1A-20

L1A-22

L1A-15

BE-28

BF-12

C05

C05

GFCI

GFCI

BC-26 BC-20

BC-22

BC-24

BC-32

BC-12 BC-19

BC-23 BC-21 BC-31

BC-34

BC-36

BC-37

BC-35

AC-20

PANEL 'DP2'

AHU LTS &

RECEPTS

L1A-21

CA-14

CA-13

PBB

C08

AC-13

AC-7

AC-8

AC-9

AC-12

AC-11

AC-10

AC-18

AC-5

AC-6

AC-2

EX. EF

L1A-18

C02

C02 C03

C05

C03

RTU-20.2

SUPPLY

ON ROOF

PANEL 'DP2'

RTU LTS &

RECEPTS

PANEL 'BE'

E7.01

L1A-5

P06

P07

P11 P11

P13

PLUMB. FIXTURE PSU

ABOVE CLG.

PLUMB. FIXTURE PSU

ABOVE CLG.

WB1

48"

LRC

A126B

C03

BC-39

P04

ENABLES/DISABLES

"EVENT" SEQUENCE

M M

M M

M

UNIT A

UNIT C

UNIT B

UNIT D

ADDITIONEXISTING

NORTH KEYPLAN

PROJECT NO.

DRAWN

REVIEWED

No part of this drawing may be used or reproduced in any form or by any means, or stored in a database or retrieval system, without prior written permission of

GMB Copyright 2019 All Rights Reserved c

ISSUANCES

616.796.0200 www.gmb.com

B

IM

/5 -4

L

A K

E O

R

IO

N W

E B

B E

R E

L E

M E

N T

A R

Y A

D D

IT

IO

N S

A N

D R

E N

O V

A T

IO

N

S /5

-4

E

.r v t

/2

/2

:5

:0

P M

E2.1A

5-4740

UNIT 'A' POWER PLAN

MCK

RDG

W E

B B

E R

E L

E M

E N

T A

R Y

S

IT

E A

N D

B U

IL

D

IN

G

I M

P R

O V

E M

E N

T S

L A

K E

O R

IO

N

C O

M M

U N

IT

Y

S C

H O

O L

S

L A

K E

O R

IO

N

M

IC

H

IG

ELECTRICAL KEYNOTES

C02 (2) 12.6 SQ. IN. CABLE PATHWAY PENETRATION DEVICE (FIRE)

PER SECTION 27 05 28

C03 (2) 4" CONDUIT SLEEVES FOR DIV. 27 COMMUNICATIONS

CABLING

C05 (2) 6 SQ. IN. CABLE PATHWAY PENETRATION DEVICE (FIRE)

PER SECTION 27 05 28

C07 (3) 2" CONDUIT SLEEVES FOR DIV. 27 COMMUNICATIONS

CABLING

C08 (2) 6.7 SQ. IN. CABLE PATHWAY PENETRATION DEVICE

(SMOKE) PER SECTION 27 05 28

C09 PROTECT EX. COMMUNICATIONS EQUIPMENT, RACKS, AND

ASSOCIATED CABLING FROM THE INGRESS OF DUST AND

DEBRIS DURING CONSTRUCTION PERIOD. COORDINATE ANY

REQUIRED TEMPORARY DISCONNECTION OF POWER OR

COMMUNICATIONS CABLING WITH THE OWNER AND

CONSTRUCTION MANAGER.

P02 BARRIER-FREE AUTOMATIC DOOR OPERATOR, FURNISHED

AND INSTALLED BY ARCH. TRADES, WIRED BY DIV. 26 PER

MANUFACTURER'S INSTALLATION INSTRUCTIONS. INTERFACE

AS REQUIRED WITH ACCESS CONTROL SYSTEM PER SECTION

28 13 00.

P03 INSTALL ALL DEVICES UNDER MILLWORK DESK ON

DUAL-CHANNEL (POWER & COMMUNICATIONS) SURFACE

RACEWAY SYSTEM PER SECTION 26 05 35. COORDINATE

CUTOUTS IN VERTICAL WORKSURFACE SUPPORTS WITH

MILLWORK CONTRACTOR TO PERMIT INSTALLATION AND

CONTINUED REMOVAL OF RACEWAY COVER SECTIONS.

CONFIRM EXACT DEVICE LOCATIONS WITH OWNER PRIOR TO

INSTALLATION ONCE FURNITURE PLANS HAVE BEEN

DEVELOPED.

P04 DUAL-CHANNEL (POWER & COMMUNICATIONS) SURFACE

RACEWAY SYSTEM AS SPECIFIED, CONTINUOUS RUN WITH

SINGLE VERTICAL DROP FROM ACCESSIBLE CEILING SPACE

AND ACTIVATIONS/FITTINGS AS INDICATED.

P05 UNDERGROUND CONDUITS FOR FLOOR BOX(ES), ROUTED

OVER TO AND UP NEW WALL TO ABOVE ACCESSIBLE

SUSPENDED CEILING SPACE. COORDINATE CONCRETE

FLOOR CUTTING AND PATCHING W/ ARCH. TRADES.

P06 ESTABLISH NEW CONCRETE-ENCASED GROUNDING

ELECTRODE IN FOOTING OF NEW ADDITION, INTERCONNECT

WITH GROUNDING ELECTRODE SYSTEM AT SERVICE

ENTRANCE OR NEAREST SEPARATELY-DERIVED SYSTEM PER

NEC AND SPECIFICATION REQUIREMENTS.

P07 BOND METAL STRUCTURE OF ADDITION TO METAL

STRUCTURE OF EXISTING BUILDING PER NEC REQUIREMENTS.

P08 RECONNECT NEW RECEPTACLE TO EXISTING BRANCH

CIRCUIT AS EXTENDED FROM FORMER TELEVISION OR VIDEO

PROJECTOR LOCATION (REFER TO DEMOLITION PLAN).

MODIFY CONDUIT/RACEWAYS AND CONDUCTORS AS REQ'D.

P11 RECESS BOXES FOR DEVICES SHOWN IN EX. MASONRY WALL,

DRILL THROUGH WALL TO CONNECT REQ'D CONDUIT

PATHWAYS, AND ROUTE SURFACE-MOUNTED

CONDUIT/RACEWAY WITHIN ADJACENT STORAGE ROOM TO

ABOVE SUSPENDED CEILING

P13 FEED SURFACE RACEWAY UNDER MILLWORK RECEPTION

DESK FROM ACCESSIBLE CEILING WITH VERTICAL

DUAL-CHANNEL (POWER & COMMUNICATIONS) SURFACE

RACEWAY SYSTEM PER SECTION 26 05 35 ON WALL. MAKE

CONNECTIONS BEHIND DESK AND ABOVE WALL-MOUNTED

FIN-TUBE RADIANT HEAT UNIT WHERE NOT VISIBLE YET

ACCESSIBLE. MAKE POWER CONNECTIONS WITH 3/4" OR

LARGER FMC CONDUIT. PROVIDE GROMMETED OPENINGS ON

BOTH RACEWAYS TO FACILITATE ROUTING OF

COMMUNICATIONS/SECURITY CABLES ACROSS THE GAP

THROUGH A HOLE IN BACK OF DESK; FREE AREA SHALL BE AT

LEAST (2) 1-1/4" TRADE DIA. OR EQUIVALENT.

NORTH 1/8" = 1'-0"

UNIT 'A' POWER PLAN

01.22.2020BIDS &

CONSTRUCTION

02.06.2020ADDENDUM 001

03.10.2020BULLETIN 001

04.21.2020BULLETIN 003

07.24.2020BULLETIN 011

T

T

T

T

DD

D2

D

D

D D

D

D2

D

D

D

D

D D

NOTES

Clock installation requirements:

* Height of box needed for the clocks: 7.5 ft from the ground to bottom of the box, or 4” from the ceiling to top of the box, whichever is lower.

* Size of the box needed at classroom and office: 2-gang box

* Size of the box needed at hallways: 2-gang box

NOTES

Clock installation requirements:

* Height of box needed for the clocks: 7.5 ft from the ground to bottom of the box, or 4” from the ceiling to top of the box, whichever is lower.

* Size of the box needed at classroom and office: 2-gang box

* Size of the box needed at hallways: 2-gang box

W W

D

2A

D

2A

2A D

W

W

2D 2D

D

W

2A

D

D

D

W

W

2D2D

2D

DW

2D

D

D

W

D

D

D

D

D

D D

D

A

D2

D

S S

S

S S

S

S

S

S

S

S

S

S

S

S

S

S

S

Strobe

WW

W

D

D

W

W

D

Prepared by Plante Moran Legend:

Interactive Flat Panel

General Data (1 drop per triangle unless noted)

PA – PA Buttons

Wireless AP

AV Cabling (IFP or Audio Ehancement Box)

Clock

PA Speaker

Digital Clock (see note below)

Dual-sided Digital Clock (see note below)

Audio Enhancement/PA (4 equally spaced speakers)

Teacher location

S

D

D2

T

D

P

W

A

C

DN

B F

BF

BF

BF

BF

BF

BF

BF B

F

B F

B F

B F

T

ID

S

A C

S

T

AV

A V

A V

A

A

V

A V

S

V

A V

AV

AV

V

F

AV

F A

V

AV

AV

AV

A V

AV

AV

A V

ID

1/15

1/6

1/10

D

1/20

A V

S S

S

S

A V

D

D

D

D

D

D D

D

AV

AV

F

7.5

3 1515

1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.01.

2. REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

3. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF SMOKE DAMPERS AND

COMBINATION FIRE/SMOKE DAMPERS. E.C. SHALL PROVIDE 120VAC POWER

FROM DEDICATED 20A/1P BRANCH CIRCUIT (WITH BREAKER LOCKING

MECHANISM) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA (DAMPERS

MAY BE GROUPED ON EACH CIRCUIT), TERMINATED W/ BOX-COVER FUSIBLE

SWITCH AT EACH DAMPER. ALSO PROVIDE FIRE ALARM DUCT SMOKE

DETECTOR WITHIN 5 FEET OF EACH DAMPER (UNLESS COVERED BY ANOTHER

DUCT DETECTOR WITHIN 5 FEET) AND A FIRE ALARM ADDRESSABLE RELAY FOR

INTERLOCKING DAMPER W/ CORRESPONDING HVAC UNIT PER CODE

REQUIREMENTS.

4. PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN

ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR

PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS

CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES

INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST

FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.

5. COORDINATE THE INSTALLATION AND ROUGH-IN REQUIREMENTS (BOXES,

CONDUIT, ETC. IN WALLS AND CEILINGS) FOR THE FOLLOWING SYSTEMS WITH

COMMUNICATIONS AND ELECTRONIC SAFETY/SECURITY CONTRACTORS

ENGAGED VIA SEPARATE BID PACKAGE(S) (NOT IN THIS CONTRACT), INCLUDING

BUT NOT LIMITED TO:

A. NETWORK CABLING SYSTEMS

B. NETWORK ELECTRONICS (SWITCHES, ACCESS POINTS, ETC.)

C. TELEPHONE SYSTEMS

D. INSTRUCTIONAL TECHNOLOGY EQUIPMENT

E. AUDIO-VIDEO SYSTEMS AND EQUIPMENT

F. INTERIOR DIGITAL SIGNAGE SYSTEM AND DISPLAYS

G. INTERCOM/PAGING SYSTEM

H. DISTRIBUTED CLOCK SYSTEM

I. ACCESS CONTROL SYSTEM

J. VIDEO SURVEILLANCE SYSTEM

6. REVIEW ALL OTHER DISCIPLINE PLANS FOR AREAS WHERE REMOVAL AND

REINSTALLATION OF EXISTING CEILINGS WILL BE REQUIRED TO ACCOMMODATE

THE DEMOLITION AND INSTALLATION OF DUCTWORK, PIPING, AND STRUCTURE.

A. PROVIDE TEMPORARY SUPPORT, RELOCATION, OR REMOVAL OF ALL

EXISTING ELECTRICAL AND ELECTRONIC SAFETY/SECURITY ITEMS

MOUNTED ON OR IN CEILINGS. REINSTALL THE SAME ITEMS TO MATCH

EXISTING CONDITIONS WHEN CEILING IS REINSTALLED.

B. COORDINATE WITH OTHER TRADES TO MODIFY ANY ITEMS ABOVE CEILINGS

AS REQUIRED TO ACCOMMODATE INSTALLATIONS, INCLUDING BUT NOT

LIMITED TO CONDUIT, JUNCTION BOXES, CABLE PATHWAYS, ETC.

C. FIELD-VERIFY EXTENT OF WORK REQUIRED; NOT ALL ITEMS ARE SHOWN

ON DRAWINGS.

D. COORDINATE WITH CONSTRUCTION MANAGER'S DIRECTIVES.

POWER GENERAL NOTES

PANEL 'BF'

PANEL 'BE'

PANEL 'DPB'

EX. PANEL 'AE'

EX. PANEL 'RP1' EX. PANEL 'LP1'

EX. XFMR 'T-RP1'

EX. PANEL 'DP1'

EX. PANEL 'AD'

XFMR 'T-B1'

P-20.1

P-20.2

RTU-20.2

EXHAUST

ON ROOF

ACH-20.1

CLASSROOM

B129

MECHANICAL

B132

COPY ROOM

B130

KILN

B115

WOMENS TOILET

B114

MENS TOILET

B113

JAN.

B118

OFFICE

B126

STORAGE

B119

OFFICE

B133

STAFF TOILET

B131

VESTIBULE

B105

OFFICE

A128

CLOSET

B116

OFFICE

B139

CLASSROOM

B137

MECH. ENCLOSURE

B120

STORAGE

B117

CLASSROOM

B128

CORRIDOR

B106

CORRIDOR

B101

GYMNASIUM

B121

RAMP

B122

PLATFORM

B123

STAIR

B124

OFFICE

B108

OFFICE

B107

TOILET

B109

TEACHER LOUNGE/WORK AREA

B110

CORRIDOR

B112

VESTIBULE

B127

MUSIC

B125

WOMENS TOILET

B135

MENS TOILET

B136

OFFICE

B138

OFFICE

A132

CORRIDOR

B134

CLASSROOM

B102

CLASSROOM

B104

CLASSROOM

B103

STORAGE

B140

VUV-20.08

VUV-20.09

VUV-20.07

VUV-20.06

VUV-20.05

WG/PC

WG/PC

PC

WL WL

EHD EHD

EHD EHD

WB1

48"

WB1

48"

WB1

48"

CORD REEL CORD REEL

CORD REEL CORD REEL

CLG CLG

CLG CLG

GFCI

44"

GFCI

44"

GFCI

44"

GFCI

44"

E7.01

8 SIM

E7.01

8 SIM

E7.01

8 SIM

E7.01

8 SIM

E7.01

8 SIM

EF-20.3

ON ROOF

44"

GFCI

44"

GFCI

44"

44"

44"

E7.01 8

44" 44"

44"

44"

44"

44" 44"

44"

GFCI

B-20.1

B-20.2

NEMA 4

JUNCTION BOX

P08

P08

P08

P08

P08

44"

44"

C09

E7.01

8 SIM

P08

DWH DWH

RP-1

GFT-20.1

WFP-20.1

PANEL 'DP2'

SWBD. 'MSB'

EF-20.2

ON ROOF

PANEL 'DP2'

UH-20.1

GFT-20.2

BE-18

BE-20

BE-24

BE-27

PANEL 'DP2'

PANEL 'DP2'

PANEL 'DP2'

BE-29

BE-31

BE-33

BMS/ATC PANEL(S)

E7.01

44"

AE-16 AE-18

AE-20 AE-22

GFCI

44"

AE-14

AE-12

AE-11

AE-7

AE-10

AE-9

AE-8

AE-5

AE-6

AE-3

AE-4 AE-1

BE-28

BF-28

BF-30

GFCI

GFCI

BF-33

BF-36

BF-12

BF-11

BF-6

BF-9

BF-7

BF-8

BF-4

BF-10

BF-2

BF-26

INSTALL FEEDER SPLICE IN 30"W X 48"L X 36"D

UNDERGROUND JUNCTION BOX PER SECTION

26 05 34 (COVER LOGO "ELECTRIC"), JOIN

CONDUCTORS WITH WATERPROOF LUG-TYPE

CONNECTORS. VERIFY EXACT J.B. SIZE WITH

NEC RULES AND FIELD-VERIFIED CONDITIONS.

SAWCUT EX. CONCRETE PAD AND SLAB AS

REQ'D FOR CONDUIT INSTALLATION, BACKFILL

AND COMPACT SOILS, PATCH PAD/SLAB IN

MECH. ENCLOSURE TO INFILL ANY REMAINING

OPENINGS, THICKNESS TO MATCH EXISTING

NEW U.G. FEEDER CONDUITS FROM SWBD. 'MSB'

DRILLED THROUGH ENCLOSURE WALL FOUNDATION;

REFER TO SHEET ES2.01 FOR PLAN CONTINUATION

AND SHEET E4.02 FOR SIZE/QUANTITY

ELEVATE CHILLER FEEDER CONDUIT ABOVE

CONCRETE SLAB/PAD INSIDE MECH. ENCLOSURE

W/ SUITABLE HARDWARE PER SECTION 26 05 29

EX. U.G. CONDUITS TO PANEL 'DP1',

RE-PURPOSED FROM SERVICE

CONDUCTORS TO FEEDER

CONDUCTORS; REFER TO SHEET

E4.02 FOR SIZE/QUANTITY

BE-22

RP1-38

P15

28" 28"

AE-13

SBB

C02

C02 C03

P04

P04

P04

P04

PLUMB. FIXTURE PSU

ABOVE CLG.

PLUMB. FIXTURE PSU

ABOVE CLG.

PLUMB. FIXTURE PSU

ABOVE CLG.

PLUMB. FIXTURE PSU

ABOVE CLG.

GFCI P01

C11

C11

CLOSET

B132A

MECH. MEZZANINE

B201

EX. AHU-201

EX. AHU-203

EX. AHU-204

EX. AHU-202 P-20.4P-20.3

EX. PANEL

'DP1'

EX. PANEL

'DP1'

WFP-20.2

EX. PANEL

'DP1'

UNIT A

UNIT C

UNIT B

UNIT D

ADDITIONEXISTING

NORTH KEYPLAN

PROJECT NO.

DRAWN

REVIEWED

No part of this drawing may be used or reproduced in any form or by any means, or stored in a database or retrieval system, without prior written permission of

GMB Copyright 2019 All Rights Reserved c

ISSUANCES

616.796.0200 www.gmb.com

C

L o ca l

P ro je ct s\

-4

E

C E

N T

R A

L

M at tk .r v t

/6

/2

:2

:3

E2.1B

5-4740

UNIT 'B' POWER PLAN

MCK

RDG

W E

B B

E R

E L

E M

E N

T A

R Y

S

IT

E A

N D

B U

IL

D

IN

G

I M

P R

O V

E M

E N

T S

L A

K E

O R

IO

N

C O

M M

U N

IT

Y

S C

H O

O L

S

L A

K E

O R

IO

N

M

IC

H

IG

C02 (2) 12.6 SQ. IN. CABLE PATHWAY PENETRATION DEVICE (FIRE)

PER SECTION 27 05 28

C03 (2) 4" CONDUIT SLEEVES FOR DIV. 27 COMMUNICATIONS

CABLING

C09 PROTECT EX. COMMUNICATIONS EQUIPMENT, RACKS, AND

ASSOCIATED CABLING FROM THE INGRESS OF DUST AND

DEBRIS DURING CONSTRUCTION PERIOD. COORDINATE ANY

REQUIRED TEMPORARY DISCONNECTION OF POWER OR

COMMUNICATIONS CABLING WITH THE OWNER AND

CONSTRUCTION MANAGER.

C11 PROVIDE RETROFIT/SPLIT CABLE PATHWAY PENETRATION

DEVICES (FIRE-RATED) PER SECTION 27 05 28 AS NECESSARY

TO SLEEVE ALL EXISTING AND NEW CABLING THROUGH NEW

FIRE BARRIER WALL, PLUS LEAVE 25% FREE AREA FOR

FUTURE CABLING. DEVICES SHALL BE MINIMUM OF (2) 6 SQ.

IN. / 2" DIA. FREE AREA SIZE. FIELD-VERIFY EX. CONDITIONS

AND ADJUST LOCATIONS/QUANTITY AS NECESSARY.

P01 RECONNECT NEW RECEPTACLE TO EXISTING BRANCH

CIRCUIT AS PRESENT AT EX. OUTLET BOX.

P04 DUAL-CHANNEL (POWER & COMMUNICATIONS) SURFACE

RACEWAY SYSTEM AS SPECIFIED, CONTINUOUS RUN WITH

SINGLE VERTICAL DROP FROM ACCESSIBLE CEILING SPACE

AND ACTIVATIONS/FITTINGS AS INDICATED.

P08 RECONNECT NEW RECEPTACLE TO EXISTING BRANCH

CIRCUIT AS EXTENDED FROM FORMER TELEVISION OR VIDEO

PROJECTOR LOCATION (REFER TO DEMOLITION PLAN).

MODIFY CONDUIT/RACEWAYS AND CONDUCTORS AS REQ'D.

P15 MOUNT CORD REELS TO STRUCTURE ABOVE SUSPENDED

CEILING SUCH THAT REELS ARE ACCESSIBLE AND CORDS

DROP DOWN THROUGH AND ARE CENTERED IN THE GAP

BETWEEN CEILING ELEMENTS. ADJUST CORD STOP SUCH

THAT RETRACTED HEIGHT OF BOX IS 8'-0" AFF.

NORTH 1/8" = 1'-0"

UNIT 'B' POWER PLAN

NORTH 1/8" = 1'-0"

GYM MECH. MEZZ. POWER PLAN

01.22.2020BIDS &

CONSTRUCTION

02.06.2020ADDENDUM 001

04.21.2020BULLETIN 003

05.07.2020BULLETIN 004

T

T

T

T

T

T

D

D

D D

S

D

D

D

D

D2

D

D2

D

D D

D

D

D

D

2A D

W

2D

D

D

W

W

D

2A

2A D

W

2D

W2D

D

W2D 2D

W

2A D

A

D D

D

D

W

W

W W

D

2A

D

D

A

2A

2A

MDF

D

Strobe

S

S

S

S

S S

S

SSS

S

S

S

S

S

W W

W

W

W

W

W

W

Strobe

Prepared by Plante Moran Legend:

Interactive Flat Panel

General Data (1 drop per triangle unless noted)

PA – PA Buttons

Wireless AP

AV Cabling (IFP or Audio Ehancement Box)

Clock

PA Speaker

Digital Clock (see note below)

Dual-sided Digital Clock (see note below)

Audio Enhancement/PA (4 equally spaced speakers)

Teacher location

S

D

D2

T

D

P

W

A

C

BF

BF

BF

BF

BF

B F

B F

BF

B F

B F

B F

BF

BF

BF

B F

B F

B F

B F

BF

BF

F A

C P

F F

M

M

M

M

S S

S

TS

TS

AV

A V

AV

AV

AV

AV AV

AV

AV

A V

AV

FB

AV

F

FB1

FB1

FB1

FB1

A V

AV

1/8

1/6

1/10

1/6

1/20

1/15

1/15

TS

FS

1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.01.

2. REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

3. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF SMOKE DAMPERS AND

COMBINATION FIRE/SMOKE DAMPERS. E.C. SHALL PROVIDE 120VAC POWER

FROM DEDICATED 20A/1P BRANCH CIRCUIT (WITH BREAKER LOCKING

MECHANISM) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA (DAMPERS

MAY BE GROUPED ON EACH CIRCUIT), TERMINATED W/ BOX-COVER FUSIBLE

SWITCH AT EACH DAMPER. ALSO PROVIDE FIRE ALARM DUCT SMOKE

DETECTOR WITHIN 5 FEET OF EACH DAMPER (UNLESS COVERED BY ANOTHER

DUCT DETECTOR WITHIN 5 FEET) AND A FIRE ALARM ADDRESSABLE RELAY FOR

INTERLOCKING DAMPER W/ CORRESPONDING HVAC UNIT PER CODE

REQUIREMENTS.

4. PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN

ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR

PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS

CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES

INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST

FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.

5. COORDINATE THE INSTALLATION AND ROUGH-IN REQUIREMENTS (BOXES,

CONDUIT, ETC. IN WALLS AND CEILINGS) FOR THE FOLLOWING SYSTEMS WITH

COMMUNICATIONS AND ELECTRONIC SAFETY/SECURITY CONTRACTORS

ENGAGED VIA SEPARATE BID PACKAGE(S) (NOT IN THIS CONTRACT), INCLUDING

BUT NOT LIMITED TO:

A. NETWORK CABLING SYSTEMS

B. NETWORK ELECTRONICS (SWITCHES, ACCESS POINTS, ETC.)

C. TELEPHONE SYSTEMS

D. INSTRUCTIONAL TECHNOLOGY EQUIPMENT

E. AUDIO-VIDEO SYSTEMS AND EQUIPMENT

F. INTERIOR DIGITAL SIGNAGE SYSTEM AND DISPLAYS

G. INTERCOM/PAGING SYSTEM

H. DISTRIBUTED CLOCK SYSTEM

I. ACCESS CONTROL SYSTEM

J. VIDEO SURVEILLANCE SYSTEM

6. REVIEW ALL OTHER DISCIPLINE PLANS FOR AREAS WHERE REMOVAL AND

REINSTALLATION OF EXISTING CEILINGS WILL BE REQUIRED TO ACCOMMODATE

THE DEMOLITION AND INSTALLATION OF DUCTWORK, PIPING, AND STRUCTURE.

A. PROVIDE TEMPORARY SUPPORT, RELOCATION, OR REMOVAL OF ALL

EXISTING ELECTRICAL AND ELECTRONIC SAFETY/SECURITY ITEMS

MOUNTED ON OR IN CEILINGS. REINSTALL THE SAME ITEMS TO MATCH

EXISTING CONDITIONS WHEN CEILING IS REINSTALLED.

B. COORDINATE WITH OTHER TRADES TO MODIFY ANY ITEMS ABOVE CEILINGS

AS REQUIRED TO ACCOMMODATE INSTALLATIONS, INCLUDING BUT NOT

LIMITED TO CONDUIT, JUNCTION BOXES, CABLE PATHWAYS, ETC.

C. FIELD-VERIFY EXTENT OF WORK REQUIRED; NOT ALL ITEMS ARE SHOWN

ON DRAWINGS.

D. COORDINATE WITH CONSTRUCTION MANAGER'S DIRECTIVES.

POWER GENERAL NOTES

PANEL 'CA'

SWBD. 'MSB'

XFMR 'T-C1'

PANEL 'DPC'

NEW 480V UTILITY

XFMR

OFFICE

A122

OFFICE

A123

CLASSROOM

C125

CLASSROOM

C121

STORAGE

C122

TOILET

C116

VESTIBULE

A118

MEDIA PRODUCTIONS

C102

TOILET

C123

STORAGE

C115

CLASSROOM

D119

JAN.

C118

VESTIBULE

C126

ELECTRICAL

C127

BREAKOUT

C106

STORAGE

C105

TOILET

C124 WOMENS TOILET

C119

MENS TOILET

C117

STORAGE

C120

HALL

D101

CLASSROOM

D102

STORAGE

C108

TOILET

C109

STAFF TOILET

C110

TELECOMM

C114

STORAGE

C113

BREAKOUT

C112

MEDIA CENTER

C103

OFFICE

C104

MECHANICAL

A119

CLASSROOM

A120

HALL

C101

CORRIDOR

A121

CLASSROOM

A124

EXTENDED LEARNING AREA

C111

CLASSROOM

C107

HALL

C128

VUV-20.10 VUV-20.11

VUV-20.12

VUV-20.04

VUV-20.03

EHD

EHD EHD

EHD

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

GFCI

44"

GFCI

GFCI

GFCI

44"

EWC

GFCI

GFCI

GFCI

GFCI

WL

GFCI

E7.01

E7.01

8 SIM

WL

CUH-20.4

EF-20.4

ON ROOF

EF-20.5

ON ROOF

EF-20.6

ON ROOF

UH-20.2

GFCI

WL

GFCI

WL

GFCI

WL

GFCI

WL

GFCI

12"x4" CABLE TRAY

"x

C A

B L

E T

R A

Y

"x

4" C

A B

L E

T R

Y

12"x4" CABLE TRAY

12"x4" CABLE TRAY

"x

C

A B

L E

T R

8"x2" CABLE TRAY

8"x2" CABLE TRAY

P08

P08

COMM. EQUIP.

RACK(S), N.I.C.

P05

P05

P05

P05

P05

P05

P05

P05

E7.01

TYP.

E7.01

TYP.

E7.01

TYP.

EF-20.9

ON ROOF

EF-20.11

ON ROOF

C05

C05

BC-22

BC-24

BC-34

BC-36

BC-37

CA-39

CA-37

CA-14

CA-13

CA-18

CA-20

CA-26

CA-21

CA-19

CA-16

CA-17

CA-15

CA-38

CA-36

CA-35

CA-32

CA-30

CA-34

CA-1 CA-2

CA-31

CA-28

CA-29 CB-36

CB-37

CB-38

CB-35

CB-33

CB-32

CB-34

CB-1

CB-19

CB-16

CB-17

CB-25

CB-14

CB-15

CB-13

CA-27

CA-25

CA-24

CA-23

CA-22

CA-33

CA-12

CA-3

CB-2

CB-18

SBB

PBB

C06

C03 C10

C10

C10

C10

C03

C10

C08

E7.01

P06

P07

P12

PLUMB. FIXTURE PSU

ABOVE CLG.

PLUMB. FIXTURE PSU

ABOVE CLG.

PLUMB. FIXTURE PSU

ABOVE CLG.

PLUMB. FIXTURE PSU

ABOVE CLG.

C06

UNIT A

UNIT C

UNIT B

UNIT D

ADDITIONEXISTING

NORTH KEYPLAN

PROJECT NO.

DRAWN

REVIEWED

No part of this drawing may be used or reproduced in any form or by any means, or stored in a database or retrieval system, without prior written permission of

GMB Copyright 2019 All Rights Reserved c

ISSUANCES

616.796.0200 www.gmb.com

C

L o ca l

P ro je ct s\

-4

E

C E

N T

R A

L

M at tk .r v t

/2

/2

:1

:0

UNIT 'C' POWER PLAN

MCK

RDG

W E

B B

E R

E L

E M

E N

T A

R Y

S

IT

E A

N D

B U

IL

D

IN

G

I M

P R

O V

E M

E N

T S

L A

K E

O R

IO

N

C O

M M

U N

IT

Y

S C

H O

O L

S

L A

K E

O R

IO

N

M

IC

H

IG

C03 (2) 4" CONDUIT SLEEVES FOR DIV. 27 COMMUNICATIONS

CABLING

C05 (2) 6 SQ. IN. CABLE PATHWAY PENETRATION DEVICE (FIRE)

PER SECTION 27 05 28

C06 (3) 13 SQ. IN. CABLE PATHWAY PENETRATION DEVICE (SMOKE)

PER SECTION 27 05 28

C08 (2) 6.7 SQ. IN. CABLE PATHWAY PENETRATION DEVICE

(SMOKE) PER SECTION 27 05 28

C10 (3) 4" CONDUIT SLEEVES FOR DIV. 27 COMMUNICATIONS

CABLING

P05 UNDERGROUND CONDUITS FOR FLOOR BOX(ES), ROUTED

OVER TO AND UP NEW WALL TO ABOVE ACCESSIBLE

SUSPENDED CEILING SPACE. COORDINATE CONCRETE

FLOOR CUTTING AND PATCHING W/ ARCH. TRADES.

P06 ESTABLISH NEW CONCRETE-ENCASED GROUNDING

ELECTRODE IN FOOTING OF NEW ADDITION, INTERCONNECT

WITH GROUNDING ELECTRODE SYSTEM AT SERVICE

ENTRANCE OR NEAREST SEPARATELY-DERIVED SYSTEM PER

NEC AND SPECIFICATION REQUIREMENTS.

P07 BOND METAL STRUCTURE OF ADDITION TO METAL

STRUCTURE OF EXISTING BUILDING PER NEC REQUIREMENTS.

P08 RECONNECT NEW RECEPTACLE TO EXISTING BRANCH

CIRCUIT AS EXTENDED FROM FORMER TELEVISION OR VIDEO

PROJECTOR LOCATION (REFER TO DEMOLITION PLAN).

MODIFY CONDUIT/RACEWAYS AND CONDUCTORS AS REQ'D.

P12 COORDINATE COMMUNICATIONS CONNECTIONS REQUIRED

FOR MONITORING AND NETWORK ADMINISTRATION OF

ELECTRONIC SAFETY/SECURITY EQUIPMENT WITH OWNER,

OWNER'S MONITORING SERVICE PROVIDER(S), AND OWNER'S

COMMUNICATIONS CONTRACTOR. ALL CONNECTIONS SHALL

BE PROTECTED FROM TAMPERING AND ACCIDENTAL

DISCONNECTION.

NORTH 1/8" = 1'-0"

UNIT 'C' POWER PLAN

01.22.2020BIDS &

CONSTRUCTION

02.06.2020ADDENDUM 001

04.21.2020BULLETIN 003

T T

T

D2

D D

D

D

D

D

D

D

D

D D

2D D

2D

D

D

D

D

D

W

W

W

W

W

W

D

D

W

W

S

S

S

S

55" LCD

Prepared by Plante Moran Legend:

Interactive Flat Panel

General Data (1 drop per triangle unless noted)

PA – PA Buttons

Wireless AP

AV Cabling (IFP or Audio Ehancement Box)

Clock

PA Speaker

Digital Clock (see note below)

Dual-sided Digital Clock (see note below)

Audio Enhancement/PA (4 equally spaced speakers)

Teacher location

S

D

D2

T

D

P

W

A

C

BFBF

B F

B F

BF

B F

B F

BF

B F

BF

C

C R

AV

AV

A V

A V

A V

A V

A V

AV

AV

AV

A V

A V

FB

A V

A V

AV

AV

FB1

FB1

FB1

FB1

A V

1/8

1/15

1/15

1/15

AV

AV

F

F

D

D

1/2 1/20

1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.01.

2. REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

3. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF SMOKE DAMPERS AND

COMBINATION FIRE/SMOKE DAMPERS. E.C. SHALL PROVIDE 120VAC POWER

FROM DEDICATED 20A/1P BRANCH CIRCUIT (WITH BREAKER LOCKING

MECHANISM) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA (DAMPERS

MAY BE GROUPED ON EACH CIRCUIT), TERMINATED W/ BOX-COVER FUSIBLE

SWITCH AT EACH DAMPER. ALSO PROVIDE FIRE ALARM DUCT SMOKE

DETECTOR WITHIN 5 FEET OF EACH DAMPER (UNLESS COVERED BY ANOTHER

DUCT DETECTOR WITHIN 5 FEET) AND A FIRE ALARM ADDRESSABLE RELAY FOR

INTERLOCKING DAMPER W/ CORRESPONDING HVAC UNIT PER CODE

REQUIREMENTS.

4. PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN

ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR

PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS

CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES

INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST

FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.

5. COORDINATE THE INSTALLATION AND ROUGH-IN REQUIREMENTS (BOXES,

CONDUIT, ETC. IN WALLS AND CEILINGS) FOR THE FOLLOWING SYSTEMS WITH

COMMUNICATIONS AND ELECTRONIC SAFETY/SECURITY CONTRACTORS

ENGAGED VIA SEPARATE BID PACKAGE(S) (NOT IN THIS CONTRACT), INCLUDING

BUT NOT LIMITED TO:

A. NETWORK CABLING SYSTEMS

B. NETWORK ELECTRONICS (SWITCHES, ACCESS POINTS, ETC.)

C. TELEPHONE SYSTEMS

D. INSTRUCTIONAL TECHNOLOGY EQUIPMENT

E. AUDIO-VIDEO SYSTEMS AND EQUIPMENT

F. INTERIOR DIGITAL SIGNAGE SYSTEM AND DISPLAYS

G. INTERCOM/PAGING SYSTEM

H. DISTRIBUTED CLOCK SYSTEM

I. ACCESS CONTROL SYSTEM

J. VIDEO SURVEILLANCE SYSTEM

6. REVIEW ALL OTHER DISCIPLINE PLANS FOR AREAS WHERE REMOVAL AND

REINSTALLATION OF EXISTING CEILINGS WILL BE REQUIRED TO ACCOMMODATE

THE DEMOLITION AND INSTALLATION OF DUCTWORK, PIPING, AND STRUCTURE.

A. PROVIDE TEMPORARY SUPPORT, RELOCATION, OR REMOVAL OF ALL

EXISTING ELECTRICAL AND ELECTRONIC SAFETY/SECURITY ITEMS

MOUNTED ON OR IN CEILINGS. REINSTALL THE SAME ITEMS TO MATCH

EXISTING CONDITIONS WHEN CEILING IS REINSTALLED.

B. COORDINATE WITH OTHER TRADES TO MODIFY ANY ITEMS ABOVE CEILINGS

AS REQUIRED TO ACCOMMODATE INSTALLATIONS, INCLUDING BUT NOT

LIMITED TO CONDUIT, JUNCTION BOXES, CABLE PATHWAYS, ETC.

C. FIELD-VERIFY EXTENT OF WORK REQUIRED; NOT ALL ITEMS ARE SHOWN

ON DRAWINGS.

D. COORDINATE WITH CONSTRUCTION MANAGER'S DIRECTIVES.

POWER GENERAL NOTES

PANEL 'CB'

PANEL 'CC'

XFMR 'T-C2'

CLASSROOM

D117

TOILET

C116

CLASSROOM

D113

CLASSROOM

D106

CLASSROOM

D107

STORAGE

D115

BREAKOUT

D118

COPY

D111

ELECTRICAL

D112

HALL

D109

VESTIBULE

D108

STORAGE

C115

CLASSROOM

D119

JAN.

C118

MENS TOILET

C117

STORAGE

C120

JAN.

D116

HALL

D101

CLASSROOM

D102

CLASSROOM

D103

CLASSROOM

D104

CLASSROOM

D105

TELECOMM

C114

STORAGE

C113

BREAKOUT

C112

EXTENDED LEARNING AREA

D114

CLASSROOM

D110

EXTENDED LEARNING AREA

C111

VUV-20.13

VUV-20.14

VUV-20.15

VUV-20.16

VUV-20.22

VUV-20.20

VUV-20.19

VUV-20.18

VUV-20.17

EHD

EHD

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

WB1

48"

GFCI

44"

GFCI

GFCI

44"

VUV-20.21

GFCI

44"

EWC

EWC

GFCI

GFCI

WL

GFCI

WL

GFCI

WL

GFCI

WL

GFCI

44"

44"

44"

44"

CUH-20.5

EF-20.7

ON ROOF

EF-20.8

ON ROOF

WL

GFCI

"x

4" C

A B

L E

T R

8"x4" C

ABLE TRAY

12"x4" C A

B L

E T

R

12"x4" C

B L

E T

R

B L

E T

R

B L

E T

R

12"x4" CABLE TRAY

12"x4" CABLE TRAY

COMM. EQUIP.

RACK(S), N.I.C.

44"

44"

P05

P05

P05

P05

P05

E7.01

TYP.

E7.01

TYP.

E7.01

TYP.

EF-20.11

ON ROOF

CB-36

CB-37

CB-38

CB-35

CB-33

CB-32

CB-34

CB-1

CB-19

CB-16

CB-17

CB-25

CB-14

CB-15

CB-13

CB-21

CB-22

CB-20

CB-3

CB-4 CB-23

CB-24

CB-42

CB-43

CB-5

CC-3

CC-13

CC-12

CC-14

CC-15

CC-17

CC-16

CC-4

CC-5

CC-19

CC-20

CC-18

CC-21

CC-22

CC-2

CC-24

CC-23

CC-26

CC-27

CC-28

CC-25

CC-31

CC-1

CC-30

CC-29

CC-32

CC-33

CB-27

CB-28

CB-25

CB-26

CB-29

CB-31

CB-2

CB-30

CB-44

CB-18

SBB

C10

C10

C10

C03

C03

C10

C10

C10

PLUMB. FIXTURE PSU

ABOVE CLG.

BASEMENT

D001

WL

GFCI

AHU-20.2 SUPPLY

AHU-20.2 EXHAUST

EF-20.10

UH-20.3

AHU LTS &

RECEPTS

SWBD. 'MSB'

CB-41

CB-39

CB-40

UNIT A

UNIT C

UNIT B

UNIT D

ADDITIONEXISTING

NORTH KEYPLAN

PROJECT NO.

DRAWN

REVIEWED

No part of this drawing may be used or reproduced in any form or by any means, or stored in a database or retrieval system, without prior written permission of

GMB Copyright 2019 All Rights Reserved c

ISSUANCES

616.796.0200 www.gmb.com

C

L o ca l

P ro je ct s\

-4

E

C E

N T

R A

L

M at tk .r v t

/2

/2

:1

:2

E2.1D

UNIT 'D' POWER PLAN

MCK

RDG

W E

B B

E R

E L

E M

E N

T A

R Y

S

IT

E A

N D

B U

IL

D

IN

G

I M

P R

O V

E M

E N

T S

L A

K E

O R

IO

N

C O

M M

U N

IT

Y

S C

H O

O L

S

L A

K E

O R

IO

N

M

IC

H

IG

C03 (2) 4" CONDUIT SLEEVES FOR DIV. 27 COMMUNICATIONS

CABLING

C10 (3) 4" CONDUIT SLEEVES FOR DIV. 27 COMMUNICATIONS

CABLING

P05 UNDERGROUND CONDUITS FOR FLOOR BOX(ES), ROUTED

OVER TO AND UP NEW WALL TO ABOVE ACCESSIBLE

SUSPENDED CEILING SPACE. COORDINATE CONCRETE

FLOOR CUTTING AND PATCHING W/ ARCH. TRADES.

NORTH 1/8" = 1'-0"

UNIT 'D' POWER PLAN

NORTH 1/8" = 1'-0"

BASEMENT POWER PLAN

01.22.2020BIDS &

CONSTRUCTION

02.06.2020ADDENDUM 001

04.21.2020BULLETIN 003

S

W

W

S

S

Early Childhood Center - Technology

Prepared by Plante Moran

Legend:

Interactive Flat Panel

General Data

PA – PA Buttons

Wireless AP

AV Cabling (IFP or Audio Enhancement Box)

Clock

PA Speaker

Digital Clock

Dual-sided Digital Clock

Audio Enhancement/PA

Teacher location

S

D

D2

T

D

P

W

A

C

BF

B F

B F

B F

B F

B F

B F

B F

BF

ATS

F

C P

T

ATS

X

X

24X 42 24X 36

24X 48

X

X

24X 42

X

24X 48

D

TS TS

7.5 7.5

F

S S

S

F

AV

AV

A

AV

A V

AV

A V

A V

A V

A V

A V

AV

A V

AV

A V

A V

AV

AV

AV

A V

A V

AV

AV

A V

A V

A

F

AV

S

S

S S

S

S

S

C

S

S

S

S

S

S

S

S

CR

C R

CR CR

D D D

S

ID

S

1/4

1/8

1/2

1/10

1/4

1/8

1/20

IC

K P

E

1.5

TSTS

FS

CR

C R

C R

1/12

FS FS

1.5

1/20

A V -S1

A V -S1

A V -S1

A V -S1

A V -S1

A V -S1

A V -S1

A V -S1

A V -D

A V -C1

A V -W

AV-W2

A V -C

C R

CR

D

D

D

D

D

D

R

R

R

AV

A V

A V

AVAV

S

S

CR

S

BF

X

X

24X42 24X36

24X48

X

X

24X42

X

24X48

K

C1

C

C1

IC

1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.01.

2. REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

3. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF SMOKE DAMPERS AND

COMBINATION FIRE/SMOKE DAMPERS. E.C. SHALL PROVIDE 120VAC POWER

FROM DEDICATED 20A/1P BRANCH CIRCUIT (WITH BREAKER LOCKING

MECHANISM) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA (DAMPERS

MAY BE GROUPED ON EACH CIRCUIT), TERMINATED W/ BOX-COVER FUSIBLE

SWITCH AT EACH DAMPER. ALSO PROVIDE FIRE ALARM DUCT SMOKE

DETECTOR WITHIN 5 FEET OF EACH DAMPER (UNLESS COVERED BY ANOTHER

DUCT DETECTOR WITHIN 5 FEET) AND A FIRE ALARM ADDRESSABLE RELAY FOR

INTERLOCKING…