This document provides supplemental retaining wall parameters for a geotechnical engineering study of the USDA-ARS Knipling-Bushland Research Laboratory Modernization Project. The retaining wall parameters include recommended active lateral earth pressure values and friction angles for various on-site formations and lithologies that may be encountered, including clayey gravel, lean clay, limestone, and select fill. Concrete retaining walls are planned as part of the facility improvement and expansion. The retaining wall parameters were not included in the original May 29, 2019 geotechnical engineering report but are necessary for design of the planned retaining walls. The Army Corps of Engineers Engineering District Fort Worth is the agency overseeing the solicitation for the USDA-ARS Knipling-Bushland Research Laboratory Modernization Project.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARIAS
GEOPROFESSIONALS
To: Mr. Jon C. DeLay, P.E.
Company: Merrick & Company
From: Jerry D. Shepherd, P.E., D.GE Kacy M. Crawford, P.E.
Date: April21, 2020
Page: 1 of 1
Arias Job No.: 2018-933
Subject: Retaining Wall Parameters: USDA ARS KBUSLIRL Kerrville, Texas
Arias Geoprofessionals, Inc. (Arias) previously prepared a geotechnical engineering study for the above referenced project. The results of our study were originally presented in Arias Geotechnical Engineering Report, project number 2018-933, dated May 29, 2019 and revised July 2, 2019.
Please contact me for any additional parameters that are needed.
Sincerely, Arias & Associates, Inc.
TBPE Registration No: F-32 c~~ i~j)
4 ‘.~c5~ ~ “~~r •.*..
JERRY D.SHEPHERD ~
a ~
112142 ••‘~‘
Retaining wall recommendations were not within the scope of work for the above referenced Report.
Concrete retaining walls are now planned as part of the improvement and expansion of the facility, and recommended retaining wall parameters for the site are provided below in Table 1. The parameters presented for the Select Fill is an assumed value, since we do not know what the Select FilIwill be ultimately utilized at the site
Table 1: Retaining Wall Parameters
Formation and ~ - - Active Lateral Earth Pressure Values Lithology ¶•~ ~‘ ‘~ Friction, 0 EFD
~PCI (°) . . (pc~ Clayey Gravel (GC) 125 22 0.45 57
Lean Clay (CL) 120 20 0.40 45
Limestone 135 36 0.25 35
Select Fill 125 30 0.33 42
4/21/2020
~~96 rry D. Shepherd, P.E., D.GE Senior Geotechnical Engineer
Kacy . Crawford, P.E.