QUESTIONS AND ANSWERS FOR GENERATOR HVAC.pdf

PDF 115 KB Posted

Attached to
PROCURE & INSTALL EMERGENCY GENERATOR AND A/C UNITS
Solicitation number
HSFE02-12-R-0004
Issued by

About this file

QUESTIONS AND ANSWERS

View the file

Other files

File Type Posted
NOTICE OF AWARD.pdf PDF
QUESTIONS AND ANSWERS FOR GENERATOR HVAC- Updated 06-14-2012.pdf PDF
HVAC 4.jpg JPG image
QUESTIONS AND ANSWERS FOR GENERATOR HVAC- Updated 05-31-2012.pdf PDF
HVAC PIC 1.jpg JPG image
HVAC PIC 2.jpg JPG image
HVAC 3.jpg JPG image
FRONT 3.JPG JPG image
FRONT 1.JPG JPG image
FRONT 2.JPG JPG image
REAR 7.JPG JPG image
REAR 2.JPG JPG image
REAR 3.JPG JPG image
REAR 1.JPG JPG image
REAR 5.JPG JPG image
REAR 6.JPG JPG image
REAR 4.JPG JPG image
HSFE02-12-R-0004 A00003 —
Sign-In Sheet.pdf PDF
QUESTIONS AND ANSWERS FOR GENERATOR HVAC- Updated 05-14-2012.pdf PDF
HSFE02-12-R-0004 A00002 —
A1a Existing Building.pdf PDF
QUESTIONS AND ANSWERS FOR GENERATOR HVAC- Updated 05-10-2012.pdf PDF
2094036-37.TIF TIF image
3-5813F.TIF TIF image
3-5815F.TIF TIF image
2094035-36.TIF TIF image
2094033-34.TIF TIF image
2135294-5-8.TIF TIF image
2135295-6-8.TIF TIF image
3-5814F.TIF TIF image
2146816-1-8.TIF TIF image
2094034-35.TIF TIF image
2094032-33.TIF TIF image
RAPIDGATE.pdf PDF
HSFE02-12-R-0004 A00001 —
Attachment A- SOW for Generator. Earle- 4-2-12.pdf PDF
HSFE02-12-R-0004.pdf PDF
Attachment C- General Decision Number NJ120037.pdf PDF
Attachment B- SOW for HVAC Earle 4-2-12.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

QUESTIONS AND ANSWERS FOR GENERATOR & HVAC PROJECT

1) Size of the gas pipe line in bldg C-54?

2” Feed at building, according the NJ Gas Company representative the pipe is sufficient base on a 250-400 KW Generator. But final determination will be made once we supply them with

Generator Size.

2) Where is the main gas valve located?

Main Gas Valve is located next to Boiler Room, on side of building.

3) Who is running the feed?

GC is responsible to run feed to Generator from Supply and can tap into line.

4) How do you obtain an Air Permit?

PWD Environmental Officer can help us as well as the GC. We are responsible to submit application and pay for the permit.

5) What permits are actually necessary for the generator?

Just an Air Permit.

6) Is this going to be a design- build project?

This is going to be somewhat of a design-build project. You will design the layout, at your own cost

(for your technical proposal), and FEMA is going to be evaluating your design.

7) What kind of controls are in there now?

VAV

8) Do you have As-builts of HVAC system?

Provided by PWD electronically

9) Are all the ducts, pipe being changed out?

The GC is responsible to make those determinations.

10) The old HVAC unit- what is happening to that?

The NAVY wants the old HVAC units. They will provide a dumpster for this. Piping’s will be left up to the GC.

11) Do you have floor plans (heights, ceiling, actual scaled drawings)?

PWD Supplied Drawings

12) Any better drawings?

No there are no better drawings

13) Can you provide the number of VAV’s and their locations?

PWD Supplied Drawings shows locations.

14) Any mechanical designs?

PWD Supplied Drawings

15) Where will the staging area be?

Outside of the warehouse (the rear parking lot).

16) Badges, who pays for them? Cost of the background investigation?

Contractor bears all of these costs. All information can be found at www.rapidgate.com (this will be uploaded in FBO).

17) What are the work hours?

7 am to 4:30 pm.

18) Is the gov’t providing the gas meter or the gas meter monitor?

The NJ Natural Gas Company will install a new Gas Meter and Monitor at no cost to

Government.

http://www.rapidgate.com/