This technical report summarizes the results of a hazardous materials inspection conducted at the United States Department of Agriculture Agricultural Research Service Knipling-Bushland U.S. Livestock Insects Research Laboratory in Kerrville, Texas. The inspection identified polychlorinated biphenyl-containing lighting ballasts, mercury-containing fluorescent light tubes, equipment containing ozone depleting substances, various petroleum products and chemical substances, and hazardous waste present in satellite accumulation facilities, laboratory fume hoods, and storage cabinets on site. The inspection was performed in support of an upcoming modernization project at the laboratory, which will involve demolition of various structures. Remediation and proper disposal of identified hazardous materials and wastes will be required prior to commencement of construction.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ENVIRONMENTAL SCIENCE, ENGINEERING & INDUSTRIAL HYGIENE SERVICES
Middletown, MD ~ Morgantown, WV Corporate Office: 200 W Main Street, Middletown, MD 21769 Tel: (301) 694-5687 ~ Fax: (301) 694-9799
TRANSMITTAL
DATE: June 3, 2019
BEC PROJECT NUMBER: TX18002
PROJECT NAME: United States Department of Agriculture (USDA)
Agriculture Research Service (ARS), Plains Area (PA) Knipling-Bushland U.S. Livestock Insects Research Laboratory (KBUSLIRL) 2700 Fredericksburg Road Kerrville, Texas 7808-9184
FORWARDED TO: MERRICK & COMPANY
5970 Greenwood Plaza Boulevard Greenwood Village, Colorado 80111
Merrick Project #64019927-00
ATTENTION: Mr. Jon C. DeLay, P.E.
Sr. Project Manager
SUBJECT ITEM(S): 17 May 2019-USDA Kerrville Hazardous Materials Inspection–Final Technical Report
COMMENTS: For Your Use & Distribution
USDA ARS KBUSLIRL HAZARDOUS MATERIALS/WASTES & PETROLEUM PRODUCT SURVEY
KERRVILLE, TEXAS FINAL TECHNICAL REPORT
PCBs, MERCURY, PETROLEUM, HAZARDOUS MATERIALS INSPECTION
Conducted at:
UNITED STATES DEPARTMENT of AGRICULTURE
AGRICULTURAL RESEARCH SERVICE
KNIPLING-BUSHLAND
U.S. LIVESTOCK INSECTS RESEARCH LABORATORY
2700 FREDERICKSBURG ROAD
KERRVILLE, TEXAS 7808-9184
Prepared for:
BEC Project #TX18002
Fieldwork Conducted:
March 24, 2019 – April 3, 2019
Report Date: May 17, 2019
Middletown, MD ~ Morgantown, WV Corporate Office: 200 W Main Street, Middletown, MD 21769 Tel: (301) 694‐5687 ~ Fax: (301) 694‐9799
PCBs, MERCURY, PETROLEUM, HAZARDOUS MATERIALS INSPECTION
Conducted at:
Knipling-Bushland U.S. Livestock Insects Research Laboratory
TABLE OF CONTENTS
SECTION 1.0 SITE DESCRIPTION & SCOPE OF WORK 1
SECTION 2.0 HAZARDOUS MATERIALS INSPECTION 1
Section 2.1 Polychlorinated-Biphenyl Containing Materials 1
Section 2.2 Mercury Containing Materials 2
Section 2.3 O Zone Depleting Substances 2
Section 2.4 Petroleum & Other Chemical Containing Substances 2
Section 2.5 Hazardous Waste 2
Section 2.6 Hazardous Materials Inspection Limitations 2
SECTION 3.0 CONCLUSIONS & RECOMMENDATIONS 3
Section 3.1 Conclusions 3
Section 3.2 Recommendations 3
APPENDICES
APPENDIX A: PCB Containing Material
APPENDIX B: Mercury Containing Materials
APPENDIX C: O Zone Depleting Substances
APPENDIX D: Petroleum & Other Chemical Products
APPENDIX E: Observed Hazardous Waste
APPENDIX F: Hazardous Waste Manifest
APPENDIX G: BEC Photo Sheet
BOGGS ENVIRONMENTAL CONSULTANTS, INC.
On-site Fieldwork & Final Technical Report By: Technical Report Reviewed By;
Andrew Hanson Mark A. Boggs
Project Manager President/CEO http://boggsenvironmental.com/
SECTION 1.0 SUBJECT SITE DESCRIPTION & SCOPE OF WORK
Project Site: United States Department of Agriculture (USDA)
Agriculture Research Service (ARS), Plains Area (PA)
Knipling-Bushland U.S. Livestock Insects Research Laboratory (KBUSLIRL)
2700 Fredericksburg Road
Requester Name:
Requestor Address: Jon C. DeLay, P.E.
Sr. Project Manager
Subject Site Description & Scope of Work:
The subject site, Knipling-Bushland U.S. Livestock Insects Research Laboratory (KBUSLIRL), provides important tick and blood-feeding fly research capabilities supporting long-standing cooperative efforts among the USDA ARS Animal
Plant Health Inspection Service (APHIS), USDA ARS Veterinary Service (VS), and the U.S. cattle industry.
The scope of work was to survey all improvements present at the KBUSLIRL grounds for hazardous materials/wastes and petroleum products, in support of a major modernization project scheduled to commence at KBUSLIRL in the near future. These hazardous materials/wastes and/or petroleum products are required to undergo proper removal and disposal
(or transfer from planned work zones to other areas of operation for reuse, as applicable) prior to commencement of the modernization project, It is our understanding nearly all existing structures are slated for demolition to accommodate the modernization project. The structures to undergo demolition include, but may not necessarily be limited to, the following: two barns; three research labs; two insect rearing facilities; three insect research labs; storage garage; ten isolation pens; feed shed and related pens; and two animal shelters
BEC conducted the hazardous materials survey under contract to Merrick & Company (Merrick) of Denver, Colorado.
Merrick is a prime contractor to the USDA ARS providing architectural/engineering (A/E) building design and construction period services. BEC understands USDA ARS requested the survey to determine applicability (and impact) of (i) United States (US) Environmental Protection Agency (EPA) / (ii) Texas Department of State Health Services
(TDSHS) environmental pollution/public health protective regulations and (iii) US Occupational Safety and Health
Administration (US OSHA) worker protection regulations to the planned construction work activities associated with the laboratory modernization project.
SECTION 2.0 HAZARDOUS MATERIALS INSPECTION
2.1 Background
BOGGS ENVIRONMENTAL CONSULTANTS, INC. conducted the hazardous materials survey at the subject site, located at 2700 Fredericksburg road, Kerrville, Texas, between March 24, 2019 and April 3, 2019.
BEC conducted interviews with the Owners to become familiar with the building history, conceptual modernization scope of work, limits of the inspection, and reviewed historic Hazardous Waste shipping manifests, prior to proceeding with the field inspection.
BEC notes the survey did not involve exploratory demolition to access hidden (enclosed) construction conditions nor inventory of laboratory supply/storage cabinets; only readily-accessible building areas, of which were deemed subject to disturbance during the planned renovation/demolition work, underwent visual inspection during the course of the survey.
http://boggsenvironmental.com/
Visual observations were made for materials and substances, including but not necessarily limited to, those listed hereunder:
hazardous materials, hazardous waste, petroleum products, chemical substances:
polychlorinated-biphenyl (PCB) compounds -containing dielectric fluids within electrical lighting fixture ballasts and electric transformers, mercury containing fluorescent light tubes, electrical switches, thermometers, thermostats, ozone depleting substances, and, chemical-containing substances
2.1 Polychlorinated-Biphenyl Containing Materials
Electrical lighting fixture ballasts missing labels or not labeled as “Non-PCB” were presumed to contain PCBs, and were inventoried, as such. BEC provides the descriptions of identified PCB containing light ballasts located at the subject site hereunder in Appendix A: PCB Containing Materials
2.2 Mercury Containing Materials
Multiple materials labeled by their manufacturer as containing low-pressure mercury and/or phosphorus vapors were present at the subject site. Fluorescent light tubes without green end caps are presumed to contain mercury vapors.
BEC provides the descriptions of identified mercury-containing light tubes located at the subject site in Appendix B:
Mercury Containing Materials
2.3 Ozone Depleting Substances
BEC identified the following equipment that contains or potentially contains ozone depleting substances (ODS) such as compressed refrigerant gases, during this site investigation. BEC provides the descriptions of identified ODS-containing storage vessels located at the subject site in Appendix C: Ozone Depleting Substances
2.4 Petroleum & Other Chemical Containing Products
BEC advises, during the course of the investigation, potential hazardous chemicals were observed at subject site. BEC provides the descriptions of identified petroleum products and other chemical substances located at the subject site in
Appendix D: Other Chemicals & Petroleum Products
2.5 Hazardous Waste
BEC advises, during the course of the investigation, containers labeled as hazardous were observed at the subject site.
Satellite hazardous waste accumulation facilities were observed at the subject site. The contents of the satellite hazardous waste facilities, laboratory fume hoods, and/or hazardous material/waste storage cabinets are required to undergo proper packaging, collection/transport, and appropriate disposal prior to commencement of the renovation/demolition work. BEC provides the descriptions of the hazardous waste identified at the subject site hereunder in Appendix E: Observed Hazardous Waste.
It is relevant to note, review of historical KBUSLIRL hazardous waste generation reports, provided in Appendix F:
Hazardous Waste Manifest, revealed the subject site generates less than one hundred kilograms (<100 Kg) of hazardous waste on a monthly basis. This level of hazardous waste generation is classified by the US EPA Resource
Conservation and Recovery Act, as a Very Small Quantity Generator (RCRA-VSQG).
2.6 Limitations
The above inspection was characterized by making observations for materials present at readily-accessible building areas. All readily-accessible areas were inspected, in accordance with generally accepted engineering work practices.
BEC advises the materials listed in the appendices were present during the course of the survey, however, specialized management programs require routine collection, transport, and disposal (or recycle/reuse) of these materials in accordance with federal and state regulations. Accordingly, the inventory of materials observed during the survey is subject to change. Therefore, BEC makes no warranty, expressed or implied, the materials inventory will remain, as observed during the course of the survey.
SECTION 3.0 CONCLUSIONS & RECOMMENDATIONS
3.1 Conclusions
1. BEC concludes, based upon onsite visual inspection, multiple electrical lighting fixture ballasts are present at the subject site. Some of these ballasts are subject to the requirements of the US EPA Toxic Substance
Control Act (TSCA) of 1976, including the Frank R. Lautenberg Chemical Safety for the 21st Century Act of
2016. Specifically, “Polychlorinated Biphenyls (PCBs) Manufacturing, Processing, Distribution in
Commerce, And Use Prohibitions” (40 CFR Part 761) regulations apply to disposal and/or recycling of PCB containing ballast.
2. BEC concludes, based upon the onsite visual inspection, fluorescent light tubes, containing elemental inorganic metallic mercury, are present at the subject site. These light tubes are subject to the requirements of the US EPA Resource Conservation and Recovery Act (RCRA) of 1976, including the Federal Hazardous and Solid Waste Amendments of 1984. Specifically, “Standards for Universal Waste Management” (40 CFR
Part 273) and “Identification & Listing of Hazardous Waste” (40 CFR Part 261) regulations apply to handling and management (removal and disposal) of fluorescent light tubes containing mercury and/or phosphorus.
3. BEC concludes, based upon the onsite visual inspection, equipment that contains or potentially contains ozone depleting substances (ODS) are present at the subject site. These ODS are subject to the requirements of the
US EPA Clean Air Act of 1970 (40 CFR Part 62), including the “Title VI- Ozone Layer Protection” amendments of 1990.
4. BEC concludes, based upon onsite visual inspection, hazardous waste is present at the subject site. This waste is subject to the requirements of the US EPA Toxic Substance Control Act (TSCA) of 1976, including the
Frank R. Lautenberg Chemical Safety for the 21st Century Act of 2016. In general, “Solid Wastes” (40 CFR
Part 260- 262) and specifically, “Identification & Listing of Hazardous Waste” (40 CFR Part 260) regulations apply to identification, segregation, packaging, shipping, and disposal of this waste.
5. BEC concludes, based upon onsite visual inspection, petroleum products are present at the subject site. The petroleum product is subject to the requirements of the US EPA Toxic Substance Control Act (TSCA) of
1976, including the Frank R. Lautenberg Chemical Safety for the 21st Century Act of 2016. Specifically, “Standards for the Management of Used Oil” (40 CFR Part 279) regulations apply to identification, segregation, packaging, shipping, and disposal of this waste.
6. BEC concludes, based upon the onsite visual inspection, various chemicals and paints used in the maintenance and upkeep of the buildings are present at the subject site and will need to be properly disposed of in accordance with Federal, State and local regulations.
SECTION 3.0 CONCLUSIONS & RECOMMENDATIONS
3.2 Recommendations
1. BEC recommends visual inspection of each electrical lighting fixture for PCBs, prior to renovation/demolition work activities disturbing and/or damaging the ballast. The completed survey involved visual inspection of a number of fixtures representative of the entire lot of fixtures; not every fixture was dismantled to accommodate visual inspection. PCB ballast should undergo disposal in accordance with local, state, and Federal regulations.
Non-leaking PCB ballast should be disposed in accordance with 40 CFR 761.50 (b)(2)(i) and 40 CFR 761.60
(b)(2)(i).
Any PCB ballast found to be leaking should be stored in accordance with 40 CFR 761.65 (c)(1) for up to 30 days and/or 40 CFR 761.65 (b) for longer than 60 days. Leaking PCB ballast should be disposed in accordance with 40
CFR 761.50 (b)(2) and 40 CFR 761.62 (a) or (c).
2. BEC recommends visual inspection of each fluorescent light tube for the manufacturer’s labels indicating the presence of mercury, prior to renovation/demolition work activities disturbing and/or damaging the light tubes.
The completed survey involved visual inspection of a number of light tubes representative of the entire lot of light tubes; not every light tube was removed from the lighting fixture to accommodate visual inspection. Precaution should be taken during removal, storage, and disposal of fluorescent light tubes to avoid breakage. BEC recommends, in accordance with recognized industry practices, recycling of all mercury-containing fluorescent lamp tubes, pursuant to their removal.
3. BEC recommends, in accordance with recognized industry practice, all paints, chemicals, and petroleum products shall be removed- in accordance with local, state, and federal regulations- prior to renovation/demolition work activities disturbing and/or damaging these materials. Transfer all materials for proper reuse and/or recycling or disposal.
4. BEC recommends all compressed refrigerant gases (ODS) undergo proper recovery and reclamation by a licensed
ODS technician, prior to renovation/demolition work activities disturbing and/or damaging the ODS-containing vessels.
5. BEC recommends compliance with existing site hazardous waste management program requirements for transfer, packaging, and shipping/disposal of all hazardous materials and/or wastes, prior to renovation/demolition work activities disturbing and/or damaging vessels containing hazardous waste.
6. Observe recognized industry standards in securing and safekeeping all transportation bills of lading, shipping manifests, disposal receipts, and/or certificates of destruction or recycling in accordance with appropriate recordkeeping practices.
APPENDIX A
PCB CONTAINING MATERIAL
PCB CONTAINING MATERIALS
Description Location/Building PCB Quantity
Light Tube Ballasts 1, 2, 4, 5, 7, 11, 13, 14, 15, 19, 21, 22, 27, 28, 32, 35, 36, 38, 39 Non-PCB 276 Each
PCB Containing Light Ballasts 37 PCB 30 Each
Horseshoe Light Tube Ballasts 1 Non-PCB 4 Each
Integrated Ballast for 4' Mini Light Tubes 1, 2, 3, 5, 6, 8, 9, 29, 30, 37, 38, 39, 40 Presumed PCB 611 Each
Pole Mounted Transformers Throughout PCB 25 Each
ENVIRONMENTAL SCIENCE, ENGINEERING AND INDUSTRIAL HYGIENE SERVICES
APPENDIX B
MERCURY CONTAINING MATERIALS
Description Location/Building Mercury Quantity
4' Light Tube 4, 11, 14, 15, 19, 21, 22, 27, 28, 30, 32, 35, 36, 37, 38, 39 Yes ~695 Each
Horseshoe Light Tube 1 Yes ~8 Each
2' Light Tube 1, 2, 5, 38 Yes ~13 Each
12" Light Tube 7, 13, 36 Yes ~60 Each
4' Mini Light Tube 1, 2, 3, 5, 6, 8, 9, 29, 30, 37, 38, 39, 40 Yes ~614 Each
Description Location/Building Mercury Quantity
Bi Metal Thermostat Building #13 No 1 Each
Honeywell Thermostat Building #32 Yes 1 Each
Thermostat (Electric Heat) Building #37 Yes 1 Each
MERCURY CONTAINING LIGHT TUBES
MERCURY CONTAINING THERMOSTATS
APPENDIX C
OZONE DEPLETING SUBSTANCES
OZONE DEPLETING SUBSTANCES
Description Location Quantity
Refrigerant (Likely R-22) for 2 AC Units Building #1 West Exterior Unavailable
R410A Refrigerant for Trane Exterior AC Compressor Building #2 Unavailable
R-22 Refrigerant for Avis AC Unit Building #2 150-300 psi
R-22 Refrigerant for 2 Localized Ruud AC Units Building #3 East Exterior 150-300 psi
Refrigerant (Likely R-22 or R-12) for 8 Window AC Units Building #4 < 3 lb
R-22 Refrigerant for Avis AC Unit Building #4 150-300 psi
R-22 Refrigerant for Avis AC Unit Building #5 150-300 psi
R-22 Refrigerant for Avis AC Unit Building #6 150-300 psi
R-22 Refrigerant for Avis AC Unit Building #8 150-300 psi
Refrigerant (Likely R-22 or R-12) for Window AC Unit Building #9 < 3 lb
Refrigerant (Likely R-22) for Daya AC Compressor Building #9 Unavailable
Refrigerant (Likely R-22 or R-12) for 2 Window AC Units Building #11 < 3 lb
R410A Refrigerant for Compressor Building #11 13 lb
Refrigerant (Likely R-22 or R-12) for 2 Window AC Units Building #15 < 3 lb
Refrigerant (Likely R-22) for AC Unit Building #21 < 3 lb
Refrigerant (Likely R-22 or R-12) for 6 Window AC Units Building #22 < 3 lb
Refrigerant (Likely R-22 or R-12) for 3 Window AC Units Building #28 < 3 lb
R410R Refrigerant for Coleman AC Compressor Building #29 3 lb 7 oz
R-22 Refrigerant for Avis AC Unit Building #35 150-300 psi
Refrigerant (Likely R-22) for AC Unit Building #36 Unavailable
Refrigerant (Likely R-22) for AC Unit Building #37 East Exterior Unavailable
Refrigerant (Likely R-22) for AC Unit Building #37 West Exterior Unavailable
Refrigerant (Likely R-22 or R-12) for Ruud AC Unit Building #37A Unavailable
R410A Refrigerant for Tappan AC Compressor Building #38 6.63 kg
R-22 Refrigerant for Avis AC Compressor Building #38 150-300 psi
R410A Refrigerant for Tappan AC Compressor Building #39 6.63 kg
R-22 Refrigerant for Avis AC Compressor Building #39 150-300 psi
R-22 Refrigerant for Avis AC Compressor Building #40 150-300 psi
Refrigerant (Likely R-22 or R-12) for Window AC Unit Building #40B < 3 lb
APPENDIX D
PETROLEUM & OTHER CHEMICAL PRODUCTS
PETROLEUM AND OTHER CHEMICAL PRODUCTS
Substance Location Quantity
Nuclaic Acid Building #38 8 Litres
Hazardous Material Building #39 18 Gallons
Acetone Building #10 40 Gallons
Silver Nitrate Building #5 5 Gallons
Acetone Building #5 4 Gallons
Ethyl Alcohol Building #5 1 Gallon
Methanol Building #5 4 Gallons
Chlorinated Waste Solvent Building #9 1 Gallon
Acetone Building #9 1 Gallon
TCE Building #9 2 Litres
Acetone Building #9 1 Gallon
Paint Building #17 3 Gallons
Spray Paint Cannister Building #17 4 Each
Hydraulic Oil Building #17 1 Gallon
Gasoline Building #17 5 Gallons
Lubricants Building #13 1 Can
Aerosol Paints Building #13 12 Cans
Gasoline Building #31 10 Gallons
Diesel Fuel Building #31 20 Gallons
Used Oil Building #31 220 Gallons
Live Bacteria Additive Building #31 55 Gallons
Motor Oil Building #31 15 Gallons
Latex Paint Building #31 30 Gallons
Isopropyl Alcohol Building #31 5 Gallons
Enamel Building #31 6 Gallons
Hydraulic Oil Building #31 2 Gallons
Various Alcohols Building #37 Flamable Cabinet 10 Gallons
Spray Paint Cannister Building #7 50 Each
Paint Building #7 10 Gallons
Dichloroethane Building #7 1-2 Litres
Isopropyl Alcohol Building #7 5 Litres
A33 Disinfectant Building #40B 5 Gallons
Diesel Fuel Generator South of Building #30 150 Gallons
Diesel Fuel Generator South of Building # 150 Gallons
APPENDIX E
OBSERVED HAZARDOUS WASTE
OBSERVED HAZARDOUS WASTE
Substance Location Quantity
Membrane Stain Building #38 1 Pint
Proprente Stain Gel Building #38 1 Pint
Chloroform Building #38 1 Pint
Phenols Building #38 1 Pint
Methanol Building #38 1 Pint
Imidazole Building #38 1 Pint
Hydrochloric Acid Building #39 1 Pint
Isopropyl Alcohol Building #39 1 Pint
Methanol Building #39 1 Gallon
Ethanol Building #39 1 Gallon
Buffer Building #23 1 Gallon
Sodium Phosphate Building #23 1 Gallon
Acetic Acid Building #23 1 Gallon
Isopropyl Alcohol Building #23 4 Litres
Phenol Alcohol Building #23 2 Litres
Phenol Chlorination Building #23 3 Litres
Phenol Chloroform Ethanol Building #37 1 Gallon
Phenaly Chloroform Ethanol Building #37 1 Cup
Chloroform/Isopropyl Alcohol Building #37 1 Pint
Isopropyl Alcohol/Ethanol Building #37 1 Pint
Hydrochloric Acid Building #37 1 Pint
Binding Buffer Building #37 1 Pint
Acidic Buffer Building #37 1 Pint
Acetone Building #37 1 Pint
Hydroacetic Acid Building #37 1 Pint
Biological Waste Building #37A 1 Bag
APPENDIX F
HAZARDOUS WASTE MANIFEST
APPENDIX G
BEC PHOTO SHEET
Knipling – Bushlands U.S. Livestock Insects Research Laboratory
PCB Containing Light Ballast
Mercury Containing 4’ Light Tube
Mercury Containing Horseshoe Light Tube
Mercury Containing 2’ Light Tube
Mercury Containing Mini Light Tube
Mercury Containing Thermostat
Pole Mounted Transformer
Petroleum & Other Chemical Products
| Hazardous Materials Report Transmittal |
| 17 May 2019 - USDA Kerrville - Hazardous Materials Inspection - Final Technical Report |