I_-_451524-1-38-01_10_TELECOMMUNICATIONS_S&S.pdf

PDF 3 MB Posted

Attached to
LAP - Regional Traffic Management Center Facility Construction Federal Funded Project FPID:451524-1-58-01 FAIN:D324-034B- Re-solicit
Solicitation number
PD 25-26.049
Issued by
Escambia County, Florida

About this file

This is a Telecommunications Symbols Legend and General Notes document for the Regional Traffic Management Center Facility Construction project (FPID: 451524-1-58-01) in Escambia County, Florida, prepared by HALFF Associates, Inc. The document provides comprehensive technical specifications and design standards for telecommunications infrastructure installation, including data and telephone outlets, wireless access points, cable tray systems, conduit routing, and grounding requirements. The project encompasses multiple building systems across interconnected spaces, with detailed plans showing floor layouts for north and south sections, site plans indicating underground conduit runs to a communications pullbox (COMM-PB01), and connections to a Server/Bench Test room (147). Key telecommunications components include 8 wireless access points distributed throughout the facility, 48-port patch panels for network connectivity, CAT6A data cabling terminations, and fire-rated pathway systems for cable penetrations through rated walls. The specifications mandate compliance with BICSI, EIA, and TIA industry standards, with all installations subject to ADA requirements and proper coordination with other building trades including HVAC, electrical, and structural systems.

The document establishes minimum installation standards requiring 1-inch conduit for twisted-pair cabling, plenum-rated cables for above-ceiling installations, proper cable support at 3-5 foot intervals, and comprehensive labeling protocols using self-laminating labels positioned within 3-6 inches of termination points. All conduit penetrations through fire-rated barriers must utilize EZ Path Series zero-maintenance fire-rated pathway systems, and telecommunications bonding conductors must be minimum #6 AWG stranded annealed copper. The specifications require a telecommunications main grounding busbar (TMGB) in the communications room with connections to the building's electrical grounding system, and mandate that contractors conduct wireless site surveys with heat maps and propagation analysis to optimize access point placement. Underground conduit runs are specified at 36 inches below grade with traceable wire and detectable warning tape at 12 inches below grade, and all installations must include proper slack and routing flexibility to accommodate future equipment changes and maintenance requirements.

View the file

Other files

File Type Posted
LAP_-_Regional_Traffic_Management_Center_Facility_Construction_Federal_Funded_Project_FPID:451524-1-58-01_FAIN:D324-034B-_Re-solicit_(Addendum_#8_Revision).pdf PDF
LAP_-_Regional_Traffic_Management_Center_Facility_Construction_Federal_Funded_Project_FPID:451524-1-58-01_FAIN:D324-034B-_Re-solicit_(Addendum_#7_Revision).pdf PDF
451524-1-38-01_SPECS_02-06-26.pdf PDF
451524-1-38-01_PLANS_02-06-26.pdf PDF
L_-_451524-1-38-01_TSPS_S&S.pdf PDF
H_-_451524-1-38-01_07_MECHANICAL_S&S.pdf PDF
K_-_451524-1-38-01_Plans_S&S.pdf PDF
E-_451524-1-38-01_09_ITS_S&S.pdf PDF
M_-_451524-1-38-01_08___ELECTRICAL_S&S.pdf PDF
F-_451524-1-38-01_04_STUCTURAL_S&S.pdf PDF
K_-_451524-1-38-01_Plans_S&S.pdf PDF
M_-_451524-1-38-01_08___ELECTRICAL_S&S.pdf PDF
G_-_451524-1-38-01_03_LANDSCAPE_S&S.pdf PDF
I_-_451524-1-38-01_10_TELECOMMUNICATIONS_S&S.pdf PDF
L_-_451524-1-38-01_TSPS_S&S.pdf PDF
J_-_451524-1-38-01_11_SECURITY_S&S.pdf PDF
E-_451524-1-38-01_09_ITS_S&S.pdf PDF
J_-_451524-1-38-01_11_SECURITY_S&S.pdf PDF
G_-_451524-1-38-01_03_LANDSCAPE_S&S.pdf PDF
H_-_451524-1-38-01_07_MECHANICAL_S&S.pdf PDF
F-_451524-1-38-01_04_STUCTURAL_S&S.pdf PDF
I_-_451524-1-38-01_10_TELECOMMUNICATIONS_S&S.pdf PDF
C-_451524-1-38-01_06_PLUMBING_S&S.pdf PDF
A-_451524-1-38-01_01__GEOTECHNICAL_S&S.pdf PDF
D_-_451524-1-38-01_02_CIVIL_S&S.pdf PDF
D_-_451524-1-38-01_02_CIVIL_S&S.pdf PDF
C-_451524-1-38-01_06_PLUMBING_S&S.pdf PDF
B_-_451524-1-38-01_05_FIRE_PROTECTION_S&S.pdf PDF
A-_451524-1-38-01_01__GEOTECHNICAL_S&S.pdf PDF
B_-_451524-1-38-01_05_FIRE_PROTECTION_S&S.pdf PDF
LAP_-_Regional_Traffic_Management_Center_Facility_Construction_Federal_Funded_Project_FPID:451524-1-58-01_FAIN:D324-034B-_Re-solicit_(Addendum_#3_Revision).pdf PDF
LAP_-_Regional_Traffic_Management_Center_Facility_Construction_Federal_Funded_Project_FPID:451524-1-58-01_FAIN:D324-034B-_Re-solicit_(Addendum_#2_Revision).pdf PDF
31_31_16-Termite_Treatment.pdf PDF
LAP_-_Regional_Traffic_Management_Center_Facility_Construction_Federal_Funded_Project_FPID:451524-1-58-01_FAIN:D324-034B-_Re-solicit.pdf PDF
[O]_O_-Agreement.ModifiedA_LAP_Sample.pdf PDF
Wage_Rates.txt TXT text file
P_-_Question_&_Answer_Report_24-25.086.pdf PDF
FHWA_1273_(2)_(2).pdf PDF
LAP_Division_1_Specifications.pdf PDF
O_-Agreement.ModifiedA_LAP_Sample.pdf PDF
M_-_451524-1-38-01_08___ELECTRICAL_S&S.pdf PDF
L_-_451524-1-38-01_TSPS_S&S.pdf PDF
K_-_451524-1-38-01_Plans_S&S.pdf PDF
J_-_451524-1-38-01_11_SECURITY_S&S.pdf PDF
H_-_451524-1-38-01_07_MECHANICAL_S&S.pdf PDF
G_-_451524-1-38-01_03_LANDSCAPE_S&S.pdf PDF
F-_451524-1-38-01_04_STUCTURAL_S&S.pdf PDF
E-_451524-1-38-01_09_ITS_S&S.pdf PDF
D_-_451524-1-38-01_02_CIVIL_S&S.pdf PDF
C-_451524-1-38-01_06_PLUMBING_S&S.pdf PDF
Show 40 more

Latest 50 of 52 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TELECOMMUNICATIONS SYMBOLS LEGEND

ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.

SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO

SCALE.

SYMBOL DESCRIPTION

DATA/TELEPHONE OUTLET. WALL MOUNTED -

STUB 1" CONDUIT ABOVE ACCESSIBLE

CEILING. MOUNT 15" AFF. PROVIDE WITH (1)

BLUE CAT6A DATA DROP.

DATA OUTLET. WALL MOUNTED - STUB 1"

CONDUIT ABOVE ACCESSIBLE CEILING. MOUNT

15" AFF. PROVIDE WITH (1) BLUE CAT6A

DATA DROP.

NOTES:

1. MOUNT ALL DEVICES AS INDICATED ABOVE, UNO ON

PLAN

2. 48" AFF INDICATES TO TOP OF DEVICE

15" AFF INDICATES TO BOTTOM OF DEVICE

ALL OTHER MOUNTING HEIGHTS INDICATE TO

CENTERLINE OF DEVICE

FLOOR MOUNTED DATA OUTLET - FLUSH

MOUNTED UNO. PROVIDE WITH (1) BLUE

CAT6A DATA DROP.

WIRELESS ACCESS POINT - PROVIDE WITH

(2) BLUE CAT-6A DATA DROP. PROVIDE WITH

10' SLACK FOR ACCESS POINT PLACEMENT.

TO BE TERMINATED IN CAT-6A DUAL JACK

SURFACE MOUNT BOX (BISCUIT).

AP

WIREMESH CABLE TRAY

A. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF

ALL POWER SOURCE WIRING IN ACCORDANCE WITH

ARCHITECTURAL MILLWORK. ALL INSTALLATIONS SHALL

COMPLY WITH ADA REQUIREMENTS.

B. CONTRACTOR SHALL VERIFY ALL REQUIREMENTS BEFORE

ANY ROUGH-IN IN ORDER TO COORDINATE

MANUFACTURER'S DRAWINGS FOR EQUIPMENT LOCATION

AND INSTALLATION ACCESSORIES.

C. COORDINATE ROUTING FOR CONDUIT UP IN JOIST AND

FOR SUSPENDING REQUIREMENTS IN ACCORDANCE WITH

STRUCTURAL PLANS.

D. ALL INTERCOM, DATA, CAMERA, AND TV DEVICES SHALL

BE STUBBED UP TO ABOVE ACCESSIBLE CEILING AND TO

CABLE TRAY IF PRESENT. THE CONTRACTOR SHALL

PROVIDE J-HOOKS AND CONDUITS TO EXTEND CABLING

TO WALLS.

E. ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL

USE THE EZ PATH SERIES FIRE-RATED ZERO

MAINTENANCE PATHWAY UNO. FOLLOW MANUFACTURER

USAGE AND INSTALLATION INSTRUCTIONS. REFER TO

DETAIL 9 ON SHEET T501.

F. CONDUITS SHALL BE REAMED AND COMPLETED WITH

CONNECTORS AND INSULATED BUSHINGS AT BOTH ENDS.

G. BETWEEN ANY TWO PULL POINTS THERE SHALL BE NO

CONDUIT WITH GREATER THAN 180 DEGREES OF BENDS

OR EQUIVALENT.

H. WHERE CONDUIT LENGTH EXCEEDS 100FT AND/OR TWO

90 DEGREE BENDS OR EQUIVALENT PROVIDE PULL

BOXES AS REQUIRED.

I. ALL ZONE CONDUITS (HOME RUN) FOR LOW VOLTAGE

COMMUNICATIONS CABLING SHALL BE MARKED AT THEIR

TERMINUS WITH A TAG THAT IDENTIFIES "DATA,

INTERCOM, ETC" (ROOM NAME AND NUMBER) WHERE THE

OTHER END OF THE CONDUIT TERMINATES.

J. ALL CABLES ABOVE CEILING SHALL BE PLENUM RATED.

ALL CABLES BELOW SLAB SHALL BE INDOOR/OUTDOOR

RATED.

K. FURNISH AND INSTALL 8'H X 4'W X 3/4"T VERTICALLY

HUNG, GRADE AC, PLYWOOD IN COMMUNICATION ROOMS

AS INDICATED ON PLANS. PAINT PLYWOOD WITH TWO

COATS OF FIRE RETARDANT TO MATCH EXISTING WALL

FINISH. COORDINATE WITH ARCHITECT, PRIME

CONTRACTOR, AND OWNER FOR INSTALLATION OF

BACKBOARD. REFER TO DRAWINGS FOR PROPOSED

LOCATION AND DETAILS.

L. MINIMUM CONDUIT SIZE FOR TWISTED PAIR CABLING

(LOW VOLTAGE) SHALL BE NOT SMALLER THAN 1" TRADE

SIZE.

M. THE CONTRACTOR SHALL FULLY REVIEW ALL ELECTRICAL

POWER PLANS TO IDENTIFY ALL RESPONSIBILITIES AND

SCOPE OF WORK.

N. DO NOT ROUTE FIRE ALARM RELATED CABLING IN SAME

CABLE TRAY, AS OTHER LOW VOLTAGE SYSTEMS.

UTILIZE DEDICATED J-HOOKS OR CONDUITS FOR ALL

FIRE ALARM RELATED CABLING.

O. ABOVE CEILING CABLE SUPPORTING HARDWARE. IN

CONJUNCTION WITH THE SPECIFIED CABLE TRAY,

ACCEPTABLE METHOD INCLUDES BUT IS NOT LIMITED TO

J-HOOKS. CABLE SHOULD BE PROPERLY SUPPORTED

WITH J-HOOK PATHWAY INSTALLED EVERY 3-5 FT.

CABLE CROSS SECTION AREA SHOULD BE CALCULATED

TO A 40% RATIO.

P. FURNISH AND INSTALL A COMPLETE HORIZONTAL AND

VERTICAL 1-IN BEND RADIUS CONTROL TO HELP

PREVENT DEGRADATION OF CABLE PERFORMANCE.

Q. THE CONTRACTOR DOCUMENTS DEPICT LOW VOLTAGE

SYSTEMS WHICH ARE INTENDED TO BE COMPLETE AND

FUNCTIONING SYSTEMS.

R. STRICTLY ADHERE TO ALL BICSI, EIA AND TIA

RECOMMENDED INSTALLATION PRACTICES.

TELECOMMUNICATIONS PLAN NOTES

S. CATALOG NUMBERS REFERENCED THROUGHOUT THE

DRAWINGS AND SPECIFICATIONS ARE INTENDED TO

CONVEY A GENERAL UNDERSTANDING OF THE TYPE OF

QUALITY OF THE PRODUCT REQUIRED. WHERE WRITTEN

DESCRIPTIONS DIFFER FROM INFORMATION CONVEYED

BY A CATALOG NUMBER, THE WRITTEN DESCRIPTION

SHALL GOVERN. NO EXTRA CHARGE SHALL BE ALLOWED

BECAUSE A CATALOG NUMBER IS FOUND TO BE

INCOMPLETE OR OBSOLETE.

T. FURNISH AND INSTALL APPROPRIATE BACKING IN WALLS

AS REQUIRED FOR MOUNTING BRACKETS AND OTHER

WALL MOUNTED EQUIPMENT PER MANUFACTURER

REQUIREMENTS.

U. TELECOMMUNICATIONS BONDING CONDUCTOR SHALL BE

MINIMUM SIZE #6 AWG STRANDED ANNEALED COPPER

CONDUCTOR WITH GREEN INSULATED PVC JACKET.

ENSURE GROUND CONTINUITY BY PROPERLY BONDING ALL

APPROPRIATE CABLING, CLOSURES, CABINETS, SERVICE

BOXES, AND FRAMEWORK TO TELECOMMUNICATIONS

GROUNDING BUSBAR.

V. FURNISH AND INSTALL WIRE MESH CABLE TRAY AS

SHOWN ON THE DRAWING SET.

W. ALL CONDUITS, CABLE TRAY, CABLE HOOKS AND OTHER

RACEWAYS SHALL BE COORDINATED WITH OTHER

TRADES PRIOR AND DURING BUILDING CONSTRUCTION TO

AVOID DELAYS AND CONFLICTS.

X. RACEWAYS SHALL BE PROPERLY GROUNDED PER NEC.

Y. CABLES SHALL BE LABELED ON A VISIBLE PART OF THE

CABLE WITHIN THREE TO SIX (3-6) INCHES OF

TERMINATION POINT WITH SELF-LAMINATING LABELS VIA

PANDUIT LABELER AND SOFTWARE.

Z. LABELS SHALL BE VISIBLE IF FACEPLATE IS REMOVED

AND NUMBERED SEQUENTIALLY BEGINNING CLOCKWISE

FROM THE FIRST OUTLET TO THE LEFT OF THE MAIN

ENTRANCE TO THE ROOM.

AA. ALL TRENCHING, EXCAVATION, AND BACKFILL IS THE

RESPONSIBILITY OF THE GENERAL CONTRACTOR.

BB. FURNISH AND INSTALL THROUGH-WALL FIRE RATED

PATHWAY DEVICES PROVIDING AN F-RATING RATING

EQUAL TO THE RATING OF THE BARRIER IN WHICH THE

DEVICE IS INSTALLED AS REQUIRED.

CC. COORDINATE EXACT LOCATION AND HEIGHTS FOR DATA

AND VOICE OUTLETS WITH ELECTRICAL OUTLETS.

DD. THE PLACEMENT OF WIRELESS ACCESS POINTS SHOWN

IN THE DIAGRAMS IS FOR ILLUSTRATIVE PURPOSES

ONLY. THE CONTRACTOR IS REQUIRED TO CONDUCT A

WIRELESS SITE SURVEY, INCLUDING A HEAT MAP AND

WIRELESS PROPAGATION ANALYSIS, TO DETERMINE THE

OPTIMAL PLACEMENT OF DEVICES.

TELECOMMUNICATIONS GENERAL ABBREVIATIONS

ABS ABOVE BACK SPLASH

AFF ABOVE FINISHED FLOOR

ARS AREA OF RESCUE SYSTEM

BFC BELOW FINISHED CEILING

BOCT BOTTOM OF CABLE TRAY

C CONDUIT

CB CIRCUIT BREAKER

CLG CEILING

EC EMPTY CONDUIT

EP ELECTRICAL PRIMARY

EX/(E) EXISTING

F FUSE

G GROUND (EQUIPMENT)

GAP GENERATOR ANNUNCIATOR PANEL

GFI GROUND FAULT INTERRUPTER

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

MTD MOUNT OR MOUNTED

MTG MOUNTING

(N) NEW

NL NIGHT LIGHT

NC NORMALLY CLOSED

N.O. NORMALLY OPEN

NF NONFUSED

NIC NOT IN CONTRACT

RCPT(S) RECEPTACLE(S)

PNL PANEL

SD SMOKE DAMPER

S.O. SPACE ONLY

SP SPARE

S.T. SHUNT TRIP

SW SWITCH

TYP TYPICAL

UF UNDERFLOOR

UG UNDERGROUND

UNO UNLESS NOTED OTHERWISE

WG WIRE GUARD

WP WEATHER PROOF

WP/WIU WEATHERPROOF w/

WHILE-IN-USE COVER

XFMR TRANSFORMER

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FLORIDA 32309

TEL. (850) 224-4400

HALFF ASSOCIATES, INC.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FL 32309

GABRIEL BENAVIDES JR. P.E

PE NO. 97009

T H E

O F F

IC

IA

L

R E C O R D

O F

T H

IS

S

E E T

E

E L E C T R O N

IC

F

IL

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

FINANCIAL PROJECT IDCOUNTYROAD NO.

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

TN001TELECOMMUNICATIONS GENERAL

NOTES AND LEGENDS

ESCAMBIA 451524-1-38-01

NORTH W

STREET

TELECOMMUNICATIONS SHEET INDEX

SHEET

SHEET TITLE

TN001 TELECOMMUNICATIONS GENERAL NOTES AND LEGENDS

TN100 TELECOMMUNICATIONS SITE PLAN

TN101 TELECOMMUNICATIONS OVERALL FLOOR PLAN

TN102 TELECOMMUNICATIONS FLOOR PLAN NORTH

TN103 TELECOMMUNICATIONS FLOOR PLAN SOUTH

TN201 TELECOMMUNICATIONS ENLARGED PLANS

TN401 TELECOMMUNICATIONS SCHEDULES

TN501 TELECOMMUNICATIONS DETAILS I

TN502 TELECOMMUNICATIONS DETAILS II

No. Date Issue / Revision ah3602 Snapshot

R

PROPOSED BUILDING

N O R T H

W E S T

S T R E E T

FUN CITY BLVD

EME

RGE

NCY

VE

HICLE

PAR

KIN

G

EXIS

TING

EOC

SERVER/BENCH

TEST

COMM-

PB01

EXISTING ATMS

SPLICE BOX

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FLORIDA 32309

TEL. (850) 224-4400

HALFF ASSOCIATES, INC.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FL 32309

GABRIEL BENAVIDES JR. P.E

PE NO. 97009

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

FINANCIAL PROJECT IDCOUNTYROAD NO.

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

TN100

TELECOMMUNICATIONS SITE PLAN

ESCAMBIA 451524-1-38-01

NORTH W

STREET

TELECOMMUNICATIONS SITE PLAN

20'0' 80'40'

KEY NOTES:

1. PROVIDE WITH 36"X36" IN-GROUND ENCLOSURE EQUAL TO

OLDCASTLE H-SERIES: 3636 WITH TIER 15 COVER FOR

INTERNET SERVICE PROVIDER (ISP). CONTRACTOR TO ROUTE

FLEXIBLE CONDUIT THROUGH BASE OF PULLBOX.

2. EXTEND (2) 4" CONDUITS FOR ISP AND (2) 2" SPARE

CONDUITS FROM COMM-PB01 TO SERVER/BENCH TEST ROOM

146. TO BE BURIED AT DEPTH OF 36' BELOW GRADE.

PROVIDE WITH TRACEABLE WIRE AND DETECTABLE

WARNING TAPE TO BE BURIED AT A DEPTH OF 12" BELOW

GRADE.

3. EXTEND (2) 2" CONDUITS FROM COMM-PB01 TO EXISTING

ATMS SPLICE BOX. FIELD VERIFY DEPTH PRIOR TO ROUGH-

IN. REFER TO SHEET ITS105.

GENERAL NOTES:

A. REFER TO SHEET TN001 FOR TELECOMMUNICATIONS

GENERAL LEGEND AND NOTES.

No. Date Issue / Revision

TN103

TN102

BOCT - ~15' - 2"

SIZE - 12"x4"

BOCT - ~15' - 2"

SIZE - 12"x4"

BOCT - ~8' - 0"

SIZE - 12"x4"

B O C T

S

IZ

E

"x

SERVER/BENCH

TEST

TYP.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FLORIDA 32309

TEL. (850) 224-4400

HALFF ASSOCIATES, INC.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FL 32309

GABRIEL BENAVIDES JR. P.E

PE NO. 97009

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

FINANCIAL PROJECT IDCOUNTYROAD NO.

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

TN101TELECOMMUNICATIONS OVERALL

FLOOR PLAN

ESCAMBIA 451524-1-38-01

NORTH W

STREET

TELECOMMUNICATIONS OVERALL FLOOR PLAN

8'0' 32'16'

KEY NOTES:

1. CONTRACTOR SHALL COORDINATE FINAL ROUTE OF CABLE

TRAY WITH OTHER BUILDING SYSTEMS SUCH AS HVAC

DUCT, CONDUIT, AND WATER LINES. PROVIDE BEST ROUTE

IN A MULTI-DISCIPLINE SHOP DRAWINGS FOR REVIEW.

MAKE FIELD ADJUSTMENTS AS NECESSARY FOR A FULL AND

FUNCTIONAL SYSTEMS THATS INSTALLED IN ACCORDANCE

WITH BICSI AND INDUSTRY STANDARDS.

GENERAL NOTES:

A. REFER TO SHEET TN001 FOR TELECOMMUNICATIONS

GENERAL LEGEND AND NOTES.

No. Date Issue / Revision

AP

APAP

AP-3

AP-1AP-2

R E F

T N

FILE

STORAGE

MEDIA

ROOM

NEXUS

CONFERENCE

COLLAB

OFFICE

COLLAB

OFFICE

COLLAB

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

RESTROOM

RESTROOM

CORRIDOR

120.2

CORRIDOR

120.1

CORRIDOR

120.3

AUTO

COLLABORATION

OPEN

OFFICE

RESTROOM

114CORRIDOR

120.5

SUPPLIES

/ TECH

CORRIDOR

120.4

JANITORIAL

/ UTILITY

DATA

VISUALIZATION

SUPPORT

115.2

ELEC.

MAIL /

SUPPLIES

COORIDOR

DIGITAL

RECEPTION

VESTIBULE

DATA

VISUALIZATION

SPACE

115.1

1 1

R E F

T N

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FLORIDA 32309

TEL. (850) 224-4400

HALFF ASSOCIATES, INC.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FL 32309

GABRIEL BENAVIDES JR. P.E

PE NO. 97009

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

FINANCIAL PROJECT IDCOUNTYROAD NO.

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

TN102TELECOMMUNICATIONS FLOOR

PLAN NORTH

ESCAMBIA 451524-1-38-01

NORTH W

STREET

TELECOMMUNICATIONS FLOOR PLAN NORTH

KEY NOTES:

GENERAL NOTES:

A. REFER TO SHEET TN001 FOR TELECOMMUNICATIONS

GENERAL LEGEND AND NOTES.

4'0' 16'8'

1. EXTEND A 1" CONDUIT TO NEAREST WALL CAVITY CLOSEST

TO CABLE TRAY. REFER TO DRAWING TN101 FOR SUGGESTED

CABLE TRAY ROUTING. TYPICAL OF ALL FLOOR BOX DATA

DROPS.

No. Date Issue / Revision

AP

AP

AP

AP AP

4 4 4

AP-8

AP-6

AP-5AP-4

AP-7

TN201

R E F

T N

R E F

T N

FAMILY

FAMILY

RTMC

TRAINING/MEETING

ROOM

FOOD

STORAGE

TMC

STORAGE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

SERVER/BENCH

TEST

OFFICE

MEN

CHASE

WOMEN

FURNITURE

STORAGE

134 MECHANICAL

ELEC

FIRE

SUPPRESSION

OFFICE

CORRIDOR

BREAK

ROOM

MEDIA

COVERAGE

ROOM

FOOD

STORAGE

BREAK

ROOM

CORRIDOR

CONTROL

ROOM

CORRIDOR

136.1

UPS

CORRIDOR

TYP.

3 3 3

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FLORIDA 32309

TEL. (850) 224-4400

HALFF ASSOCIATES, INC.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FL 32309

GABRIEL BENAVIDES JR. P.E

PE NO. 97009

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

FINANCIAL PROJECT IDCOUNTYROAD NO.

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

TN103TELECOMMUNICATIONS FLOOR

PLAN SOUTH

ESCAMBIA 451524-1-38-01

NORTH W

STREET

TELECOMMUNICATIONS FLOOR PLAN SOUTH

KEY NOTES:

GENERAL NOTES:

A. REFER TO SHEET TN001 FOR TELECOMMUNICATIONS

GENERAL LEGEND AND NOTES.

4'0' 16'8'

1. CONTRACTOR SHALL COORDINATE FINAL DATA DROP

LOCATION WITH ELECTRICAL SHOP DRAWINGS AND FINAL

ELECTRICAL/MECHANICAL EQUIPMENT PLACEMENT.

2. EXTEND A 1" CONDUIT TO NEAREST WALL CAVITY CLOSEST

TO CABLE TRAY. REFER TO DRAWING TN101 FOR SUGGESTED

CABLE TRAY ROUTING. TYPICAL OF ALL FLOOR BOX DATA

DROPS.

3. J-HOOKS FASTENED TO THE ACCESS FLOOR PEDESTALS TO

ROUTE CABLE UNDER RAISED FLOOR TO SERVER/BENCH

TEST 147. REFER TO SHEET TN201 FOR PATHWAY

PENETRATION THROUGH FIRE RATED WALL.

4. COORDINATE WITH MECHANICAL CONTRACTOR PRIOR TO

ROUGH-IN.

No. Date Issue / Revision

SERVER (BY 0THERS)

VIDEO WALL (BY 0THERS)

NETWORK (BY 0THERS)

BUSINESS

NETWORK

FROM

COMM-PB01

ELECTRONIC

SAFETY AND

SECURITY

SERVER/BENCH

TEST

ABOVE ACCESSIBLE CEILING

UNDER ACCESS

FLOOR

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FLORIDA 32309

TEL. (850) 224-4400

HALFF ASSOCIATES, INC.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FL 32309

GABRIEL BENAVIDES JR. P.E

PE NO. 97009

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

FINANCIAL PROJECT IDCOUNTYROAD NO.

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

TN201TELECOMMUNICATIONS ENLARGED

PLANS

ESCAMBIA 451524-1-38-01

NORTH W

STREET

2'0' 8'4'

TELECOMMUNICATIONS FLOOR PLAN ENLARGED SERVER/CHASE/BENCH TEST

KEY NOTES:

GENERAL NOTES:

A. REFER TO SHEET TN001 FOR TELECOMMUNICATIONS

GENERAL LEGEND AND NOTES.

1. TELEPHONE BOARD - COVER ENTIRE SURFACE OF WALL

WITH 3/4" PLYWOOD AND PAINT PLYWOOD WITH TWO COATS

OF FIRE RETARDANT PAINT. PAINT COLOR SHALL BE WHITE.

MOUNT PLYWOOD 8" AFF TO AVOID DAMAGING THE PLYWOOD

WITH THE GRADE 'A' SURFACE EXPOSED.

2. TELECOMMUNICATIONS GROUNDING BAR.

3. (2) 4" CONDUIT STUB-UPS FOR ISP SERVICES. CONTRACTOR

SHALL EXTEND CONDUIT 6-INCHES ABOVE FLOOR AND

PROVIDE END CAP. EACH RACEWAY SHALL BE PROVIDED

WITH TWO NYLON PULL STRINGS.

4. (2) 2" CONDUIT STUB-UPS SPARES. CONTRACTOR SHALL

EXTEND CONDUIT 6-INCHES ABOVE FLOOR AND PROVIDE

END CAP. EACH RACEWAY SHALL BE PROVIDED WITH TWO

NYLON PULL STRINGS.

5. FOR EVERY FIRE RATED PENETRATED WALL, PROVIDE ZERO

MAINTENANCE EZ-PATH SLEEVES TO RETAIN FIRE RATING

ON WALL.

6. PROVIDE WITH 12"X4" LADDER CABLE TRAY SYSTEM.

7. (2) 1-1/2" CONDUITS FROM SERVER/BENCH TEST 147 TO

ABOVE ROOF LINE CAPPED.

No. Date Issue / Revision

FILLER PANEL

FILLER PANEL

(BLUE) TELECOMMUNICATIONS PANEL 1/SWITCH 1

FILLER PANEL

(BLUE) TELECOMMUNICATIONS PANEL 2/SWITCH 2

FILLER PANEL

FILLER PANEL

FILLER PANEL

FILLER PANEL

FILLER PANEL

BUSINESS NETWORK CABINET 4

FRONT VIEW

BUSINESS NETWORK CABINET 4

REAR VIEW

FILLER PANEL

8" BLUE PATCH CABLES

COPPER PATCH

PANEL ETHERNET

SWITCH

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FLORIDA 32309

TEL. (850) 224-4400

HALFF ASSOCIATES, INC.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FL 32309

GABRIEL BENAVIDES JR. P.E

PE NO. 97009

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

FINANCIAL PROJECT IDCOUNTYROAD NO.

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

TN401

TELECOMMUNICATIONS SCHEDULES

ESCAMBIA 451524-1-38-01

NORTH W

STREET

35 DATA - DIGITAL RECEPTION 118

34 DATA - UPS 153

33 DATA - ELEC 150

32 DATA - MECH 149

31 DATA - OPEN OFFICE 120

30 DATA - OPEN OFFICE 120

29 DATA FLOOR BOX - NEXUS CONFERENCE 109

28 DATA FLOOR BOX - AUTO COLLABORATION 108

27 DATA FLOOR BOX - AUTO COLLABORATION 108

26 DATA - COLLAB OFFICE 123

25 DATA - COLLAB OFFICE 123

24 DATA - COLLAB OFFICE 122

23 DATA - COLLAB OFFICE 122

22 DATA - COLLAB OFFICE 121

21 DATA - COLLAB OFFICE 121

20 DATA - OFFICE 105

19 DATA - OFFICE 105

18 DATA - OFFICE 104

17 DATA - OFFICE 104

16 DATA - OFFICE 103

15 DATA - OFFICE 103

14 DATA - OFFICE 102

13 DATA - OFFICE 102

12 DATA - OFFICE 101

11 DATA - OFFICE 101

10 DATA - MEDIA ROOM 107

9 DATA - MEDIA ROOM 107

8 ACCESS POINT -8 - CONTROL ROOM 148

7 ACCESS POINT -7 - MEDIA COVERAGE ROOM 139

6 ACCESS POINT -6 - CONTROL ROOM 148

5 ACCESS POINT -5 - RTMC TRAINING/MEETING ROOM 132

4 ACCESS POINT -4 - RTMC TRAINING/MEETING ROOM 132

3 ACCESS POINT -3 - OPEN OFFICE 120

2 ACCESS POINT -2 - CORRIDOR 120.2

1 ACCESS POINT -1 - CORRIDOR 120.4

CKT Circuit Description

Location: SERVER/BENCH TEST 147

TELECOMMUNICATIONS PATCH PANEL 1

39 DATA - OFFICE 146

38 DATA - OFFICE 146

37 DATA - OFFICE 145

36 DATA - OFFICE 145

35 DATA - OFFICE 144

34 DATA - OFFICE 144

33 DATA - OFFICE 143

32 DATA - OFFICE 143

31 DATA - OFFICE 142

30 DATA - OFFICE 142

29 DATA - OFFICE 141

28 DATA - OFFICE 141

27 DATA - OFFICE 140

26 DATA - OFFICE 140

25 DATA FLOOR BOX - MEDIA COVERAGE ROOM 139

24 DATA FLOOR BOX - CONTROL ROOM 148

23 DATA FLOOR BOX - CONTROL ROOM 148

22 DATA FLOOR BOX - CONTROL ROOM 148

21 DATA FLOOR BOX - CONTROL ROOM 148

20 DATA FLOOR BOX - CONTROL ROOM 148

19 DATA FLOOR BOX - CONTROL ROOM 148

18 DATA FLOOR BOX - CONTROL ROOM 148

17 DATA FLOOR BOX - CONTROL ROOM 148

16 DATA FLOOR BOX - CONTROL ROOM 148

15 DATA FLOOR BOX - CONTROL ROOM 148

14 DATA FLOOR BOX - CONTROL ROOM 148

13 DATA FLOOR BOX - CONTROL ROOM 148

12 DATA FLOOR BOX - CONTROL ROOM 148

11 DATA FLOOR BOX - CONTROL ROOM 148

10 DATA FLOOR BOX - CONTROL ROOM 148

9 DATA FLOOR BOX - CONTROL ROOM 148

8 DATA FLOOR BOX - CONTROL ROOM 148

7 DATA FLOOR BOX - CONTROL ROOM 148

6 DATA FLOOR BOX - CONTROL ROOM 148

5 DATA FLOOR BOX - CONTROL ROOM 148

4 DATA FLOOR BOX - CONTROL ROOM 148

3 DATA FLOOR BOX - CONTROL ROOM 148

2 DATA FLOOR BOX - CONTROL ROOM 148

1 DATA FLOOR BOX - CONTROL ROOM 148

CKT Circuit Description

Location: SERVER/BENCH TEST 147

TELECOMMUNICATIONS PATCH PANEL 2

TYPICAL COPPER PATCH PANEL JACK TO ETHERNET SWITCH PORT DETAIL

No. Date Issue / Revision

DATA OUTLET

DATA OUTLET

DATA OUTLET

DATA OUTLET

DATA OUTLET

DATA OUTLET

CEILING

FLOOR

WALL

LONG RADIUSPVC SCHEDULE 40

STRAP

GRC

GRC

BUSHING

BUSHING

EMT

GRC UNION

INNER DUCT WITH

FIBRE, COPPER,

TELEPHONE AND

FIRE ALARM

TAPE WITH 2" 3M ELECTRICAL TAPE

STRAP

STRAP

GRCPVC

FINAL GRADE OR

TOP OF SLAB

GRC

COUPLING

GRC

NIPPLE

CONCRETE

ENVELOPE

30"

MINIMUM

CONDUIT

BASE

SPACER

PVC THREADED

ADAPTER

90° GRC

BEND

WRAP GRC CONDUIT WITH

CORROSION PROTECTION TAPE

(3M CO. CAT. #50 OR EQUAL)

GRC

COUPLING

1"C

CEILING MOUNT

WAP

SUPPORT BOX FROM

STRUCTURE

XXX-XXXX

PATCH PANEL PORT, NUMERIC (01-48)

PATCH PANEL IDENTIFIER, ALPHA (A,B,C...)

DATA (D), VOICE (V), OTHER (O)

#### - MDF/IDF ROOM NUMBER

CABLE JACKETCABLE LABEL

NOTES:

1. DETAIL SHOWN REPRESENTS A 4-PAIR HORIZONTAL LINK TERMINATING IN A

TELECOMMUNICATIONS SPACE ON A RACK MOUNT PATCH PANEL.

BUSBAR

CLEAR COVER

XXX-TMGB

IDENTIFIER DESIGNATING A TELECOMMUNICATIONS

MAIN GROUNDING BUSBAR (TMGB) OR

TELECOMMUNICATIONS GROUNDING BUSBAR (TGB)

TELECOMMUNICATIONS SPACE IDENTIFIER (TR)

BCT/XXX-XXX

MDF

ELECTRICAL ENTRANCE FACILITY OR STRUCTURAL

BCT/XXX-XXX

IT CLOSET

ELECTRICAL ENTRANCE FACILITY OR STRUCTURAL

DETAIL A

DETAIL B

COMMUNICATION SYSTEM EQUIPMENT

COMMUNICATION SYSTEM EQUIPMENT

TO EXTERNAL

GROUNDING

ELECTRODE SYSTEM

GROUND BUS CONDUCTORS

CONTRACTOR TO SIZE

GROUND CONDUCTOR AS

PER OWNER PROVIDED

LOADS

ELECTRICAL

PANEL

NEUTRAL

GROUND BOND

RGB

RGB

TMGB

EQUIPMENT GROUNDING

CONDUCTOR. CONTRACTOR TO

SIZE GROUND CONDUCTOR AS

PER OWNER PROVIDED LOADS

AREA 2

AREA 1

INTERNAL PERIMETER

GROUNDING CONDUCTORS

(WALL MOUNTED)

TMGB

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FLORIDA 32309

TEL. (850) 224-4400

HALFF ASSOCIATES, INC.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FL 32309

GABRIEL BENAVIDES JR. P.E

PE NO. 97009

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

FINANCIAL PROJECT IDCOUNTYROAD NO.

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

TN501

TELECOMMUNICATIONS DETAILS I

ESCAMBIA 451524-1-38-01

NORTH W

STREET

FOUR PORT OUTLET

TWO PORT OUTLET

WALL PENETRATION DETAIL

TYPICAL CONDUIT STUB-UP DETAIL

WIRELESS ACCESS POINT MOUNTING DETAIL

HORIZONTAL LINK CABLE LABEL DETAIL

GROUNDING BUSBAR LABEL DETAIL

BONDING CONDUCTOR LABEL DETAIL

TYPICAL SINGLE-POINT INTERNAL GROUNDING SYSTEM

No. Date Issue / Revision

LC

LC

2"

5/8" HARDWARE

MOUNTING BOLT

INSULATOR FABRICATED FROM FLAME

RESISTANT FIBERGLASS-REINFORCED

THERMOSET POLYSTER MOLDING

COMPOUND (TYPICAL OF BOTH SIDES)

LOCK WASHER

GROUND BAR (COPPER) 1/4" x 4" x LENGTH

COORDINATE EXACT LENGTH WITH NUMBER OF CABLES

CONNECTING - MIN. 13" IN RAISED FLOOR AREA & MIN.

21" IN MAIN ELECTRICAL ROOM

2"

EQUAL

5/8" HARDWARE

EQUAL

LOCK WASHER

2"

HOLES DRILLED W/NUMBER

& SIZE AS REQUIRED

SECURED TO WALL

LOCK WASHER

5/8"

HARDWARE

TO MAIN AC

ELECTRICAL SERVICE

BONDING CONDUCTOR FOR

TELECOMMUNICATIONS (BCT)

TO

STRUCTURAL STEEL

TO RACKS, CABLE

RUNWAY, CABLE

SHEATHS

TELECOMMUNICATIONS EQUIPMENT

BONDING CONDUCTOR (TEBC)

TELECOMMUNICATIONS MAIN

GROUNDING BUS BAR (TMGB)

BUSBAR LABEL

LANG BARRELL TWO-HOLE

CRIMP LUG (TYPICAL)

NOTES:

1.PROVIDE WITH SPECIFIED CLEAR COVER

TO ELECTRO STATIC

DISCHARGE MAT

LOCK WASHER

FIRE-RATED WALL

4" ZERO-

MAINTENANCE

MECHANICAL FIRE

STOP

STEEL SLEEVE

CABLES

SINGLE PATHWAY INSTALLATION:

• THROUGH 6" ROUND OPENING OR

4-1/8" BY 4-5/8" OPENING.

• PROVIDE WITH REQUIRED HARDWARE

FOR A COMPLETE INSTALLATION.

MULTIPLE OR GANGED INTALLATION:

• PROVIDE WITH BRACKET AND OTHER

REQUIRED HARDWARE FOR A

COMPLETE AND SECURE FIT

BETWEEN STUDS 24" APART.

5-GANG 4" ZERO-MAINTENENCE FIRE

STOP SYSTEM

TEBC(TELECOMMUNICATION

EQUIPMENT BONDING

CONDUCTOR)

IRREVERSIBLE

COMPRESSION CONNECTOR

TO

TMGB

RACK BONDING

CONDUCTOR - ALL

CONDUCTORS

ROUTED TO TMGB

INDIVIDUAL

EQUIPMENT BONDING

CONDUCTORS FROM

EACH PIECE OF

EQUIPMENT AND RACK

TO THE RACK

BONDING CONDUCTOR

RACK BONDING

CONDUCTOR

EXTENDED TO

BOTTOM OF RACK

TO ACCOMMODATE

FUTURE GROWTH

RACK ISOLATION

GROUND PLATES

IF APPLICABLE

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FLORIDA 32309

TEL. (850) 224-4400

HALFF ASSOCIATES, INC.

2255 KILLEARN CENTER BLVD.

SUITE 200

TALLAHASSEE, FL 32309

GABRIEL BENAVIDES JR. P.E

PE NO. 97009

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

FINANCIAL PROJECT IDCOUNTYROAD NO.

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

TN502

TELECOMMUNICATIONS DETAILS II

ESCAMBIA 451524-1-38-01

NORTH W

STREET

WALL MOUNTED TMGB DETAIL

ZERO-MAINTENANCE MECHANICAL TYPE FIRE STOP SYSTEM

RACK/ENCLOSURE BONDING DETAIL

No. Date Issue / Revision

Sheets
TN001 - TELECOMMUNICATIONS GENERAL NOTES AND LEGENDS
TN100 - TELECOMMUNICATIONS SITE PLAN
TN101 - TELECOMMUNICATIONS OVERALL FLOOR PLAN
TN102 - TELECOMMUNICATIONS FLOOR PLAN NORTH
TN103 - TELECOMMUNICATIONS FLOOR PLAN SOUTH
TN201 - TELECOMMUNICATIONS ENLARGED PLANS
TN401 - TELECOMMUNICATIONS SCHEDULES
TN501 - TELECOMMUNICATIONS DETAILS I
TN502 - TELECOMMUNICATIONS DETAILS II