J-1502000-07.d Vehicle Fueling Station Equipment Description.xlsx

XLSX spreadsheet 39 KB Posted

Attached to
Base Operations Support (BOS) Services at U. S. Naval Air Station (NAS) Sigonella and its outlying support activities, Sicily, Italy
Solicitation number
N6247025R0020
Issued by

About this file

This Excel file is a Vehicle Fueling Station System Description attachment (J-1502000-07.d) for a naval base operations support contract at Naval Air Station Sigonella in Sicily, Italy. The document details a comprehensive fuel infrastructure system consisting of fuel receiving and delivery sections, which includes multiple underground double-walled storage tanks for diesel and mogas (motor gasoline) with capacities ranging from 20,000 to 50,000 liters, installed in 2005.

The fueling station system encompasses two off-load stations for receiving fuel from commercial trucks, storage tanks, and fuel dispensers activated by electronic keys for government vehicle fueling. The preventive maintenance (PM) program covers the entire system, including piping, cathodic protection systems, oil-water separators, and associated equipment. The facility includes multiple components such as storage tanks (TK1-TK8), dispensers, lay-bays, a control room, and two eyewash stations, with all equipment manufactured by Kammarer and located in Building 615. The document is part of a solicitation (N6247025R0020) issued by the Department of the Navy Naval Facilities Engineering Command for Base Operations Support Services.

View the file

Other files

File Type Posted
Solicitation Amendment N6247025R00200012 SF 30.pdf PDF
Solicitation Amendment N6247025R00200011 SF 30.pdf PDF
J-14 PPI Responses (Ament 0010).pdf PDF
Annex 1606001 C Water (Overseas) - Amend 0010.pdf PDF
J-1606001-03 Water System Description and Inventory - Amend 0010.xlsx XLSX spreadsheet
Solicitation Amendment N6247025R00200010 SF 30.pdf PDF
J-1402000 Unaccompanied Housing - Amend 0010.pdf PDF
J-1601000 Utility Management - Amend 0010.pdf PDF
Annex 1402000 C Unaccompanied Housing - Amend 0010.pdf PDF
Solicitation Amendment N6247025R00200009 SF 30.pdf PDF
J-1602000 Electrical - Amend 0008.pdf PDF
J-13 PPI Responses (Ament 0008).pdf PDF
J-1502000-05 Base Systems Description - Amend 0008.xlsx XLSX spreadsheet
Annex 1601000 C Utility Management - Amend 0008.pdf PDF
Solicitation Amendment N6247025R00200008 SF 30.pdf PDF
Annex 1602000 C Electrical - Amend 0008.pdf PDF
Annex 1606001 C Water (Overseas) - Amend 0008.pdf PDF
J-1606001-04 Historical Critical Spare Parts Inventory - Amend 0004.xlsx XLSX spreadsheet
Annex 1503030 C Integrated Solid Waste Management - Amend 0008.pdf PDF
Annex 1502000 C Facility Investment - Amend 0008.pdf PDF
Annex 1800000 C Environmental New Sig - Amend 0008.pdf PDF
Annex 1601000 C Utility Management - Amend 0007.pdf PDF
J-10 Pre-Proposal Site Visit Sign-In Sheet (Amend 0007).pdf PDF
J-1601000 Utility Management - Amend 0007.pdf PDF
J-11 Pre-Proposal Conference Presentation Sigonella BOS (Amend 0007).pdf PDF
J-1606001-03 Water System Description and Inventory Amend 0007.xlsx XLSX spreadsheet
J-1503020 Pest Control New Sig BOSC RFP - Amend 0007.pdf PDF
Annex 1503030 C Integrated Solid Waste Management - Amend 0007.pdf PDF
Annex 1503010 C Custodial - Amend 0007.pdf PDF
J-1606001 Water (Overseas) Amend 0007.pdf PDF
J-0200000-12 ELINs Sigonella - Amend 0007.xlsx XLSX spreadsheet
Solicitation Amendment N6247025R00200007.pdf PDF
J-12 PPI Responses (Ament 0007).pdf PDF
J-1503030-06 Solid Waste Containers Inventory - Amend 0007.xlsx XLSX spreadsheet
Annex 1502000 C Facility Investment Amend 0007.pdf PDF
J-1503010-06.a Custodial Inventory and Frequencies - Amend 0007.xlsx XLSX spreadsheet
Annex 1503020 C Pest Control - Amend 0007.pdf PDF
J-1502000-05 Base Systems Description RFP - Amend 0007.xlsx XLSX spreadsheet
Annex 1402000 C Unaccompanied Housing - Amend 0007.pdf PDF
Annex 1501000 C Facility Management - Amend 007.pdf PDF
Annex 0200000 C Management and Administration Amend 0007.pdf PDF
J-1502000-04 Anticipated E_U_R Work Orders - Amend 0007.pdf PDF
J-1502000 Facility Investment - Amend 0007.pdf PDF
Solicitation Amendment N6247025R00200006.pdf PDF
Solicitation Amendment N6247025R00200005 SF 30.pdf PDF
Solicitation Amendment N6247025R00200004.pdf PDF
Annex 0200000 C Management and Administration Amend 0003.pdf PDF
Solicitation Amendment N6247025R00200003.pdf PDF
Annex 1502000 C Facility Investment Amend 0003.pdf PDF
Annex 0100000 General Information- Amendment 0002.pdf PDF
Show 40 more

Latest 50 of 144 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Description Aviation Fuel Sys

ATTACHMENT J-1502000-07.d (Tab 018)
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Funding Activity: NAVSUP FUELS - DLA ENERGY FUNDED
The Vehicle Fueling Station System consists of a fuel receiving section and a fuel delivering section. The fuel receiving section consists of two off-load stations (lay-bays) for the receipt of diesel or unleaded fuel from commercial trucks, piping terminals, and storage tanks. The fuel delivery section consists of fuel dispensers activated using electronic keys to enable the disbursement of fuel into Government vehicles. Preventive Maintenance (PM) Program responsibility includes entire system and components from the connection to the commercial fuel trucks to the fuel delivery endpoints at the fuel dispensers, and includes all visible and pit accessible piping, cathodic protection systems, oil water separators and all miscellaneous equipment as listed.

Fueling Station List

ATTACHMENT J-1502000-07.d
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Facility Listing
Facility NumberBuilding NameTab
613Reference Section C, Annex 0200000 Management and Administration, Spec Item 2.6.2 Dissemination of InformationOWS
614Up-Lift St.
615Dispenser
615ATank 1
615BTank 2
615CTank 3
615DTank 4
615ETank 5
615FTank 6
615GTank 7
615HTank 8
616Control Room
n/aPipingPiping
n/aDispenser - Lay-BaysLay-Bays
n/aEyewash

TK1-TK2

ATTACHMENT J-1502000-07.d
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Preventive Maintenance (PM)
Fuel 3 TK-1 AND TK-2 DIESEL FUEL STORAGE TANKS
DESCRIPTIONQUANTITYMANUFACTURERMODEL No.SERIAL No.CAPACITYLOCATIONYEAR OF INST.
BELOGROUND DOUBLE WALLED TANK 1 & 22KAMMARER50000 LTBLDG. 6152005
2" VENT VALVES2
2' & 4" PIPINGI.Q.
2" & 4" THREADED JOINTSI.Q.
TAGSVARIOUS
LABELING AND FLOW DIRECTION ARROWSVARIOUS
ATG8Veeder-Root

TK3-TK4

ATTACHMENT J-1502000-07.d
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Preventive Maintenance (PM)
Fuel 3 TK-3 AND TK-4 DIESEL FUEL SERVICE TANKS
DESCRIPTIONQUANTITYMANUFACTURERMODEL No.SERIAL No.CAPACITYLOCATIONYEAR OF INST.
BELOGROUND DOUBLE WALLED TANK 3 & 42KAMMARER20000 LTBLDG. 6152005
2" VENT VALVES2
2' & 4" PIPINGI.Q.
2" & 4" THREADED JOINTSI.Q.
TAGSVARIOUS
LABELING AND FLOW DIRECTION ARROWSVARIOUS

TK6-TK7

ATTACHMENT J-1502000-07.d
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Preventive Maintenance (PM)
Fuel 3 TK-6 AND TK-7 MOGAS FUEL SERVICE TANKS
DESCRIPTIONQUANTITYMANUFACTURERMODEL No.SERIAL No.CAPACITYLOCATIONYEAR OF INST.
BELOGROUND DOUBLE WALLED TANK2KAMMARER20000 LTBLDG. 6152005
2" VENT VALVES2
2' & 4" PIPINGI.Q.
2" & 4" THREADED JOINTSI.Q.
TAGSVARIOUS
LABELING AND FLOW DIRECTION ARROWSVARIOUS

SLOP TANK 8

ATTACHMENT J-1502000-07.d
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Preventive Maintenance (PM)
Fuel 3 SLOP TANK 8
DESCRIPTIONQUANTITYMANUFACTURERMODEL No.SERIAL No.CAPACITYLOCATIONYEAR OF INST.
BELOGROUND DOUBLE WALLED TANK1KAMMARER20000 LTBLDG. 6152005
VENT VALVE1
PIPINGI.Q.
THREADED JOINTSI.Q.
TAGSVARIOUS
LABELING AND FLOW DIRECTON ARROWSVARIOUS

PIPING

ATTACHMENT J-1502000-07.d
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Preventive Maintenance (PM)
Fuel 3 PIPING SYSTEMS
DESCRIPTIONQUANTITYMANUFACTURERMODEL No.SERIAL No.CAPACITYLOCATIONYEAR OF INST.
PipelinesVARIOUS
TREATED CONNECTIONSVARIOUS
LABELLINGVARIOUS
TAGSVARIOUS
ARROW FLOW INDICATORSVARIOUS

EYE WASH

ATTACHMENT J-1502000-07.d
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Preventive Maintenance (PM)
Fuel 3 EYE WASH STATIONS
DESCRIPTIONQUANTITYMANUFACTURERMODEL No.SERIAL No.CAPACITYLOCATIONYEAR OF INST.
EYE WASH2

DISPENSER

ATTACHMENT J-1502000-07.d
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Preventive Maintenance (PM)
Fuel 3 MOGAS & DIESEL DISPENSERS (Facility 615)
DESCRIPTIONQUANTITYMANUFACTURERMODEL No.SERIAL No.CAPACITYLOCATIONYEAR OF INST.
DISPENSER METERS: ALL MECHANICAL AND4
DISPENSER HEAD: ALL MECHANICAL AND4
HOSES4
NOZZELS4
DISPENSER CASING2

LAY-BAYS

ATTACHMENT J-1502000-07.d
VEHICLE FUELING STATION SYSTEM DESCRIPTION
Preventive Maintenance (PM)
Fuel 3 MOGAS & DIESEL LAY-BAYS
DESCRIPTIONQUANTITYMANUFACTURERMODEL No.SERIAL No.CAPACITYLOCATIONYEAR OF INST.
THREADED JOINTSVARIOUS
TAGSVARIOUS
LABELING AND FLOW DIRECTON ARROWSVARIOUS