This document is a comprehensive security management standards guideline prepared by Austin Water's Design Project Manager for the replacement, repair, and renovation of integrated security systems at new or existing facilities. The guideline establishes standardized protocols for Access Control Systems (ACS), Intrusion Detection Systems (IDS), and Video Surveillance Systems (VMS) utilizing Genetec Security Center/OmniCast as the unified platform. The document specifies approved manufacturers including Genetec/Mercury for access control boards, DMP XR500 Series for intrusion detection, and Axis cameras for video surveillance. All security contractors must be Genetec Elite Gold Certified, with specific requirements for cabling, conduit pathways, network connectivity, and device installations across facility types including main entrances, secure vestibules, staff entry doors, MDF/IDF rooms, MEP rooms, and external gates. The standards address rough-in requirements, power specifications, grounding protocols, and integration with fire alarm systems and elevator controls.
The document establishes detailed technical specifications for security wiring including plenum-rated cables with minimum gauge requirements (ranging from 18-22 gauge depending on application), conduit sizing and installation standards, and power distribution requirements (120VAC for circuit power, 12VDC and 24VDC for device power). All installations must comply with the National Electric Code (NEC) and American with Disabilities Act (ADA) requirements, with specific attention to recessed versus surface-mounted installations and weatherproofing for exterior applications. The contractor bears responsibility for providing all ACS software, electronics, power supplies, security wiring, network drops, conduit installation, testing, as-built documentation, and operation and maintenance manuals. Final acceptance requires substantial completion inspections, continuity testing, formal acceptance testing, and warranty provisions including one-year parts and labor coverage beginning upon final owner acceptance.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IFB_5000_MAS1005_ATT_5_v1.docx | DOCX document | |
| IFB_5000_MAS1005_ATT_1_v1.docx | DOCX document | |
| IFB_5000_MAS1005_ATT_8_v1.docx | DOCX document | |
| IFB_5000_MAS1005_ATT_7_v1.docx | DOCX document | |
| IFB_5000_MAS1005_ATT_10_v1.docx | DOCX document | |
| IFB_5000_MAS1005_ATT_2_v1.pdf | ||
| IFB_5000_MAS1005_ATT_9_v1.docx | DOCX document | |
| IFB_5000_MAS1005_ATT_12_v1.docx | DOCX document | |
| IFB_5000_MAS1005_PAC1_v1.docx | DOCX document | |
| IFB_5000_MAS1005_ATT_4_v1.pdf | ||
| IFB_5000_MAS1005_ATT_11_v1.docx | DOCX document | |
| IFB_5000_MAS1005_BID_DOC_v1.xlsx | XLSX spreadsheet | |
| IFB_5000_MAS1005_ATT_6_v1.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 | P a g e
SECURITY MANAGEMENT INTEGRATED SECURITY SYSTEM
Replacement & Repair GUIDELINES for
NEW or EXISTING FACILITY.
AND RENOVATION CONSTRUCTION
Version 2024.5.01
Prepared By:
Mike Postell Design Project Manager
11 | P a g e
PART 9 - AUSTIN WATER SECURITY SYSTEM STANDARDS
9.1 Integrated Security Management System- Genetec Security Center/Omni Cast
A. Genetec is a program name that encompasses all the physical security systems that safeguard and monitor the numerous facilities throughout Austin Water’s area of operation.
It is intended to be a unified platform consisting of access control, video surveillance, and intrusion detection systems, and various sub-systems that interface or integrate to provide additional security, such as intercoms, vehicle gates, turnstiles, and perimeter fencing. This allows Austin Water to monitor, maintain and perform administrative duties within a single
GUI.
B. New facilities or renovations shall be designed to integrate into the Owner’s existing Genetec Security platform architectures and subsystems, unless otherwise approved by the Owner.
9.2 Security Cabling and Conduit Pathways
A. General
1. This section addresses common wiring principles and techniques that Austin Water has standardized for security cabling, network drops, conduit and rough-in requirements required to support the ACS.
2. Cabling, rough-ins, and conduit pathway requirements listed herein are typical and shall be recessed whenever possible. In the case of renovation or retrofit, cabling and pathway shall be recessed whenever possible such as when a device is mounted on existing drywall etc. Any exposed conduit pathways or back boxes shall be carefully coordinated with the Owner. At no time is wire mold permitted unless specifically specified by Austin Water’s Security Dept.
B. Security Cabling
1. Security wiring shall be provided with 10 feet of slack inside the applicable MDF/IDF Room and 5 feet of slack above the access-controlled door left neatly coiled and stored.
2. Security wiring shall be labeled 2-inches from both ends per Austin Water standards.
Jacketing shall be stripped back near point of termination. Unused conductors on any wire shall be trimmed back and properly covered to avoid potential shorts. Cable shielding, drain wires, and other insulating materials shall be neatly cut to avoid shorting with other conductor cables.
3. Heat shrink labels shall be applied to the exposed jacketing to cover and protect the transition point from the overall jacket to the individual conductors for added protection. The use of electrical tape for these transition points is not permitted.
4. Outdoor wire harness terminations or splices shall be properly soldered, and heat shrink shall be applied to provide maximum protection to the connection.
5. All exterior card reader doors that receive double pole double throw (DPDT) door position switches will require (1) additional cable tied to the intrusion detection system.
6. All double doors that receive door position switches shall be wired in series and operate as one input for monitoring on an ACS or IDS.
7. All cable carrying data or voice transmissions is shielded. All other cables are shielded where necessary for interference-free signals.
8. Color-coding is accomplished by using solidly colored insulation (i.e., all. Grounding conductors, where insulated, is colored solid green or identified with green color as required by the National Electric Code (NEC).
9. Run all wire and cable continuously from device location to the final point of
12 | P a g e termination. No mid-run cable splices are allowed.
10. Wire and cable within power distribution cabinets and other security enclosures is neatly installed, completely terminated, pulled tight with slack removed and routed in such a way as to allow direct, unimpeded access to the equipment within the enclosure. All wire and cable are bundled and tied. Hook and Loop straps are the preferred method of tying down cabling. Zip ties or Tye wraps are not permitted.
11. Provide grommets and strain relief material where necessary to avoid abrasion of wire and excess tension on wire and cable. Lock rings and nylon threaded bushings shall be used to secure conduit connections to security enclosures.
12. Make connections with solder-less devices, mechanically and electrically secured in accordance with the manufacturers’ recommendations. Wire nuts are not an acceptable means of connecting wire and cable. Wire bean connectors where utilized shall be rated for the environment for they are installed.
13. Neatly bundle and wrap all horizontally run (above accessible ceilings and not within conduit) wire and cable at three-meter intervals. Provide support as required. All supports shall be UL listed for the application.
14. All System wiring within vertical riser shafts (as required) is bundled, wrapped, and tied to the structure at three-meter intervals to isolate it from other wire and cable within the shaft. Additionally, all wire and cable within the shaft is supported at least every two floors using Greenlee Slack Grips (Split Mesh Lace Closing) or approved equal. Provide all personnel and equipment necessary to install and support the cable.
All equipment is UL listed for the application.
C. Conduit, Boxes, and Raceways
1. The conduit system is provided by the electrical contractor. However, Security
Contractor provides all conduit necessary for complete installation, but not provided by the electrical contractor, in finished areas concealed in chases, furring, concrete slabs and/or above suspended ceilings. No exposed conduit is to be installed within public areas.
2. Conduit is carefully installed, properly and adequately supported as required to comply with the requirements outlined herein and as required by the NEC to provide a neat, Workmanlike installation. Horizontal conduit runs are supported by clamps, pipe straps, special brackets, or heavy iron tie, tied to the black iron structural members supporting the ceiling. Fastening of conduit to masonry walls, floor or partitions require malleable pipe clips with screws and suitable expansion sleeves.
3. All conducts are cut accurately to measurements established at the building and is installed without springing or forcing.
4. All required inserts are drilled-in, and all openings required through concrete or masonry is saw cut or core drilled with tools specifically designed for this purpose.
5. Swab out and remove all burs from conduit before any wires are pulled.
6. Layout and install conduit run as to avoid proximity to hot pipes. In no case shall a conduit be run within proximity of such pipes, except where crossings are unavoidable and then the conduit is kept at least 1” from the covering of the pipe crossed.
7. Provide fire stops where conduits penetrate fire rated walls and/or floors.
8. All conduit installation, whether run exposed or concealed, is approved prior to installation by the Owner.
13 | P a g e
9.3 Access Control System
A. General
1. A typical Access Control System shall consist of but not limited to: ACS software, (Coordinate with Owner on additional software that maybe required), licensing, data gathering panel(s), card reader(s), request to exit device(s), door position switch(s), lockdown button(s), door release, power supplies, wiring, electrified door hardware, low voltage power supplies, magnetic door hold-open devices, door management alarm devices, interface to fire alarm system interface and video intercom system.
2. This section addresses device locations, door hardware coordination, power, security wiring, network drops, conduit and rough-in requirements required to support the ACS.
3. All ACS software, electronics, power supplies, and security wiring shall be Contractor Provided. Security Contractor must be Genetec Elite Gold Certified.
4. All electrified door hardware shall be Contractor Provided with additional requirements and direction from the Owner’s Security Department based on function.
5. Electrified door hardware power supplies shall be Contractor Provided.
6. All network drops shall be Contractor Provided with Structured Cabling experience.
Contractor may subcontract for specialty Fiber installation with prior approval from Austin Water Security Department.
7. All conduit, steel channel raceway, back boxes, penetrations, cores, sleeves, 120VAC power, high voltage cabling, terminations and grounding shall be installed by the Security Vendors electrical Contractor.
B. Approved Manufacturer
1. Genetec/Mercury Boards is the approved ACS Manufacturer for Austin Water.
C. ACS Server
1. Owner provides and maintains the server infrastructure and environment for the current ACS for all facilities.
2. Any new ACS servers required for a new construction project shall be Owner Provided/ Owner Installed unless otherwise directed by Owner.
3. For renovations and existing facilities, the existing server and infrastructure shall be utilized unless otherwise directed by Owner.
4. The Security Designer shall coordinate with Owner to ensure the server is adequately sized to meet the requirements of the ACS.
5. Any network drops and rough-in requirements required for the servers shall be coordinated with the Technology Designer at the time of design.
D. Client Workstation
1. The client workstation shall be Owner Provided / Owner Installed.
2. Security Contractor shall coordinate with Austin Water Security Department to ensure the client workstation is adequately sized to meet the requirements of the
ACS.
3. The Security Designer & Security Contractor shall coordinate all network drops and rough-in requirements with technology Designer at the time of design.
14 | P a g e
E. ACS Software
1. Austin Water has standardized Genetec Security Center/ Omni Cast Integration Software.
2. Software version shall be coordinated with Owner prior to any installation to ensure compatibility with existing system architecture.
3. The Contractor shall provide, install, and configure any additional software as required on the Owner Provided / Owner Installed server as required for and new construction and renovation projects.
4. The Contractor shall provide, install, and configure all software on the Owner Provided/ Owner Installed client workstation unless otherwise directed by the Owner.
F. ACS Licensing
1. The Contractor shall provide, install, and configure all licensing on the Owner Provided / Owner Installed server associated with the ACS.
2. The Contractor shall provide, install, and configure all licensing on the Owner Provided / Owner Installed client workstation associated with the ACS.
3. The Contractor shall provide, install, and configure all licensing on the controller board(s) / card reader(s) / door openings as required to provide a fully functional access control system.
G. ACS Data Controlling Boards (Genetec Cloud link) & (Mercury LP1502)
1. The Mercury Boards are typically configured in four (4), eight (8) or sixteen (16) position door controller panels with associated access control power supplies.
2. The primary intelligent controller is Genetec CLOUDLINK and Mercury LP1502 Intelligent Board all sub-panels shall be in the applicable MDF room unless the distance makes it necessary to locate sub-panels in applicable IDF Rooms. One Genetec Cloud link and One Mercury LP1502 is required per MDF/IDF closet.
3. The Genetec Cloud link & Mercury Boards and sub-panels shall be wall mounted in the applicable MDF/IDF rooms on a security riser backboard inside a Life Safety enclosure or specified Stainless Steel Hoffman enclosure.
4. All security communications shall be OSDP Version 2 or Wiegand from the card reader to the control panel(s).
5. The security communications from the control panel(s) shall be at a minimum AES-
128 or higher encryption.
6. The typical maximum distance from a Controlling Board or sub-panel board to an ACS device shall not exceed 300 feet.
H. Security Wiring
1. Interconnections of Controllers primary and sub panels boards:
a. Minimum 20-gauge, 2-Conductor, Plenum Shielded twisted pair RS-485 cable with drain.
2. Power and Power Distribution Board Connections within enclosure:
a. Minimum 18-gauge, 2-Conductor, Plenum Non-Shielded cable.
15 | P a g e
I. Conduit And Rough-In Requirements
1. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
2. MDF / IDF rooms shall have sleeves leading from the nearest corridor into the security closet areas. All sleeves shall be installed with lock rings, and bushings on both ends and 200 lbs. pull string.
3. Security panels and power supplies shall be mounted on fire rated plywood backer board.
4. 1” conduit from the 120VAC circuit to the power supply enclosure. Conduit shall be located nearest the termination point to avoid overlapping of low voltage cabling.
J. Power Requirements
1. Power for the Controller and sub boards shall be 120VAC & 24VDC.
2. Networked-based Cloud link & Mercury boards shall be PoE unless otherwise directed by Owner.
3. All non-PoE board’s locations will require at least one (1) dedicated 120VAC 20A emergency circuit hard-wired at the security riser backboard.
4. Genetec Cloud link & Mercury LP1502 shall be installed in a manufacturer approved power supply enclosure unless otherwise directed by Owner.
K. Network Connectivity
1. The Security Designer shall coordinate all network drops and rough-in requirements with Technology Designer at the time of design.
2. All primary intelligent Genetec Cloud link & Mercury LP1502 will require one (1) plenum-rated Category 6 cables from the applicable MDF/IDF Room to the enclosure.
3. PoE Based Sub-panels require one (1) plenum-rated Category 6 cables from the applicable MDF/IDF Room to the panel enclosure.
L. ACS Communications
1. All Controllers (primary and sub) shall be connected via RS-485 for communication between the panels within the MDF/IDF enclosure(s)
M. Power Supply and Power Distribution
1. General
a. Provide ACS manufacturers with approved power supply enclosure designed to house the Genetec Cloud link & Mercury Boards, Power supplies, and power distribution modules as required for each MDF / IDF location.
b. Enclosures shall include prefabricated backplanes and stand-offs designed to mount the ACS boards without requiring additional drilling or modifications.
c. Mounting of ACS boards on the enclosure door or “double stacking” boards on top of each other are not permitted unless specified by Austin Water Security Department.
16 | P a g e
d. Power Supplies and Enclosures shall be sized to allow room for growth (20% minimum)
e. Provide tamper switch for monitoring on the ACS.
2. Security Wiring
a. Tamper Switch:
1) Minimum 20-Gauge, 2-Conductor, Non-Shielded cable
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. MDF / IDF rooms shall have sleeves leading from the nearest corridor into the security closet areas. All sleeves shall be installed with lock rings, and bushings on both ends and 200 lbs. pull string.
c. Security panels and power supplies shall be mounted on fire rated plywood backer board.
d. Conduit for the 120VAC circuit for the power supply shall be located nearest the termination point to avoid overlap of low voltage cabling.
4. Power Requirements
a. All power supply enclosure locations will require at least one (1) dedicated 120VAC 20 Amp emergency circuit hard-wired at the security riser backboard.
b. Power for the Mercury Controller Boards shall be 24VDC.
c. Power for the power distribution boards and relay modules shall be 12/24 VDC depending on the device installed.
5. Network Connectivity
a. The Security Designer shall coordinate all network drops and rough-in requirements with Technology Designer at the time of design.
b. Provide one (1) additional plenum-rated Category 6 cables from the applicable MDF/IDF Room to the power supply enclosure for connection to the power supply network module. This is in addition to a data cable provided for a controller in the enclosure.
N. Card Reader Door
1. General
a. The Security Designer shall coordinate all card reader locations with the owner during the design process.
b. The Security Designer shall coordinate all American with Disabilities Act (ADA) door opener synchronization wire size, termination point(s) and relays with the ADA motor(s).
c. The Security Designer shall comply with ADA mounting requirements.
d. The card readers shall be properly mounted to a 1-gang box and sealed from weather/moisture.
e. Access control doors associated with automatic door operators shall have a means to delay the open impulse of the operator prior to the electrified door hardware unlatching.
f. Typical Access Control Door locations include but may not be limited to:
1) Main Entrance Doors
17 | P a g e
2) Secure Vestibule Areas
3) Staff Entry Doors
4) MDF/IDF Rooms
5) MEP Rooms
6) Designated Pedestrian Gates
7) Standalone Buildings
8) Other doors as designated by Austin Water
9)
2. Security Wiring
a. Interior
1) Typical Card Reader Door:
a) Minimum 4-Element Composite Plenum OSDP cable comprised of:
(1) 22-Gauge, 2-Twisted Pair, Shielded OSDP cable (Card Reader)
(2) 18-Gauge, 4-Conductor, Non-Shielded cable (Lock Power)
(3) 22-Gauge, 4-Conductor, Non-Shielded cable (Request to Exit)
(4) 22-Gauge, 2-Conductor, Non-Shielded cable (Door Contact)
2) Additional Card Reader for Read In / Read Out:
a) Minimum 22-Gauge, 2-Twisted pair, Plenum Shielded OSDP cable.
3) Door Operator Interface:
a) Minimum 18-Gauge, 6-Conductor, Plenum Shielded cable.
b. Exterior
1) Card Reader:
a) Minimum 18-Gauge, 2-Twisted Pair, Direct Burial Shielded OSDP cable
2) Door Position Switch:
a) Minimum 18-Gauge, 2-Conductor, Direct Burial Non-Shielded cable
3) Request to Exit:
a) Minimum 18-Gauge, 4-Conductor, Direct Burial, Non-Shielded cable
4) Lock Power:
a) Minimum 18-Gauge, 4-Conductor, Direct Burial, Non-Shielded cable
5) Gate Interface:
a) Minimum 18-gauge, 6-Conductor, Direct Burial, Non-Shielded cable
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. A 4”x4”x2” back backbox shall be mounted above the door with conduit pathways to the:
1) Card Reader
a) Wall Mount: ¾” conduit to a recessed 1-gang extra deep back box with 1-gang plaster ring.
18 | P a g e
b) Masonry or Stone: ¾” conduit to a surface mount 2-gang back box on interior wall, with ¾” conduit stubbed directly behind card reader location.
c) Mullion Mount: ¾” conduit down the storefront channel to the card reader mounting height with minimum 200 lbs. pull string or mule tape.
d) Mounting location shall meet all ADA requirements.
2) Request to Exit
a) Ceiling Mount: ½” conduit from back box stubbed into accessible ceiling space. Mount to ceiling tiles with low voltage 1-gang bracket and trim plate where required. This is the preferred method.
b) Wall Mount: ½” conduit from back box to 1-gang back box installed horizontally approximately 6 inches centered above door. Mount with trim plates where required.
c) Mullion Mount: ½” conduit down the storefront channel to the REX mounting location with minimum 200 lbs. pull string or mule tape.
d) Integral to door hardware: ¾” conduit down door frame to power transfer hinge location. (Share conduit with lock power where possible).
3) Door Contact
a) Recessed: ½” conduit stubbed into door frame. Provide block out for grouted door frames.
b) Surface mount: ½” conduit stubbed into door frame or back box where required. Provide block out for grouted door frames. Provide armored cable for exterior or industrial track mount installations.
4) Lock Power
a) Integral to electrified door hardware: ¾” conduit down door frame to power transfer hinge location. (Share conduit with integral request to exit where possible).
5) Auto / Sliding Door Operator (where applicable)
a) ¾” conduit to door operator control panel cable inlet knock out (share with other low voltage cable if possible)
4. Power Requirements
a. Power for the card readers shall 12VDC, locking devices shall be 24VDC and provided via the security wiring from their respective power supplies, which are located at the applicable controller power supply location.
5. Network Connectivity
a. The Security Designer shall coordinate all network drops and rough-in requirements with Technology Designer at the time of design.
19 | P a g e
O. Vehicle Gate
a. The Security Designer shall coordinate card readers at vehicle gate locations with the Owner and Gate Consultant during the design process.
b. The Security Designer shall coordinate all remote release wire size, termination point(s) and relays with the gate motor.
c. The Security Designer shall comply with ADA mounting requirements.
d. The card readers shall be properly mounted to a vehicle pedestal and sealed from weather/moisture.
2. Security Wiring
a. Card Reader:
1) Minimum 18-Gauge, 2-Twisted Pair, Direct Burial Shielded OSDP cable
b. Lock Power:
1) Minimum 18-Gauge, 4-Conductor, Direct Burial, Non-Shielded cable
c. Gate Interface:
a) Minimum 18-gauge, 6-Conductor, Direct Burial, Non-Shielded cable
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Provide conduit pathways from building to an above ground pull box that shall be mounted near the gate with conduit pathways to the:
1) Card Reader
a) ¾” conduit stubbed into vehicle pedestal enclosure (share conduit with vehicle pedestal intercom if possible).
2) Gate Interface (Open/Close Status, Request to Exit, Remote Release)
a) Conduit from pull box stubbed into gate motor enclosure.
b) Coordinate with Gate Consultant for exact pathway location and conduit requirements.
4. Power Requirements
a. Power for the card readers shall 12VDC, remote release input shall be via dry contact closures from the applicable DGP and associated power supply.
b. Additional devices at the pedestal such as LED lights shall be coordinated with the
20 | P a g e
MEP Consultant for additional power / step down transformers as required.
P. Elevator Access Control Interfacing
a. Designer shall coordinate elevator hall call and floor control requirements with Owner.
b. The Security Designer shall coordinate with the Architectural/Engineering design team and the elevator consultant during the design process to ensure the appropriate interface is provided to allow call function to be controlled via the access control security system.
c. Software integration with the ACS and Elevator Control Panel is preferred.
d. Whereas hardwire relay interfacing is required, provide a locked security interface enclosure near the elevator control panel, where located. A separate enclosure is to be provided for each elevator. Security Contractor is responsible for providing enclosure, relays, cabling and coordinating termination with the Elevator Contractor.
e. Coordinate provision and installation of Coax media converters if needed to provide power and signaling form the Security devices thru travel cable to elevator cab. All elevator control panel cable terminations shall be performed by the elevator Contractor.
2. Elevator Hall Call Control
a. Elevators shall primarily be equipped with a card reader on the ground floor typically.
b. When in the card reader control mode, the call button shall be disabled. The passenger shall be required to hold their access card up to a card reader mounted adjacent to the call button. Upon a valid card read, the access control system shall enable the call button. The passenger must then push the desired call button. Once the passenger has pushed the button, the elevator control system shall illuminate the button and call the elevator. The button shall remain lit when activated.
c. Whereas relay interfacing is utilized, the Elevator Contractor provide one pair of terminals per controlled call button such that a dry contact closure across the terminals to the security system shall enable the call button. The button shall remain enabled for as long as the dry contact is closed.
3. Elevator Floor Control
a. Owner to designate elevators requiring floor control.
b. Whereas card reader in the elevator cab is installed, passengers shall be required to hold their access card up to a card reader in the elevator cab. Upon a valid card
21 | P a g e read, the access control system shall enable floor buttons based on the user’s access levels. Buttons for authorized floors shall illuminate. The passenger must then push the desired floor button. Once the passenger has pushed the button, the elevator control system will take the passenger to the desired floor. The button shall remain lit when activated until the floor has been reached.
c. Whereas relay interfacing is utilized, the Elevator Contractor shall provide one pair of terminals per controlled floor button such that a dry contact closure across the terminals to the security system shall enable the floor button. The button shall remain enabled for as long as the dry contact is closed.
4. Security Wiring
a. Elevator Interface Relays
1) Minimum 18-Gauge, 2- Conductor, Plenum Non-Shielded cable
b. Hall Call Card Reader:
1) Minimum 22-Gauge, 2-Twisted pair, Plenum Shielded OSDP cable.
c. Elevator Cab Card Reader:
1) Elevator travel cable provided by Elevator Contractor
2) Minimum 22-Gauge, 2-Twisted pair, Plenum Shielded OSDP cable.
5. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
1) Wall mounted card reader:
a) ¾” conduit with to a 2-gang deep box and 1-gang plaster ring stubbed into nearest accessible ceiling.
b) Back box mounting location shall meet all ADA requirements.
2) Card reader mounted in elevator cab:
a) Coordinate elevator travel cable and power conversion requirements with Elevator Consultant.
b) Elevator Contractor shall be responsible for all drilling and mounting of ACS device within the elevator cab.
3) Elevator Interface Enclosure (Floor Control Only):
a) ACS manufacturer approved enclosure mounted on fire-rated plywood near elevator control panel designed to house DGP’s and elevator relays as required for controlled access.
b) Coordinate conduit requirements from security interface to elevator control panel.
6. Power Requirements
a. Power for the card reader at the elevator shall be 12VDC and provided via security wiring from the DGP, which is located at the nearest applicable MDF/ IDF.
22 | P a g e
b. Power for travel cable / media conversion devices for elevator cab card readers shall be coordinated with the MEP and Elevator Consultants.
Q. Request to Exit Device(s)
1. General
a. All locations shall be carefully coordinated with and approved by the Owner throughout the design process.
b. For new construction projects, the Security Designer shall coordinate with the Architectural/Engineering design team and Hardware Consultant throughout the design process to determine when request to exit device(s) are required to be integrated into the electrified door hardware.
c. For retrofit and renovation projects where the existing door hardware may remain, the Security Designer shall evaluate whether requests to exits are to be integrated in the electrified door hardware or request to exit motion sensors will be required.
d. If applicable, all access-controlled door(s) with electrified strikes shall receive a request to exit motion sensor above the door.
23 | P a g e
e. Typical locations include but may not be limited to:
1) All Doors with Card readers
2. Security Wiring
a. Refer to “Access Control Door” section.
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Refer to “Access Control Door” section for Request to Exit conduit and rough-in requirements.
4. Power Requirements
a. The Security Designer shall coordinate all power requirements with MEP Designer at the time of design.
b. Power for the request to exit devices shall be 24VDC and provided via security wiring from a centralized power supply, which is located at the applicable Genetec Cloud link /Mercury Boards or sub-panel head end.
R. Door Position Switches
1. General
a. All locations shall be carefully coordinated with and approved by the Owner throughout the design process.
b. The Security Designer shall incorporate door position switches on all card reader doors.
c. The Door position switches shall be recessed where possible. In areas where recessed door position switches cannot be utilized, the Security Contractor shall utilize surface mounted door position switches with armored cable.
d. If applicable, card reader doors on the facility perimeter shall receive Double Pole / Double Throw (DPDT) door position switches to allow the doors to be monitored by both the Access Control System and Intrusion Detection System.
e. All double doors that receive door position switches shall be wired in series.
f. Door position switches shall match color and finish of door frames where possible.
g. Typical locations include but may not be limited to:
1) All doors with card readers
2) Other doors as designated by Owner.
2. Security Wiring
a. Refer to “Access Control Door” section.
24 | P a g e
a. The Security Designer shall coordinate rough-in requirements with MEP Designer at the time of design.
b. Recessed door contact
1) 1/2” conduit to door frame.
c. Surface mount industrial door contact with armored cable.
1) 1/2” conduit to door frame or 1-gang back box if mounted in exterior environment.
2) Include mounting hardware and brackets for gate installations.
4. Power Requirements
a. The Security Designer shall coordinate all power requirements with MEP Designer at the time of design.
S. Duress
1. General
a. All locations shall be carefully coordinated with and approved by the Owner throughout the design process.
b. The Security Designer shall coordinate with the Architectural/Engineering design team and the Owner for mounting locations, procedures and/or related requirements.
c. Devices shall be a latching type and require keyed reset to disarm.
d. Typical location includes but may not be limited to:
1) Reception Area
2) Administrative Area
3) Cashier Areas
2. Security Wiring
a. Under Desk
1) Minimum 18-gauge, 2-Conductor, Plenum Non-Shielded with Metal-Clad Armored Cable
b. Wall Mount:
1) Minimum 18-gauge, 2-Conductor, Plenum Non-Shielded cable.
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Coordinate rough-in location with desk and cabinetry.
c. Undercounter mount:
1) ¾” conduit stubbed out to accessible lay in ceiling with 200 lbs. pull string to 2-gang back box with 1-gang plaster ring in knee space.
2) Metal 1-gang cover plate with hole and rubber grommet for armored cable.
3) Armored flexible metal conduit from back box to under desk button secured with metal fasteners. Use appropriately sized screws or fasteners to secure armored cable without penetrating through surface of counter.
25 | P a g e
4) No adhesive tape shall be permitted.
d. Wall mount:
1) ¾” conduit stubbed out to accessible lay in ceiling with 200 lbs. pull string to 2-gang back box with 1-gang plaster ring on wall.
2) Mounting location shall meet all ADA requirements.
5. The Security Designer shall coordinate all power requirements with MEP Designer at the time of design.
T. Door Release Buttons
1. General
a. All locations shall be carefully coordinated with and approved by the Owner throughout the design process.
b. The Security Designer shall provide under desk mounted buttons where required.
c. The Security Designer shall coordinate with the Architectural/Engineering design team and the Owner for door release procedures and/or requirements.
d. Devices shall be momentary unless otherwise directed by Owner.
e. Typical locations include but may not be limited to:
1) Reception Area
2) Administrative Area
3) Guard Station
2. Security Wiring
a. Under Desk
1) Minimum 18-gauge, 2-Conductor, Plenum Non-Shielded with Metal-Clad Armored Cable
b. Wall Mount:
1) Minimum 18-gauge, 2-Conductor, Plenum Non-Shielded cable.
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Undercounter mount:
1) ¾” conduit stubbed out to accessible lay in ceiling with 200 lbs. pull string to 2-gang back box with 1-gang plaster ring in knee space.
2) Metal 1-gang cover plate with holes and rubber grommet for armored cable.
3) Armored flexible metal conduit from back box to under desk button secured with metal fasteners. Use appropriately sized screws or fasteners to secure armored cable without penetrating through surface of counter.
4) No adhesive tape shall be permitted.
c. Wall mount:
2-gang back box with 1-gang plaster ring on wall.
26 | P a g e
2) Mounting location shall meet all ADA requirements.
a. The Security Designer shall coordinate all power requirements with MEP Designer at the time of design.
27 | P a g e
U. Electrified Door Hardware
a. For New Construction, the Security Designer shall coordinate with the Architectural/Engineering design team and Door Hardware Consultant throughout the design process to ensure the ACS and door hardware are properly coordinated and all requirements are met.
2. Typical Door Preparation
a. All door and door frame prep for U.L. Listed doors shall be performed by a certified U.L.
listed Contractor to maintain U.L. rating.
3. Power Requirements
a. The Security Designer shall coordinate all power requirements with MEP Designer at the time of design.
b. Power for the ACS devices at the door shall be 24VDC and provided via security wiring from a centralized power supply, which is located at the applicable Controller, or sub-panel located at the nearest MDF / IDF.
4. Typical Conduit rough-in requirements
a. Refer to “Access Control Door” section for typical rough-in requirements.
V. ACS Interface to Fire Alarm System
1. To provide for the automated unlocking of certain emergency egress doors controlling access throughout a building in a life safety situation, a hardwired interface from the fire alarm system will be required.
2. The Security Designer shall coordinate all power requirements with MEP Designer at the time of design.
3. The Security Designer shall coordinate with the Owner and Architectural/Engineering design team to determine what, if any interface, with the fire alarm system is required.
W. Door Management Alarm
1. General
a. All locations shall be carefully coordinated with and approved by the Owner throughout the design process.
b. The Security Designer shall coordinate with the Architectural/Engineering design team and the owner for Door Management Alarm procedures and/or requirements.
c. Typical locations include but may not be limited to:
1) Exterior doors monitored by the IDS.
2) Other doors as designated by the Owner.
2. Security Wiring
a. Power:
1) Minimum 18-gauge, 2-Conductor, Plenum Non-Shielded cable
b. Tamper:
1) Minimum 22-gauge, 2-Conductor, Plenum Non-Shielded cable
c. Door Position Sensor:
28 | P a g e
1) Minimum 22-gauge, 2-Conductor, Plenum Non-Shielded cable
d. Alarm Reset:
1) Minimum 22-gauge, 2-Conductor, Plenum Non-Shielded cable
e. Door Forced / Door Held Alarm Output
1) Minimum 18-gauge, 4-Conductor, Plenum Non-Shielded cable
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Door Management Alarm
1) ¾” conduit stubbed out to accessible lay in ceiling with 200 lbs. pull string to 2-gang back box with 2-gang plaster ring.
4. Power Requirements
a. The Security Designer shall coordinate all power requirements with MEP Designer at the time of design.
b. Power for the DMA shall be 24VDC and provided via the security wiring from a centralized power supply, which is located at the applicable DGP or sub-panel.
X. Audio Intercom System
1. General
a. All locations shall be carefully coordinated with and approved by the Owner throughout the design process.
b. The intercom system is comprised of a SIP audio intercom interfaced with a PBX call manager that communicates to the Owner SIP phone system. Owner shall designate call priorities and ring down function on a per project basis.
c. Intercoms shall Axis or 2NP and be SIP based unless otherwise directed by Owner.
d. PBX call manager shall be Owner Provided / Owner Installed.’
e. All network drops shall be Contractor Provided by Structured Cabling Security Contractor.
f. The intercom phone (Grand stream) will answer incoming calls from the Axis intercom call station and shall have the ability to release an electrified lock associated with the ACS. The door release shall be connected to the ACS as a I/O point and programed as a remote release input on the Grand stream Phone panel.
g. The Security Designer shall coordinate with the Architectural/Engineering design team and the Owner for mounting locations, procedures and/or related requirements.
h. Typical intercom locations include but may not be limited to:
1) Main Entrances
2) Employee / Staff Entrances
3) Vehicle Gates
a. Door Release Relays (as required)
29 | P a g e
1) Minimum 18-gauge, 4-Conductor, Plenum Non-Shielded cable
3. Typical Conduit rough-in requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Recessed mount intercom:
1) ¾” conduit from flush mount 2-gang back box with 2-gang plaster ring stubbed into nearest accessible ceiling.
c. Surface mount intercom:
1) ¾” conduit from surface mount 2-gang on-wall back box stubbed into nearest accessible ceiling.
d. Vehicle Pedestal:
1) ¾” conduit stubbed into vehicle pedestal enclosure (share conduit with vehicle pedestal card reader if possible).
4. Network Connectivity
a. The Security Designer shall coordinate all network drops and rough-in requirements with Technology Designer at the time of design.
b. All Master Intercoms shall require one (1) Category 6 cable rated for the environment it is installed in from the applicable MDF/IDF room.
c. Vehicle pedestals or other out of exterior distance locations will require a powered fiber / fiber media converter solution.
5. Power Requirements
a. All Master Intercom stations shall receive power via a Security Contractor or Owner Provided / Owner Installed Power over Ethernet (POE) switch.
b. Coordinate power requirements for powered fiber / fiber with media converter solutions with Security Contractor Consultant.
Y. Turnstiles
1. General
a. The Security Designer shall coordinate card readers at turnstile locations with the Owner and Architectural / Engineering design team throughout the design process.
b. The Security Designer shall coordinate all remote release wire size, termination point(s) and relays with the turnstile installer.
c. The Security Designer shall comply with ADA mounting requirements.
d. Provide provisions for turnstiles to be prepped to allow concealed mounting of Owner’s access control card readers inside the turnstile casework.
2. Conduit And Rough-In Requirements
a. Coordinate all rough-in requirements with MEP Designer at the time of design.
b. Card Reader:
1) ¾” conduit stubbed into card reader pedestal enclosure or turnstile. (Share with turnstile interface if possible).
c. Turnstile interface:
30 | P a g e
1) Conduit stubbed from accessible ceiling to turnstile control panel. (Share with card reader if possible).
2) Coordinate with turnstile installer for exact pathway, location, and conduit requirements.
3. Power Requirements
a. Power for the card readers shall 12VDC, remote release input shall be via dry contact closures from the applicable DGP and associated power supply.
b. Additional devices at the pedestal such as LED lights shall be coordinated with the MEP Consultant for additional power / step down transformers as required.
9.4 Intrusion Detection System
1. A typical Intrusion Detection System shall consist of but not be limited to digital alarm panels, expansion modules, Network / Cellular dialer, arm/disarm keypads, motion sensors, door position switches, glass break detection, duress buttons, power supplies, battery(s), perimeter fiber, radar, and wiring.
2. This section addresses device locations, door hardware coordination, power, security wiring, network drops, conduit and rough-in requirements required to support the IDS.
3. All IDS software, electronics, power supplies, and security wiring shall be Contractor Provided / Contractor Installed by Division 28 Security Contractor.
4. All network drops shall be Security Contractor Provided.
5. All conduit, steel channel raceway, back boxes, penetrations, cores, sleeves, 110VAC power, high voltage cabling, terminations and grounding shall be installed by the Division 26 Electrical Contractor.
6. Programming and configuration of the IDS and ancillary devices shall be Contractor Provided / Contractor Installed.
B. Approved Manufacturer
1. DMP XR500 Series is the acceptable IDS manufacturer for Austin Water.
C. IDS Software
1. Austin Water has standardized on the Genetec Security Center Software. The DMP XR500 series panel will be programmed into Genetec Security Center and programmed for remote Arm/Disarm/Bypass from Genetec and locally at site location via DMP Keypad.
2. Software version shall be coordinated with Owner prior to any installation to ensure compatibility with existing system architecture.
3. The Contractor shall provide, install, and configure any additional software as required on the Owner Provided / Owner Installed server as required for and new construction and renovation projects.
D. Digital Alarm Panel (DAP)
1. General
a. The primary DAP and all expansion modules shall be mounted in the applicable MDF room unless the distance makes it necessary to locate expansion modules in applicable IDF rooms.
b. The DAPs and expansion modules shall be walled mounted in the applicable MDF/IDF rooms on a security riser backboard.
31 | P a g e
c. Provide a manufacturer approved security enclosure for DAP and expansion modules.
d. The maximum-security wiring distance from a DAP or expansion module(s) to an IDS device shall not exceed 300 feet.
2. Security Wiring
a. Interconnections of DAP and Expansion Modules:
1) Minimum 20-gauge, 4-Conductor, Plenum Non-Shielded cable
b. Power and Power Distribution Board Connections within enclosure:
1) Minimum 20-gauge, 2-Conductor, Plenum Non-Shielded cable.
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. MDF / IDF rooms shall have sleeves leading from the nearest corridor into the security closet areas. All sleeves shall be installed with bushing on both ends and 200 lbs. pull string.
c. Security panels and power supplies shall be mounted on fire rated plywood backer board.
d. DAP Enclosure:
1) Conduit stub outs with lock rings nylon bushings in quantities as required for security cabling into the security enclosure.
e. Conduit from DAP power transformer location stubbed into security enclosure with lock ring and nylon bushing for low voltage cable pathway.
4. Power Requirements
a. The Security Designer shall coordinate all power requirements with MEP Designer at the time of design.
b. All DAPs and expansion modules will require a dedicated 120VAC 20A emergency circuit hard-wired power per security enclosure for peripheral device power.
Provide plug outlet for DAP power transformers.
E. Power Supply and Power Distribution
1. General
a. Provide IDS manufacturer approved power supply enclosure designed to house the DAPs, Power supplies, expansion and power distribution modules as required for each MDF / IDF location.
b. Enclosures shall include prefabricated backplanes and stand-offs designed to mount the IDS boards without requiring additional drilling or modifications.
c. Mounting of IDS boards on the enclosure door or “double stacking” boards on top of each other are not permitted.
d. Power Supplies and Enclosures shall be sized to allow room for growth (20% minimum)
e. Provide tamper switch for monitoring on the IDS.
32 | P a g e
a. Tamper Switch:
1) Minimum 20-Gauge, 2-Conductor, Non-Shielded cable
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. MDF / IDF rooms shall have sleeves leading from the nearest corridor into the security closet areas. All sleeves shall be installed with lock rings, and bushings on both ends and 200 lbs. pull string.
c. Security panels and power supplies shall be mounted on fire rated plywood backer board.
d. Conduit for the 120VAC circuit for the power supply shall be located nearest the termination point to avoid overlap of low voltage cabling.
4. Power Requirements
a. All power supply enclosure locations will require at least one (1) dedicated 120VAC 20A emergency circuit hard-wired at the security riser backboard.
b. Power for the DGP’s shall be 24VDC.
c. Power for the power distribution boards and relay modules (as required) shall be 12/24 VDC depending on the device installed.
5. Network Connectivity
a. The Security Designer shall coordinate all network drops and rough-in requirements with Technology Designer at the time of design.
b. Provide one (1) additional plenum-rated Category 6 cables from the applicable MDF/IDF Room to the power supply enclosure for connection to the power supply network module. This is in addition to a data cable provided for a DAP in the enclosure.
F. Arm/Disarm Keypad
1. General
a. The Security Designer shall coordinate card readers at specific locations with the Owner and Architectural / Engineering design team throughout the design process.
b. Provide a manufacturer with an approved key locked security enclosure for keypads as required.
c. Keypad shall connect to the IDS communication bus line.
d. The maximum-security wiring distance from a keypad to a DAP shall not exceed 300 feet.
e. Typical Keypad Locations:
1) Main Entry Vestibule
2) Employee / Staff Entrances
3) Cashier’s / Vault Room
4) Other areas as designated by Owner.
a. Minimum 18-Gauge, 4-Conductor, Plenum Non-Shielded cable
33 | P a g e
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Wall mount keypad:
1) ¾” conduit stubbed out to accessible lay in ceiling with 200 lbs. pull string to 2-gang back box with 2-gang plaster ring.
4. Power Requirements
a. Power for the keypad shall be 12VDC and provided via the security wiring from a centralized power supply, which is located at the applicable DAP or expansion module.
G. Motion Detectors
1. General
a. All locations shall be carefully coordinated with and approved by the Owner throughout the design process.
b. Provide gimbal mounts brackets for angling of wall mount motion detectors where required.
c. The maximum-security wiring distance from a motion detector to a DAP or expansion module shall not exceed 300 feet.
d. Typical locations include but may not be limited to:
1) All First Floor Administration Offices with Exterior Windows
2) All Entry and Exit Points
3) All Floors Above the First Floor accessible by unsecured stairwells
4) Hallways and major cross-corridors with exterior windows
5) Exterior mechanical / electrical rooms
6) Other areas as designated by Owner.
2. Security Wiring
a. Minimum 22-Gauge, 4-Conductor, Plenum Non-Shielded cable
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Wall mount:
1) ¾” conduit stubbed out to accessible lay in ceiling with 200 lbs. pull string to 2-gang back box with 1-gang plaster ring.
c. Ceiling Mount with accessible ceiling:
1) Mount to ceiling tiles with low voltage 1-gang bracket and trim plate where required.
d. Ceiling Mount with no accessible ceiling:
1) ¾” conduit from nearest accessible ceiling to 2-gang back box with 1-gang plaster ring and 200 lbs. pull string.
34 | P a g e
a. Power for the motion detectors shall be 12 VDC and provided via security wiring from a centralized power supply, which is located at the applicable IDP or expansion module.
H. Glass Break Detectors
1. General
a. All locations shall be carefully coordinated with and approved by the Owner throughout the design process.
b. The maximum-security wiring distance from a motion detector to an IDP or expansion module shall not exceed 300 feet.
c. Typical locations include but may not be limited to:
1) All First-Floor areas with Exterior Windows
2) All Entry and Exit Points
3) Hallways and major cross-corridors with exterior windows
4) Other areas as designated by Owner.
2. Security Wiring
a. Minimum 22-Gauge, 4-Conductor, Plenum Non-Shielded cable
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Wall mount:
1) ¾” conduit stubbed out to accessible lay in ceiling with 200 lbs. pull string to 2-gang back box with 1-gang plaster ring.
c. Ceiling Mount with accessible ceiling:
1) Mount to ceiling tile with low voltage 1-gang bracket and trim plate where required.
4. Power Requirements
a. Power for the devices shall be 12 VDC and provided via security wiring from a centralized power supply, which is located at the applicable IDP or expansion module.
I. Fence Intrusion Detection
1. General
a. All locations shall be carefully coordinated with and approved by the Owner throughout the design process.
b. Coordinate with Technology Designer for installation of insensitive fiber from fence intrusion detection processor unit.
c. The maximum-security wiring distance from the to a IDP or expansion module shall not exceed 300 feet.
d. Typical locations include but may not be limited to:
1) Fence perimeter of buildings as designated by Owner.
35 | P a g e
a. Minimum 18-Gauge, 4-Conductor, Direct Burial Non-Shielded cable for alarm input relays as required.
3. Conduit And Rough-In Requirements
a. The Security Designer shall coordinate all rough-in requirements with MEP Designer at the time of design.
b. Provide underground conduit pathway from building interior to sensitive fiber termination…