HHS0016834v2 Attachment G-1 Project Drawings.pdf

PDF 19 MB Posted

Attached to
RFP HHS0016834v2, Project 24-101-AUL, Fire Alarm Upgrades, Austin, TX
Solicitation number
HHS0016834v2
Issued by
Travis County, Austin City, Texas

About this file

This is a project drawings document for fire alarm system upgrades at the Austin State Supported Living Center in Austin, Texas, prepared by Texas Health and Human Services. The project involves the installation of new NFPA 72-compliant fire alarm systems in Buildings 533 and 732, including addressable fire alarm control units, smoke and carbon monoxide detectors, horn/strobes, heat detectors, manual pull stations, monitoring modules, and control modules. The scope includes removal of existing fire alarm systems, installation of 520 Hz and 177 candela notification devices in resident sleeping areas, and installation of new fiber optic lines to transmit fire alarm signals from Buildings 533 and 732 to the main panel. The contractor must conduct a site investigation before bidding, prepare a detailed phasing plan for owner approval, and coordinate all work with the owner and operator. Work is required during nights and weekends to maintain building operations, with owner approval required for any work during normal business hours (8 AM–5 PM). The contractor must maintain OSHA compliance, obtain an "A" rating from ISNET World, and provide submittals for review prior to placing purchase orders and scheduling work.

The contractor is responsible for all labor, tools, materials, equipment, and incidental operations required to complete the work, with all debris disposal in accordance with federal, state, and local regulations at no additional cost to the owner. The contractor must provide detailed shop drawings for review and approval prior to fabrication, including riser diagrams, graphical sequence of operations matrices, power connection details, and floor plans showing device addresses and circuitry. A field project manager with minimum NICET Level III certification in fire alarm system technology and a designer with NICET Level III certification or a licensed professional fire protection engineer must be assigned to the project. All equipment must be new and listed by Underwriters Laboratories; the system must be non-proprietary with components available from multiple sources for procurement and servicing. The contractor must maintain as-built drawings on site during construction and deliver a complete set of electronic as-built drawings upon project completion, with all changes and revisions recorded, including the horizontal and vertical locations of buried utilities that differ from contract drawings.

View the file

Other files

File Type Posted
HHS0016834 v2 Addendum Item 02 Site Visit Sign-in.pdf PDF
HHS0016834v2 Exhibit E Pricing Proposal Form.pdf PDF
ESBD_506029_1778076486633_RFP HHS0016834v2 Addendum 02 Revision.pdf PDF
HHS0016834v2 Exhibit F Evaluation Tool.pdf PDF
Addendum Item #3, Door Magnet Data Sheets.pdf PDF
HHS0016834 v2 Addendum Item 01 PPC Sign-In.pdf PDF
HHS0016834 v2 Addendum 01 PCS121.pdf PDF
HHS0016834 v2 Addendum 02 PCS121.pdf PDF
HHS0016834v2 Attachment G-2 Project Manual.pdf PDF
HHS0016834v2 Attachment I Uniform Terms and Conditions.pdf PDF
HHS0016834v2 Attachment B Uniform General Conditions.pdf PDF
HHS0016834v2 Attachment D Facility Specific Policies.pdf PDF
HHS0016834v2 Exhibit D Info Disclosure Financial Form.pdf PDF
HHS0016834v2 Attachment H Negotiated Modifications - Cover.pdf PDF
HHS0016834v2 Attachment F Respondent's Pricing - Cover.pdf PDF
HHS0016834v2 Exhibit G Site Visit Parking and Staging.pdf PDF
HHS0016834v2 Exhibit A Solicitation Affirmations.pdf PDF
Addendum item #4, HHS Responses to Questions.pdf PDF
HHS0016834v2 Exhibit B Draft Contract.pdf PDF
HHS0016834v2 Attachment E Prevailing Wage Rates.pdf PDF
HHS0016834v2 Exhibit C Exceptions.pdf PDF
HHS0016834v2 Attachment C Project Special Conditions.pdf PDF
HHS0016834v2 Attachment A Contract Affirmations.pdf PDF
ESBD_506029_1776092752168_HHS0016834v2 Attachments No Drawings.zip ZIP file
ESBD_506029_1776092564423_RFP HHS0016834v2.pdf PDF
ESBD_506029_1776092607825_HHS0016834v2 Exhibits.zip ZIP file
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment G-1 Project Drawings

TEXAS HEALTH AND HUMAN SERVICES

AUSTIN STATE SUPPORTED LIVING CENTER

BUILDING 533 & 732

AUSTIN, TEXAS

FIRE ALARM UPGRADES

SEPTEMBER 9, 2024

DRAWING INDEX

C0.0 COVER

C1.0 OVERALL SITE PLAN

C1.1 FIBER LINE ROUTE PLAN

C1.2 DETAILS

FA0.01 FIRE ALARM GENERAL NOTES AND LEGEND

FA1.01 FIRE ALARM DEMO PLAN BUILDING 533

FA1.02 FIRE ALARM DEMO PLAN BUILIDNG 732

FA2.01 FIRE ALARM FLOOR PLAN BUILDING 533

FA2.02 FIRE ALARM FLOOR PLAN BUILDING 732

FA2.03 FIRE ALARM PENTHOUSE PLAN BUILDING 732

FA6.01 FIRE ALARM DETAILS

GENERAL SCOPE OF WORK:

• INSTALL NEW FIRE ALARM SYSTEMS THROUGHOUT BUILDINGS 533 AND 732.

• EQUIP BUILDINGS 732 AND 533 WITH SMOKE AND CARBON MONOXIDE DETECTION PER HHS STANDARDS.

• INSTALL 520 HZ AND 177 CD DEVICES IN RESIDENT SLEEPING AREAS IN COMPLIANCE WITH NFPA 72.

• INSTALL NEW FIBER LINES TO TRANSMIT FIRE ALARM SIGNALS FROM BUILDING 533 AND 732 TO MAIN PANEL AT THE SITE.

1. SCOPE OF WORK:

WORK TO BE PERFORMED TO CONSIST OF FURNISHING ALL LABOR, TOOLS, MATERIALS, EQUIPMENT, AND PERFORMING ALL WORK REQUIRED AS SHOWN ON THESE DRAWINGS, CONTRACT DOCUMENTS, AND PER THE AWARDED RFP DOCUMENTS. INCIDENTAL OPERATIONS NOT SPECIFICALLY MENTIONED HEREIN MAY BE REQUIRED. CONTRACTOR SHALL PERFORM A SITE INVESTIGATION BEFORE BIDDING AND COMMENCING WORK.

2. WORK COORDINATION:

THE CONTRACTOR SHALL PREPARE A DETAILED PHASING PLAN FOR APPROVAL BY THE OWNER AND OPERATOR. ADDITIONALLY, PRIOR TO COMMENCEMENT OF WORK, THE CONTRACTOR SHALL COORDINATE EACH OPERATION AND SEQUENCE WITH THE OWNER AND OPERATOR. CONTRACTOR SHALL COMPLY WITH THE OWNER'S REQUIREMENTS FOR WORKING HOURS, DELIVERY AND HANDLING OF MATERIAL, CONSTRUCTION WASTE REMOVAL, AND PLANT SAFETY REQUIREMENTS. DURING CONSTRUCTION, BUILDING AREAS WILL REMAIN OCCUPIED AND OPERATIONAL.

3. HOURS OF OPERATION:

UNLESS OTHERWISE APPROVED BY THE OWNER OR OPERATOR, THE CONTRACTOR SHALL WORK NIGHTS AND WEEKENDS TO COMPLETE THE WORK. THE

OWNER MUST APPROVE ALL WORK DURING NORMAL BUSINESS HOURS 8AM - 5 PM.

4. PERSONNEL AND PROPERTY PROTECTION:

CONTRACTOR SHALL CONFORM TO CURRENT OSHA & OWNER SAFETY PROGRAM REQUIREMENTS. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO ADEQUATELY PROTECT PERSONS AND PROPERTY IN THE AREAS OF WORK. CONTRACTOR SHALL HAVE AN "A" RATING FROM ISNET

WORLD.

5. DISPOSAL:

CONTRACTOR SHALL NOT DISPOSE OF ANY MATERIAL ON THE OWNER'S PROPERTY. CONTRACTOR SHALL DISPOSE OF ALL DEBRIS/MATERIAL IN ACCORDANCE WITH FEDERAL, STATE, AND LOCAL REGULATIONS AT NO EXTRA COST TO THE OWNER.

6. CLEANING UP:

AT THE CLOSE OF EACH WORK DAY CONTRACTOR SHALL ENSURE THE SITE IS CLEANED TO THE SATISFACTION OF THE OWNER AND OPERATOR.

ENFORCEMENT OF THE PROVISIONS OF THESE GENERAL REQUIREMENTS BY SUBCONTRACTORS WILL BE THE RESPONSIBILITY OF THE PRIME

CONTRACTOR.

7. ACCEPTANCE:

ALL WORK IS SUBJECT TO INSPECTION, APPROVAL AND ACCEPTANCE BY THE OWNER AND OPERATOR.

8. DIMENSIONS AND FIELD CONDITIONS:

CONTRACTOR SHALL VERIFY IN THE FIELD ALL EXISTING CONDITIONS, ELEVATIONS, AND DIMENSIONS, AND SHALL NOTIFY THE OWNER, OPERATOR, AND DESIGNER OF RECORD IF ANY DISCREPANCIES OR INTERFERENCES ARE FOUND. NOTIFICATION SHALL BE GIVEN BEFORE STARTING THE WORK OR THE FABRICATION OF ANY COMPONENT. NOTE ALL DRAWINGS ARE GIVEN DIAGRAMMATICALLY AND MAY BE SUBJECT TO IN FIELD INTERFERENCES.

9. SUBMITTAL REVIEW

CONTRACTOR SHALL PROVIDE ALL SUBMITTALS AS REQUIRED TO THE OWNER, OPERATOR, AND DESIGNER OF RECORD PRIOR TO PLACING ANY PURCHASE ORDERS AND SCHEDULING ANY WORK. CONTRACTOR SHALL ALLOW THE TIME FOR REVIEW OF SUBMITTALS AS STIPULATED IN THE CONTRACT.

10. UTILITY SHUT-OFF NOTICE

OUTAGE OF ANY SERVICE (E.G. ELECTRICAL, WATER, ETC...) SHALL BE COORDINATED WITH THE OWNER AND OPERATOR A MINIMUM OF SEVEN (7) DAYS

PRIOR TO THE OUTAGE.

11. SHOP DRAWINGS

THE CONTRACTOR SHALL PROVIDE DETAILED SHOP DRAWING FOR REVIEW AND APPROVAL PRIOR TO FABRICATION.

12. AS-BUILT DRAWINGS:

THE CONTRACTOR SHALL MAINTAIN AT THE JOB SITE ONE FULL-SIZE SET OF DRAWINGS FOR RECORDING, IN RED PENCIL, ALL CHANGES AND/OR REVISIONS WHICH HAVE BEEN MADE FROM THE CONTRACT DRAWINGS, INCLUDING BURIED OR CONCEALED CONSTRUCTION AND UTILITY FEATURES REVEALED DURING THE COURSE OF CONSTRUCTION. THE CONTRACTOR SHALL RECORD THE HORIZONTAL AND VERTICAL LOCATION OF ALL BURIED UTILITIES THAT DIFFER FROM THE DRAWINGS. THESE DRAWINGS SHALL BE AVAILABLE FOR REVIEW BY THE OWNER OR OPERATOR AT ALL TIMES. UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL INCORPORATE ALL CHANGES AND REVISIONS INTO A FULL SET OF AS-BUILTS DRAWINGS AND SHALL DELIVER THIS

FULL SET TO THE OWNER AND OPERATOR UPON COMPLETION OF THE CONTRACT.

13. SIGNAGE

SIZE, MATERIAL, COLOR, LOCATION AND WORDING FOR EXTERIOR AND INTERIOR SIGNAGE SHALL MATCH EXISTING OWNER STANDARDS AND BE APPROVED BY THE OWNER AND OPERATOR. THIS INCLUDES, BUT IS NOT LIMITED TO, ALL CONSTRUCTION CAUTION AND WARNING SIGNS.

TEXAS REGISTERED ENGINEERING FIRM F-10573

801 TRAVIS, SUITE 2000

HOUSTON, TX 77002

PHONE: 713-237-9800

FAX: 713-237-9801

CHECKED BY

PROJECT NUMBER

SHEET DATE

DRAWN BY

F il e

N a m e

D a te /T im e

SHEET NUMBER

SHEET NAME

C

D M

S \R e v it

P ro je c ts

\A U

L F ir e A la rm

U p g ra d e s

R E m il y .H e n ry A

B N

V .r v t

/9

/2

:1

:4

A

M

09/09/24

AUL FIRE ALARM

UPGRADES DRAWING

PACKAGE

A U

L F ir e

A la rm U p g ra d e s

H e a lt h a n d H u m a n S e rv ic e s

W th

S t

A u s ti n

T X

762401161.00

N o

D e s c ri p ti o n

D a te

IS

S

U E

F O

R P

E R

M

IT

/0

/2

09 SEPTEMBER, 2024

09/09/2024

IS

S

U E

F O

R P

E R

M

IT

/0

9/

IS

S

U E

F O

R P

E R

M

IT

/0

9/

IS

S

U E

F O

R P

E R

M

IT

/0

9/

IS

S

U E

F O

R P

E R

M

IT

/0

9/

CONTRACTOR SHALL INSTALL A NEW, NFPA 72 CODE COMPLIANT FIRE ALARM SYSTEM AND REMOVE THE

EXISTING FIRE ALARM SYSTEM FOR BUILDINGS 533 AND 732.

CONTRACTOR SHALL ONLY BEGIN REMOVING EXISTING FIRE ALARM SYSTEM ONCE NEW FIRE ALARM

SYSTEM IS FULLY INSTALLED, COMMISSIONED, AND ACCEPTED.

CONTRACTOR SHALL INSTALL AN ADDRESSABLE FIRE ALARM SYSTEM THROUGHOUT BUILDING IN

ACCORDANCE WITH APPLICABLE CODES AND STANDARDS LISTED ON THIS SHEET AND BOOK

SPECIFICATION SECTION 284621.11, INCLUDING HORN/STROBES, SMOKE DETECTORS, SMOKE ALARMS, HEAT DETECTORS, MANUAL PULL STATIONS, MONITORING MODULES AND CONTROL MODULES.

AUDIO AND VISUAL NOTIFICATION SHALL BE GLOBAL / GENERAL EVACUATION OF ENTIRE FACILITY.

MASS NOTIFICATION IS NOT A REQUIREMENT OF THIS PROJECT; INTELLIGIBILITY AND ASSOCIATED

REQUIREMENTS DO NOT APPLY.

THE FACU AND SUPPORTING HEAD-END EQUIPMENT SHALL BE INSTALLED AS SHOWN ON SHEETS FA2.03 AND FA2.04. PROVIDE NAC PANELS AS NEEDED. PRELIMINARY DESIGN ESTIMATES APPROXIMATELY 1

NAC PANEL PER LEVEL. PROVIDE NEW DACT FOR OFF-SITE MONITORING.

MONITOR MODULES WILL BE PROVIDED TO MONITOR THE EXISTING PIVS AT BUILDING 732 AS WELL AS

THE DOMESTIC WATER PUMP WHEN IT IS OPERATING ON GENERATOR POWER.

THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS.

THE CONTRACTOR IS RESPONSIBLE FOR RESTORING INTERIOR FINISHES TO LIKE-ORIGINAL CONDITION WHERE CUTTING AND PATCHING IS REQUIRED. WHERE PAINTING IS REQUIRED, CONTRACTOR SHALL MATCH PAINT COLOR AND OBTAIN OWNER APPROVAL FOR COLOR SELECTION PRIOR TO APPLICATION.

CONTRACTOR SHALL PROVIDE A FIBER OPTIC OUTPUT FROM THE FIRE ALARM PANEL THAT WILL BE

PICKED UP BY CIVIL TO ROUTE TO BUILDING 543.

NON-PROPRIETARY: FIRE ALARM SYSTEM SHALL BE AVAILABLE FROM MULTIPLE SOURCES FOR BOTH PROCUREMENT AND SERVICING. SYSTEMS EXCLUSIVELY AVAILABLE FOR PROCUREMENT AND SERVICE

FROM ONLY THE MANUFACTURER ARE PROHIBITED.

THERE ARE EXISTING FIRE AND SMOKE DAMPERS THROUGHOUT THE FACILITY. THE TOTAL QUANTITIES AT THIS TIME ARE UNKNOWN. CONTRACTOR SHALL INCLUDE AN ALLOWANCE FOR 20 SMOKE AND FIRE

DAMPERS. FINAL COUNT TO BE COORDINATED IN FIELD BY CONTRACTOR.

SCOPE OF WORK FIRE PROTECTION LEGEND

NEW WORK

EXISTING WORK

DEMOLITION WORK

SIGNALING LINE CIRCUIT

NOTIFICATION APPLIANCE CIRCUIT

1-HR RATED SEPARATION

2-HR RATED SEPARATION

STROBE, CEILING-MOUNTED, MULTI-CANDELA, 'CD' INDICATES

INTENSITY SETTING.

STROBE, WALL-MOUNTED, MULTI-CANDELA, 'CD' INDICATES

INTENSITY SETTING.

COMBINATION HORN-STROBE, CEILING-MOUNTED, MULTI-

CANDELA, 'CD' INDICATES INTENSITY SETTING.

COMBINATION HORN-STROBE, WALL-MOUNTED, MULTI-CANDELA,

'CD' INDICATES INTENSITY SETTING.

HORN - WALL MOUNTED

COMBINATION SMOKE/CARBON MONOXIDE DETECTOR, CEILING

MOUNTED

DUCT SMOKE DETECTOR

MANUAL PULL STATION

MONITOR MODULE

CONTROL MODULE

HEAT DETECTOR

FIRE ALARM CONTROL UNIT

NOTIFICATION APPLIANCE CIRCUIT EXPANDER PANEL

DIGITAL ALARM COMMUNICATOR TRANSMITTER

CARBON MONOXIDE DETECTOR

FIRE ALARM DOCUMENT BOX

P

CM

MM

FACU

NAC

DACT

CD

CD

CD

CD

CO

DOC

INTERNATIONAL CODE COUNCIL

IBC - INTERNATIONAL BUILDING CODE - 2021 EDITION

IFC - INTERNATIONAL FIRE CODE - 2021 EDITION

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 - NATIONAL ELECTRIC CODE - 2023 EDITION

NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE - 2010 EDITION

NFPA 101 - LIFE SAFETY CODE - 2012 EDITION

ADDITIONAL STANDARDS

THE FACILITY GUIDELINES INSTITUTE [FGI] GUIDELINES FOR THE DESIGN AND CONSTRUCTION OF

HOSPITALS - 2021 EDITION

TEXAS ADMINISTRATIVE CODE [TAC], TITLE 26, PART 1, CHAPTER 551 INTERMEDIATE CARE FACILITIES FOR

INDIVIDUALS WITH AN INTELLECTUAL DISABILITY OR RELATED CONDITIONS

APPLICABLE CODES AND STANDARDS

(THESE NOTES APPLY TO ALL FIRE ALARM DRAWINGS)

1. ALL DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE NOT INTENDED TO BE USED FOR EXACT

MEASURE OR FABRICATION. CONTRACTOR SHALL INSTALL ALL FIRE ALARM COMPONENTS IN

ACCORDANCE WITH ALL APPLICABLE CODES. CONTRACTOR SHALL COORDINATE INSTALLATION OF

SYSTEM CONDUIT AND OTHER COMPONENTS WITH ALL OTHER TRADES.

2. IN CASE OF DISPUTE AS TO INTENT OF DRAWING OR SPECIFICATIONS, OBTAIN OWNER'S WRITTEN

APPROVAL BEFORE PROCEEDING WITH BID.

3. DESIGN AND INSTALL THE FIRE ALARM SYSTEM TO MEET THE REQUIREMENTS OF ALL CODES AND

STANDARDS AS APPLICABLE AND AS LISTED ON THIS SHEET.

4. THE CONTRACTOR SHALL PROVIDE A FIELD PROJECT MANAGER THROUGHOUT THE PROJECT WITH A

MINIMUM OF NICET LEVEL III CERTIFICATION IN FIRE ALARM SYSTEM TECHNOLOGY.

5. THE CONTRACTOR SHALL HAVE A DESIGNER WITH A MINIMUM NICET LEVEL III CERTIFICATION IN FIRE

ALARM SYSTEM TECHNOLOGY OR A LICENSED PROFESSIONAL FIRE PROTECTION ENGINEER IN

RESPONSIBLE CHARGE OF THE FIRE ALARM SYSTEM DESIGN.

6. TRADE PERMIT REQUIRED. THE CONTRACTOR SHALL PREPARE AND SUBMIT SHOP DRAWINGS TO THE LOCAL AHJ FOR THE FIRE ALARM SYSTEM INCLUDING ALL NFPA 72 REQUIRED ELEMENTS, WHICH INCLUDES BUT IS NOT LIMITED TO A RISER, GRAPHICAL SEQUENCE OF OPERATIONS MATRIX, POWER CONNECTION DETAILS, FLOOR PLANS SHOWING ALL DEVICE ADDRESSES, POWER SUPPLIES, CIRCUITRY AND ZONING PROPOSED FOR THE PROJECT/SYSTEM, IN SUFFICIENT DETAIL TO CLEARLY REVIEW AND BUILD THE SYSTEM. PROVIDE INTERIOR PANEL WIRING AND DEVICE POINT-TO-POINT CONNECTION DETAIL

DRAWINGS FOR ALL EQUIPMENT.

7. SHOP DRAWINGS SHALL BE SUPPLEMENTED WITH CATALOG CUT SHEETS FOR ALL DEVICES AND MATERIALS, ADDRESSABLE CIRCUIT LOADING, NOTIFICATION APPLIANCE CIRCUIT LOADING, WATTAGE

CALCULATIONS, BATTERY CALCULATIONS, CURRENT DRAW AND VOLTAGE DROP CALCULATIONS.

8. FIELD CHANGES IN THE LOCATIONS OF EQUIPMENT FROM THOSE SHOWN ON APPROVED SHOP

DRAWINGS SHALL BE IDENTIFIED AND APPROVED IN WRITING PRIOR TO INSTALLATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR RECTIFYING UNAUTHORIZED NONCOMPLIANT CHANGES AT NO ADDITIONAL

CHARGE TO THE OWNER.

9. THE CONTRACTOR SHALL MAINTAIN ACCURATE RED-LINE CONSTRUCTION WORKING DRAWINGS ON SITE. FOLLOWING COMMISSIONING, CONTRACTOR SHALL PREPARE "AS-BUILT" DRAWINGS IN ELECTRONIC

FORMAT, REFLECTING ACCURATE FIELD CONDITIONS.

10. THE CONTRACTOR IS SPECIFICALLY RESPONSIBLE FOR ALL MEANS AND METHODS OF JOB SAFETY.

ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE CODES AND REGULATIONS.

11. IF THE CONTRACTOR OPTS TO INSTALL EQUIPMENT OTHER THAN THAT SPECIFIED, HE/SHE SHALL BE

RESPONSIBLE FOR PERFORMING THE NECESSARY DESIGN SERVICES TO ACCOMMODATE THE

EQUIPMENT. ANY SUCH CHANGES SHALL BE DESIGNED BY A LICENSED PROFESSIONAL ENGINEER.

12. ALL EQUIPMENT SHALL BE NEW UNLESS OTHERWISE NOTED.

13. PROVIDE TRANSIENT SURGE SUPPRESSION FOR THE FIRE ALARM SYSTEM POWER SUPPLY AND FOR

ALL CIRCUITS LEAVING THE BUILDING.

14. ALL DEVICES NEEDED FOR A COMPLETE AND WORKING FIRE ALARM SYSTEM ARE NOT SHOWN ON THESE CONCEPT DRAWINGS. PROVIDE EQUIPMENT AS NECESSARY FOR A FULLY OPERATIONAL SYSTEM.

15.ENTIRE FIRE ALARM SYSTEM SHALL BE COMMISSIONED AND TESTED PRIOR TO TURN OVER TO OWNER.

DURING COMMISSIONING, CONTRACTOR SHALL ENSURE ALL DOORS ON MAGNETIC HOLD OPEN CLOSE AT

THE SAME TIME.

INSTALLATION REQUIREMENTS

16. THE INSTALLING CONTRACTOR SHALL CONTRACT WITH A SINGLE SOURCE FOR SUPPLYING JOB MATERIALS, SERVICES, AND PROGRAMMING, INCLUDING FINAL INSPECTION/TEST SERVICES AND UL

LISTING FOR THE COMPLETED FIRE ALARM SYSTEM.

17. EACH COMPONENT OF THE FIRE ALARM SYSTEM SHALL BE LISTED FOR THE INTENDED USE BY

UNDERWRITERS LABORATORIES, INC. (UL), AND SHALL BEAR THE "UL" LABEL.

18. ALL WIRING, RACEWAYS, CONDUITS AND BOXES FOR NEW AND RELOCATED DEVICES SHALL BE NEW.

PROVIDE A PERMANENT LABEL FOR EACH WIRE/CIRCUIT (WITHIN ALL PANELS, CABINETS AND JUNCTION

BOXES) INDICATING IT'S APPLICATION/USE/SERVICE.

19. WIRING SHALL BE INSTALLED ABOVE CEILINGS AND WITHIN BUILDING CONSTRUCTION WHEREVER POSSIBLE. OBTAIN WRITTEN OWNER APPROVAL FOR EXPOSED WIRING/RACEWAYS IN FINISHED AREAS.

20. PAINT JUNCTION BOXES, TERMINAL CABINETS, BACK BOXES AND COVERS WITH RED PAINT. RED FINISH

SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE (NEC).

21. ALL TERMINAL CABINETS AND JUNCTION BOXES SHALL BE LABELED WITH WHITE LETTERS INDICATING

"FIRE ALARM."

22. ALL SYSTEM POWER AND GROUND CIRCUITS SHALL BE TYPE "THHN" SOLID COPPER SIZED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS, APPLICABLE CODES, AND IN EMT-TYPE CONDUIT.

23. IN ALL AREAS WITH DROP CEILINGS, CEILING-MOUNT FIRE ALARM DEVICES SHALL BE LOCATED IN THE

CENTER OF THE CEILING TILE.

24. ALL EQUIPMENT SHALL BE SEMI-FLUSH-MOUNTED WHERE POSSIBLE.

25. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED. WHERE WALL-MOUNTED VISIBLE AND COMBINATION AUDIBLE/VISIBLE ALARM NOTIFICATION APPLIANCES ARE REQUIRED, THEY SHALL BE MOUNTED SUCH THAT THE ENTIRE LENS IS A MINIMUM OF 80-INCHES AND MAXIMUM OF 96-INCHES ABOVE THE FINISHED FLOOR OR WITHIN 6-INCHES OF THE CEILING (WHICH EVER IS LOWER). UNLESS OTHERWISE NOTED: FIRE ALARM FIELD DEVICES SHALL BE WHITE; NOTIFICATION DEVICES SHALL BE

MARKED 'FIRE' WITH RED LETTERING; STROBE LENSES SHALL BE CLEAR.

26. ADDRESSABLE CONTROL/RELAY MODULES UTILIZED FOR ANY SHUTDOWN OR ACTIVATION FUNCTIONS

SHALL BE MOUNTED WITHIN THREE (3) FEET OF THE CONTROLLED CIRCUIT OR DEVICE.

27. INSTALLATION AND TERMINATIONS OF ALL WIRE SHALL CONFORM TO THE MANUFACTURER'S

RECOMMENDATIONS.

28. COORDINATE ALL NEW WORK WITH OTHER TRADES TO AVOID CONFLICTS DURING CONSTRUCTION.

CIRCUIT AND PATHWAY REQUIREMENTS

29. NAC: LIMIT NAC DESIGN LOAD TO 80% ON ANY INDIVIDUAL CIRCUIT TO ALLOW FOR FUTURE GROWTH.

30. SIGNALING LINE CIRCUITS SHALL BE CLASS B.

31. NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLASS B.

32. INITIATING DEVICE CIRCUITS SHALL BE CLASS B.

33. NFPA 72 PATHWAY SURVIVABILITY REQUIREMENT: BUILDING 732, LEVEL 1 - FULLY SPRINKLERED BUILDING IN ACCORDANCE WITH NFPA 13 WITH ANY INTERCONNECTING CONDUCTORS, CABLES, OR OTHER PHYSICAL PATHWAYS PROTECTED BY METAL RACEWAYS OR METAL ARMORED CABLES. BUILDING 533, LEVEL 0 IN ACCORDANCE WITH NFPA 13 WITH ANY INTERCONNECTING CONDUCTORS, CABLES, OR

OTHER PHYSICAL PATHWAYS PROTECTED BY METAL RACEWAYS OR METAL ARMORED CABLES.

34. SECONDARY POWER SHALL BE SUPPLIED VIA BATTERIES. SIZE BATTERIES FOR 24-HRS OF STANDBY AND 5-MINS OF ALARM. FIRE ALARM EQUIPMENT IS PROVIDED WITH NORMAL BUILDING POWER FOR

PRIMARY POWER SOURCE.

FIRE ALARM DEMOLITION NOTES

35. EXISTING FIRE ALARM SYSTEM SHALL BE REMOVED ONLY AFTER THE NEW FIRE ALARM SYSTEM IS INSTALLED AND COMMISSIONED AND ACCEPTED IN ORDER TO MAINTAIN A FULLY FUNCTIONAL FIRE ALARM

SYSTEM WITHIN THE BUILDING AT ALL TIMES.

36. AFFIX "NOT IN SERVICE" PLACARDS TO NEW EQUIPMENT THAT HAS NOT YET BEEN COMMISSIONED AND

THEN OLD EQUIPMENT AWAITING DEMOLISHING FOLLOWING NEW SYSTEM ACCEPTANCE.

FIRE ALARM GENERAL NOTESFIRE ABBREVIATIONS

ACT ACOUSTICAL CEILING TILE

AFF ABOVE FINISHED FLOOR

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AS AUTOMATIC SPRINKLER

CD CANDELA

CFM CUBIC FEET PER MINUTE

COR CONTRACT OFFICER'S REPRESENTATIVE

CRAC COMPUTER ROOM AIR CONDITIONING

ESFR EARLY SUPPRESSION FAST RESPONSE

ETR EXISTING TO REMAIN

FA FIRE ALARM

FACU FIRE ALARM CONTROL UNIT

FP FIRE PROTECTION

FSD FIRE SMOKE DAMPER

FT FEET

GPM GALLONS PER MINUTE

HVAC HEATING, VENTILATION, AIR CONDITIONING

IBC INTERNATIONAL BUILDING CODE

ICC INTERNATIONAL CODE COUNCIL

IDC INITIATING DEVICE CIRCUIT

IN INCHES

LED LIGHT EMITTING DIODE

MAX MAXIMUM

MIN MINIMUM

MTG MEETING

MULTI. MULTI-PERSON OFFICE

NAC NOTIFICATION APPLIANCE CIRCUIT

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

OFF OFFICE

PSI POUNDS PER SQUARE INCH

RR RESTROOM

RSCP RELEASING SERVICE CONTROL PANEL

RTU ROOF TOP UNIT

SLC SIGNALING LINE CIRCUIT

SQFT SQUARE FEET

STOR STORAGE

V VOLTS

VAC VOLT, ALTERNATING CURRENT

VDC VOLT, DIRECT CURRENT

W WATTS

FIRE ALARM SHEET LIST

SHEET

NUMBER SHEET NAME

FA0.01 FIRE ALARM GENERAL NOTES AND LEGEND

FA1.00 FIRE ALARM SITE PLAN

FA2.01 FIRE ALARM DEMO PLAN BUILDING 533

FA2.02 FIRE ALARM DEMO PLAN BUILDING 732

FA2.03 FIRE ALARM FLOOR PLAN BUILDING 533

FA2.04 FIRE ALARM FLOOR PLAN BUILDING 732

FA2.05 FIRE ALARM PENTHOUSE PLAN BUILDING 732

FA6.01 FIRE ALARM DETAILS

TEXAS REGISTERED ENGINEERING FIRM F-10573

801 TRAVIS, SUITE 2000

HOUSTON, TX 77002

PHONE: 713-237-9800

FAX: 713-237-9801

CHECKED BY

PROJECT NUMBER

SHEET DATE

DRAWN BY

F il e

N a m e

D a te /T im e

SHEET NUMBER

SHEET NAME

C

D M

S \R e v it

P ro je c ts

\A U

L F ir e A la rm

U p g ra d e s

R E m il y .H e n ry A

B N

V .r v t

/9

/2

:1

:0

A

M

FA0.01

09/09/24

LEH

KMKR

FIRE ALARM GENERAL

NOTES AND LEGEND

A U

L F ir e

A la rm U p g ra d e s

H e a lt h a n d H u m a n S e rv ic e s

W th

S t

A u s ti n

T X

762401161.00

N o

D e s c ri p ti o n

D a te

IS

S

U E

F O

R P

E R

M

IT

/0

/2

AS AN ALTERNATE, CONTRACTOR TO INSTALL ALL NEW MAGNETIC DOOR LOCKS. OWNER FURNISHED, CONTRACTOR INSTALLED.

CONTRACTOR TO USE THE QUANTITY OF DOOR CONTOL MODULES AS THE QUANTITY OF HOLD OPEN DEVICES.

FIBER LINE ROUTED THROUGH

STEAM TUNNEL. ALL FIBER SHALL

BE INSTALLED IN CONDUIT.

FA2.03

FA2.04

REFER TO CIVIL FOR NEW

UNDERGROUND FIBER LINE

TEXAS REGISTERED ENGINEERING FIRM F-10573

801 TRAVIS, SUITE 2000

HOUSTON, TX 77002

PHONE: 713-237-9800

FAX: 713-237-9801

CHECKED BY

PROJECT NUMBER

SHEET DATE

DRAWN BY

F il e

N a m e

D a te /T im e

SHEET NUMBER

SHEET NAME

C

D M

S \R e v it

P ro je c ts

\A U

L F ir e A la rm

U p g ra d e s

R E m il y .H e n ry A

B N

V .r v t

/9

/2

:1

:0

A

M

FA1.00

09/09/24

LEH

KMKR

FIRE ALARM SITE

PLAN

A U

L F ir e

A la rm U p g ra d e s

H e a lt h a n d H u m a n S e rv ic e s

W th

S t

A u s ti n

T X

762401161.00

1/4" = 1'-0"1

FIRE ALARM SITE PLAN

N

4'0 8' 16'

1/8" = 1'-0"

N

PLAN TRUE

N o

D e s c ri p ti o n

D a te

IS

S

U E

F O

R P

E R

M

IT

/0

/2

KEYED NOTES

1 STEAM TUNNEL ENTRANCE LOCATED OUTSIDE OF BUILDING. CONTRACTOR TO

PROVIDE CONDUIT AND FIBER PENETRATION FROM FACU TO OUTSIDE BUILDING INTO

STEAM TUNNEL.

2 EXISTING FIBER LINE TO BE REUSED FOR BUILDING 732 INTEGRATION TO SECURITY

BUILDING. CONTRACTOR TO CONFIRM ROUTE AND EXISTING DARK FIBER PRIOR TO

BID AND CONSTRUCTION.

3 EXISTING SECURITY BUILDING. CONTRACTOR TO PENETRATE INTO BUILDING AND

CONNECT FIBER LINE INTO EXISTING FIRE ALARM SYSTEM FOR REPORTING.

CONTRACTOR IS RESPONSIBLE FOR ALL INTERCONNECTIONS AND

DEVICES/ACCESSORIES REQUIRED FOR THAT INTERCONNECTION. COORDINATE ANY

REQUIRED SHUTDOWN WITH FACILITY PRIOR TO WORK.

P

P P

FACU

P

P

Room

Room

Room

Room

Room

Room

Room

STAIRS

S101

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

STAIRS

S101

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

1. THE EXISTING FIRE ALARM SYSTEM IS TO BE DEMOLISHED. QUANTITIES AND TYPES OF DEVICES ARE

ESTIMATED. CONTRACTOR TO CONDUCT OWN SITE WALK TO VERIFY QUANTITIES.

2. SURFACES TO BE REPAIRED AS FOLLOWS

A. DRY WALL: ANY DAMAGE TO DRYWALL SHALL BE REPAIRED AND REPAINTED TO MATCH EXISTING.

B. CEILING TILES: CEILING TILES TO BE REPLACED. NEW CEILING TILES TO MATCH EXISTING.

C. BLOCK WALL: WHERE EXISTING WALL MOUNTED DEVICES ARE REMOVED, PROVIDE STAINLESS

STEEL PLATE.

3. ALL WIRING IS TO BE REMOVED.

FIRE ALARM DEMO SHEET NOTES

TEXAS REGISTERED ENGINEERING FIRM F-10573

801 TRAVIS, SUITE 2000

HOUSTON, TX 77002

PHONE: 713-237-9800

FAX: 713-237-9801

CHECKED BY

PROJECT NUMBER

SHEET DATE

DRAWN BY

F il e

N a m e

D a te /T im e

SHEET NUMBER

SHEET NAME

C

D M

S \R e v it

P ro je c ts

\A U

L F ir e A la rm

U p g ra d e s

R E m il y .H e n ry A

B N

V .r v t

/9

/2

:1

:0

A

M

FA2.01

09/09/24

LEH

KMKR

FIRE ALARM DEMO

PLAN BUILDING 533

A U

L F ir e

A la rm U p g ra d e s

H e a lt h a n d H u m a n S e rv ic e s

W th

S t

A u s ti n

T X

762401161.00

1/8" = 1'-0"1

FIRE ALARM BUILDING 533 - LEVEL 1 - DEMO PLAN

N

4'0 8' 16'

1/8" = 1'-0"

N

PLAN TRUE

1/8" = 1'-0"2

FIRE ALARM BUILDING 533 - LEVEL 2 - DEMO PLAN

N o

D e s c ri p ti o n

D a te

IS

S

U E

F O

R P

E R

M

IT

/0

/2

P

A N

N

P

P

P

P

P

P

P

P

P

15 15

P

P

F A

C U

ANN

STORAGE

STORAGE

1078 STORAGE

RISER

STORAGE

STORAGE

STORAGE

STORAGE

STORAGE

STORAGE

Room

STORAGE

MECHANICAL ROOM

Room

STORAGE

STORAGE

OFFICE

OFFICE

STORAGE

STORAGE

STORAGE

MECHANICAL

RR

CUSTODIAL

DAY ROOM

MECHANICAL ROOM

OFFICE

CONFERENCE

RR

OFFICE

FAMILY ROOM

CONFERENCE

OFFICE

STORAGE

STORAGE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

RR

STORAGE

MECH

NURSES OFFICE

E117

SLEEPING ROOM

E119

SLEEPING ROOM

E116

SLEEPING ROOM

E114

LAUNDRY

E113

BATHROOM

E109

OFFICE

E107

SLEEPING ROOM

E105

SLEEPING ROOM

E103

SLEEPING ROOM

E101

SLEEPING ROOM

E104

SLEEPING ROOM

E102DAY ROOM

E106

DAY ROOM

E115

OFFICE

E112

MEDS

E108

DINING ROOM

DINING ROOM

OFFICE

TEST KITCHEN

RR

RR

KITCHEN

OFFICE

Room

ELEC

Room

Room

SLEEPING ROOM

D102

SLEEPING ROOM

D104

SLEEPING ROOM

D101

SLEEPING ROOM

D103

SLEEPING ROOM

D105

OFFICE

D107

BATHROOM

D109

Room

D108

Room

D112

STORAGE

D110

RISER

D110A

Room

D113

SLEEPING ROOM

D114

SLEEPING ROOM

D116

SLEEPING ROOM

D119

SLEEPING ROOM

D117 Room

D115

RISER

D122

STORAGE

D120

BREAK ROOM

RR

D121

Room

MECH

RESTROOM

STORAGE

SLEEPING ROOM

SLEEPING ROOM

SLEEPING ROOM

DAY ROOM

OFFICE

OFFICE

108 OFFICE

RESTROOM

LAUNDRY

DAY ROOM

SLEEPING ROOM

SLEEPING ROOM

SLEEPING ROOM

NURSES OFFICE

1. THE EXISTING FIRE ALARM SYSTEM IS TO BE DEMOLISHED. QUANTITIES AND TYPES OF DEVICES ARE

ESTIMATED. CONTRACTOR TO CONDUCT OWN SITE WALK TO VERIFY QUANTITIES.

2. SURFACES TO BE REPAIRED AS FOLLOWS

A. DRY WALL: ANY DAMAGE TO DRYWALL SHALL BE REPAIRED AND REPAINTED TO MATCH EXISTING.

B. CEILING TILES: CEILING TILES TO BE REPLACED. NEW CEILING TILES TO MATCH EXISTING.

C. BLOCK WALL: WHERE EXISTING WALL MOUNTED DEVICES ARE REMOVED, PROVIDE STAINLESS

STEEL PLATE.

3. ALL WIRING IS TO BE REMOVED.

FIRE ALARM DEMO SHEET NOTES

TEXAS REGISTERED ENGINEERING FIRM F-10573

801 TRAVIS, SUITE 2000

HOUSTON, TX 77002

PHONE: 713-237-9800

FAX: 713-237-9801

CHECKED BY

PROJECT NUMBER

SHEET DATE

DRAWN BY

F il e

N a m e

D a te /T im e

SHEET NUMBER

SHEET NAME

C

D M

S \R e v it

P ro je c ts

\A U

L F ir e A la rm

U p g ra d e s

R E m il y .H e n ry A

B N

V .r v t

/9

/2

:1

:1

A

M

FA2.02

09/09/24

LEH

KMKR

FIRE ALARM DEMO

PLAN BUILDING 732

A U

L F ir e

A la rm U p g ra d e s

H e a lt h a n d H u m a n S e rv ic e s

W th

S t

A u s ti n

T X

762401161.00

N

0 8' 16' 24'

3/32" = 1'-0" N

PLAN TRUE

3/32" = 1'-0"1

FIRE ALARM BUILDING 732 - DEMO PLAN

N o

D e s c ri p ti o n

D a te

IS

S

U E

F O

R P

E R

M

IT

/0

/2

P

P

P

15 15

75 75

FACU

P

P

75 75 75

30 15

15 15

15 30

15 15

NAC

P

DACT

Room

Room

STAIRS

S101

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

DOC

Room

Room

Room

Room

STAIRS

S101

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

1. REFER TO FA0.01 FOR LEGEND, ABBREVIATIONS, AND NOTES

2. REQUIRED CANDELA RATINGS OF STROBES DEPEND ON FINAL TILE INSTALLATION LOCATION IN SOME ROOMS. CONTRACTOR IS RESPONSIBLE FOR ADJUST THE CANDELA RATING TO SERVE THE FINAL INSTALLATION LOCATION (E.G., A 30-CD CEILING STROBE THAT ENDS UP 16-FT FROM A WALL SHOULD

BE INCREASED TO THE NEXT CANDELA RATING IN ACCORDANCE WITH NFPA 72).

3. ALL SMOKE DETECTION DEVICES SHALL BE COMBINATION SMOKE AND CARBON MONOXIDE

DETECTORS.

4. ALL SURFACE MOUNTED CONDUIT SHALL BE OFFSET FROM DEVICE SO THAT IT IS ABUTTED AGAINST THE WALL. CONTRACTOR TO PROVIDE SECURING BRACKETS TO THE WALL SO THAT IT CANNOT BE GRIPPED FULLY AROUND THE CONDUIT. SECURING BRACKETS SHALL BE 2 HOLE TYPE AND SHALL NOT

HAVE EXPOSED SCREWS.

5. ALL EXPOSED CONDUIT SHALL BE PAINTED TO MATCH THE SURFACE IT IS MOUNTED TO. IN AREAS WITH MULTIPLE COLORS, THE CONDUIT SHALL BE PAINTED TO MATCH EACH COLOR SURFACE IT IS

MOUNTED TO.

FIRE ALARM SHEET NOTES

TEXAS REGISTERED ENGINEERING FIRM F-10573

801 TRAVIS, SUITE 2000

HOUSTON, TX 77002

PHONE: 713-237-9800

FAX: 713-237-9801

CHECKED BY

PROJECT NUMBER

SHEET DATE

DRAWN BY

F il e

N a m e

D a te /T im e

SHEET NUMBER

SHEET NAME

C

D M

S \R e v it

P ro je c ts

\A U

L F ir e A la rm

U p g ra d e s

R E m il y .H e n ry A

B N

V .r v t

/9

/2

:1

:1

A

M

FA2.03

09/09/24

LEH

KMKR

FIRE ALARM FLOOR

PLAN BUILDING 533

A U

L F ir e

A la rm U p g ra d e s

H e a lt h a n d H u m a n S e rv ic e s

W th

S t

A u s ti n

T X

762401161.00

KEYED NOTES

1 OFFICE IS INTENDED FOR SINGLE PERSON OCCUPANCY. NO STROBE REQUIRED.

2 FURNISH AND INSTALL SMOKE DETECTOR ABOVE FIRE ALARM CONTROL UNIT.

3 FURNISH AND INSTALL DUCT SMOKE DETECTOR IN THE RETURN OF MECHANICAL

EQUIPMENT 2,000 CFM AND LARGER. CONTRACTOR TO CONFIRM FINAL COUNT OF

DEVICES IN THIS AREA.

N

4'0 8' 16'

1/8" = 1'-0"

PLAN TRUE

1/8" = 1'-0"1

FIRE ALARM BUILDING 533 - LEVEL 1 - FIRE ALARM PLAN

1/8" = 1'-0"2

FIRE ALARM BUILDING 533 - LEVEL 2 - FIRE ALARM PLAN N

N o

D e s c ri p ti o n

D a te

IS

S

U E

F O

R P

E R

M

IT

/0

/2

P

P

P

177 177

15 15

P

177177177

15 15

120120

120 120

120120120

P

P

P

P

30 75

P

FACU

CM CM

CM

CM

CM

CM

CM

177 177

15 15

P

MM

MM

MM

MM

MM

MM

MM

P

P

P

P

151515 15 15 15

P P P

CM

MM

MM

CM CM CM CMCM CM CM

CMCM

CMCM

CM

CM

CMCM

CM

CM CM CM

CMCM

CM CM CM

CM

CM

CM

ANN

ANN

ANN

A N

N

ANN

177 177 177

177177

177 177177 177177177

177 177

177 177 177

177 177

177177177

15 15

P

MM MM

CM

P

MM

MM

MM

CM

CM

CM

PP P P

PP

5 5

CO

DACT

1 1 1 11

1 1

1 1 1

1 1 1

SLEEPING ROOM

D102

SLEEPING ROOM

D104

DAY ROOM

D106

Room

D108

Room

D112

BATHROOM

D109

OFFICE

D107

SLEEPING ROOM

D105

SLEEPING ROOM

D103

SLEEPING ROOM

D101

SLEEPING ROOM

D114

SLEEPING ROOM

D116

SLEEPING ROOM

D119

Room

D115

SLEEPING ROOM

D117

STORAGE

D120

RISER

D122

RR

D121

BREAK ROOM

Room

MECH

RESTROOM

STORAGE

SLEEPING ROOM

DAY ROOM

SLEEPING ROOM

SLEEPING ROOM

LAUNDRY

OFFICE

OFFICE

OFFICE

RESTROOM

NURSES OFFICE

SLEEPING ROOM

SLEEPING ROOM

SLEEPING ROOM

RISER

RISER

D110A

STORAGE

D110

DINING ROOM

DINING ROOM

OFFICE

TEST KITCHEN

STORAGE

OFFICE

Room

ELEC

Room

KITCHEN

RR

RR

STORAGE

STORAGE

STORAGE

STORAGE

RISER

STORAGE

STORAGE

MECHANICAL ROOM

CONFERENCE

FAMILY ROOM

STORAGE

STORAGE

1063 OFFICE

OFFICE

RR

CONFERENCE

Room

OFFICE

STORAGE

MECHANICAL

STORAGE

STORAGE

RR

CUSTODIAL

DAY ROOM

OFFICE

OFFICE

STORAGE

STORAGE

OFFICE

OFFICE

MECH

1001OFFICE

OFFICE

OFFICE

RR

STORAGE

DAY ROOM

E115

NURSES OFFICE

E117

OFFICE

E112

MEDS

E108

BATHROOM

E109

LAUNDRY

E113

SLEEPING ROOM

E114

SLEEPING ROOM

E116

SLEEPING ROOM

E119

OFFICE

E107

SLEEPING ROOM

E105

SLEEPING ROOM

E103

SLEEPING ROOM

E101

SLEEPING ROOM

E104

SLEEPING ROOM

E102

RISER

4 4 4

10 10

101010 101010101010

10 10

10 10

10101010

Room

D113

DAY ROOM

CO

CO

DAY ROOM

E106

STORAGE

STORAGE

STORAGE

STORAGE

MECHANICAL ROOM

Room

Room

CO

CO

CO

12 12

DOC

1. REFER TO FA0.01 FOR LEGEND, ABBREVIATIONS, AND NOTES

2. REQUIRED CANDELA RATINGS OF STROBES DEPEND ON FINAL TILE INSTALLATION LOCATION IN SOME ROOMS. CONTRACTOR IS RESPONSIBLE FOR ADJUST THE CANDELA RATING TO SERVE THE FINAL INSTALLATION LOCATION (E.G., A 30-CD CEILING STROBE THAT ENDS UP 16-FT FROM A WALL SHOULD

BE INCREASED TO THE NEXT CANDELA RATING IN ACCORDANCE WITH NFPA 72).

3. TIE-IN ALL EXISTING DOOR HOLDERS TO NEW FIRE ALARM SYSTEM VIA CONTROL MODULES.

4. PROVIDE HEAT DETECTORS IN LIEU OF SMOKE DETECTORS IN KITCHENS AND LAUNDRIES.

5. ALL SMOKE DETECTION DEVICES SHALL BE COMBINATION SMOKE AND CARBON MONOXIDE

DETECTORS.

6. ALL SURFACE MOUNTED CONDUIT SHALL BE OFFSET FROM DEVICE SO THAT IT IS ABUTTED AGAINST THE WALL. CONTRACTOR TO PROVIDE SECURING BRACKETS TO THE WALL SO THAT IT CANNOT BE GRIPPED FULLY AROUND THE CONDUIT. SECURING BRACKETS SHALL BE 2 HOLE TYPE AND SHALL NOT

HAVE EXPOSED SCREWS.

7. ALL EXPOSED CONDUIT SHALL BE PAINTED TO MATCH THE SURFACE IT IS MOUNTED TO. IN AREAS WITH MULTIPLE COLORS, THE CONDUIT SHALL BE PAINTED TO MATCH EACH COLOR SURFACE IT IS

MOUNTED TO.

FIRE ALARM SHEET NOTES

TEXAS REGISTERED ENGINEERING FIRM F-10573

801 TRAVIS, SUITE 2000

HOUSTON, TX 77002

PHONE: 713-237-9800

FAX: 713-237-9801

CHECKED BY

PROJECT NUMBER

SHEET DATE

DRAWN BY

F il e

N a m e

D a te /T im e

SHEET NUMBER

SHEET NAME

C

D M

S \R e v it

P ro je c ts

\A U

L F ir e A la rm

U p g ra d e s

R E m il y .H e n ry A

B N

V .r v t

/9

/2

:1

:1

A

M

FA2.04

09/09/24

LEH

KMKR

FIRE ALARM FLOOR

PLAN BUILDING 732

A U

L F ir e

A la rm U p g ra d e s

H e a lt h a n d H u m a n S e rv ic e s

W th

S t

A u s ti n

T X

762401161.00

KEYED NOTES

1 FURNISH AND INSTALL CONTROL MODULE TO RELEASE DOOR HOLD-OPEN DEVICE

UPON ANY FIRE ALARM ACTIVATION.

2 FURNISH AND INSTALL CARBON MONOXIDE DETECTOR TO SERVE KITCHEN

EQUIPMENT. CARBON MONOXIDE DETECTOR SHALL BE AN SLC DEVICE ON THE FIRE

ALARM SYSTEM, NOT A 120V DEVICE.

3 OFFICE IS INTENDED FOR SINGLE PERSON OCCUPANCY. NO STROBE REQUIRED.

4 STORAGE ROOM IS LESS THAN 100 SQFT AND DOES NOT REQUIRE A STROBE.

5 FURNISH AND INSTALL 520-HZ 177 CD NOTIFICATION DEVICE IN SLEEPING

OCCUPANCY.

6 FURNISH AND INSTALL 120V COMBINATION SMOKE AND CARBON MONOXIDE ALARM

FOR LOCAL DETECTION AND NOTIFICATION. DEVICE SHALL BE HARDWIRED WITH

BATTERY BACKUP. SOUNDER BASE MUST BE CAPABLE OF SUPPLYING 520-HZ

NOTIFICATION.

7 FURNISH AND INSTALL SMOKE DETECTOR ABOVE FIRE ALARM CONTROL UNIT.

8 FURNISH AND INSTALL MONITOR MODULES FOR SPRINKLER TAMPER AND FLOW

SWITCHES.

9 FURNISH AND INSTALL MONITOR MODULE TIE IN TO KITCHEN ANSUL SYSTM.

10 FURNISH AND INSTALL 120V 177 CD DEDICATED STROBE DEVICE FOR NOTIFICATION

OF SMOKE ALARM ACTIVATION.

11 FURNISH AND INSTALL DUCT SMOKE DETECTOR IN THE RETURN OF MECHANICAL

EQUIPMENT 2,000 CFM AND LARGER. CONTRACTOR TO CONFIRM FINAL COUNT OF

DEVICES IN THIS AREA.

12 FURNISH AND INSTALL MONITOR MODULE ON EXISTING POST INDICATOR VALVE (PIV).

13 FURNISH AND INSTALL MONITOR MODULE TO MONITOR WHEN DOMESTIC WATER

PUMP IS RUNNING ON GENERATOR POWER.

14 FURNISH AND INSTALL CONTROL MODULE FOR EXISTING SMOKE DAMPER.

15 EXTERIOR SPRINKLER WATER FLOW ALARM.

N

0 8' 16' 24'

3/32" = 1'-0"

PLAN TRUE

3/32" = 1'-0"1

FIRE ALARM BUILDING 732 - FIRE ALARM PLAN N

N o

D e s c ri p ti o n

D a te

IS

S

U E

F O

R P

E R

M

IT

/0

/2

30 30

PENTHOUSE

P1

PENTHOUSE

P2

PENTHOUSE

P3 PENTHOUSE

P4

CO CO

CO

CO

1 1

1 1 1 1

TEXAS REGISTERED ENGINEERING FIRM F-10573

801 TRAVIS, SUITE 2000

HOUSTON, TX 77002

PHONE: 713-237-9800

FAX: 713-237-9801

CHECKED BY

PROJECT NUMBER

SHEET DATE

DRAWN BY

F il e

N a m e

D a te /T im e

SHEET NUMBER

SHEET NAME

C

D M

S \R e v it

P ro je c ts

\A U

L F ir e A la rm

U p g ra d e s

R E m il y .H e n ry A

B N

V .r v t

/9

/2

:1

:1

A

M

FA2.05

09/09/24

LEH

KMKR

FIRE ALARM

PENTHOUSE PLAN

BUILDING 732

A U

L F ir e

A la rm U p g ra d e s

H e a lt h a n d H u m a n S e rv ic e s

W th

S t

A u s ti n

T X

762401161.00

3/32" = 1'-0"1

FIRE ALARM PENTHOUSE FLOOR PLAN

N o

D e s c ri p ti o n

D a te

IS

S

U E

F O

R P

E R

M

IT

/0

/2

KEYED NOTES

1 FURNISH AND INSTALL DUCT SMOKE DETECTOR IN THE RETURN OF MECHANICAL

EQUIPMENT 2,000 CFM AND LARGER. CONTRACTOR TO CONFIRM FINAL COUNT OF

DEVICES IN THIS AREA.

N

0 8' 16' 24'

3/32" = 1'-0"

N

PLAN TRUE

T-BAR

CLIP

DROP CEILING TILE

4" X 4" SQUARE

CONDUIT BOX

ALL STROBES AND HORN/STROBES SHALL BE INSTALLED IN

CEILING TILES TO THE MAXIMUM EXTENT PRACTICAL. THE

INSTALLING CONTRACTOR SHALL PROVIDE THE NECESSARY

MOUNTING HARDWARE TO ACHIEVE THIS PURPOSE.

T-BAR

DROP TILE

CEILING

GRID

MOUNTING BASE

MINIMUM 3/4" CONDUIT

4" X 4" X 1-1/2"

JUNCTION

BOX

4" X 4" X 1-1/2"

OCTAGONAL

BOX

FLEX CONDUIT,

MAXIMUM

6'-0" LONG

SUSPENDED

CEILING SYSTEM

DETECTOR

MINIMUM 3/4" CONDUIT

TEE BAR BOX

HANGER

NOTE: MEASUREMENTS SHOWN ARE TO THE

CLOSEST POINT ON THE DETECTOR.

ACCEPTED

HERE

NEVER HERE

WALL MOUNTED

SMOKE/HEAT

DETECTOR

CEILING

SIDE WALL

FINISHED WALL

PULL DOWN

FIRE ALARM

MAGNETIC

DOOR HOLDER

FIREFIRE

MANUAL PULL

STATION

FINISHED FLOOR

AUDIO/VISUAL &

VISUAL-ONLY

DEVICES

SLEEPING AREAS:

≥24-INCHES

SYNCHRONIZE MORE THAN TWO APPLIANCES IN

ANY FIELD OF VIEW. NFPA 72 2013 EDITION (§

18.5.5.4.2)

80" MIN

96" MAX

48" MAX (ADA)

42" MIN/54" MAX (NFPA)

MAX

5-FT

DOOR

WIDTH LESS

3"

6"

CEILING MOUNTED

SMOKE/HEAT DETECTOR

HVAC SUPPLY

DIFFUSER

MIN

3-FT 4"

4"

MAX

12"

FLOOR

LCD ANNUNCIATOR

FIRE ALARM

CONTROL UNIT

CEILING

48"

MANUAL PULL STATION

A C

TIV

A

TE

A U D

IB

LE

N

O

TIF

IC

A

TIO

N A

PP

LI

A N C

ES

AUTOMATIC SPRINKLER WATER FLOW SWITCH

AUTOMATIC SPRINKLER TAMPER SWITCH

FACU CIRCUIT FAULT (OPEN, GROUND, SHORT)

OTHER TROUBLE CONDITION

PRIMARY AC POWER LOSS

FIRE ALARM INPUT A

C

TIV

A

TE

V

IS

U A L

N O

TIF

IC

A

TIO

N A

PP

LI

A N C

ES

A

LA

R M

C O N D

IT

IO

N A

T F A C U

SU

P E R

VIS

O R Y C

O N D

IT

IO

N A

T F A C U

TR

O U B

LE

C O N D

IT

IO

N A

T F A C U

DUCT SMOKE DETECTOR

TR

A N

SM

IT

S

IG

N A L

TO

R

E M

O

TE M

O N

IT

O R

IN

G S

TA

TIO

N

SH

U

TD

O W

N A

IR

H

A N D

LE

R

MONITOR MODULE, KITCHEN ANSUL SYSTEM

AREA SMOKE DETECTOR

TR

A N

SM

IT

S

IG

N A L

TO

A

N N U N C

IA

TO

R P

A N

EL

SLEEPING UNIT SMOKE ALARM

A C

TIV

A

TE

H Z S

O U N D

ER

B A S E 1

C

D L

O C A L

STR

O B E

R

ELE

A S E F

IR

E D

O O R

AREA CARBON MONOXIDE DETECTOR

EXTE

R

IO

R W

A

TE

R F

LO

W

H O R N

MONITOR MODULE, POST INDICATOR VALVE

MONITOR MODULE, DOMESTIC WATER PUMP GENERATOR

FACU NAC

LEVEL 1

CD CD

P MM CM

CO

FACU NAC

LEVEL 1

LEVEL 2

CD CD

P

NAC

CD CD

P

INLET TUBE HOLES FACE

UPSTREAM OF AIRFLOW

DO NOT INSERT

RUBBER PLUG

RETURN TUBE SLANT

CUT FACE ORIENTED

DOWNSTREAM OF AIRFLOW

AIRFLOW

DIRECTION

TUBE SUPPORT HOLE THROUGH OPPOSITE SIDE

ONLY FOR DUCTS MORE THAN 3FT (0.9 M) WIDE

TEXAS REGISTERED ENGINEERING FIRM F-10573

801 TRAVIS, SUITE 2000

HOUSTON, TX 77002

PHONE: 713-237-9800

FAX: 713-237-9801

CHECKED BY

PROJECT NUMBER

SHEET DATE

DRAWN BY

F il e

N a m e

D a te /T im e

SHEET NUMBER

SHEET NAME

C

D M

S \R e v it

P ro je c ts

\A U

L F ir e A la rm

U p g ra d e s

R E m il y .H e n ry A

B N

V .r v t

/9

/2

:1

:1

A

M

FA6.01

09/09/24

LEH

KMKR

FIRE ALARM DETAILS

A U

L F ir e

A la rm U p g ra d e s

H e a lt h a n d H u m a n S e rv ic e s

W th

S t

A u s ti n

T X

762401161.00

NOT TO SCALE1

CEILING STROBE/HORN MOUNTING

NOT TO SCALE2

CEILING DETECTOR MOUNTING

NOT TO SCALE3

FIRE ALARM INSTALLATION

NOT TO SCALE4

FACU

NOT TO SCALE8

FIRE ALARM INPUT/OUTPUT MATRIX

N o

D e s c ri p ti o n

D a te

IS

S

U E

F O

R P

E R

M

IT

/0

/2

NOT TO SCALE7

BUILDING 732 FIRE ALARM CONCEPTUAL RISER

NOT TO SCALE6

BUILDING 533 FIRE ALARM CONCEPTUAL RISER

N.T.S.5

DUCT SMOKE DETECTOR DETAIL

Sheets
000 - AUL FIRE ALARM UPGRADES DRAWING PACKAGE
Attachment H Cover Sheet.pdf
HHS0007879 Attachment H-1.pdf
1) COVER SHEET
1) COVER SHEET
Blank Page
2) TOC-TEC
2) TOC-TEC
Blank Page
3) 010000 Special Conditions
3) 010000 Special Conditions
Blank Page
4) 013000 Submittals, shop drawings
5) 013000A-Contract Progress Schedule
6) 013000B-ShopDwg Log
7) 014000 Reference Standards Codes 2017
7) 014000 Reference Standards Codes 2017
Blank Page
8) 015000 Construction Facilities
8) 015000 Construction Facilities
Blank Page
9) 017000 Closeout
9) 017000 Closeout
Blank Page
10) 028400-PCB Remediation
10) 028400-PCB Remediation
Blank Page
11) 033000 Cast-In-Place Concrete
11) 033000 Cast-In-Place Concrete
Blank Page
12) 260513-MV Cables
12) 260513-MV Cables
Blank Page
13) 260519-LV Cables
13) 260519-LV Cables
Blank Page
14) 260526-Grounding & Bonding
15) 260529-Hangers & Supports
16) 260533-Raceways
16) 260533-Raceways
Blank Page
17) 260553-Identification
17) 260553-Identification
Blank Page
18) 260573-ArcFlash-Short-Coordination
19) 261200-MV Transformers
20) 262413-LV Switchboards
20) 262413-LV Switchboards
Blank Page
21) 262416-LV Panelboards
21) 262416-LV Panelboards
Blank Page
22) 263213-ENGINE GENERATORS
22) 263213-ENGINE GENERATORS
Blank Page
23) 263600-TRANSFER SWITCHES
23) 263600-TRANSFER SWITCHES
Blank Page
24) 312000-Earthwork
25) 323113-CHAIN LINK FENCES AND GATES
25) 323113-CHAIN LINK FENCES AND GATES
Blank Page