This is a Scope of Work document for Solicitation No. IFB 1100 AGM1007 issued by the City of Austin Electric Utility, operating as Austin Energy, for the supply of precast concrete manholes to be used in underground transmission, distribution, and communication systems. The contractor must supply precast concrete manholes engineered and fabricated to provide structurally safe designs, along with all necessary vehicles, equipment, and accessories for delivery and placement. The contractor shall deliver orders within seven calendar days of placement and confirm shipment quantities within two hours of notification. The initial contract term is twenty-four months, with the option for the City to extend the contract for up to three additional twelve-month periods at its sole discretion. The contractor must provide certified engineering data stamped by a registered professional engineer prior to manufacturing and designate a single point of contact skilled in providing and handling precast concrete manholes.
The document specifies that precast concrete manholes must conform to multiple standards and codes including ASTM A-615, ASTM C-478, ASTM C-858, AASHTO HS-20 loading, and ACI 318, with a minimum compressive strength of 4,000 psi in 28 days. Manholes must be rated for AASHTO HS-20 traffic loading and designed for burial depths of either three feet with 36-inch diameter access openings or five feet with 48-inch diameter access openings. No protective coating or liner is required. The contractor shall provide itemized invoices with specific information including invoice number, date, delivery order number, item descriptions, quantities, unit prices, and any applicable discounts. Invoices should be emailed to Santiago.Reyes@austinenergy.com. The City's Contract Manager is Patrick Rogers (512-480-3043, Patrick.Rogers@austinenergy.com), and the City's Procurement Specialist is Lorena McBee (512-978-0873, Lorena.McBee@austintexas.gov). No information regarding pricing terms, set asides, incumbents, or funding sources is provided in this document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IFB_1100_AGM1007_ATT_7_v1.docx | DOCX document | |
| IFB_1100_AGM1007_ATT_6_v1.docx | DOCX document | |
| IFB_1100_AGM1007_ADD_2_v1.pdf | ||
| CSP_6100_CLMB344_BID_DOC_5_v1.pdf | ||
| IFB_1100_AGM1007_0600_v1.xls | XLS spreadsheet | |
| IFB_1100_AGM1007_0500_v2.docx | DOCX document | |
| IFB_1100_AGM1007_ATT_4_v1.docx | DOCX document | |
| IFB_1100_AGM1007_ATT_5_v1.docx | DOCX document | |
| IFB_1100_AGM1007_ATT_1_v1.docx | DOCX document | |
| IFB_1100_AGM1007_ATT_2_v1.pdf | ||
| IFB_1100_AGM1007_ATT_3_v1.pdf | ||
| IFB_1100_AGM1007_ATT_8_v1.docx | DOCX document | |
| IFB_1100_AGM1007_PAC1_v4.docx | DOCX document | |
| IFB_1100_AGM1007_ATT_3_v2.pdf | ||
| IFB_1100_AGM1007_ADD_1_v1.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR PROPOSAL NO. __________
CITY OF AUSTIN
SCOPE OF WORK
PRECAST CONCRETE MANHOLES
SOLICITATION NO. IFB 1100 AGM1007
1.0 Purpose
1.1 The City of Austin Electric Utility, dba Austin Energy, requires a qualified Contractor to supply precast concrete manholes. The precast concrete manholes shall be engineered and fabricated to provide a structurally safe design.
1.2 The precast concrete manholes will be used by Austin Energy (AE) for the underground transmission, distribution, and communication systems.
2.0 Term of Contract
2.1 This Contract shall remain in effect for an initial term of twenty-four (24) months or the City terminates the Contract. This Contract may be extended beyond the initial term for up to three (3) additional twelve (12) month periods at the City’s sole option.
3.0 Contractor’s Requirements
The Contractor shall:
3.1 Supply all vehicles, equipment and accessories required to deliver, safely lift and place the manhole in the excavation for the manhole at the Austin Energy job site.
3.2 Present Austin Energy with the engineering data for the manholes, stamped/certified by a registered professional engineer prior to any manufacturing. The certified engineering data shall state the structural integrity for the manhole configurations listed in Attachment A.
4.0 Single Point of Contact
4.1 Provide a single point of contact (SPOC) who is skilled, knowledgeable, and experienced in providing and handling precast concrete manholes. The SPOC must comply with all SOW requirements.
4.2 Provide the SPOC’s office number, email address, and after hours phone number to the Contract Manager, within five (5) days after contract award.
4.3 During times the SPOC is unavailable (due to vacation, travel, etc., for example), provide a designee for the SPOC to the Contract Manager. The designee shall meet the same requirements as specified for the SPOC and shall have the same authority as the SPOC.
5.0 City’s Responsibilities
The City will:
5.1 Provide a point of contact to the awarded Contractor.
5.2 Provide a Delivery Order (DOM) for each order. No work shall be performed without a reference DOM.
6.0 Delivery Requirements and Locations
The Contractor shall:
6.1 Ensure delivery is made within seven (7) calendar days after the order is placed (either verbally or in writing). All orders must be shipped complete unless arrangements for partial shipments are made in advance.
6.2 Confirm the quantity to be shipped on all orders within two (2) hours of notification by phone from the City.
6.3 Delivery to locations that will vary and will be issued by Austin Energy with each order.
6.4 Provide, with each delivery, a shipping or delivery ticket showing the description of each item, quantity, and unit price.
6.5 In accordance with Specification E-0897, deliver and place the requested manhole(s) in the excavation designated for the manhole at the AE job site, and shall coordinate the date and time of placement with the order requestor.
6.6 Not make deliveries on City-recognized legal holidays, unless otherwise requested by the City.
7.0 Specific Invoice Requirements
7.1 The City’s preference is to have invoices emailed to Santiago.Reyes@austinenergy.com
7.2 For questions regarding your invoice/payment please contact the City Contract Manager.
7.3 At a minimum, invoices shall be itemized and contain the following information, or they will not be processed and will be returned to the Contractor for correction:
7.3.1 A unique invoice number
7.3.2 Invoice date
7.3.3 Purchase order or delivery order number
7.3.4 Description of the goods or services provided
7.3.5 The Contractor’s name and remit to address
7.3.6 Any discounts or markups, if applicable.
8.0 Applicable Standards
The Manholes shall conform to or exceed applicable requirements of the following standards and codes:
8.1 ASTM A-615 Grade 60 for Rebar
8.2 ASTM A-185 Grade 65 for Mesh
8.3 ASTM C-857 Minimum Structural Design Loading for Underground Precast Concrete Utility Structures
8.4 AASHTO HS 20 Loading
8.5 ACI 318 for Structural Concrete
8.6 ASTM C150 for Portland Cement
8.7 ASTM C478 for Standard Specification for Precast Reinforced Concrete Manhole Sections
8.8 ASTM C858 Standard Specification for Underground Precast Concrete Utility Structures ASTM C478 for standard
9.0 Design Loads
The precast concrete manholes (Attachment I) shall be:
9.1 Rated for AASHTO HS-20 loading. Traffic (live load = 16,000lbs) shall approach the structure from any direction.
9.2 Designed to be installed with the top of the vault to have a burial depth 3 feet or 5 feet below grade, whichever is specified.
9.3 Designed for a burial depth of 3 feet; and provided with access openings that are 36 inches in diameter.
9.4 Designed for a burial depth of 5 feet; and provided with access openings that are 48 inches in diameter.
10.0 Physical Requirements
10.1 The Contractor shall fabricate precast concrete manholes in accordance with Attachment I.
10.2 The precast concrete manhole windows shall be a non-reinforced concrete membrane. The dimensions of the windows and thickness of the non-reinforced concrete membrane shall be as shown on the attached drawings (Attachment I).
10.3 Minimum compressive strength of concrete shall not be less than 4,000 psi in 28 days.
10.4 The concrete cover for reinforcement shall be provided as shown in the attached drawings (Attachment I). If not noted on drawings, the concrete cover for reinforcement shall be 1.5 inches minimum for main reinforcing bars and ¾ inch for stirrups and ties.
10.5 The concrete finish shall be free of rock pockets and honeycombed areas.
10.6 The interior walls, ceiling and exterior surfaces exposed shall be smooth.
10.7 Knockout and duct openings shall be beveled on the exterior surface.
10.8 Inserts shall be provided as shown in the attached drawings (Attachment I).
10.9 No protective coating or liner is required on manholes used by Austin Energy.
11.0 Designation of Key Personnel
The City and the Contractor resolve to keep the same key personnel assigned to this engagement throughout its term. In the event that it becomes necessary for the Contractor to replace any key personnel, the replacement will be an individual having equivalent experience and competence in executing projects such as the one described herein. Additionally, the Contractor shall promptly notify the City and obtain approval for the replacement. Such approval shall not be unreasonably withheld. The Contractor’s and City’s key personnel are identified as follows:
| Name/ Title |
| Phone Number |
| Email Address |
| City Contract Manager |
| Patrick Rogers |
| 512-480-3043 |
| Patrick.Rogers@austinenergy.com |
| City Contract Administrator, Procurement Specialist |
| Lorena McBee |
| 512-978-0873 |
| Lorena.McBee@austintexas.gov |
Scope of Work
File details come from the government source that posted it. Updated .