AC INFO.xlsx

XLSX spreadsheet 41 KB Posted

Attached to
Split-Unit HVAC Replacement
Solicitation number
H9242126QE047
Issued by

About this file

This is an Air Conditioning (AC) inventory and assessment spreadsheet documenting the status of split-unit HVAC systems across multiple buildings at Joint Base Lewis-McChord. The spreadsheet tracks 16 nonfunctional ductless heat pump A/C units requiring replacement, organized by building location (Buildings 9160/9162, 9190, 9934, and 9983), with detailed technical specifications including evaporator and condenser models (predominantly Mitsubishi MSZA17NA, Daikin FTX/FHQ/FCQ series, and other manufacturers), refrigerant types (primarily 410A), thermostat settings (ranging from 59-101 degrees), and current operational status (RED for faulty, GREEN for functional). Each unit entry captures the make/model, room number, fault descriptions, condenser location, and access requirements (roof access, ladder access, or no roof access needed).

The inventory reveals widespread system failures requiring remediation, including error codes (E4, 1102, 5-blink codes), condensation issues, battery-depleted remotes, power failures, and fan inoperability. Additional maintenance issues documented include full condensation pipes, water damage, filter cleaning needs, and lightning protection removal concerns. This technical assessment directly supports the replacement contract H9242126QE047, which requires contractors to remove all 16 nonfunctional units and install new cooling-only split A/C systems with external condensation pumps, purge and test drain lines, and perform full testing. The performance period runs September 28, 2026 through November 12, 2026, with a mandatory site visit on September 18, 2026 at 1:30 p.m. (PDT) at 9190 Cramer Ave and a written questions deadline of September 21, 2026 at 5:00 p.m. (EDT).

View the file

Other files

File Type Posted
AC INFO_update.xlsx XLSX spreadsheet
HVAC Replacement RFIs_additional (002).docx DOCX document
HVAC Replacement RFIs_all.docx DOCX document
Solicitation Amendment H9242126QE0470001 SF 30.pdf PDF
PWS_1SFG_MICC_Split Units_Updated final.docx DOCX document
HVAC Floor Plan_Split Units.pptx PPTX presentation
FAR_52.212-1_Addendum_-_Instructions_to_Offerors_(1SFG_HVAC_Replacement).docx DOCX document
Pierce County Wage Determination.txt TXT text file
HVAC Floor Plan_Split Units.pptx PPTX presentation
PWS_1SFG_MICC_Split Units_Updated_2.docx DOCX document
Solicitation - H9242126QE047 - CO Signed.pdf PDF
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HQ

LABEL #ROOM #MAKEEVAP MODEL #REFRIGERANTTHERMOSTATSET TEMPSTATUSFAULTCONDENSOR MODEL #LOCATIONFAULT
SR 126128DAIKINFTX24NMVJU410AREMOTE72REDNEED TROUBLESHOOT??NEED ROOF ACCESS
?154DAIKINFHQ24PVJU??YES70GREENNEED LADDER TO SEARCH FOR DATA PLATE/ERROR CODE U3??NEED ROOF ACCESS
B11B11DAIKINFHQ24PVJU??YES67GREENNEED LADDER TO SEARCH FOR DATA PLATE??NEED ROOF ACCESS
B11(2)B11DAIKINFHQ24PVJU??YES69GREENNEED LADDER TO SEARCH FOR DATA PLATE??NEED ROOF ACCESS
SR 232B22DAIKINFHQ24PVJU??YES70GREENNEED LADDER TO SEARCH FOR DATA PLATE??NEED ROOF ACCESS
B25(LEFT)B25DAIKINFCQ42TAVJU?YES69REDERROR CODE E4??NEED ROOF ACCESS
B25(RIGHT)B25DAIKINFCQ42TAVJU?YES70REDCLEAN FILTER??NEED ROOF ACCESS
B25(CENTER)B25DAIKINFCQ42TAVJU?YES70GREENN/A??NEED ROOF ACCESS
?GCRDAIKINFCQ42TAVJU ??REMOTE?REDCONDENSATION PUMP??NEED ROOF ACCESS

2nd BN

LABEL #ROOM #MAKEEVAP MODEL #REFRIGERANTTHERMOSTATSET TEMPSTATUSFAULTCONDENSOR MODEL #LOCATIONFAULT
SS-1???????????
SS-2G105ADAIKINFTX12NMVJU410AYES72GREENN/A???
SS-3???????????
SS-4G103BDAIKINFTX12NMVJU410AYES72GREENN/A???
SS-5G103ADAIKINFTX12NMVJU410AYES72GREENN/A???
SS-6G108DAIKINFAQ18PVJU410AYES72GREENN/A???
SS-7G109DAIKINFAQ18PVJU410AYES72GREENN/A???
SS-8H120DAIKINFAQ18PVJU410AYES72GREENN/A???
SS-9G205ADAIKINFTX18NMVJU410AYES72GREENN/A???
SS-10G205BDAIKINFTX18NMVJU410AYES72GREENN/A???
SS-11G203ADAIKINFTX12NMVJU410AYES72GREENN/A???
SS-12G203BDAIKINFTX18NMVJU410AYES72GREENN/A???
SS-13G207DAIKIN?410AYES72GREENN/A???
SS-14G208DAIKIN?410AYES72GREENN/A???
2nd MPBLDG 9946
SS-2108DAIKINFTX18NMVJU410AYES78GREENTHERMOSTAT WAS TURNED OFFRX18NMVJU?

3rd BN

LABEL #ROOM #MAKEEVAP MODEL #REFRIGERANTTHERMOSTATSET TEMPSTATUSFAULTCONDENSOR MODEL #LOCATIONFAULT
AC-1?TRANE?????N/A4TWA3036A4000AACENTERLIGHTNING PROTECTION REMOVED
AC-2.0H120MITSUBISHIPAR-UO1MEDU?YES?REDERROR CODE: 1102PUMY-P6ONKMUCENTERLIGHTNING PROTECTION REMOVED
AC-2.1H120MITSUBISHIPAR-UO1MEDU?YES?REDERROR CODE: 1102PUMY-P6ONKMUCENTERLIGHTNING PROTECTION REMOVED
AC-3G108MITSUBISHIMSZA17NA410AREMOTE72REDPUMP FAIL?/CONDENSATION TUBE FULLMUZ-A17NACENTERLIGHTNING PROTECTION REMOVED
AC-4G109MITSUBISHIMSZA17NA410AREMOTE?REDCHANGE REMOTE BATTERIES/CONDENSATION TUBEMUZ-A17NACENTERLIGHTNING PROTECTION REMOVED
AC-5G103AMITSUBISHIMSZA17NA410AREMOTE72GREENCLEAN REMOTE CONTACTS/CONDENSATION TUBEMUZ-A17NALEFT WINGLIGHTNING PROTECTION REMOVED
AC-6G103BMITSUBISHIMSZA17NA410AREMOTE?REDCHANGE REMOTE BATTERIES/CONDENSATION TUBEMUZ-A17NALEFT WINGLIGHTNING PROTECTION REMOVED
AC-7G105AMITSUBISHIMSZA17NA410AREMOTE?REDREMOTE NEEDS BATTERIESMUZ-A17NARIGHT WINGLIGHTNING PROTECTION REMOVED/INSULATION FUBAR
AC-8G105BMITSUBISHIMSZA17NA410AREMOTE?REDREMOTE NEEDS BATTERIESMUZ-A17NARIGHT WINGLIGHTNING PROTECTION REMOVED/INSULATION FUBAR
AC-9G203AMITSUBISHIMSZA17NA410AREMOTE72REDCONDENSATION LEAK/5 BLINK ERROR CODEMUZ-A17NALEFT WINGLIGHTNING PROTECTION REMOVED
AC-10?MITSUBISHI?410A???N/AMUZ-A17NALEFT WINGLIGHTNING PROTECTION REMOVED
AC-11G205AMITSUBISHIMSZA17NA410AREMOTE70GREENCLEAN FILTERSMUZ-GL18NARIGHT WINGLIGHTNING PROTECTION REMOVED
AC-12G205BMITSUBISHIMSZGL18NA410AREMOTE70GREENCLEAN FILTERSMUZ-GL18NARIGHT WINGLIGHTNING PROTECTION REMOVED

4th BN

LABEL #ROOM #MAKEEVAP MODEL #REFRIGERANTTHERMOSTATSET TEMPSTATUSFAULTCONDENSOR MODEL #LOCATIONFAULT
BLDG 9160

? 139 FRIEDRICH 401TAQP00756 ? REMOTE ? RED CHANGE REMOTE BATTERIES/CHANGE FILTERS/FURTHER TROUBLESHOOT ? ? NEED ROOF ACCESS

BLDG 9162

? 139 INTERTECH 12H49YIMI ? REMOTE ? RED COMPLETELY FUBAR ? ? NEED ROOF ACCESS

GSB

LABEL #ROOM #MAKEEVAP MODEL #REFRIGERANTTHERMOSTATSET TEMPSTATUSFAULTCONDENSOR MODEL #LOCATIONFAULT
GSBBLDG 9937
AC-1113MITSUBISHIMSZA17NA410AREMOTE68GREENCLEAN WATER??N/A
AC-2277MITSUBISHIMSZA17NA410AREMOTE65REDCONDENSATION PIPE/WATER DAMAGE??N/A
AC-3248MITSUBISHIMSZA17NA420AREMOTE64GREENCONDENSATION PIPE FULL/WATER DAMAGE??N/A

B CO. BLDG 9940

AC-1B133MITSUBISHIMSZA17NA410AREMOTE59REDFAN INOP/WATER DAMAGE/5 BLINK ERROR CODEMUZ-A17NAEXTERNALFAN INOP
AC-2B213MITSUBISHIMSZA17NA410AREMOTE?REDNO POWER TO UNITMUZ-A17NAEXTERNALFAN INOP
AC-3B217MITSUBISHI?410A??REDNO ACCESS TO ROOM/CYPHER LOCK NEEDS BATTERIESMUZ-A17NAEXTERNALFAN INOP
AC-4A114MITSUBISHIMSZA17NA410AREMOTE?REDNO POWER TO UNITMUZ-A17NAEXTERNALFAN INOP
AC-5A115MITSUBISHIMSZA17NA410AREMOTE?REDREMOTE NEEDS BATTERIESMUZ-A17NAEXTERNALN/A

HAZMAT BLDG 9938

SS-1 111 MITSUBISHI MSZA17NA 410A REMOTE ? GREEN REPLACE BATTERIES IN REMOTE/CLEAN FILTER MUZ-A17NA EXTERNAL FAN INOP

DIVE LOCKER BLDG 9936

AC-1 121 MITSUBISHI MSZA17NA 410A REMOTE 72 GREEN N/A MUZ-A17NA ? N/A

SFASC BLDG 9983

?G102MITSUBISHIPKA-A18HA4410AYES68GREEN03/10/14 INSTALLATION DATE?ROOFNO ROOF ACCESS
?G103MITSUBISHIPKA-A18HA4410AYES70GREEN03/10/14 INSTALLATION DATE?ROOFNO ROOF ACCESS
?G202MITSUBISHIPKA-A18HA4410AYES101RED03/10/14 INSTALLATION DATE/WATER DAMAGE/ERROR CODE?ROOFNO ROOF ACCESS
?G203MITSUBISHIPKA-A18HA4410AYES70GREEN03/10/14 INSTALLATION DATE?ROOFNO ROOF ACCESS

KENNELS BLDG 9785

107TR DAIKIN FTX12NMVSU 410A YES 70 GREEN N/A RX12NMVJU EXTERNAL N/A

External BLDGs

LABEL #ROOM #MAKEEVAP MODEL #REFRIGERANTTHERMOSTATSET TEMPSTATUSFAULTCONDENSOR MODEL #LOCATIONFAULT
INDOOR RANGEBLDG 9658

AC-1 115 MITSUBISHI PKA-A12HA 410A YES 70 GREEN N/A PUYA12NHA3 FAN NOT RUNNING

THOR GYM BLDG 9655

? ? DAIKIN FTX24AXVJU 410A REMOTE 68 GREEN N/A RK24AXVJU ? N/A

LANGUAGE LAB BLDG 9142

AC3 104 DAIKIN FTXS18LVJU 410A REMOTE ? GREEN CHANGE REMOTE BATTERIES ? ? NEED ROOF ACCESS

Sheet2

BLDG #ROOM #LABEL #MAKEEVAP MODEL #REFRIGERANTTHERMOSTATCONDENSOR MODEL #CONDENSOR LOCATION
9934H120AC-2.0MITSUBISHIPAR-UO1MEDU410AYESPUMY-P6ONKMUROOF CENTER
9934H120AC-2.1MITSUBISHIPAR-UO1MEDU410AYESPUMY-P6ONKMUROOF CENTER
9934G108AC-3MITSUBISHIMSZA17NA410AREMOTEMUZ-A17NAROOF CENTER
9934G109AC-4MITSUBISHIMSZA17NA410AREMOTEMUZ-A17NAROOF CENTER
9934G103AAC-5MITSUBISHIMSZA17NA410AREMOTEMUZ-A17NAROOF LEFT WING
9934G103BAC-6MITSUBISHIMSZA17NA410AREMOTEMUZ-A17NAROOF LEFT WING
9934G105AAC-7MITSUBISHIMSZA17NA410AREMOTEMUZ-A17NAROOF RIGHT WING
9934G105BAC-8MITSUBISHIMSZA17NA410AREMOTEMUZ-A17NAROOF RIGHT WING
9934G203AAC-9MITSUBISHIMSZA17NA410AREMOTEMUZ-A17NAROOF LEFT WING
9934G203BAC-10MITSUBISHIMSZA17NA410A?MUZ-A17NAROOF LEFT WING
9934G205AAC-11MITSUBISHIMSZA17NA410AREMOTEMUZ-GL18NAROOF RIGHT WING
9934G205BAC-12MITSUBISHIMSZGL18NA410AREMOTEMUZ-GL18NAROOF RIGHT WING
9983G202N/AMITSUBISHIPKA-A18HA4410AYESPUZ-A18NHA4ROOF CENTER
9160W139N/AFRIEDRICH401TAQP00756410AREMOTEMR12C1JROOF LEFT WING
9160E139N/AINTERTECH12H49YOMI410A?12H49YIMIROOF RIGHT WING
9190GCRN/ADAIKINFCQ42TAVJU410AREMOTERZQ42MVJUROOF CENTER

File details come from the government source that posted it. Updated .