This is a Submittal Log for the National Guard Readiness Center Addition project located in Kalaeloa, Oahu, Hawaii. The comprehensive document outlines detailed submittal requirements across 33 divisions of construction, including General Requirements, Concrete, Masonry, Metals, Wood, Thermal and Moisture Protection, Openings, Finishes, Specialties, Equipment, Furnishings, Fire Suppression, Plumbing, HVAC, Electrical, Communications, Electronic Safety, and Utilities. The project has a Federal Project Number of 150084 and is being managed by AECOM, with the general contractor to be determined (TBD).
The Submittal Log provides an extensive matrix for each division, specifying required product data, shop drawings, samples, sustainable design submittals, qualification statements, warranties, and other documentation that must be submitted by subcontractors. Each section includes specific specification section numbers, detailed submittal descriptions, and columns for tracking submission dates, receipt dates, and return dates. The log serves as a comprehensive tracking tool to ensure all necessary documentation is properly reviewed and approved throughout the construction process, covering everything from material certifications and test reports to operation and maintenance manuals and record drawings.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation Amendment - W912J625QA0110001.pdf | ||
| HI ARNG READINESS CENTER ADDITION - SPECIFICATIONS.pdf | ||
| Solicitation Amendment W912J625QA0110001 SF 30.pdf | ||
| PWS Readiness Center Addition Commissioning Services_.pdf | ||
| WD 2015-5689 Revision 26 (07-08-2025).pdf | ||
| Detailed offer spreadsheet.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FORWARD TO FOR REVIEW
AECOM HAWAII
1001 BISHOP STREET SUITE 1600
HONOLULU, HAWAII 96813
DATE SENT TO
AECOM HAWAII
DATE RECEIVED
FROM
AECOM HAWAII
A P
P R
O V
E D
A S
S U
B M
IT
T
E D
(A
A P
P R
O V
E D
E X
C E
P T
A S
N O
T
(B
A P
P R
O V
E D
E X
C E
P T
A S
N O
T E
R
S U
B M
IS
S
IO
N
R E
Q U
IR
E
D
C
D
IS
A P
P R
O V
(E
IN
F
O R
M A
T
IO
N O
N L Y
S U
B M
IT
T
A L
(F
013100 PROJECT MANAGEMENT AND COORDINATION
Product
013200 CONSTRUCTION PROGRESS DOCUMENTATION
Qualification Statements
013300 SUBMITTAL PROCEDURES
Product Data
Shop Drawings
Samples
Samples for Initial Selection
Samples for Verification
Product
Coordination Drawings
Qualification Statements
Welding Certificates
Material Test Reports
Product Test Reports
Research/Evaluation Reports
Preconstruction Test Reports
Warranty
Compatibility Test Reports
Design Data
Field Test Reports
Installer Certificates
Manufacturer Certificates
Manufacturer's Field Reports
Wiring diagrams
014000 QUALITY REQUIREMENTS
Samples
Product
Qualification Statements
010000 GENERAL REQUIREMENTS
Product Data
Product
016000 PRODUCT REQUIREMENTS
Product Data
Samples
Product
Material Test Reports
Research/Evaluation Reports
017300 EXECUTION
Qualification Statements
017310 CUTTING AND PATCHING
Product
017419 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
Qualification Statements
017700 CLOSEOUT PROCEDURES
Product Data
Product
017839 PROJECT RECORD DOCUMENTS
Product Data
Product
017900 DEMONSTRATION AND TRAINING
Product
Qualification Statements
150084
REVIEW
AECOM
TITLE / DESCRIPTION SUBC-ONTRACTOR NAME
SUBMITTAL LOG
Project: NATIONAL GUARD READINESS CENTER ADDITION Kalaeloa Oahu Hawaii Federal Project No.:
C O
P
IE
S R
E C
E
IV
E D
D A
T E
S E
N T
T O
C O
N T
R A
C T
IN
G
O F
F
IC
E R
A T
U S
P F
O H
A W
A
II
D A
T E
R E
T U
R N
E D
T O
C O
N T
R A
C T
U
T
II
Q
G E
N E
R A
L C
O N
T R
A C
T O
S
C
General Contractor: CONTRACTOR TBD Architect and Engineers:
DIVISION 01 - GENERAL REQUIREMENTS
S U
B M
IT
T
A L N
U M
B E
R
DATE RECEIVED
AT HAWAII ARMY
NATIONAL GUARD
(HIARNG) D
A
T E
R E
Q U
IR
E
D T
O R
E T
U R
N T
N E
R A
L C
O N
T R
A C
T O
R
N A
M E
N E
R A
L C
O N
T R
A C
T O
R
SPECIFICATION SECTION NUNMBER
ACTION
1001 BISHOP STREET SUITE 1600
HONOLULU, HAWAII 96813
DATE SENT TO
AECOM HAWAII
DATE RECEIVED
FROM
AECOM HAWAII
A P
P R
O V
E D
A S
S U
B M
IT
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T E
S U
B M
IS
S
IO
N
R E
Q U
IR
E
D
C
D
IS
A P
P R
O V
IN
F
O R
M A
T
IO
N O
N L Y
S U
B M
IT
T
024119 SELECTIVE DEMOLITION
Qualification Statements
Warranty
REVIEW
DIVISION 02 - EXISTING CONDITIONS
SUBC-ONTRACTOR NAME
Project:
TITLE / DESCRIPTION
DATE RECEIVED
AT HAWAII ARMY
NATIONAL GUARD
(HIARNG)
General Contractor:
SPECIFICATION SECTION NUNMBER
CONTRACTOR TBD
ACTION
S U
B M
IT
T
A L N
U M
B E
R
SUBMITTAL LOG
AECOM
150084
D A
T E
R E
T U
R N
E D
T O
C O
N T
R A
C T
U
T
II
Q
G E
N E
R A
L C
O N
T R
A C
T O
C
D A
T E
R E
Q U
IR
E
D T
O R
E T
U R
N
N E
R A
L C
O N
T R
A C
T O
R
N A
M E
N E
R A
L C
O N
T R
A C
T O
R
NATIONAL GUARD READINESS CENTER ADDITION Kalaeloa Oahu Hawaii
Architect and Engineers:
Federal Project No.:
D A
T E
S E
N T
T O
C O
N T
R A
C T
F
IC
E R
A T
U S
P F
O H
A W
A
II
C O
P
IE
S R
E C
E
IV
1001 BISHOP STREET SUITE 1600
HONOLULU, HAWAII 96813
DATE SENT TO
AECOM HAWAII
DATE RECEIVED
FROM
AECOM HAWAII
A P
P R
O V
E D
A S
S U
B M
IT
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T E
S U
B M
IS
S
IO
N
R E
Q U
IR
E
D
C
D
IS
A P
P R
O V
IN
F
O R
M A
T
IO
N O
N L Y
S U
B M
IT
T
032000 Product Data: For the following:
1. Each type of steel reinforcement.
2. Bar supports.
3. Mechanical splice couplers.
032000 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
032000 Shop Drawings: Comply with ACI SP-066
1. Include placing drawings that detail fabrication, bending, and placement.
2. Include bar sizes, lengths, materials, grades, bar schedules, stirrup spacing, bent bar diagrams, bar arrangement, location of splices, lengths of lap splices, details of mechanical splice couplers, details of welding splices, tie spacing, hoop spacing, and supports for concrete reinforcement.
032000 Construction Joint Layout: Indicate proposed construction joints required to build the structure.
1. Location of construction joints is subject to approval of Architect.
032000 Welding certificates.
1. Reinforcement to Be Welded: Welding procedure specification in accordance with AWS D1.4/D1.4M.
032000 Material Certificates: For each of the following, signed by manufacturers:
1. Epoxy-Coated Reinforcement: CRSI's "Epoxy Coating Plant Certification."
032000 Material Test Reports: For the following, from a qualified testing agency:
1. Steel Reinforcement:
a. For reinforcement to be welded, mill test analysis for chemical composition and carbon equivalent of the steel in accordance with ASTM A706/A706M.
2. Mechanical splice couplers.
032000 Field quality-control reports.
032000 Minutes of preinstallation conference.
033000 Product Data: For each of the following.
1. Portland cement.
2. Fly ash.
3. Slag cement.
4. Blended hydraulic cement.
5. Aggregates.
6. Admixtures
a. Include limitations of use, including restrictions on cementitious materials, supplementary cementitious materials, air entrainment, aggregates, temperature at time of concrete placement, relative humidity at time of concrete placement, curing conditions, and use of other admixtures.
7. Vapor retarders.
8. Liquid floor treatments.
9. Curing
10. Joint fillers.
033000 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
033000 Design Mixtures: For each concrete mixture, include the following:
1. Mixture identification.
2. Minimum 28-day compressive strength.
3. Durability exposure class.
4. Maximum w/cm.
5. Calculated equilibrium unit weight, for lightweight concrete.
6. Slump limit.
7. Air content.
8. Nominal maximum aggregate size.
9. Indicate amounts of mixing water to be withheld for later addition at Project site if permitted.
10. Intended placement method.
11. Submit alternate design mixtures when characteristics of materials, Project conditions, weather, test results, or other circumstances warrant adjustments
033000 Shop Drawings:
1. Construction Joint Layout: Indicate proposed construction joints required to construct the structure.
a. Location of construction joints is subject to approval of the Architect.
033000 Concrete Schedule: For each location of each Class of concrete indicated in "Concrete Mixtures" Article, including the following:
1. Concrete Class designation.
2. Location within Project.
3. Exposure Class designation.
4. Formed Surface Finish designation and final finish.
5. Final finish for floors.
6. Curing process.
7. Floor treatment if any.
033000 Material Certificates: For each of the following, signed by manufacturers:
1. Cementitious materials.
2. Admixtures.
3. Curing compounds.
4. Vapor retarders.
5. Joint-filler strips.
SUBMITTAL LOG
Project: NATIONAL GUARD READINESS CENTER ADDITION Kalaeloa Oahu Hawaii Federal Project No.:
D A
T E
R E
Q U
IR
E
D T
O R
E T
U R
N
N E
R A
L C
O N
T R
A C
T O
R
N A
M E
N E
R A
L C
O N
T R
A C
T O
R
DIVISION 03 - CONCRETE
C O
P
IE
S R
E C
E
IV
E D
REVIEW ACTION
D A
T E
S E
N T
T O
C O
N T
R A
C T
F
IC
E R
A T
U S
P F
O H
A W
A
II
DATE RECEIVED
AT HAWAII ARMY
NATIONAL GUARD
(HIARNG) TITLE / DESCRIPTION SUBC-ONTRACTOR NAMES
U
B M
IT
T
A L N
U M
B E
R
D A
T E
R E
T U
R N
E D
T O
C O
N T
R A
C T
U
T
II
Q
G E
N E
R A
L C
O N
T R
A C
T O
C
AECOM
SPECIFICATION SECTION NUNMBER
150084
General Contractor: CONTRACTOR TBD Architect and Engineers:
033000 Material Test Reports: For the following, from a qualified testing agency:
1. Portland cement.
2. Fly ash.
3. Slag cement.
4. Blended hydraulic cement.
5. Aggregates.
6. Admixtures:
033000 Research Reports: For concrete admixtures in accordance with ICC's Acceptance Criteria AC198.
033000 Preconstruction Test Reports: For each mix design.
033000 Field quality-control reports.
033000 Minutes of preinstallation conference.
034100 Product Data: For each type of product.
034100 Design Mixtures: For each precast concrete mixture. Include compressive strength and water-absorption tests.
034100 Shop Drawings:
1. Include member locations, plans, elevations, dimensions, shapes and sections, openings, support conditions, and types of reinforcement, including special reinforcement.
2. Detail fabrication and installation of precast structural concrete units, including connections at member ends and to adjoining construction.
3. Indicate joints, reveals, and extent and location of each surface finish.
4. Indicate separate face and backup mixture locations and thicknesses.
5. Indicate welded connections by AWS standard symbols. Show size, length, and type of each weld.
6. Detail loose and cast-in hardware, lifting and erection inserts, connections, and joints.
7. Indicate locations, tolerances, and details of anchorage devices to be embedded in or attached to structure or other construction.
8. Include and locate openings larger than by 10 inches.
9. Indicate location of each precast structural concrete unit by same identification mark placed on panel.
10. Indicate relationship of precast structural concrete units to adjacent materials.
11. Indicate estimated camber for precast floor slabs with concrete toppings.
(continued below)
034100 (continued from above)
12. Indicate shim sizes and grouting sequence.
13. Design Modifications: If design modifications are proposed to meet performance requirements and field conditions, submit design calculations and Shop
Drawings. Do not adversely affect the appearance, durability, or strength of units when modifying details or materials and maintain the general design concept.
14. Comprehensive engineering analysis signed and sealed by the qualified professional engineer responsible for its preparation. Show governing panel types, connections, and types of reinforcement, including special reinforcement. Indicate location, type, magnitude, and direction of loads imposed on the foundation from precast concrete.
034100 Delegated Design Submittal: For precast structural concrete indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
034100 Qualification Data: For Installer, Fabricator, and Testing Agency.
034100 Welding certificates.
034100 Material certificates: For the following, from manufacturer;
1. Cementitious materials.
2. Reinforcing materials and prestressing tendons.
3. Admixtures.
4. Bearing pads.
5. Structural-steel shapes and hollow structural sections.
034100 Material Test Reports: For aggregates.
034100 Source quality-control reports.
034100 Field quality-control and special inspection reports.
035300 Product Data: For each type of product.
039950 Product Data: For each of the following:
a. Submit manufacturer's product data and installation instructions.
039950 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
039950 Mock-Up: Prepare a test area minimum 2 by 2 feet in size to verify suitability of the stain, sealer and final appearance.
039950 Samples: For manufacturer's standard colors for stain.
1001 BISHOP STREET SUITE 1600
HONOLULU, HAWAII 96813
DATE SENT TO
AECOM HAWAII
DATE RECEIVED
FROM
AECOM HAWAII
A P
P R
O V
E D
A S
S U
B M
IT
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T E
S U
B M
IS
S
IO
N
R E
Q U
IR
E
D
C
D
IS
A P
P R
O V
IN
F
O R
M A
T
IO
N O
N L Y
S U
B M
IT
T
042200 Product Data: For each type of product.
042200 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
042200 Shop Drawings: For reinforcing steel. Detail bending, lap lengths, and placement of unit masonry reinforcing bars. Comply with ACI 315.
042200 Samples: For each type and color of the following:
1. Exposed CMUs.
2. Pre-faced CMUs.
3. Pigmented and colored-aggregate mortar.
042200 Material Certificates: For each type and size of product. For masonry units, include material test reports substantiating compliance with requirements.
042200 Mix Designs: For each type of mortar and grout. Include description of type and proportions of ingredients.
1. Include test reports for mortar mixes required to comply with property specification. Test in accordance with ASTM C109/C109M for compressive strength, ASTM C1506 for water retention, and ASTM C91/C91M for air content.
2. Include test reports, in accordance with ASTM C1019, for grout mixes required to comply with compressive strength requirement.
SUBMITTAL LOG
Project: NATIONAL GUARD READINESS CENTER ADDITION Kalaeloa Oahu Hawaii Federal Project No.:
D A
T E
R E
Q U
IR
E
D T
O R
E T
U R
N
N E
R A
L C
O N
T R
A C
T O
R
N A
M E
N E
R A
L C
O N
T R
A C
T O
R
DIVISION 04 - MASONRY
C O
P
IE
S R
E C
E
IV
E D
REVIEW ACTION
D A
T E
S E
N T
T O
C O
N T
R A
C T
F
IC
E R
A T
U S
P F
O H
A W
A
II
DATE RECEIVED
AT HAWAII ARMY
NATIONAL GUARD
(HIARNG) TITLE / DESCRIPTION SUBC-ONTRACTOR NAMES
U
B M
IT
T
A L N
U M
B E
R
D A
T E
R E
T U
R N
E D
T O
C O
N T
R A
C T
U
T
II
Q
G E
N E
R A
L C
O N
T R
A C
T O
C
AECOM
SPECIFICATION SECTION NUNMBER
150084
General Contractor: CONTRACTOR TBD Architect and Engineers:
1001 BISHOP STREET SUITE 1600
HONOLULU, HAWAII 96813
DATE SENT TO
AECOM HAWAII
DATE RECEIVED
FROM
AECOM HAWAII
A P
P R
O V
E D
A S
S U
B M
IT
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T E
S U
B M
IS
S
IO
N
R E
Q U
IR
E
D
C
D
IS
A P
P R
O V
IN
F
O R
M A
T
IO
N O
N L Y
S U
B M
IT
T
051200 Product Data:
1. Structural-steel materials.
2. High-strength, bolt-nut-washer assemblies.
3. Shear stud connectors.
4. Anchor rods.
5. Threaded rods.
6. Forged-steel hardware.
7. Shop primer.
8. Galvanized-steel primer.
9. Etching cleaner.
10. Galvanized repair paint.
11. Shrinkage-resistant grout.
051200 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
` 051200 Shop Drawings: Show fabrication of structural-steel components.
1. Include details of cuts, connections, splices, camber, holes, and other pertinent data.
2. Include embedment drawings.
3. Indicate welds by standard AWS symbols, distinguishing between shop and field welds, and show size, length, and type of each weld. Show backing bars that are to be removed and supplemental fillet welds where backing bars are to remain.
4. Indicate type, size, and length of bolts, distinguishing between shop and field bolts. Identify pretensioned and slip-critical high-strength bolted connections.
5. Identify members and connections of the seismic-load-resisting system.
6. Identify demand critical welds.
7. For structural-steel connections indicated to comply with design loads, include structural analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
051200 Welding Procedure Specifications (WPSs) and Procedure Qualification Records (PQRs): Provide according to AWS D1.1, "Structural Welding Code - Steel," for each welded joint qualified by testing, including the following:
1. Power source (constant current or constant voltage).
2. Electrode manufacturer and trade name, for demand critical welds.
051200 Qualification Data: For qualified Installer, fabricator, professional engineer, and testing agency.
051200 Welding certificates.
051200 Paint Compatibility Certificates: From manufacturers of topcoats applied over shop primers, certifying that shop primers are compatible with topcoats.
051200 Mill test reports for structural-steel materials, including chemical and physical properties
051200 Product Test Reports: For the following:
1. Bolts, nuts, and washers including mechanical properties and chemical analysis.
2. Direct-tension indicators.
3. Tension-control, high-strength bolt-nut-washer assemblies.
4. Shear stud connectors.
5. Shop primers.
6. Non-shrink grout.
051200 Source quality-control reports.
051200 Field quality-control reports.
052100 Product Data: For each type of joist, accessory, and product.
052100 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
052100 Shop Drawings:
1. Include layout, designation, number, type, location, and spacing of joists.
2. Include joining and anchorage details; bracing, bridging, and joist accessories; splice and connection locations and details; and attachments to other construction.
052100 Welding certificates.
052100 Manufacturer certificates.
052100 Paint compatibility certificates.
052100 Mill Certificates: For each type of bolt.
052100 Field quality-control reports.
053100 Product Data:
1. Roof deck.
2. Composite floor deck.
053100 Shop Drawings:
1. Include layout and types of deck panels, anchorage details, reinforcing channels, pans, cut deck openings, special jointing, accessories, and attachments to other construction.
053100 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
053100 Certificates:
1. Welding certificates.
2. Product Certificates: For each type of steel deck.
053100 Test and Evaluation Reports:
1.
2. Research Reports: For steel deck, from ICC-ES showing compliance with the building code.
053100 Field Quality-Control Submittals:
1. Field quality-control reports.
150084
REVIEW
AECOM
TITLE / DESCRIPTION SUBC-ONTRACTOR NAME
SUBMITTAL LOG
Project: NATIONAL GUARD READINESS CENTER ADDITION Kalaeloa Oahu Hawaii Federal Project No.:
C O
P
IE
S R
E C
E
IV
E D
D A
T E
S E
N T
T O
C O
N T
R A
C T
F
IC
E R
A T
U S
P F
O H
A W
A
II
D A
T E
R E
T U
R N
E D
T O
C O
N T
R A
C T
U
T
II
Q
G E
N E
R A
L C
O N
T R
A C
T O
C
General Contractor: CONTRACTOR TBD Architect and Engineers:
DIVISION 05 - METALS
S U
B M
IT
T
A L N
U M
B E
R
DATE RECEIVED
AT HAWAII ARMY
NATIONAL GUARD
(HIARNG) D
A
T E
R E
Q U
IR
E
D T
O R
E T
U R
N
N E
R A
L C
O N
T R
A C
T O
R
N A
M E
N E
R A
L C
O N
T R
A C
T O
R
053100 Qualification Statements: For welding personnel and testing agency.
054000 Product Data: For each type of cold-formed steel framing product and accessory.
1. Load-bearing wall framing
2. Ceiling joist framing.
3. Soffit framing.
054000 Shop Drawings:
1. Include layout, spacings, sizes, thicknesses, and types of cold-formed steel framing; fabrication; and fastening and anchorage details, including mechanical fasteners.
2. Indicate reinforcing channels, opening framing, supplemental framing, strapping, bracing, bridging, splices, accessories, connection details, and attachment to adjoining work.
054000 Delegated Design Submittal: For cold-formed steel framing.
054000 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
054000 Qualification Data: For testing agency.
054000 Welding certificates
054000 Product Certificates: For each type of code-compliance certification for studs and tracks
054000 Product Test Reports: For each listed product, for tests performed by manufacturer and witnessed by a qualified testing agency or a qualified testing agency.
1. Steel sheet.
2. Expansion anchors.
3. Power-actuated anchors.
4. Mechanical fasteners.
5. Vertical deflection clips.
6. Horizontal drift deflection clips
7. Miscellaneous structural clips and accessories.
054000 Research Reports:
1. For nonstandard cold-formed steel framing from ICC-ES or other qualified testing agency acceptable to authorities having jurisdiction.
2. For sill sealer gasket/termite barrier, showing compliance with ICC-ES AC380.
054400 Product Data: For each type of product Sustainable Design Submittals:
054400 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
054400 Shop Drawings:
1. Include layout, spacings, sizes, thicknesses, and types of cold-formed steel trusses; fabrication; and fastening and anchorage details, including mechanical fasteners.
2. Indicate reinforcing channels, opening framing, supplemental framing, strapping, bracing, bridging, splices, accessories, connection details, and attachment to adjoining work.
054400 Delegated Design Submittal: For cold-formed steel trusses.
054400 Welding certificates.
054400 Product test reports. For each listed product, for tests performed by ICC-ES or other qualified testing agency or by manufacturer and witnessed by a qualified testing agency.
1. Steel sheet.
2. Expansion anchors.
3. Power-actuated anchors.
4. Mechanical fasteners.
5. Miscellaneous structural clips and accessories.
054400 Research Reports: For post-installed anchors and power-actuated fasteners, or for non-standard cold formed steel framing, from ICC-ES or other qualified testing agency acceptable to authorities having jurisdiction
054400 Field quality-control reports.
055000 Product Data - Paint Products
055000 Product Data - Grout
055000 Shop Drawings - Show fabrication and installation details for metal fabrications. Include plans, elevations, sections, and details of metal fabrications and their connections. Show anchorage and accessory items.
055000 Samples for Verification - For each type and finish of cast and extruded nosing.
055000 Delegated-Design Submittal - For installed products indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
055000 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
055000 Product data - Manufactured Metal Ladders
055000 Product data - Metal bollards
055000 Product Data - Abrasive Metal Nosings
055000 Product Data - Elevator Pit Sump Covers
055000 Shop Drawings - Show fabrication and installation details. Include plans, elevations, sections, and details of metal fabrications and their connections. Show anchorage and accessory items. Provide Shop Drawings for the following:
1. Elevator machine beams, hoist beams, and divider beams.
2. Steel shapes for supporting elevator door sills.
3. Metal ladders.
4. Elevator pit sump covers.
5. Metal bollards.
6. Abrasive Metal Nosings.
055000 Certificates -
1. Qualification Data: For qualified professional engineer.
2. Welding certificates.
3. Paint Compatibility Certificates: From manufacturers of topcoats applied over shop primers, certifying that shop primers are compatible with topcoats.
055000 Research Reports - For Pot-installed anchors.
055000 Delegted Design Engineer Qualificatuions
055113 Product Data -
1. Abrasive Nosings
2. Shop Primer Products
3. Epoxy-Resin-Filled Stair Treads
4. Grout
055113 Shop Drawings -
1. Include plans, elevations, sections, details, and attachments to other work.
2. Indicate sizes of metal sections, thickness of metals, profiles, holes, and field joints.
3. Include plan at each level.
4. Indicate profile and dimensions of epoxy-resin-filled treads.
055113 Samples for Verification: For each type and finish of nosing.
055113 Delegated Design Submittal: For stairs, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
055113 Sustainable Design Submittals -
1. See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
001 055213 Product Data -
1. Manufacturer's product lines of mechanically connected railings.
2. Railing brackets.
3. Grout, anchoring cement, and paint products.
4. Post-installed anchors
5. Shop primer.
6. Metal finishes.
7. Paint products.
055213 Shop Drawings - Include plans, elevations, sections, details, and attachments to other work
055213 Samples for Initial Selection: For products involving selection of color, texture, or design
055213 Samples for Verification - For each type of exposed finish required.
1. Sections of each distinctly different linear railing member, including handrails, top rails, posts, and balusters, including finish.
2. Fittings and brackets.
3. Assembled Sample of railing system, made from full-size components, including top rail, post, handrail, and infill. Sample need not be full height.
055213 Delegated Design Submittal - For railings, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
055213 Sustainable Design Submittals -
1. See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
1001 BISHOP STREET SUITE 1600
HONOLULU, HAWAII 96813
DATE SENT TO
AECOM HAWAII
DATE RECEIVED
FROM
AECOM HAWAII
A P
P R
O V
E D
A S
S U
B M
IT
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T E
S U
B M
IS
S
IO
N
R E
Q U
IR
E
D
C
D
IS
A P
P R
O V
IN
F
O R
M A
T
IO
N O
N L Y
S U
B M
IT
T
061000 Product Data - For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details. -
1. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Indicate type of preservative used and net amount of preservative retained.
2. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Include physical properties of treated materials based on testing by a qualified independent testing agency.
3. For fire-retardant treatments, include physical properties of treated lumber both before and after exposure to elevated temperatures, based on testing by a qualified independent testing agency in accordance with ASTM D5664.
4. For products receiving a waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site.
061000 Sustainable Design Submittals -
1. See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
061000 Evaluation Reports - For the Following, from ICC-ES -
1. Rreservative-treated wood.
2. Fire-retardant-treated wood..
061600 Product Data: 1. Wall sheathing.
061600 Product Data Submittals - For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details.
1. For products receiving waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site.
061600 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
061600 Product Data: 1. Wall sheathing.
061600 Product Data Submittals - For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details.
1. For products receiving waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to
Project site.
061600 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
064116 Product Data: For each type of product. 1. Include data for fire-retardant treatment from chemical-treatment manufacturer and certification by treating plant that treated materials comply with requirements.
064116 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
064116 Shop Drawings -
1. Include plans, elevations, sections, and attachment details.
2. Show large-scale details.
3. Show locations and sizes of furring, blocking, and hanging strips, including concealed blocking and reinforcement specified in other Sections.
4. Show locations and sizes of cutouts and holes for items installed in plastic-laminate architectural cabinets.
5. Apply AWI Quality Certification Program label to Shop Drawings.
064116 Samples: For each exposed product and for each color and texture specified, in manufacturer's or manufacturer's standard size.
064116 Samples for Initial Selection: For each type of exposed finish.
064116 Samples for Verification: For the following:
1. Plastic Laminates: 8 by 10 inches, for each type, color, pattern, and surface finish required.
a. Provide one sample applied to core material with specified edge material applied to one edge.
2. Thermally Fused Laminate (TFL) Panels: 8 by 10 inches, for each color, pattern, and surface finish.
a. Provide edge banding on one edge.
3. Corner Pieces:
a. Cabinet-front frame joints between stiles and rails and at exposed end pieces, 18 inches high by 18 inches wide by 6 inches deep.
b. Miter joints for standing trim.
4. Exposed Cabinet Hardware and Accessories: One full-size unit for each type and finish.
066400 Product Data: For each type of product.
066400 Samples: For plastic paneling and trim accessories, in manufacturer's standard sizes.
066400 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
150084
REVIEW
AECOM
TITLE / DESCRIPTION SUBC-ONTRACTOR NAME
SUBMITTAL LOG
Project: NATIONAL GUARD READINESS CENTER ADDITION Kalaeloa Oahu Hawaii Federal Project No.:
C O
P
IE
S R
E C
E
IV
E D
D A
T E
S E
N T
T O
C O
N T
R A
C T
F
IC
E R
A T
U S
P F
O H
A W
A
II
D A
T E
R E
T U
R N
E D
T O
C O
N T
R A
C T
U
T
II
Q
G E
N E
R A
L C
O N
T R
A C
T O
C
General Contractor: CONTRACTOR TBD Architect and Engineers:
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
S U
B M
IT
T
A L N
U M
B E
R
DATE RECEIVED
AT HAWAII ARMY
NATIONAL GUARD
(HIARNG) D
A
T E
R E
Q U
IR
E
D T
O R
E T
U R
N
N E
R A
L C
O N
T R
A C
T O
R
N A
M E
N E
R A
L C
O N
T R
A C
T O
R
1001 BISHOP STREET SUITE 1600
HONOLULU, HAWAII 96813
DATE SENT TO
AECOM HAWAII
DATE RECEIVED
FROM
AECOM HAWAII
A P
P R
O V
E D
A S
S U
B M
IT
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T
A P
P R
O V
E D
E X
C E
P T
A S
N O
T E
S U
B M
IS
S
IO
N
R E
Q U
IR
E
D
C
D
IS
A P
P R
O V
IN
F
O R
M A
T
IO
N O
N L Y
S U
B M
IT
T
071700 Product Data: For each type of product. - 1. Include construction details, material descriptions, and installation instructions.
071700 Shop Drawings: Include installation details for waterproofing, penetrations, and interface with other work
071700 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
071700 Samples: For each of the following products, in sizes indicated. - 1.Waterproofing: 6 inches (150 mm) square.
2.Protection Course: 6 inches (150 mm) square.
072100 Product Data for each item indicated.
072100 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
072423 Product Data: For each EIFS component, trim, and accessory.
072423 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
072423 Samples: For each exposed product and for each color and texture specified, 8 inches square in size.
072423 Samples for Initial Selection: For each type of finish-coat color and texture indicated. 1. Include similar
Samples of exposed accessories involving color selection.
072423 Samples for Verification: 24-inch square panels for each type of finish-coat color and texture indicated, prepared using same tools and techniques intended for actual work, including .
1. Include a typical control joint filled with sealant of color selected, as specified in Section 079200 "Joint Sealants."
072423 Qualification Data: For Installer.
072423 Manufacturer Certificates: Signed by DEFS manufacturer, certifying the following:
1. DEFS substrate is acceptable to DEFS manufacturer.
2. Accessory products installed with EIFS, including joint sealants, flashing, whether or not furnished by DEFS manufacturer and whether or not specified in this Section, are acceptable to DEFS manufacturer.
072423 Product Certificates: For cementitious materials and aggregates, from manufacturer.
072423 Product Test Reports: For each DEFS assembly and component, for tests performed by a qualified testing agency.
072423 Field quality-control reports
072423 Sample Warranty: For manufacturer's special warranty.
072423 Closeout Submittal - Maintenance Data: For DEFS to include in maintenance manuals.
072726 Product Data: Include manufacturer's written instructions for evaluating, preparing, and treating each substrate; technical data; dry film thickness; and tested physical and performance properties of products. Low-build air barriers, vapor permeable.
072726 Shop Drawings: For air-barrier assemblies.
1. Show locations and extent of air-barrier materials, accessories, and assemblies specific to Project conditions.
2. Include details for substrate joints and cracks, counterflashing strips, penetrations, inside and outside corners, terminations, and tie-ins with adjoining construction.
3. Include details of interfaces with other materials that form part of air barrier.
072726 Qualification Data: For Installer. Include list of ABAA-certified installers and supervisors employed by Installer, who work on Project.
072726 Product Certificates: From air-barrier manufacturer, certifying compatibility of air barriers and accessory materials with Project materials that connect to or that come in contact with the barrier.
072726 Product Test Reports: For each air-barrier assembly, for tests performed by a qualified testing agency.
072726 Field quality-control reports
074113.16 Product Data: For standing-seam metal roof panels. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each type of panel and accessory.
074113.16 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
074113.16 Shop Drawings:
1. Include fabrication and installation layouts of metal panels; details of edge conditions, joints, panel profiles, corners, anchorages, attachment system, trim, flashings, closures, and accessories; and special details.
2. Accessories: Include details of the flashing, trim, and anchorage systems, at a scale of not less than 1-1/2 inches per 12 inches.
074113.16 Samples for Initial Selection: For each type of metal panel indicated with factory-applied color finishes.
1. Include similar Samples of trim and accessories involving color selection.
2. Final color shall match Building 29.
3. Submit samples to The Government for approval.
074113.16 Samples for Verification: For each type of exposed finish required, prepared on Samples of size indicated below.
1. Metal Panels: 12 inches long by actual panel width. Include clips, fasteners, closures, and other metal panel accessories.
074113.16 1. Metal Panels: 12 inches long by actual panel width. Include clips, fasteners, closures, and other metal panel accessories.
074113.16 Coordination Drawings: Roof plans, drawn to scale, on which the following are shown and coordinated with each other, based on input from installers of the items involved:
1. Roof panels and attachments.
2. Roof-mounted items including pipe and penetrations.
074113.16 Manufacturer Certificates: Signed by manufacturer certifying that roof panels comply with energy performance requirements specified in "Performance
Requirements" Article. 1. Submit evidence of meeting performance requirements.
074113.16 Qualification Data: For qualified professional engineer (licensed in the state of Hawaii) and testing agency
150084
REVIEW
AECOM
TITLE / DESCRIPTION SUBC-ONTRACTOR NAME
SUBMITTAL LOG
Project: NATIONAL GUARD READINESS CENTER ADDITION Kalaeloa Oahu Hawaii Federal Project No.:
C O
P
IE
S R
E C
E
IV
E D
D A
T E
S E
N T
T O
C O
N T
R A
C T
F
IC
E R
A T
U S
P F
O H
A W
A
II
D A
T E
R E
T U
R N
E D
T O
C O
N T
R A
C T
U
T
II
Q
G E
N E
R A
L C
O N
T R
A C
T O
C
General Contractor: CONTRACTOR TBD Architect and Engineers:
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
S U
B M
IT
T
A L N
U M
B E
R
DATE RECEIVED
AT HAWAII ARMY
NATIONAL GUARD
(HIARNG) D
A
T E
R E
Q U
IR
E
D T
O R
E T
U R
N
N E
R A
L C
O N
T R
A C
T O
R
N A
M E
N E
R A
L C
O N
T R
A C
T O
R
074113.16 Material Certificates: For thermal insulation and vapor retarders, from manufacturer
074113.16 Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for each product.
074113.16 Field quality-control reports.
074113.16 Warranties: Samples of special warranties.
074113.16 Closeout Submittals - Maintenance Data: For metal panels to include in maintenance manuals.
074293 Product Data: For each type of product.
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each type of panel and accessory.
074293 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
074293 Shop Drawings:
1. Include fabrication and installation layouts of metal panels; details of edge conditions, joints, panel profiles, corners, anchorages, attachment system, trim, flashings, closures, and accessories; and special details.
2. Accessories: Include details of flashing, trim, and anchorage systems, at a scale of not less than 1-1/2 inches per 12 inches.
074293 Samples for Initial Selection: For each type of metal panel indicated with factory-applied color finishes.
1. Include similar Samples of trim and accessories involving colr selection.
2. Final color of Soffit Panel shall match Building 29.
3. Submit samples to The Government for approval.
074293 Samples for Verification: For each type of exposed finish required, prepared on Samples of size indicated below.
1. Metal Panels: 12 inches long by actual panel width. Include fasteners, closures, and other metal panel accessories.
074293 Qualification Data: For Installer.
074293 Product Test Reports: For each product, tests performed by a qualified testing agency.
074293 Sample Warranties: For special warranties.
074293 Closeout Submittals - Maintenance Data: For metal panels to include in maintenance manuals.
075423 Product Data: For each type of product indicated.
075423 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
075423 Shop Drawings: For roofing system. Include plans, elevations, sections, details, and attachments to other work
1. Base flashings and membrane terminations.
2. Tapered insulation, including slopes.
3. Roof plan showing orientation of steel roof deck and orientation of membrane roofing and fastening spacings and patterns for mechanically fastened membrane roofing.
4. Insulation fastening patterns for corner, perimeter, and field-of-roof locations
075423 Samples for Verification: For the following products: 1. Sheet roofing, of color specified, including T-shaped side and end lap seam.
2. Roof insulation.
075423 Qualification Data: For qualified Installer and manufacturer
075423 Manufacturer Certificates: Signed by roofing manufacturer certifying that roofing system complies with requirements specified in "Performance Requirements"
Article.
1. Submit evidence of compliance with performance requirements.
075423 Product Test Reports: Based on evaluation of comprehensive tests performed by manufacturer and witnessed by a qualified testing agency, for components of membrane roofing system
075423 Field quality-control reports.
075423 Warranties: Sample of special warranties.
075423 Closeout Submittals - Maintenance Data: For roofing system to include in maintenance manuals.
076200 Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each manufactured product and accessory.
076200 Shop Drawings: Show fabrication and installation layouts of sheet metal flashing and trim, including plans, elevations, expansion-joint locations, and keyed details. Distinguish between shop- and field-assembled work. Include the following: 1.
Identification of material, thickness, weight, and finish for each item and location in Project.
2. Details for forming sheet metal flashing and trim, including profiles, shapes, seams, and dimensions.
3. Details for joining, supporting, and securing sheet metal flashing and trim, including layout of fasteners, cleats, clips, and other attachments. Include pattern of seams.
4. Details of termination points and assemblies, including fixed points.
5. Details of expansion joints and expansion-joint covers, including showing direction of expansion and contraction.
6. Details of special conditions.
7. Details of connections to adjoining work.
8. Detail formed flashing and trim at a scale of not less than 1-1/2 inches per 12 inches.
076200 Samples for Initial Selection: For each type of sheet metal flashing, trim, and accessory indicated with factory-applied color finishes involving color selection.
1. Final color for flashing, trim, gutters and downspouts shall match Building 29.
2. Submit Samples to The Government for approval.
076200 Samples for Verification: For each type of exposed finish required, prepared on Samples of size indicated below:
1. Sheet Metal Flashing: 12 inches long by actual width of unit, including finished seam and in required profile. Include fasteners, cleats, clips, closures, and other attachments.
2. Trim, Metal Closures, Expansion Joints, Joint Intersections, and Miscellaneous Fabrications: 12 inches long and in required profile. Include fasteners and other exposed accessories.
3. Accessories and Miscellaneous Materials: Full-size Sample.
4. Final color of exposed exterior sheet metals shall match Building 29. Submit samples to The Government for approval.
076200 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
076200 Qualification Data: For qualified fabricator.
076200 Warranty: Sample of special warranty.
076200 Closeout Submittals Maintenance Data: For sheet metal flashing and trim, and its accessories, to include in maintenance manuals.
078413 Product Data: For each type of product indicated.
078413 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
078413 Product Schedule: For each penetration firestopping system. Include location, illustration of firestopping system, and design designation of qualified testing and inspecting agency. 1. Where Project conditions require modification to a qualified testing and inspecting agency's illustration for a particular penetration firestopping condition, submit illustration, with modifications marked, approved by penetration firestopping manufacturer's fire-protection engineer as an engineering judgment or equivalent fire-resistance-rated assembly.
078413 Qualification Data: For qualified Installer.
078413 Installer Certificates: From Installer indicating penetration firestopping has been installed in compliance with requirements and manufacturer's written recommendations.
078413 Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for penetration firestopping
078443 Product Data: For each type of product indicated.
078443 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
078443 Product Schedule: For each joint firestopping system. Include location, illustration of firestopping system, and design designation of qualified testing agency.
1. Where Project conditions require modification to a qualified testing and inspecting agency's illustration for a particular penetration firestopping condition, submit illustration, with modifications marked, approved by penetration firestopping manufacturer's fire-protection engineer as an engineering judgment or equivalent fire-resistance-rated assembly.
078443 Qualification Data: For qualified Installer.
078443 Installer Certificates: From Installer indicating penetration firestopping has been installed in compliance with requirements and manufacturer's written recommendations.
078443 Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for penetration firestopping.
078443 Qualification Data: For Installer.
078443 Listed System Designs: For each joint firestopping system, for tests performed by a qualified testing agency.
078443 Closeoput Submittals: Installer Certificates: From Installer indicating that joint firestopping systems have been installed in compliance with requirements and manufacturer's written instructions.
079200 Product Data: For each type of product indicated.
1. For each Joint sealant product indicated.
079200 Samples for Initial Selection: Manufacturer's standard color charts consisting of strips of cured sealants showing the full range of colors available for each product exposed to view.
079200 Samples for Verification: For each type and color of joint sealant required, provide Samples with joint sealants in 1/2-inch- wide joints formed between two 6-inch- long strips of material matching the appearance of exposed surfaces adjacent to joint sealants. 1. At exterior locations, sealant color shall match Building 29.
2. Provide color samples to Contracting Officer for approval.
079200 Joint-Sealant Schedule: Include the following information:
1. Joint-sealant application, joint location, and designation.
2. Joint-sealant manufacturer and product name.
3. Joint-sealant formulation.
4. Joint-sealant color
079200 Qualification Data: For qualified Installer and testing agency.
079200 Product Certificates: For each kind of joint sealant and accessory, from manufacturer.
079200 Sealant, Waterproofing, and Restoration Institute (SWRI) Validation Certificate: For each sealant specified to be validated by SWRI's Sealant Validation
Program.
079200 Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, indicating that sealants comply with requirements.
079200 Field-Adhesion Test Reports: For each sealant application tested.
079200 Warranties: Sample of special warranties
079200 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
079219 Product Data:
1. Acoustical joint sealants.
079219 Samples for Initial Selection: Manufacturer's color charts consisting of strips of cured sealants, showing full range of available colors for each product exposed to view.
079219 Samples for Verification: For each type and color of acoustical joint sealant required.
1. Size: 1/2-inch- wide sealant joints formed between two 6-inch long strips of material matching the appearance of exposed surfaces adjacent to joint sealants.
079219 Acoustical Joint-Sealant Schedule: Include the following information:
1. Joint-sealant application, joint location, and designation.
2. Joint-sealant manufacturer and product name.
3. Joint-sealant formulation.
4. Joint-sealant color.
079219 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
079219 Test and Evaluation Reports:
1. Product Test Reports: For each type of acoustical joint sealant, for tests performed by qualified testing agency or manufacturer and witnessed by a qualified testing agency.
079219 Sample warranties.
079219 Closeout Sumittals:
Warranty Documentation:
1. Manufacturers' special warranties.
2. Installer's special warranties.
079513.13 Product Data: For each type of product. 1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for expansion joint cover assemblies.
079513.13 Shop Drawings: For each expansion joint cover assembly.
1. Include plans, elevations, sections, details, splices, block-out requirement, attachments to other work, and line diagrams showing entire route of each expansion joint.
2. Where expansion joint cover assemblies change planes, provide isometric or clearly detailed drawing depicting how components interconnect.
079513.13 Samples: For each expansion joint cover assembly and for each color and texture specified, full width by 4 inches long in size.
1. Include manufacturer's color charts showing the full range of colors and finishes available for each exposed metal and elastomeric-seal material.
079513.13 Samples for Verification: For each type of expansion joint cover assembly, full width by 4 inches long in size.
079513.13 Expansion Joint Cover Assembly Schedule: Prepared by or under the supervision of the supplier. Include the following information in tabular form:
1. Manufacturer and model number for each expansion joint cover assembly.
2. Expansion joint cover assembly location cross-referenced to Drawings.
3. Nominal, minimum, and maximum joint width.
4. Movement direction.
5. Materials, colors, and finishes.
6. Product options.
7. Fire-resistance ratings.
079513.13 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
079513.13 Product Test Reports: For each fire-resistance-rated expansion joint cover assembly, for tests performed by a qualified testing agency.
079513.16 Product Data: For each type of product.
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for expansion joint cover assemblies.
079513.16 Shop Drawings: For each expansion joint cover assembly.
1. Include plans, elevations, sections, details, splices, block-out requirement, attachments to other work, and line diagrams showing entire route of each expansion joint.
2. Where expansion joint cover assemblies change planes, provide isometric or clearly detailed drawing depicting how components interconnect.
079513.16 Samples: For each exposed expansion joint cover assembly and for each color and texture specified, full width by 4 inches long in size.
079513.16 Samples for Initial Selection: For each type of exposed finish.
1. Include manufacturer's color charts showing the full range of colors and finishes available for each exposed metal and elastomeric seal material.
079513.16 Samples for Verification: For each type of expansion joint cover assembly, full width by 4 inches long in size.
079513.16 Expansion Joint Cover Assembly Schedule: Prepared by or under the supervision of the supplier. Include the following information in tabular form:
1. Manufacturer and model number for each expansion joint cover assembly.
2. Expansion joint cover assembly location cross-referenced to Drawings.
3. Nominal, minimum, and maximum joint width.
4. Movement direction.
5. Materials, colors, and finishes.
6. Product options.
7. Fire-resistance ratings
079513.16 Sustainable Design Submittals - See specification 018113.14 FL - Sustainable Design Requirements - LEED v4 BD+C, New Construction.
079513.16 Product Test Reports: For each fire-resistance-rated expansion joint cover assembly, for tests performed by a qualified testing agency.
1001 BISHOP STREET SUITE 1600
HONOLULU, HAWAII 96813
DATE SENT TO
AECOM HAWAII
DATE RECEIVED
FROM
AECOM…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .