IBM17R0007_A003_Grit_Line.pdf
PDF 294 KB Posted
- Solicitation number
- IBM17R0007
About this file
IBM17R0007 A003
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Revised_Grit_Line_Specifications_8-9-2017.docx | DOCX document | |
| Mechanical_DRW__M102.docx | DOCX document | |
| Picture_II_8-8-2017.docx | DOCX document | |
| Picture_8-8-2017.docx | DOCX document | |
| Electrical___E_111.docx | DOCX document | |
| Sign-in_sheet_for_the_Grit_Line_Project_Site_Visit.pdf | ||
| J.02_Revised_Specifications_7-14-2017_1.pdf | ||
| IBM17R0007-A002_Grit_Line_SBIWTP.pdf | ||
| J.03_Drawings.zip | ZIP file | |
| IBM17R0007_A001_Grit_Line_SBIWTP.pdf | ||
| IBM17R0007_Grit_Line_SBIWTP.pdf | ||
| J.04_Wage_Determination_CA170001_06.09.2017.pdf | ||
| J.01_Grit_Line_Scope_of_Work.pdf | ||
| J.02_Specifications.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE RATING
2. AMENDMENT/MODIFICATION NO.
A003
3. EFFECTIVE DATE
08/15/2017
4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)
IBWC_CODE
International Boundary and Water Commission
(IBWC)
USIBWC - ACQUISITIONS DIV
4171 NORTH MESA, STE. C100
EL PASO, TX 79902-1441
Philip Johnson
NAME
TEL.
johnsonpk@state.gov
6. ISSUED BY IBWC_CODE
International Boundary and Water Commission (IBWC)
USIBWC - ACQUISITIONS DIV
4171 NORTH MESA, STE. C100
EL PASO, TX 79902-1441
7. ADMINISTERED BY (If other than Item 6)
9A. AMENDMENT OF SOLICITATION NO.
IBM17R0007
CONTACT DUNS
CODE FACILITY CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, country, state and ZIP Code) (X)
X 9B. DATED (SEE ITEM 11)
06/21/2017
10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X XThe above numbered solicitation is amended as set forth in item 14. The hour and date specified for receipt of Offers is extended, is not extended, Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing items 8 and 15, and returning __0__copies of the amendment;(b)By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.__0__X
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
The purpose of this amendment is to incorporate the following:
1. Response to questions, see continuation page 3.
2. Add Drawings: Mechanical #M102 and Electrical #E111.
3. Revise Grit Line Specifications.
4. Sign-in roster from site visit August 1, 2017.
As stated on the original solicitation, This is set Aside 100% for Small Business.
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
Philip Johnson
(Signature of person authorized to sign)
15B. CONTRACTOR/OFFEROR 15C. DATE SIGNED
By (Signature of Contracting Officer)
16B. UNITED STATES OF AMERICA 16C. DATE SIGNED
NSN 7540-01-152-8070
Previous edition unusable
STANDARD FORM 30 (REV. 10-83)
Prescribed by GSA FAR (48 CFR) 53.243
IBM17R0007
8. Question: I am looking at the statement of work. Based on prior experience, the 3 WIS Access F&C does not have protective grading specified. Do you want the grading or do you want as is? Some one can fall into it if not specified. This grading is separately ordered.
Response: The specified W1S access door model No. W1S2424 by Halliday shall be replaced with 15-inch HS20 Rated Galvanized Steel access hatch (detail LHS40-D01) as manufactured by Trenwa, Inc or equal.
9. Question: Can you please also specify what kind of pipe supports to use for the 8” Glass Lined ductile iron pipes inside the precast concrete trench? I don’t believe that it will be good to merely leave the ductile iron pipes inside the concrete trench without any metal braces or supports.
Response: The two 8-inch Glass Lined Ductile Iron pipe supports shall be in accordance with pipe manufacture’s rating and recommendations and per the precast concrete Trench system manufacturer’s recommendation and approved by the COR.
10. Question: Section 15052, Paragraph 1.1C.11.” Please provide Specification” Section 15140, Pipe Hangers and Supports.
Response: See response to question #9 above.
11. Question: Section 15052 Exposed Piping Installation, Paragraph 2.1. D.2a. “ Flanged Joints: a.Assemble flanged joints using 1/8-inch ring-type gaskets for raised face flanges.
Use full face gaskets for flat face flanges unless otherwise approved by COR. Gaskets shall be suitable for the service intended in accordance with the manufacturer's ratings and instruc¬tions. Gaskets shall be properly centered. “What Kind of gasket material.
“This information is usually stated in the Specification Section 15061 Ductile Iron Pipe”.
Response: The gasket shall be 1/8-inch full face flange-TyTE supplied by U.S. Pipe (United States Pipe and Foundry Company, LLC) or equal. Gaskets installations shall be in accordance with manufacturer’ instructions and recommendations and approved by the COR. Section 15061 Ductile Iron Pipe is included in the attached revised Specification.
Solicitation: IBM17R0007 Title: Replacement of the Grit lines and the Installation of new Glass Lined Ductile Iron pipes in Precast Concrete Trench at South Bay International Wastewater Treatment Plant
Questions received from prospective offerors are clarified/answered as follows:
12. Question: Section 15052, Part 3, Paragraph 3.8 D, Piping Schedule “Please supply bidder a complete list. Here the Spec. is truncated.”
Response: A complete Exposed Piping Schedule is included in the attached revised Specifications.
13. Question: Section 15068, Glass Lined Ductile Iron pipe, Part1, Paragraph 1.1B.5,8 and 9 “please provide these three specification (Section 09900 Painting, Section 15052 Exposed Piping Installation and Section 15061 Ductile Iron Pipe).
Response: The three section are included in the attached revised Specifications.
14. Question: Scope of Work, Paragraph 6. Provide and install all required conduits, fittings and wires and connect the flow meters to SCADA system and update SCADA screen to reflect new flow meters. All installation and testing shall be in accordance with manufacturer recommendations. “Please provide details where (what structures) and what travel route to install to. Please provide the testing details.
Response: The flow meters shall be installed at the SBIWTP Headworks Building.
The contractor is required to core drill through the west wall of the Headworks Local Control Center (HW-LCC). The contractor shall provide and install all required conduits, meter power, and control wiring between each meter’s location and the Programable Logic Controller (PLC) and power supply located at Headworks Local Control Center (HW-LCC). Contractor shall be required to terminate meters’ power and control wiring as directed by the COR. The programming to SCADA system shall be performed by the Government. (See attached Drawings M102 and E111.
15. Question: There appears to be various utilities to be identified (exposed) after marking or exploratory by pothole or by vacuum excavation. The cost to Relocate them will be more than your budget ($1,000,000) limit. My questions: will you approve additional RFI funding to have them relocated by contractor or will relocation be done by owner prior to installation? If contractor will relocate, any permit required by contractor from owners?
Response: None of the existing unities is anticipated to be relocated except for 3-inch buried Gate Valve (approximately 4 feet deep) and shallow street light box (29”X 23X 12”) to be relocated in same vicinity at Headworks Area (See attached picture # I). No permit is required except the approval of the COR prior to relocating. The cost for relocating of these two items shall be included in the contractor’s bid proposal.
16. Question: Secondly, relocating utility is a daunting task requiring time especially when different outside Agency owners are involved. 120 completion days might not be enough
Response: No. (see response to question #15 above).
17. Question: when we tie into the existing 6” pipeline, will we need to bypass that existing 6” line or will the existing 6” pipeline be shut down by the owner prior to our pipe connection.
Response: The contractor shall provide and install all required piping, fittings, supports, incidentals, services, and labor required to bypass the girts flows from the Grit Chambers to the Headworks during the construction period including the final tie in. The contractor shall replace the existing temporary two 6-inch pipelines bypass system with new temporary two 6-inch bypass system between the Grit Chambers and the Headworks.
The contractor shall maintain the new temporary bypass two 6-inch pipelines grit system during the construction period. The contractor shall ensure the continued operation of the Grit system at all the times during the construction period. The contractor shall comply with all contract documents requirements. (See attached picture # II) considering liquidation count. If contractor will relocate utility will you consider doing in phase thereto extending contract completion date?
| IBM17R0007 A003.pdf |
| Response to Grit Line Questions 8-14-2017.pdf |
| Sign-in sheet for the Grit Line Project Site Visit.pdf |