AC INFO.xlsx
XLSX spreadsheet 41 KB Posted
- Attached to
- Split-Unit HVAC Replacement
- Solicitation number
- H9242126QE047
- Issued by
-
United States Special Operations Command
About this file
This is an Air Conditioning (AC) inventory and assessment spreadsheet documenting the status of split-unit HVAC systems across multiple buildings at Joint Base Lewis-McChord. The spreadsheet tracks 16 nonfunctional ductless heat pump A/C units requiring replacement, organized by building location (Buildings 9160/9162, 9190, 9934, and 9983), with detailed technical specifications including evaporator and condenser models (predominantly Mitsubishi MSZA17NA, Daikin FTX/FHQ/FCQ series, and other manufacturers), refrigerant types (primarily 410A), thermostat settings (ranging from 59-101 degrees), and current operational status (RED for faulty, GREEN for functional). Each unit entry captures the make/model, room number, fault descriptions, condenser location, and access requirements (roof access, ladder access, or no roof access needed).
The inventory reveals widespread system failures requiring remediation, including error codes (E4, 1102, 5-blink codes), condensation issues, battery-depleted remotes, power failures, and fan inoperability. Additional maintenance issues documented include full condensation pipes, water damage, filter cleaning needs, and lightning protection removal concerns. This technical assessment directly supports the replacement contract H9242126QE047, which requires contractors to remove all 16 nonfunctional units and install new cooling-only split A/C systems with external condensation pumps, purge and test drain lines, and perform full testing. The performance period runs September 28, 2026 through November 12, 2026, with a mandatory site visit on September 18, 2026 at 1:30 p.m. (PDT) at 9190 Cramer Ave and a written questions deadline of September 21, 2026 at 5:00 p.m. (EDT).
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AC INFO_update.xlsx | XLSX spreadsheet | |
| HVAC Replacement RFIs_additional (002).docx | DOCX document | |
| HVAC Replacement RFIs_all.docx | DOCX document | |
| Solicitation Amendment H9242126QE0470001 SF 30.pdf | ||
| PWS_1SFG_MICC_Split Units_Updated final.docx | DOCX document | |
| HVAC Floor Plan_Split Units.pptx | PPTX presentation | |
| FAR_52.212-1_Addendum_-_Instructions_to_Offerors_(1SFG_HVAC_Replacement).docx | DOCX document | |
| Pierce County Wage Determination.txt | TXT text file | |
| HVAC Floor Plan_Split Units.pptx | PPTX presentation | |
| PWS_1SFG_MICC_Split Units_Updated_2.docx | DOCX document | |
| Solicitation - H9242126QE047 - CO Signed.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HQ
| LABEL # | ROOM # | MAKE | EVAP MODEL # | REFRIGERANT | THERMOSTAT | SET TEMP | STATUS | FAULT | CONDENSOR MODEL # | LOCATION | FAULT |
| SR 126 | 128 | DAIKIN | FTX24NMVJU | 410A | REMOTE | 72 | RED | NEED TROUBLESHOOT | ? | ? | NEED ROOF ACCESS |
| ? | 154 | DAIKIN | FHQ24PVJU? | ? | YES | 70 | GREEN | NEED LADDER TO SEARCH FOR DATA PLATE/ERROR CODE U3 | ? | ? | NEED ROOF ACCESS |
| B11 | B11 | DAIKIN | FHQ24PVJU? | ? | YES | 67 | GREEN | NEED LADDER TO SEARCH FOR DATA PLATE | ? | ? | NEED ROOF ACCESS |
| B11(2) | B11 | DAIKIN | FHQ24PVJU? | ? | YES | 69 | GREEN | NEED LADDER TO SEARCH FOR DATA PLATE | ? | ? | NEED ROOF ACCESS |
| SR 232 | B22 | DAIKIN | FHQ24PVJU? | ? | YES | 70 | GREEN | NEED LADDER TO SEARCH FOR DATA PLATE | ? | ? | NEED ROOF ACCESS |
| B25(LEFT) | B25 | DAIKIN | FCQ42TAVJU | ? | YES | 69 | RED | ERROR CODE E4 | ? | ? | NEED ROOF ACCESS |
| B25(RIGHT) | B25 | DAIKIN | FCQ42TAVJU | ? | YES | 70 | RED | CLEAN FILTER | ? | ? | NEED ROOF ACCESS |
| B25(CENTER) | B25 | DAIKIN | FCQ42TAVJU | ? | YES | 70 | GREEN | N/A | ? | ? | NEED ROOF ACCESS |
| ? | GCR | DAIKIN | FCQ42TAVJU ? | ? | REMOTE | ? | RED | CONDENSATION PUMP | ? | ? | NEED ROOF ACCESS |
2nd BN
| LABEL # | ROOM # | MAKE | EVAP MODEL # | REFRIGERANT | THERMOSTAT | SET TEMP | STATUS | FAULT | CONDENSOR MODEL # | LOCATION | FAULT |
| SS-1 | ? | ? | ? | ? | ? | ? | ? | ? | ? | ? | ? |
| SS-2 | G105A | DAIKIN | FTX12NMVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-3 | ? | ? | ? | ? | ? | ? | ? | ? | ? | ? | ? |
| SS-4 | G103B | DAIKIN | FTX12NMVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-5 | G103A | DAIKIN | FTX12NMVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-6 | G108 | DAIKIN | FAQ18PVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-7 | G109 | DAIKIN | FAQ18PVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-8 | H120 | DAIKIN | FAQ18PVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-9 | G205A | DAIKIN | FTX18NMVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-10 | G205B | DAIKIN | FTX18NMVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-11 | G203A | DAIKIN | FTX12NMVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-12 | G203B | DAIKIN | FTX18NMVJU | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-13 | G207 | DAIKIN | ? | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| SS-14 | G208 | DAIKIN | ? | 410A | YES | 72 | GREEN | N/A | ? | ? | ? |
| 2nd MP | BLDG 9946 | ||||||||||
| SS-2 | 108 | DAIKIN | FTX18NMVJU | 410A | YES | 78 | GREEN | THERMOSTAT WAS TURNED OFF | RX18NMVJU | ? |
3rd BN
| LABEL # | ROOM # | MAKE | EVAP MODEL # | REFRIGERANT | THERMOSTAT | SET TEMP | STATUS | FAULT | CONDENSOR MODEL # | LOCATION | FAULT |
| AC-1 | ? | TRANE | ? | ? | ? | ? | ? | N/A | 4TWA3036A4000AA | CENTER | LIGHTNING PROTECTION REMOVED |
| AC-2.0 | H120 | MITSUBISHI | PAR-UO1MEDU | ? | YES | ? | RED | ERROR CODE: 1102 | PUMY-P6ONKMU | CENTER | LIGHTNING PROTECTION REMOVED |
| AC-2.1 | H120 | MITSUBISHI | PAR-UO1MEDU | ? | YES | ? | RED | ERROR CODE: 1102 | PUMY-P6ONKMU | CENTER | LIGHTNING PROTECTION REMOVED |
| AC-3 | G108 | MITSUBISHI | MSZA17NA | 410A | REMOTE | 72 | RED | PUMP FAIL?/CONDENSATION TUBE FULL | MUZ-A17NA | CENTER | LIGHTNING PROTECTION REMOVED |
| AC-4 | G109 | MITSUBISHI | MSZA17NA | 410A | REMOTE | ? | RED | CHANGE REMOTE BATTERIES/CONDENSATION TUBE | MUZ-A17NA | CENTER | LIGHTNING PROTECTION REMOVED |
| AC-5 | G103A | MITSUBISHI | MSZA17NA | 410A | REMOTE | 72 | GREEN | CLEAN REMOTE CONTACTS/CONDENSATION TUBE | MUZ-A17NA | LEFT WING | LIGHTNING PROTECTION REMOVED |
| AC-6 | G103B | MITSUBISHI | MSZA17NA | 410A | REMOTE | ? | RED | CHANGE REMOTE BATTERIES/CONDENSATION TUBE | MUZ-A17NA | LEFT WING | LIGHTNING PROTECTION REMOVED |
| AC-7 | G105A | MITSUBISHI | MSZA17NA | 410A | REMOTE | ? | RED | REMOTE NEEDS BATTERIES | MUZ-A17NA | RIGHT WING | LIGHTNING PROTECTION REMOVED/INSULATION FUBAR |
| AC-8 | G105B | MITSUBISHI | MSZA17NA | 410A | REMOTE | ? | RED | REMOTE NEEDS BATTERIES | MUZ-A17NA | RIGHT WING | LIGHTNING PROTECTION REMOVED/INSULATION FUBAR |
| AC-9 | G203A | MITSUBISHI | MSZA17NA | 410A | REMOTE | 72 | RED | CONDENSATION LEAK/5 BLINK ERROR CODE | MUZ-A17NA | LEFT WING | LIGHTNING PROTECTION REMOVED |
| AC-10 | ? | MITSUBISHI | ? | 410A | ? | ? | ? | N/A | MUZ-A17NA | LEFT WING | LIGHTNING PROTECTION REMOVED |
| AC-11 | G205A | MITSUBISHI | MSZA17NA | 410A | REMOTE | 70 | GREEN | CLEAN FILTERS | MUZ-GL18NA | RIGHT WING | LIGHTNING PROTECTION REMOVED |
| AC-12 | G205B | MITSUBISHI | MSZGL18NA | 410A | REMOTE | 70 | GREEN | CLEAN FILTERS | MUZ-GL18NA | RIGHT WING | LIGHTNING PROTECTION REMOVED |
4th BN
| LABEL # | ROOM # | MAKE | EVAP MODEL # | REFRIGERANT | THERMOSTAT | SET TEMP | STATUS | FAULT | CONDENSOR MODEL # | LOCATION | FAULT |
| BLDG 9160 |
? 139 FRIEDRICH 401TAQP00756 ? REMOTE ? RED CHANGE REMOTE BATTERIES/CHANGE FILTERS/FURTHER TROUBLESHOOT ? ? NEED ROOF ACCESS
BLDG 9162
? 139 INTERTECH 12H49YIMI ? REMOTE ? RED COMPLETELY FUBAR ? ? NEED ROOF ACCESS
GSB
| LABEL # | ROOM # | MAKE | EVAP MODEL # | REFRIGERANT | THERMOSTAT | SET TEMP | STATUS | FAULT | CONDENSOR MODEL # | LOCATION | FAULT |
| GSB | BLDG 9937 |
| AC-1 | 113 | MITSUBISHI | MSZA17NA | 410A | REMOTE | 68 | GREEN | CLEAN WATER | ? | ? | N/A |
| AC-2 | 277 | MITSUBISHI | MSZA17NA | 410A | REMOTE | 65 | RED | CONDENSATION PIPE/WATER DAMAGE | ? | ? | N/A |
| AC-3 | 248 | MITSUBISHI | MSZA17NA | 420A | REMOTE | 64 | GREEN | CONDENSATION PIPE FULL/WATER DAMAGE | ? | ? | N/A |
B CO. BLDG 9940
| AC-1 | B133 | MITSUBISHI | MSZA17NA | 410A | REMOTE | 59 | RED | FAN INOP/WATER DAMAGE/5 BLINK ERROR CODE | MUZ-A17NA | EXTERNAL | FAN INOP |
| AC-2 | B213 | MITSUBISHI | MSZA17NA | 410A | REMOTE | ? | RED | NO POWER TO UNIT | MUZ-A17NA | EXTERNAL | FAN INOP |
| AC-3 | B217 | MITSUBISHI | ? | 410A | ? | ? | RED | NO ACCESS TO ROOM/CYPHER LOCK NEEDS BATTERIES | MUZ-A17NA | EXTERNAL | FAN INOP |
| AC-4 | A114 | MITSUBISHI | MSZA17NA | 410A | REMOTE | ? | RED | NO POWER TO UNIT | MUZ-A17NA | EXTERNAL | FAN INOP |
| AC-5 | A115 | MITSUBISHI | MSZA17NA | 410A | REMOTE | ? | RED | REMOTE NEEDS BATTERIES | MUZ-A17NA | EXTERNAL | N/A |
HAZMAT BLDG 9938
SS-1 111 MITSUBISHI MSZA17NA 410A REMOTE ? GREEN REPLACE BATTERIES IN REMOTE/CLEAN FILTER MUZ-A17NA EXTERNAL FAN INOP
DIVE LOCKER BLDG 9936
AC-1 121 MITSUBISHI MSZA17NA 410A REMOTE 72 GREEN N/A MUZ-A17NA ? N/A
SFASC BLDG 9983
| ? | G102 | MITSUBISHI | PKA-A18HA4 | 410A | YES | 68 | GREEN | 03/10/14 INSTALLATION DATE | ? | ROOF | NO ROOF ACCESS |
| ? | G103 | MITSUBISHI | PKA-A18HA4 | 410A | YES | 70 | GREEN | 03/10/14 INSTALLATION DATE | ? | ROOF | NO ROOF ACCESS |
| ? | G202 | MITSUBISHI | PKA-A18HA4 | 410A | YES | 101 | RED | 03/10/14 INSTALLATION DATE/WATER DAMAGE/ERROR CODE | ? | ROOF | NO ROOF ACCESS |
| ? | G203 | MITSUBISHI | PKA-A18HA4 | 410A | YES | 70 | GREEN | 03/10/14 INSTALLATION DATE | ? | ROOF | NO ROOF ACCESS |
KENNELS BLDG 9785
107TR DAIKIN FTX12NMVSU 410A YES 70 GREEN N/A RX12NMVJU EXTERNAL N/A
External BLDGs
| LABEL # | ROOM # | MAKE | EVAP MODEL # | REFRIGERANT | THERMOSTAT | SET TEMP | STATUS | FAULT | CONDENSOR MODEL # | LOCATION | FAULT |
| INDOOR RANGE | BLDG 9658 |
AC-1 115 MITSUBISHI PKA-A12HA 410A YES 70 GREEN N/A PUYA12NHA3 FAN NOT RUNNING
THOR GYM BLDG 9655
? ? DAIKIN FTX24AXVJU 410A REMOTE 68 GREEN N/A RK24AXVJU ? N/A
LANGUAGE LAB BLDG 9142
AC3 104 DAIKIN FTXS18LVJU 410A REMOTE ? GREEN CHANGE REMOTE BATTERIES ? ? NEED ROOF ACCESS
Sheet2
| BLDG # | ROOM # | LABEL # | MAKE | EVAP MODEL # | REFRIGERANT | THERMOSTAT | CONDENSOR MODEL # | CONDENSOR LOCATION |
| 9934 | H120 | AC-2.0 | MITSUBISHI | PAR-UO1MEDU | 410A | YES | PUMY-P6ONKMU | ROOF CENTER |
| 9934 | H120 | AC-2.1 | MITSUBISHI | PAR-UO1MEDU | 410A | YES | PUMY-P6ONKMU | ROOF CENTER |
| 9934 | G108 | AC-3 | MITSUBISHI | MSZA17NA | 410A | REMOTE | MUZ-A17NA | ROOF CENTER |
| 9934 | G109 | AC-4 | MITSUBISHI | MSZA17NA | 410A | REMOTE | MUZ-A17NA | ROOF CENTER |
| 9934 | G103A | AC-5 | MITSUBISHI | MSZA17NA | 410A | REMOTE | MUZ-A17NA | ROOF LEFT WING |
| 9934 | G103B | AC-6 | MITSUBISHI | MSZA17NA | 410A | REMOTE | MUZ-A17NA | ROOF LEFT WING |
| 9934 | G105A | AC-7 | MITSUBISHI | MSZA17NA | 410A | REMOTE | MUZ-A17NA | ROOF RIGHT WING |
| 9934 | G105B | AC-8 | MITSUBISHI | MSZA17NA | 410A | REMOTE | MUZ-A17NA | ROOF RIGHT WING |
| 9934 | G203A | AC-9 | MITSUBISHI | MSZA17NA | 410A | REMOTE | MUZ-A17NA | ROOF LEFT WING |
| 9934 | G203B | AC-10 | MITSUBISHI | MSZA17NA | 410A | ? | MUZ-A17NA | ROOF LEFT WING |
| 9934 | G205A | AC-11 | MITSUBISHI | MSZA17NA | 410A | REMOTE | MUZ-GL18NA | ROOF RIGHT WING |
| 9934 | G205B | AC-12 | MITSUBISHI | MSZGL18NA | 410A | REMOTE | MUZ-GL18NA | ROOF RIGHT WING |
| 9983 | G202 | N/A | MITSUBISHI | PKA-A18HA4 | 410A | YES | PUZ-A18NHA4 | ROOF CENTER |
| 9160W | 139 | N/A | FRIEDRICH | 401TAQP00756 | 410A | REMOTE | MR12C1J | ROOF LEFT WING |
| 9160E | 139 | N/A | INTERTECH | 12H49YOMI | 410A | ? | 12H49YIMI | ROOF RIGHT WING |
| 9190 | GCR | N/A | DAIKIN | FCQ42TAVJU | 410A | REMOTE | RZQ42MVJU | ROOF CENTER |
File details come from the government source that posted it. Updated .