This is a Limited Hazardous Building Materials Survey Report prepared by Big East Environmental, LLC for the Sharon Housing Trust, Inc., covering three residential properties located at 91, 93, and 95 North Main Street in Sharon, Connecticut. The inspection was conducted on October 27, 2023, and encompasses three two-family residential buildings totaling 5,679 square feet of living area situated on 0.72 acres. The survey scope included comprehensive assessment of asbestos-containing materials, lead-based paint, mold, polychlorinated biphenyls (PCBs), urea formaldehyde foam insulation (UFFI), mercury-containing components, radon in air, lead in drinking water, and lead in soil. All testing was performed by licensed and certified environmental professionals in accordance with federal NEHSAP, AHERA, EPA, and Connecticut Department of Public Health guidelines.
The survey identified three homogenous materials containing asbestos (two locations with 2% chrysotile and one with vermiculite assumed asbestos-containing). Lead-based paint was confirmed in all three buildings, with several surfaces in deteriorated condition. Lead in soil exceeded the 400 ppm action level at Building #3 (95 North Main Street) on sides C (477 ppm) and D (1,570 ppm). Lead in drinking water testing was initiated but results were incomplete in the provided document. Visual inspections identified multiple suspect asbestos-containing materials (roof shingles, tar, vapor barriers, vinyl flooring, flue cement, and floor tile adhesives) that are assumed to contain asbestos pending laboratory confirmation. Radon testing was conducted with results referenced in attached laboratory reports. No children under six years old were documented as occupying the residential units at the time of inspection.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The Sharon Housing Trust, Inc.
LIMITED HAZMAT SURVEY
REPORT
91-95 North Main Street Sharon, CT
203.354.4955 | contact@bigeastlabs.com | www.bigeastlabs.com
Big East Environmental, 57 Chestnut Street, Unit 10 Norwalk, CT 06854
TABLE OF CONTENTS
1.0 Introduction
2.0 Scope of Work
2.1 Methods
3.0 Hazardous Building Materials Survey
3.1 Asbestos Survey
3.2 Lead Based Paint Survey
3.3 Mold Survey
3.4 PCB Survey
3.5 UFFI Survey
3.6 Mercury Survey
3.7 Radon Survey
3.8 Lead in Drinking Water
3.9 Lead in Soil
4.0 Applicable Regulations
5.0 Conclusions
6.0 Limitations
Attachment 1 Site Drawings
APPENDICES
Appendix A: Asbestos Laboratory Analysis Report Appendix B: XRF Data Sheets Appendix C: Radon Laboratory Analysis Reports Appendix D: Lead in Drinking Water Laboratory Analysis Report Appendix E: Lead in Soil Laboratory Analysis Report Appendix F: Licensing and Certifications
SUBJECT SITE: 91-95 North Main Street Sharon, CT
CLIENT: The Sharon Housing Trust, Inc.
PO Box 1168
Sharon, CT 06069
INSPECTION DATE: October 27, 2023
BIG EAST PROJECT #: 23622.01
mailto:contact@bigeastlabs.com http://www.bigeastlabs.com/
1.0 INTRODUCTION
Big East Environmental, LLC performed a limited Hazardous Building Material Survey at the Subject Site located at 91-95 North Main Street, Sharon, CT. The site consists of three, two-family residential buildings situated on 0.72-acres of land. All of the residential units were occupied at the time of the inspections.
SUBJECT SITE DETAILS
Building 1 Address: 91 North Main Street, Sharon, CT Building Use: Two-family Residential Stories: Two Size: 1,764 square feet (living area) Year Built: 1900/ 1996 (actual/ effective) Construction: Sub-slab basement/ Wood Frame Construction/ Vinyl Siding/ Drywall
Interior Walls/ Pitched Asphalt Shingle Roofing/ Oil Heat
Building 2 Address: 93 North Main Street, Sharon, CT Building Use: Two-family Residential Stories: Two Size: 2,459 square feet (living area) Year Built: 1971/ 2000 (actual/ effective) Construction: Sub-slab basement/ Wood Frame Construction/ Vinyl Siding/ Drywall
Interior Walls/ Pitched Asphalt Shingle Roofing/ Oil Heat
Building 3 Address: 95 North Main Street, Sharon, CT Building Use: Two-family Residential Stories: Two Size: 1,456 square feet (living area) Year Built: 1971/ 2000 (actual/ effective) Construction: Sub-slab basement/ Wood Frame Construction/ Vinyl Siding/ Drywall
Interior Walls/ Pitched Asphalt Shingle Roofing/ Oil Heat
2.0 Scope of Work
▪ Limited non-destructive asbestos inspection in residential units
▪ Lead-based paint (LBP) survey in residential units and common areas
▪ Presumptive PCB survey (no sample collection or testing)
▪ Visual mold inspection in all units
▪ Visual inspection for urea formaldehyde foam insulation (UFFI) in all residential units
▪ Visual assessment for suspect mercury containing components & equipment in residential units.
▪ Radon in air survey
▪ Lead in soil survey
▪ Lead in drinking water survey
2.1 METHODS
ASBESTOS
Big East Environmental, LLC Connecticut licensed Asbestos Inspectors Eric Gelhaus and Steve DiNapoli performed a limited non-destructive, asbestos survey and collected bulk samples of suspect asbestos containing building materials (SACBM) throughout the residential units of the Subject Buildings. Samples were collected in accordance with federal NEHSAP (national emission standard for hazardous air pollutants) and AHERA (asbestos hazard emergency response act) guidelines for the collection of asbestos bulk samples. Asbestos samples were analyzed at SanAir Technology Laboratories, Inc. in accordance with Polarized Light Microscopy (PLM) EPA 600 methodologies. Bulk samples were collected from friable and damaged non-friable suspect asbestos containing building materials. A visual inspection for suspect-ACM was conducted throughout accessible areas of the common and mechanical rooms.
LEAD SURVEY
The lead-based paint survey was carried out by US EPA accredited and CT licensed Lead Inspector/ Risk Assessor Eduardo Guiza, with a Viken pb200i XRF instrument with radioactive source in accordance with Connecticut Department of Public Health (CT DPH) and US Environmental Protection Agency Housing and Urban Development (HUD) chapter 7 guidelines throughout the residential units and accessible common areas.
Lead in soil was assessed via soil samples collected from drip-line areas and/ or bare soil in and around the Subject Site property by US EPA certified and CT licensed Lead Risk Assessor Eric Gelhaus.
Samples were collected by hand from the top ½-inch of soil in accordance with CT DPH and US EPA HUD guidelines.
Lead in drinking water was assessed via water samples collected from drinking sources within the residential units of the Subject Site buildings by US EPA certified and CT licensed Lead Risk Assessor Eric Gelhaus. Water samples were collected on a first-draw and flush sampling protocol in accordance with the US EPA lead and copper rule. Tenants were advised to not use or run water sources for a minimum of 6-8 hours prior to the collection of the water samples.
POLYCHLORINATED BIPHENYLS
The PCB survey was limited to a visual inspection of suspect PCB containing materials in the Subject Site buildings.
MOLD
American Council for Accredited Certification Council-Certified Microbial Consultant Steve DiNapoli, carried out the visual mold inspection throughout the residential and common areas of the Subject Site buildings. Areas of visual mold and/ or water damage or intrusion were noted on location tables.
UREA FORMALDEHYDE FOAM INSULATION
The UFFI survey was carried out via visual methods to identify any signs of or locations of urea-formaldehyde foam insulation throughout the residential units of the Subject Site buildings.
MERCURY CONTAINING COMPONENTS
The mercury containing components survey was carried out via visual methods to identify potential mercury containing components and equipment throughout the residential units of the Subject Site buildings.
RADON IN AIR SURVEY
Radon in air was assessed via the placement of charcoal canisters in the basements of the Subject Site buildings. Canisters were placed in the basements for a minimum of 48-hours, then collected and shipped directly to the laboratory for analysis. Steve DiNapoli, certified radon measurement specialist with the National Radon Safety Board (NRSB) conducted the testing. Radon samples were analyzed at Radon Testing Corporation of America (RTCA) of Elmsford, NY.
All laboratory analysis reports and chains of custody are attached.
3.0 HAZARDOUS BUILDING MATERIAL SURVEY
3.1 ASBESTOS SURVEY
A total three (3) homogenous materials of suspect-asbestos containing materials (SACM) were identified as asbestos containing through laboratory analysis.
TABLE I – SUSPECT ASBESTOS CONTAINING MATERIALS
The following tables represents sampled suspect asbestos containing building materials.
Building #1 – 91 North Main Street
ID DESCRIPTION LOCATION SF/LFT* % ASBESTOS CONDITION
DW Drywall Unit 1 – Walls & Ceilings - NONE DETECTED Good/ F
FS Stucco Exterior Foundation - NONE DETECTED Good/ F
JC Joint Compound Walls & Ceilings TBD 2% CHRYSOTILE Good/ F
PF
Vinyl Floor Tile
Unit 2 – Kitchen Pantry
- NONE DETECTED Good/ NF
Mastic - NONE DETECTED Good/ NF
WG Glazing Windows - NONE DETECTED Damaged/ NF
NF – Non-Friable F – Friable Bold Text indicates an Asbestos Containing Material
Building #2 – 93 North Main Street
ID DESCRIPTION LOCATION SF/LFT* % ASBESTOS CONDITION
BP Plaster Basement Stairwell - NONE DETECTED Good/ F
FS Stucco Exterior Foundation - NONE DETECTED Good/ F
P1 Plaster Skim Coat 2nd Fl Walls & Ceiling
- NONE DETECTED Good/ F
P2 Plaster Base Coat - NONE DETECTED Good/ F
DW Drywall Attic Level - NONE DETECTED Good/ F
WC Caulk Windows – Exterior - NONE DETECTED Good/ F
WG Glazing Windows – Exterior - NONE DETECTED Good/ F
NF – Non-Friable
Building #3 – 95 North Main Street
ID DESCRIPTION LOCATION SF/LFT* % ASBESTOS CONDITION
P1 Plaster Skim Coat Walls & Ceilings
- NONE DETECTED Good/ F
P2 Plaster Base Coat - NONE DETECTED Good/ F
BDW Drywall Basement Above Boiler - NONE DETECTED Good/ F
WG Glazing Windows 24 Units 2% CHRYSOTILE Damaged/ NF
FS Stucco Exterior Foundation - NONE DETECTED Damaged/ F
VF1 Vinyl Flooring 1st & 2nd Floor Bathrooms & Kitchen
- NONE DETECTED Damaged/ NF
VFA1 Mastic - NONE DETECTED Damaged/ NF
VF3 Vinyl Floor Unit 6 Bathroom
- NONE DETECTED Damaged/ NF
VFA3 Mastic - NONE DETECTED Damaged/ NF
- Vermiculite Attic 750 sf ASSUMED + Good/ F
NF – Non-Friable
TABLE II – VISUALLY IDENTIFIED SUSPECT ASBESTOS CONTAINING MATERIALS
The following tables represents Suspect ACM that were not tested but shall be assumed as asbestos containing materials until proven negative by laboratory analysis.
Building #3 – 95 North Main Street
LOCATION MATERIAL / DESCRIPTION CONDITION
Exterior
Roof shingles Good/ NF
Flat Roof Membrane Good/ NF
Tar – Flat Roof Good/ NF
Vapor Barrier Beneath Roof Shingles Good/ NF
Vapor Barrier Behind Siding Good/ NF
Basement Flue Cement Good/ F
Units 5 & 6 Vapor Barrier Beneath Hardwood Floors Good/ NF
LOCATION MATERIAL / DESCRIPTION CONDITION
Exterior
Roof Shingles Good/ NF
Vapor Barrier Beneath Roof Shingles Good/ NF
Tar at Chimney Flashing Good/ NF
Vapor Barrier Beneath Siding Good/ NF
Basement Flue Cement Good/ F
Unit 3
Vapor Barrier Under Hardwood Floors Good/ NF
Kitchen Vinyl Flooring – Red stone pattern Good/ NF
Kitchen Vinyl Floor Adhesive/ Mastic Good/ NF
Unit 3
Vinyl Flooring – 2nd Floor Bathroom Good/ NF
Wall Tile Adhesive – 2nd Floor Bathroom Good/ NF
Cove Base (grey) – 2nd Floor Bathroom Good/ NF
Building #1 – 91 North Main Street
LOCATION MATERIAL / DESCRIPTION CONDITION
Unit 1
Vapor Barrier Beneath Hardwood Floors Good/ NF
9x9 Floor Tile (white & brown) – Hall Closet Good/ NF
Vinyl Floor & Adhesive – Kitchen Good/ NF
12x12 Floor Tile – Bathroom Good/ NF
Bathroom Wall Tile Adhesive Good/ NF
Exterior
Vapor Barrier Beneath Siding Good/ NF
Shingles – Roof Good/ NF
Vapor Barrier Beneath Roof Shingles Good/ NF
Basement Flue Cement Good/ F
Unit 2 Vapor Barrier Beneath Hardwood Floor Good/ NF
3.2 LEAD BASED PAINT SURVEY
Eduardo Guiza, EPA & CT Lead Inspector/ Risk Assessor, performed the LBP survey in the residential units utilizing a Viken pb200i XRF analyzer. The lead-based paint survey typically tests representative surfaces for each room/ area that include: four walls, ceiling, baseboards & trims, door components, window components, and any miscellaneous items such as fireplaces, cabinets, radiators, etc. Each side of a room equivalent is assigned a letter: Side A, Side B, Side C, and Side D. The side of the dwelling that faces the street is assigned Side A. The remaining walls are then assigned letter designations via clockwise methodology. If a building component tests positive for lead-based paint, then all similar building components/ testing combinations shall be assumed to contain lead-based paint, provided that the components are of the same type, age, and appearance. In the event that a lead-positive component is also found to be in deteriorated condition, it shall be classified as a Lead-Paint Hazard.
Connecticut Department of Public Health and US Department of Housing and Urban Development have set 1.0 milligrams/square centimeter (mg/cm²) or above as the definition of lead-based paint (LBP). The total lead on the report is the reading of lead in all of the paint layers down to the substrate. A positive result (POS) is a confirmed reading at or above 1.0 mg/cm², a negative result (NEG) is a confirmed reading below 1.0 mg/cm².
LEAD BASED PAINT RESULTS
ROOM
DESCRIPTION
COMPONENT SIDE SUBSTRATE SURFACE TYPE CONDITION
Unit 2, Staircase Stair Riser C Wood Impact Deteriorated
Exterior
Window Casing B Wood - Intact
Window Sill & Casing
C Wood - Deteriorated
Unit 2, Living Room Wall A,C,D Drywall - Deteriorated
Door Face D Wood Impact/ Friction Intact
Unit 2, Kitchen
Wall A,B,C,D Drywall - Intact
Wall Crown Molding
A Wood - Intact
Ceiling - Drywall - Intact
Unit 2, Bathroom 1 Wall A,B,C,D Drywall - Intact
Ceiling - Drywall - Deteriorated
Unit 2, Bedroom 1 Wall B,C,D Drywall - Intact
Ceiling - Drywall - Intact
Unit 2, Office Wall A, B Drywall - Intact
Ceiling - Drywall - Intact
ROOM
DESCRIPTION
COMPONENT SIDE SUBSTRATE SURFACE TYPE CONDITION
Unit 93-3, Living Room
Window Sill D Wood Chewable Intact
Door Frame & Jamb
A Wood Friction/ Impact Deteriorated
Unit 93-3, Bedroom 1
Wall A, D Drywall - Intact
Window Sill, Casing, & Sash Interior
D Wood Friction/ Impact/ Chewable
Deteriorated
Unit 93-3, Exterior
Column A Wood - Intact
Window Sill D Metal - Intact
Window Sill B Metal - Intact
Building #3 – 95 North Main Street
ROOM
DESCRIPTION
COMPONENT SIDE SUBSTRATE SURFACE TYPE CONDITION
Unit 6, Living Room Window Casing A Wood - Intact
Wall Baseboard D Wood Impact Intact
Unit 6, Kitchen
Wall Baseboard A Wood Impact Intact
Wall A,D Drywall - Intact
Window Sill, Casing, & Sash Interior
D Wood Friction/ Impact/ Chewable
Deteriorated
Door Frame & Jamb
C Wood Friction/Impact Intact
Unit 6, Bedroom 1
Window Sill, Casing, Well- Trough
D Wood Friction/Impact/Ch ewable
Intact
Wall Baseboard B Wood Impact Intact
Door Face, Frame, & Jamb
B Wood Friction/Impact Intact
Unit 6, Bedroom 2
Window Sill, Casing, & Sash Interior
D Wood Friction/Impact/Ch ewable
Intact
Door Face B Wood Friction/Impact Intact
Exterior
Door Face C Wood Friction/Impact Intact
Window Sill & Casing
C Metal - Intact
Porch Floor - Wood Impact Deteriorated
Unit 5, Bedroom 1
Window Sill, Casing, Well- Trough
A Wood Friction/ Impact /Chewable
Deteriorated
Door Frame & Jamb
C Wood Friction/Impact Deteriorated
Wall Baseboard C Wood Impact Deteriorated
Unit 5 Bathroom 1 Door Jamb D Wood Friction/ Impact Deteriorated
ROOM
DESCRIPTION
COMPONENT SIDE SUBSTRATE SURFACE TYPE CONDITION
Window Sill, Casing, & Sash Interior
B Wood Friction /Impact/ Chewable
Deteriorated
Unit 5, Hall 1 Wall Baseboard B Wood Impact Intact
Unit 5, Living Room Window Sill & Casing
B Wood Friction/ Impact/ Chewable
Deteriorated
Note: Tables incorporate field corrections to XRF Data Please see appendices for full XRF data report.
Summary of Results Lead based paint has been identified in each of the Subject Site buildings. Several of the lead painted surfaces were identified as having paint that is in deteriorated condition. No children believed to be under the age of six were found to be living in any of the Subject Site residential units.
3.3 LEAD IN SOIL SURVEY
Soil samples were collected from drip-line and/ or bare section of soil throughout the Subject Property.
In each location, soil is collected from the top ½” of soil. Samples were collected into laboratory supplied containers, placed on ice, and shipped under chain-of-custody protocol to Phoenix Environmental Laboratories, Inc. of Manchester, CT. Samples were analyzed for total lead concentration.
Applicable Regulations
The US EPA and CT DPH have established Soil Hazard Standards for lead in soil at greater than or equal to 400 ppm for residence with occupied by a child/ children less than 6 years old and for projects funded with HUD lead hazard reduction funds.
Sampling Data
Building #1 - 91 North Main Street
SAMPLE ID LOCATION RESULTS (ppm) ACTION LEVEL
91A Bldg 91 – Side A 98.4 400
91B Bldg 91 – Side B 148 400
91C Bldg 91 – Side C 251 400
91 D Bldg 91 – Side D 65.8 400
Building #2 - 93 North Main Street
SAMPLE ID LOCATION RESULTS (ppm) ACTION LEVEL
93A Bldg 93 – Side A 186 400
93B Bldg 93 – Side B 156 400
93C Bldg 93 – Side C 75.4 400
93 D Bldg 93 – Side D 265 400
Building #3 – 95 North Main Street
SAMPLE ID LOCATION RESULTS (ppm) ACTION LEVEL
95A Bldg 95 – Side A 224 400
95B Bldg 95 – Side B 161 400
95C Bldg 95 – Side C 477 400
95D Bldg 95 – Side D 1,570 400
All units are in PPM (parts per million)
Summary of Results
Soil hazards have been identified at Building #3 – 95 North Main Street, sides C and D.
3.4 LEAD IN DRINKING WATER
Representative drinking water samples were collected from the kitchen tap [primary source of drinking water] within each unit of the Subject Property. Water sampling involved the collection of an immediate “1st draw” sample and a “flush” water sample. Samples were collected into laboratory supplied containers, placed on ice, and shipped under chain-of-custody protocol to Phoenix Environmental Laboratories, Inc.
of Manchester, CT. Samples were analyzed for total lead.
Applicable Regulations
The US Environmental Protection Agency (EPA) and National Primary Drinking Water Regulation (NPDWR) for lead and copper under the authority of the Safe Drinking Water Act (SDWA) have set an action level for lead at 15 parts per billion (µg/L) / 0.015 parts per million (0.015 mg/L).
Sampling Data
TABLE VI - LEAD WATER SAMPLING RESULTS
SAMPLE ID LOCATION TYPE RESULTS) ACTION LEVEL
91-1-A Unit 91-1, Kitchen Sink
1st Draw 0.0023 0.015
91-1-B Flush <0.0005 0.015
91-2-A Unit 91-2, Kitchen Sink
1st Draw 0.0013 0.015
91-2-B Flush <0.0005 0.015
All units in Parts Per Million (mg/ L)
SAMPLE ID LOCATION TYPE RESULTS) ACTION LEVEL
93-3-A Unit 93-3, Kitchen Sink
1st Draw <0.0005 0.015
93-3-B Flush <0.0005 0.015
93-4-A Unit 93-4, Kitchen Sink
1st Draw <0.0005 0.015
93-4-B Flush <0.0005 0.015
Building #3 – 953 North Main Street
SAMPLE ID LOCATION TYPE RESULTS) ACTION LEVEL
95-5-A Unit 95-5, Kitchen Sink
1st Draw 0.0010 0.015
95-5-B Flush <0.0005 0.015
95-6-A Unit 95-6, Kitchen Sink
1st Draw 0.0028 0.015
95-6-B Flush <0.0005 0.015
Summary of Results
Lead in drinking water hazards have not been identified.
3.3 PCB SURVEY
Big East Environmental inspectors visually inspected window and door systems for suspect polychlorinated biphenyls (PCB) containing caulks and/ or glazing throughout the interior of the subject site buildings. Suspect PCB containing window glazing and window and door caulking was identified on the exterior of buildings # 91, 93, and 95 North Main Street. In addition, old light fixtures and ballasts were identified as possibly containing PCBs in various units of the Subject Property.
LOCATION BUILDING MATERIAL CONDITION
91 North Main Street - Exterior Window Glazing Fair
Window & Door Caulking Fair
91 North Main Street – Unit 2 Bedroom Closet Light -
93 North Main Street - Exterior Window Glazing Poor/ Damaged
Window & Door Caulking Poor/ Damaged
93 North Main Street - Unit 3
Kitchen Light Ballast -
1st Fl Closet Light Ballast -
Bathroom Light Ballast
95 North Main Street - Exterior Window Glazing Fair
Window & Door Caulking Fair
95 North Main Street - Unit 5 Kitchen Light -
Stairwell Light -
95 North Main Street - Unit 6 Laundry Room Light -
Summary of Findings Suspect PCM containing building material and components have been identified on site. The possibility for PCB containing caulks does exist in older door and window systems beneath multiple layers of caulk and/ or glazing. PCB has been documented on other sites to be present in paints and roofing materials, leading to such possibility at the Subject Site.
3.4 MOLD INSPECTION
A visual survey for mold affected building materials was conducted throughout the residential units.
Table III – Visually Identified Mold – Residential Area
LOCATION MATERIAL AMOUNT
95 North Main Street – Basement Loose Drywall <10 SF
93 North Main Street – Unit 3 Kitchen Drywall Ceiling <10 SF
91 North Main Street – Unit 2 Bathroom Drywall Ceiling <10 SF
91 North Main Street – Unit 2 Bedroom Closet
Drywall Ceiling <10 SF
Summary of Findings Suspect mold growth has been identified on interior building materials of the residential units.
3.5 UFFI SURVEY
Big East Environmental inspectors visually inspected the residential units and common areas for evidence of urea-formaldehyde foam insulation (UFFI). UFFI is a thermal insulation product used in the 1970s and 1980s. Retrofit applications of UFFI insulation was common in homes built earlier.
Big East inspectors found no evidence of UFFI insulation at the Subject Site properties.
3.6 MERCURY CONTAINING COMPONENTS
Big East Environmental inspectors visually assessed the residential units for potential mercury containing components. Suspect mercury containing components typically include thermostats, light-ballasts, and emergency exit signs.
Big East inspectors identified suspect mercury containing components in the following units;
UNIT COMPONENT TYPE AMOUNT
91 North Main Street – Unit 1 Thermostat 1
91 North Main Street – Unit 2 Light Ballast – Bedroom Closet 1
93 North Main Street – Unit 3 Thermostat 1
95 North Main Street – Unit 6 Thermostat 1
3.7 RADON SURVEY
Radon test kits, consisted of 4-inch charcoal canisters provided by the laboratory (RTCA) were placed in the basement of each Subject Property building for a minimum of 48-hours. The US EPA has set an action level for radon in air at 4.0 pico curies per liter (pCi/L).
LOCATION DATE/ TIME
STARTED
DATE/ TIME
ENDED
RESULT
91 North Main Street – Basement
10/27/23 @ 1100 10/29/23 @ 1330 6.1 pCi/L
93 North Main Street – Basement
10/27/23 @ 1100 10/29/23 @ 1330 1.6 pCi/L
95 North Main Street – Basement
10/27/23 @ 1100 10/29/23 @ 1330 1.1 pCi/L
95 North Main Street – Basement (Duplicate)
10/27/23 @ 1100 10/29/23 @ 1330 1.0 pCi/L
**pCi/L – pico curies per Liter
Summary Of Results 91 North Main Street radon in air is above the US EPAs remedial action level.
4.0 APPLICABLE REGULATIONS
Asbestos
US Environmental Protection Agency (EPA) and CT Department of Public Health (CT DPH) regulations define asbestos containing materials (ACM's) as materials containing greater than 1% asbestos (chrysotile, amosite, crocidolite, anthophyllite, actinolite or tremolite). If one or more bulk samples of a homogeneous material are found to contain greater than or equal to 1% asbestos, then all of the homogeneous material is classified as ACM.
Asbestos is regulated in CT by the Department of Public Health under the Standards for Asbestos Abatement 19a-332a.
It is required that the CT DPH and US EPA Region 1 office is notified 10 days prior to any demolition or disturbance of materials classified as Asbestos Containing and that a CT licensed asbestos abatement contractor perform any of the removal of the asbestos containing material (ACM) from the site. An independent CT DPH certified asbestos project monitor shall be retained by the owner to perform post-abatement clearance testing.
Lead-Based Paint
Exposure levels for lead in the construction industry are regulated pursuant to OSHA 29 CFR 1926.62.
Demolition activities disturbing surfaces containing lead paint which are likely to be employed, such as grinding, cuttings, and demolishing, have been known to expose workers to airborne levels of lead in excess of the permissible exposure limit (PEL). Also, any activities involving work in child-occupied facilities which will impact LBP > 1.0 mg/cm² shall be performed by firms certified with USEPA using USEPA Certified Lead Renovators and individuals with USEPA RRP training. A “child-occupied facility” means a building, or portion of a building, constructed prior to 1978, visited regularly by the same child under 6 years of age, on at least two different days within any week (Sunday through Saturday period), provided each day’s visit lasts at least 3 hours and the combined weekly visits last at least 6 hours, and the combined annual visits last at least 60 hours. Child-occupied facilities may include, but are not limited to, day care centers, preschools and kindergarten classrooms. Child occupied facilities may be located in target housing or in public or commercial buildings. With respect to common areas in public or commercial buildings that contain child-occupied facilities, the child-occupied facility encompasses only those common areas that are routinely used by children under age 6, such as restrooms, libraries and cafeterias. Common areas that children under age 6 only pass through, such as hallways, stairways, and garages are not included. In addition, with respect to exteriors of public or commercial buildings that contain child-occupied facilities, the child occupied facility encompasses only the exterior sides of the building that are immediately adjacent to the child-occupied facility or the common areas routinely used by children under age 6. The Contractor shall conduct demolition work in conformance with the OSHA/USEPA regulations, utilizing engineering controls and personal protective equipment. Disposal of construction waste containing LBP is subject to regulation under both the CTDEEP Hazardous and Special Waste Management (R.C.S.A. §§ 22a-209-1 through 16; § 22a-449(c)-11; § 22a-449(c)-13; §§ 22a-449(c)-100 through 110; and 22a-454) and USEPA RCRA Hazardous Waste Management regulations (40 CFR Parts 260 through 274).
Prior to demolition of lead-based paint coated building materials, composite sampling should be conducted for TCLP (toxicity characteristic leaching potential) analysis to determine if the materials shall be handled as lead hazardous waste. If the composite(s) all come back with lead concentrations below
5.0 mg/l, then the debris may be disposed of as solid waste. If any samples come back which are not below 5.0 mg/l of lead, then either:
1.) The portion of the structure represented by that sample must be disposed of as hazardous waste, or 2.) That portion of the structure must be reassessed by some other method, such as identifying the lead-containing components and removing them for disposal as hazardous waste.
Lead in Water
Water sample analysis results were applied to the United States Environmental Protection Agency’s (US EPA) Lead and Copper Rule, 40 CFR Part 141.80, which establishes an action level of 15 parts per billion (15 µg/L) / 0.015 parts per million (15 mg/L) for lead in water.
Lead in Soil
The CT Department of Public Health has established regulatory levels for Soil Hazard Standards at >400 ppm for lead in bare soils and in play areas. The US EPA Department of Housing and Urban Development has established soil Hazard Standards at ≥400 ppm for lead in soil.
Polychlorinated Biphenyls
Building materials containing PCBs at concentrations equal to or greater than >50 parts per million (ppm) or the equivalent units of milligrams per kilogram (mg/kg) are regulated by the EPA and characterized as PCB Bulk Product. Building materials determined to be Excluded PCB Product containing > 1 ppm PCB but < 50 ppm PCB are regulated by the CTDEEP.
EPA requirements apply and require removal of PCBs once identified, regardless of project intent as an un-authorized use of PCBs. If buildings are to remain for re-use and PCBs are identified, the EPA still requires PCB material removal once it is determined that PCBs are present. In addition to identification of source materials containing PCBs, if PCBs are present at certain concentrations, additional sampling and analysis of adjacent surfaces in contact with PCB sources, or which may have been contaminated from a source of PCBs (e.g., soil), must also be performed or remediated.
EPA requirements apply only if PCBs are present in concentrations above a specified level. Currently, PCB -containing materials at concentrations equal to or greater than 50 ppm. Note; materials containing less than <50 ppm may also be regulated unless proven to be an "Excluded PCB Product.” The definition of an Excluded PCB Product includes those products or source of the products containing <50 ppm concentration PCBs that were legally manufactured, processed, distributed in commerce, or used before October 1, 1984.
The identification of building materials containing regulated PCBs requires additional testing of the adjacent porous surfaces and/or soils, asphalts, and concrete located below source materials. The building materials adjacent to the regulated PCB material must be tested to determine if the adjacent materials are PCB contaminated and may also be considered PCB Bulk Products, if disposed with source materials. Soils, asphalts, and concrete located below source materials must be tested to determine if the materials are PCB contaminated and considered PCB Remediation Waste.
Mercury/ Universal Waste
Universal Waste Items encompass several building items that can contain hazardous and/ or regulated materials within them. Typically, these are mercury (fluorescent lamps), PCBs, oils, AC units, refrigerants, smoke alarms, and exit signs. The survey is conducted via visual means. These items should be carefully removed from work spaces prior to any disturbance. They should be properly packaged, handled and disposed of according to all federal, state, and local laws. Below are links to disposal requirements;
Fluorescent Light Tubes http://epa.gov/waste/hazard/wastetypes/universal/lamps/faqs/ftm
Mercury Containing Equipment http://www.ehd.org/pdf/sources/617.pdf
PCB Light Ballasts http://www.epa.gov/reg3wcmd/ts_pcbs.htm#ballast
Smoke Alarms http://www.epa.gov/rpdweb00/sources/smoke_dispose.html
Radon in Air The US EPA has set a remedial action level for radon in air at 4.0 pico curies per liter (pCi/L).
http://epa.gov/waste/hazard/wastetypes/universal/lamps/faqs/ftm http://www.ehd.org/pdf/sources/617.pdf http://www.epa.gov/reg3wcmd/ts_pcbs.htm#ballast http://www.epa.gov/rpdweb00/sources/smoke_dispose.html
5.0 CONCLUSIONS
• Asbestos containing materials have been identified during the limited non-destructive asbestos inspection of the residential units. Suspect-asbestos containing materials have been visually identified during the limited visual survey of the units. These items shall be assumed to be asbestos containing materials until laboratory analysis is performed. A pre-renovation/ demolition asbestos survey should be completed prior to any demolition/ disturbance of building materials.
• Lead-based paint has been identified on site during the limited LBP survey of the residential units.
Some of these surfaces were found to be in deteriorated condition. These surfaces should be managed in place with paint stabilization or component replacement methods. A lead-based paint management plan shall be implemented for the Site until all LBP has been abated. A comprehensive lead-based paint inspection, in accordance with the CT Department of Public Health Lead Poisoning Prevention and Control Program shall be conducted in residential units identified with deteriorated lead-based paint.
• Lead in soil exceeded applicable action levels at 95 North Main Street – Sides C & D.
• All lead in drinking water samples were below applicable action levels.
• No known PCB containing materials have been identified during the course of the presumptive survey. Due to the buildings age, PCB containing caulk, glazing, paint, and tars can exist in the window, door, and roofing systems.
• Visible mold growth was identified in the basement of 95 North Main Street on loose pieces of drywall placed in the area; 91 North Main Street, Unit 2 drywall ceiling of the bathroom and bedroom closet; and 93 North Main Street, Unit 3 kitchen ceiling.
• No evidence of Urea Formaldehyde Foam Insulation (UFFI) has been identified during the non-destructive visual survey.
• Suspect mercury containing thermostats were identified in buildings residential units 1, 2, 3, & 6.
• Radon in air was above the USEPA action level in the basement of Building 91 North Main Street.
6.0 LIMITATIONS
This survey was conducted utilizing non-destructive methods limiting access to possible suspect HAZAMT materials in non-accessible areas. This survey was completed solely with respect to ACM, PCBs, UFFI, Mercury, radon, lead in soil, lead in drinking water, and Lead Based Paint. While Big East Environmental strives to conduct a thorough, comprehensive inspection, some exclusion is warranted.
For 100% accuracy in the determination of hazardous materials, 100% demolition would be necessary.
Surveys conducted in occupied residential units were limited to select areas and surfaces accessible on the day of the inspection. Time constrains were placed on inspectors in some units. In completing the survey, Big East relied upon the information provided by the client, architects, and sub-contractors, etc.
(i.e., laboratories, XRF instrumentation). Big East provides no warranty for the completeness of the information provided by the sub-contractors. The inspections were completed for accessible materials only and involved the use of non-destructive sampling techniques and/ or visual identified methods.
Asbestos, lead, PCB, Mercury, UFFI, and other hazardous materials may be located in areas we could not access. Apartment 4 was not accessible for XRF testing. Big East cannot be held liable for materials identified during destructive renovation/ demolition activities. All quantities are estimates and should be field checked prior to state notification and/ or bidding purposes. This report does not serve as a technical specification for abatement purposes.
Please feel free to contact us if you have any questions regarding this investigation.
Sincerely, Eric Gelhaus, CMI Sr. Project Manager CT Asbestos Inspector EPA & CT Lead Based Paint Inspector/Risk Assessor
Stephen E. DiNapoli, LEED AP, CMC Senior Director CT licensed Asbestos Inspector/ Management Planner Council-certified Microbial Consultant
REVISIONS
# Date
00 11/15/23 Initial Descriptions
SHEET #
57 Chestnut St, Unit 10
Norwalk, CT 06854
(203) 354-4955
Lead-Based Paint Inspection
91 North Main Street Sharon, CT
LEGEND
A-D Wall Identification
NOTE: Drawings are not to scale
1ST FLOOR (Unit 1 & Stair to Unit 2) 2ND FLOOR (Unit 2)
Side A
Si de
B
Kitchen
Bed 1
Side C
Si de
D
Side A
Si de
B
Side C
Si de
D
Bed 2Bath 1
KitchenBath 1Bed 1
Office Living Room
Staircase
00 11/15/23 Initial Descriptions
SHEET #
57 Chestnut St, Unit 10
Norwalk, CT 06854
(203) 354-4955
Lead-Based Paint Inspection
93 North Main Street Sharon, CT
LEGEND
A-D Wall Identification
NOTE: Drawings are not to scale
1ST FLOOR (Unit 3) 2ND FLOOR (Unit 3)
Side A
Si de
B
Kitchen
No Access
Side C
Si de
D
Side A
Si de
B
Side C
Si de
D
Bed 2Bath 1 Bath 2
Bed 1
Living Room
No Access
00 11/15/23 Initial Descriptions
SHEET #
57 Chestnut St, Unit 10
Norwalk, CT 06854
(203) 354-4955
Lead-Based Paint Inspection
95 North Main Street Sharon, CT
LEGEND
A-D Wall Identification
NOTE: Drawings are not to scale
1ST FLOOR (Unit 5 & Unit 6) 2ND FLOOR (Unit 5 & Unit 6)
Side A
Si de
B
Side C
Side A
Si de
B
Side C
Si de
D
Porch
Bath 1
Bed 1
Living Room Living Room
Kitchen Kitchen
Porch
Bed 2 Bath 1
Bed 1
Bed 2
B at h
Unit 6 Unit 5 Unit 6 Unit 5
APPENDIX A
ASBESTOS LABORATORY REPORT
Analyst: Childress, Susan
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
DW-01 / 23061804-001
Drywall Apt. 91.1 Interior Walls + Ceilings
Off-White Non-Fibrous
Homogeneous
5% Cellulose < 1% Glass
95% Other None Detected
DW-02 / 23061804-002
Drywall Apt. 91.2 Stairwell Interior Walls + Ceilings
Off-White Non-Fibrous
Homogeneous
5% Cellulose < 1% Glass
95% Other None Detected
DW-03 / 23061804-003
Drywall Apt. 91 Basement Stairwell Interior Walls + Ceilings
Off-White Non-Fibrous
Homogeneous
5% Cellulose < 1% Glass
95% Other None Detected
FS-01 / 23061804-004
Foundation Stucco Apt. 91.2 Exterior Exterior
Grey Non-Fibrous
Homogeneous
< 1% Cellulose 100% Other None Detected
FS-02 / 23061804-005
Foundation Stucco Apt. 91.2 Exterior Exterior
Grey Non-Fibrous
Homogeneous
< 1% Cellulose 100% Other None Detected
FS-03 / 23061804-006
Foundation Stucco Apt. 91.2 Exterior Exterior
Grey Non-Fibrous
Homogeneous
< 1% Cellulose 100% Other None Detected
JC-01 / 23061804-007
Joint Compound Apt. 91.1 Interior Walls & Ceilings
White Non-Fibrous
Homogeneous
98% Other 2% Chrysotile
JC-02 / 23061804-008
Joint Compound Building 91 Basement-Boiler Interior Walls &
Not Analyzed
JC-03 / 23061804-009
Joint Compound Apt. 91.2 Stairwell Interior Walls & Ceilings
Not Analyzed
PF-01 / 23061804-010
Pantry Floor Apt. 91.2 (9x9) Unit
91.2 Kitchen, Vinyl
Cream Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 11/7/2023 Date: 11/7/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23622Project Number:
P.O. Number:
Project Name: 91 North Main St, Sharon CT
10/27/2023Collected Date:
11/7/2023 10:45:00 AMReceived Date:
11/7/2023 3:14:33 PM
23061804 SanAir ID Number
FINAL REPORT
Big East EnvironmentalName:
Address: 57 Chestnut Street
Unit #10
Norwalk, CT 06854
203-354-4955Phone:
Analyst: Childress, Susan
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
PF-01 / 23061804-010
Pantry Floor Apt. 91.2 (9x9) Unit
91.2 Kitchen, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
WG-01 / 23061804-011
Window Glazing Apt. 91.1 Bedroom Exterior
Grey Non-Fibrous
Homogeneous
100% Other None Detected
WG-02 / 23061804-012
Window Glazing Apt. 91.1 Exterior
Grey Non-Fibrous
Homogeneous
100% Other None Detected
WG-03 / 23061804-013
Window Glazing Apt. 91.1 Exterior
Grey Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 11/7/2023 Date: 11/7/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23622Project Number:
P.O. Number:
Project Name: 91 North Main St, Sharon CT
10/27/2023Collected Date:
11/7/2023 10:45:00 AMReceived Date:
11/7/2023 3:14:33 PM
23061804 SanAir ID Number
FINAL REPORT
Big East EnvironmentalName:
Address: 57 Chestnut Street
Unit #10
Norwalk, CT 06854
P a g e o f
Analyst: Mayes, Jean
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
BP-01 / 23061810-001
Basement Plaster Basement Stairwell
Grey Non-Fibrous
Heterogeneous
2% Hair 98% Other None Detected
BP-02 / 23061810-002
Basement Plaster Basement Stairwell
Grey Non-Fibrous
Heterogeneous
2% Hair 98% Other None Detected
BP-03 / 23061810-003
Basement Plaster Basement Stairwell
Grey Non-Fibrous
Heterogeneous
2% Hair 98% Other None Detected
FS-01 / 23061810-004
Foundation Stucco Exterior
Grey Non-Fibrous
Homogeneous
100% Other None Detected
FS-02 / 23061810-005
Foundation Stucco Exterior
Grey Non-Fibrous
Homogeneous
100% Other None Detected
FS-03 / 23061810-006
Foundation Stucco Exterior
Grey Non-Fibrous
Homogeneous
100% Other None Detected
P1-01 / 23061810-007 Plaster 1 (Skim Coat) Interior Walls & Ceilings: Upper Floor
White Non-Fibrous
Homogeneous
100% Other None Detected
P1-02 / 23061810-008 Plaster 1 (Skim Coat) Interior Walls & Ceilings: Upper Floor
White Non-Fibrous
Homogeneous
100% Other None Detected
P1-03 / 23061810-009 Plaster 1 (Skim Coat) Interior Walls & Ceilings: Upper Floor
White Non-Fibrous
Homogeneous
100% Other None Detected
P2-01 / 23061810-010 Plaster 2 (Base Coat) Interior Walls & Ceilings: Upper Floor
Cream Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 11/7/2023 Date: 11/7/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23622Project Number:
P.O. Number:
Project Name: 93 North Main St, Sharon CT
10/27/2023Collected Date:
11/7/2023 10:45:00 AMReceived Date:
11/7/2023 4:52:59 PM
23061810 SanAir ID Number
FINAL REPORT
Big East EnvironmentalName:
Address: 57 Chestnut Street
Unit #10
Norwalk, CT 06854
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers P2-02 / 23061810-011 Plaster 2 (Base Coat) Interior Walls & Ceilings: Upper Floor
Cream Non-Fibrous
Homogeneous
100% Other None Detected
P2-03 / 23061810-012 Plaster 2 (Base Coat) Interior Walls & Ceilings: Upper Floor
Grey Non-Fibrous
Heterogeneous
2% Hair 98% Other None Detected
DW-01 / 23061810-013
Drywall Attic Level
Various Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
DW-02 / 23061810-014
Drywall Attic Level
Various Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
DW-03 / 23061810-015
Drywall Attic Level
Various Non-Fibrous
Heterogeneous
5% Cellulose 95% Other None Detected
WC-01 / 23061810-016
Window Caulk Exterior Facade
White Non-Fibrous
Homogeneous
100% Other None Detected
WC-02 / 23061810-017
Window Caulk Exterior Facade
White Non-Fibrous
Homogeneous
100% Other None Detected
WC-03 / 23061810-018
Window Caulk Exterior Facade
White Non-Fibrous
Homogeneous
100% Other None Detected
WG-01 / 23061810-019
Window Glazing Exterior Facade
Tan Non-Fibrous
Homogeneous
100% Other None Detected
WG-02 / 23061810-020
Window Glazing Exterior Facade
Tan Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 11/7/2023 Date: 11/7/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23622Project Number:
P.O. Number:
Project Name: 93 North Main St, Sharon CT
10/27/2023Collected Date:
11/7/2023 10:45:00 AMReceived Date:
11/7/2023 4:52:59 PM
23061810 SanAir ID Number
FINAL REPORT
Big East EnvironmentalName:
Address: 57 Chestnut Street
Unit #10
Norwalk, CT 06854
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
WG-03 / 23061810-021
Window Glazing Exterior Facade
Tan Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 11/7/2023 Date: 11/7/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23622Project Number:
P.O. Number:
Project Name: 93 North Main St, Sharon CT
10/27/2023Collected Date:
11/7/2023 10:45:00 AMReceived Date:
11/7/2023 4:52:59 PM
23061810 SanAir ID Number
FINAL REPORT
Big East EnvironmentalName:
Address: 57 Chestnut Street
Unit #10
Norwalk, CT 06854 g e o
Analyst: Jones, Virginia
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers P1-01 / 23061493-001 Plaster Skim Coat Interior Walls & Ceilings Throughout
White Non-Fibrous
Homogeneous
100% Other None Detected
P1-02 / 23061493-002 Plaster Skim Coat Interior Walls & Ceilings Throughout
White Non-Fibrous
Homogeneous
100% Other None Detected
P1-03 / 23061493-003 Plaster Skim Coat Interior Walls & Ceilings Throughout
White Non-Fibrous
Homogeneous
100% Other None Detected
P2-01 / 23061493-004 Plaster Base Coat Interior Walls & Ceilings Throughout
Grey Non-Fibrous
Homogeneous
100% Other None Detected
P2-02 / 23061493-005 Plaster Base Coat Interior Walls & Ceilings Throughout
Grey Non-Fibrous
Homogeneous
100% Other None Detected
P2-03 / 23061493-006 Plaster Base Coat Interior Walls & Ceilings Throughout
Grey Non-Fibrous
Homogeneous
100% Other None Detected
BDW-01 / 23061493-007
Boiler Drywall (W/ Paper)
White Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
BDW-02 / 23061493-008
Boiler Drywall (W/ Paper)
White Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
BDW-03 / 23061493-009
Boiler Drywall (W/ Paper)
White Non-Fibrous
Heterogeneous
10% Cellulose 90% Other None Detected
WG-01 / 23061493-010
Window Glazing Exterior Facade
Grey Non-Fibrous
Homogeneous
98% Other 2% Chrysotile
Analyst:
Analysis Date: 11/7/2023 Date: 11/7/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23622Project Number:
P.O. Number:
Project Name: 95 North Main St, Sharon CT
10/27/2023Collected Date:
11/6/2023 10:40:00 AMReceived Date:
11/7/2023 8:46:34 AM
23061493 SanAir ID Number
FINAL REPORT
Big East EnvironmentalName:
Address: 57 Chestnut Street
Unit #10
Norwalk, CT 06854
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
WG-02 / 23061493-011
Window Glazing Exterior Facade
Not Analyzed
WG-03 / 23061493-012
Window Glazing Exterior Facade
Not Analyzed
FS-01 / 23061493-013
Foundation Stucco Exterior Facade
Grey Non-Fibrous
Homogeneous
100% Other None Detected
FS-02 / 23061493-014
Foundation Stucco Exterior Facade
Grey Non-Fibrous
Homogeneous
100% Other None Detected
FS-03 / 23061493-015
Foundation Stucco Exterior Facade
Grey Non-Fibrous
Homogeneous
100% Other None Detected
VF1-01 / 23061493-016
Vinyl Floor 1 (4x4 Square Pattern) 1st & 2nd Floor Bathrooms
White Non-Fibrous
Heterogeneous
15% Cellulose 85% Other None Detected
VF1-02 / 23061493-017
Vinyl Floor 1 (4x4 Square Pattern) 1st & 2nd Floor Bathrooms
White Non-Fibrous
Heterogeneous
15% Cellulose 85% Other None Detected
VFA1-01 / 23061493-018
Vinyl Floor Adhesive 1 1st & 2nd Floor Bathrooms & Kitchen
Tan Non-Fibrous
Homogeneous
100% Other None Detected
VFA1-02 / 23061493-019
Vinyl Floor Adhesive 1 1st & 2nd Floor Bathrooms & Kitchen
Tan Non-Fibrous
Homogeneous
100% Other None Detected
VF3-01 / 23061493-020
Vinyl Floor 3 (1x1 Square Pattern) Bath (Unit 6)
White Non-Fibrous
Heterogeneous
15% Cellulose 85% Other None Detected
Analyst:
Analysis Date: 11/7/2023 Date: 11/7/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23622Project Number:
P.O. Number:
Project Name: 95 North Main St, Sharon CT
10/27/2023Collected Date:
11/6/2023 10:40:00 AMReceived Date:
11/7/2023 8:46:34 AM
23061493 SanAir ID Number
FINAL REPORT
Big East EnvironmentalName:
Address: 57 Chestnut Street
Unit #10
Norwalk, CT 06854
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
VF3-02 / 23061493-021
Vinyl Floor 3 (1x1 Square Pattern) Bath (Unit 6)
White Non-Fibrous
Heterogeneous
15% Cellulose 85% Other None Detected
VFA3-01 / 23061493-022
Vinyl Floor Adhesive 3 Bath (Unit 6)
Tan Non-Fibrous
Homogeneous
100% Other None Detected
VFA3-02 / 23061493-023
Vinyl Floor Adhesive 3 Bath (Unit 6)
Tan Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 11/7/2023 Date: 11/7/2023
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
23622Project Number:
P.O. Number:
Project Name: 95 North Main St, Sharon CT
10/27/2023Collected Date:
11/6/2023 10:40:00 AMReceived Date:
11/7/2023 8:46:34 AM
23061493 SanAir ID Number
FINAL REPORT
Big East EnvironmentalName:
Address: 57 Chestnut Street
Unit #10
Norwalk, CT 06854 g e o
APPENDIX B
XRF Data Sheets
Lead Based Paint XRF Inspection Data
Big East Environmental 57 Chestnut Street, Unit 10 Norwalk, CT 06854
INSPECTION SITE: 91 North Main Street Sharon CT
INSPECTION DATE: 10/27/2023 - 10/27/2023
REPORT NUMBER: 23622
INSTRUMENT TYPE: Viken Detection Pb200i XRF Lead Paint Analyzer
ACTION LEVEL: 1.0 (mg/cm²)
STATEMENT: Lead-based Paint Testing
Inspection Date: 10/27/2023 - 10/27/2023 Inspection Site: 91 North Main Street Sharon CTAction Level: 1.0 (mg/cm²)
Report Number: 23622 Total Readings: 151 Unit Started: 10/27/2023 11:11:25 Unit Ended: 10/27/2023 15:29:12
Big East Environmental 57 Chestnut Street, Unit 10 Norwalk, CT 06854
Read # Result Job ROOM SIDE ASSEMBLY Member SUBSTRATE CONDITION Floor Color Lead (mg/cm²)
1 Negative Cal. Start. 0.9 mg/cm²
2 Positive Cal. Start. 1.0 mg/cm²
3 Positive Cal. Start. 1.0 mg/cm²
4 Negative 91 unit 1 Kitchen A Door Door Wood Intact 1st Floor White 0.1 mg/cm²
5 Negative 91 unit 1 Kitchen A Door Frame Wood Intact 1st Floor White 0.2 mg/cm²
6 Negative 91 unit 1 Kitchen A Door Jamb Wood Intact 1st Floor White 0.1 mg/cm²
7 Negative 91 unit 1 Kitchen A Wall Drywall Intact 1st Floor White 0.3 mg/cm²
8 Negative 91 unit 1 Kitchen B Wall Drywall Intact 1st Floor White 0.1 mg/cm²
9 Negative 91 unit 1 Kitchen C Wall Drywall Intact 1st Floor White 0.2 mg/cm²
10 Negative 91 unit 1 Kitchen D Wall Drywall Intact 1st Floor White 0.2 mg/cm²
11 Negative 91 unit 1 Kitchen A Window Sill Wood Intact 1st Floor White 0.1 mg/cm²
12 Negative 91 unit 1 Kitchen A Window Casing Wood Intact 1st Floor White 0.2 mg/cm²
13 Negative 91 unit 1 Kitchen A Window Sash Interior
Wood Intact 1st Floor White 0.2 mg/cm²
14 Negative 91 unit 1 Kitchen A Radiator Metal Intact 1st Floor White 0.2 mg/cm²
15 Negative 91 unit 1 Kitchen D Cabinet Up Cabinet Housing
Wood Intact 1st Floor Varnish 0.1 mg/cm²
16 Negative 91 unit 1 Kitchen D Cabinet Up Cabinet Door
Wood Intact 1st Floor Varnish 0.2 mg/cm²
17 Negative 91 unit 1 Kitchen D Ceiling Drywall Intact 1st Floor White 0.2 mg/cm²
18 Negative 91 unit 1 Bedroom
D Ceiling Drywall Intact 1st Floor White 0.2 mg/cm²
19 Negative 91 unit 1 Bedroom
A Wall Drywall Intact 1st Floor White 0.2 mg/cm²
20 Negative 91 unit 1 Bedroom
B Wall Drywall Intact 1st Floor White 0.2 mg/cm²
21 Negative 91 unit 1 Bedroom
C Wall Drywall Intact 1st Floor White 0.3 mg/cm²
22 Negative 91 unit 1 Bedroom
D Wall Drywall Intact 1st Floor White 0.2 mg/cm²
Sharon CTAction Level: 1.0 (mg/cm²)
Report Number: 23622 Total Readings: 151 Unit Started: 10/27/2023 11:11:25 Unit Ended: 10/27/2023 15:29:12
Big East Environmental 57 Chestnut Street, Unit 10 Norwalk, CT 06854
Read # Result Job ROOM SIDE ASSEMBLY Member SUBSTRATE CONDITION Floor Color Lead (mg/cm²)
23 Negative 91 unit 1 Bedroom
B Window Sill Wood Intact 1st Floor White 0.2 mg/cm²
24 Negative 91 unit 1 Bedroom
B Window Casing Wood Intact 1st Floor White 0.0 mg/cm²
25 Negative 91 unit 1 Bedroom
B Window Sash Interior
Wood Intact 1st Floor White 0.1 mg/cm²
26 Negative 91 unit 1 Bedroom
D Wall Baseboard Wood Intact 1st Floor White 0.1 mg/cm²
27 Negative 91 unit 1 Bedroom
D Door Door Wood Intact 1st Floor White 0.2 mg/cm²
28 Negative 91 unit 1 Bedroom
D Door Frame Wood Intact 1st Floor White 0.2 mg/cm²
29 Negative 91 unit 1 Bedroom
D Door Jamb Wood Intact 1st Floor White 0.1 mg/cm²
30 Negative 91 unit 1 Bathroom
A Door Jamb Wood Intact 1st Floor White 0.1 mg/cm²
31 Negative 91 unit 1 Bathroom
A Door Frame Wood Intact 1st Floor White 0.1 mg/cm²
32 Negative 91 unit 1 Bathroom
A Door Door Wood Intact 1st Floor White 0.1 mg/cm²
33 Negative 91 unit 1 Bathroom
A Wall Drywall Intact 1st Floor White 0.1 mg/cm²
34 Negative 91 unit 1 Bathroom
B Wall Drywall Intact 1st Floor White 0.2 mg/cm²
35 Negative 91 unit 1 Bathroom
C Wall Drywall Intact 1st Floor White 0.2 mg/cm²
36 Negative 91 unit 1 Bathroom
D Wall Drywall Intact 1st Floor White 0.2 mg/cm²
37 Negative 91 unit 1 Bathroom
Ceiling Drywall Intact 1st Floor White 0.2 mg/cm²
38 Negative 91 unit 1 Bathroom
Radiator Metal Intact 1st Floor White 0.2 mg/cm²
39 Negative 91 unit 1 Bedroom
A Wall Drywall Intact 1st Floor White 0.2 mg/cm²
40 Negative 91 unit 1 Bedroom
B Wall Drywall Intact 1st Floor White 0.3 mg/cm²
Sharon CTAction Level: 1.0 (mg/cm²)
Report Number: 23622 Total Readings: 151 Unit Started: 10/27/2023 11:11:25 Unit Ended: 10/27/2023 15:29:12
Big East Environmental 57 Chestnut Street, Unit 10 Norwalk, CT 06854
Read # Result Job ROOM SIDE ASSEMBLY Member SUBSTRATE CONDITION Floor Color Lead (mg/cm²)
41 Negative 91 unit 1 Bedroom
C Wall Drywall Intact 1st Floor White 0.2 mg/cm²
42 Negative 91 unit 1 Bedroom
D Wall Drywall Intact 1st Floor White 0.2 mg/cm²
43 Negative 91 unit 1 Bedroom
D Window Sill Wood Intact 1st Floor White 0.1 mg/cm²
44 Negative 91 unit 1 Bedroom
D Window Casing Wood Intact…