GR Service Elevator 3_Drawings.pdf

PDF 10 MB Posted

Attached to
Elevator Modernization- Grand Rapids, MI Federal contract opportunity
Solicitation number
47PF0025R0027
Issued by
General Services Administration Public Buildings Service Region 5

About this file

These are architectural and engineering drawings for an elevator modernization project at the Gerald R. Ford Federal Building in Grand Rapids, Michigan. The comprehensive set of documents includes detailed plans for renovating multiple elevators, specifically focusing on Service Elevator 3, with drawings covering architectural, electrical, and mechanical aspects of the project. The documents are prepared by Forbes Associates Architects and Peter Basso Associates Engineering, dated April 26, 2024, and marked as Final 100% Construction Documents.

The drawings provide extensive technical specifications for a complete elevator system overhaul, including detailed floor plans, electrical schematics, fire alarm systems, machine room layouts, and elevator lobby elevations. Key elements include replacing hoisting machines, control panels, electrical systems, mechanical equipment, lighting, and cab interiors. The project involves modernization of elevator infrastructure across multiple building levels, from the sub-basement to the penthouse, with particular attention to safety systems, emergency operations, and compliance with ASME A17.1 safety codes. The technical drawings demonstrate a comprehensive approach to upgrading the building's vertical transportation system while maintaining existing architectural and structural integrity.

View the file

Other files for this federal contract opportunity

Other files attached to Elevator Modernization- Grand Rapids, MI, newest first.
File Type Posted
47PF0025R0027_Amendment 0002.pdf PDF
47PF0025R0027_Amendment 0001.pdf PDF
Preproposal Conf Sign In Sheet_GR Elevator Modernization.pdf PDF
Preproposal Conf Agenda_GR Elevator Modernization.pdf PDF
GR Passenger Elevators 1_2_4_Drawings.pdf PDF
GR Service Elevator Spec_REV03.pdf PDF
GR Passenger Elevator Spec_REV03.pdf PDF
Preproposal Mtg Registration_GR Elevator.pdf PDF
RFP 47PF0025R0027.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

DEJ

G-001

Gerald R. Ford Federal Building MI0137ZZ

110 Michigan St. NW

Grand Rapids, Michigan 49503

Elevator Modernization - Service Elevator

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

DEJ

G-002

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

G-003

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

G-004

FLOOR PLAN

ELEVATOR PITS

A-101

ELEVATOR PIT ACCESS ROOM

ELEVATOR PIT

ELEVATOR PIT ACCESS ROOM

ELEVATOR PIT

ELEVATOR PIT ACCESS ROOM

ELEVATOR PIT

ELEVATOR PIT ACCESS ROOM

ELEVATOR PIT

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

VARIES

A-102

ELEVATOR LOBBY

CORRIDOR

CORRIDOR

ELEVATOR LOBBY

CORRIDOR

ELEVATOR LOBBY

ELEVATOR PIT ACCESS ROOM

CORRIDOR

HOISTWAY

HOISTWAY

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

FIRST FLOOR

A-103

ELEVATOR LOBBY

CORRIDOR

ELEVATOR LOBBY

VAULT

HOISTWAY

HOISTWAY

STORAGE JANITOR

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

DEJ

GUARD ROOM

A-104

ELEVATOR LOBBY

CORRIDOR

ELEVATOR LOBBY

CORRIDOR

HOISTWAY

HOISTWAY

STORAGE JANITOR

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

PENTHOUSE

A-105

CORRIDOR

CORRIDOR

MECHANICAL ROOM

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

DEJ

ELEVATOR SECONDARY

SPACE

ELEVATOR SECONDARY

SPACE

MACHINE ROOM PENTHOUSE

A-106

ELEVATOR

MACHINE ROOM

ELEVATOR

MACHINE ROOM

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

In Case Of Fire

Elevators Are Out Of Service

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

COD E B LUE

O

N

OFF

USE EXIT

USE EXIT

USE EXIT

USE EXIT

USE EXIT

USE EXIT

USE EXIT

USE EXIT

USE EXIT

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

COD E B LUE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

COD E B LUE

O

N

OFF

CODE

BLUE

In Case Of Fire

Elevators Are Out Of Service

C

ODE BL UE

O

N

OFF

USE EXIT

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

CODE BL UE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

CODE BL UE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

CODE BL UE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

CODE BL UE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

CODE BL UE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

CODE BL UE

O

N

OFF

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

CODE BL UE

O

N

OFF

ELEVATIONS

VARIES

A-201

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

ELEVATION

A-202

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

ELEVATOR

PIT ACCESS

ELEVATOR

PIT ACCESS

ELEVATOR LOBBY

ELEVATOR LOBBY

ELEVATOR LOBBY

ELEVATOR

#2

ELEVATOR

#3

ELEVATOR MACHINE ROOM

PENTHOUSE

VARIES

A-301

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

SECTION

SECTIONS

A-302

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

MACHINE ROOM PENTHOUSE

Q-106

ELEVATOR

MACHINE ROOM

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

4/26/2024

D

D

H

H

CAPACITY 3000 LBS.

OPEN CLOSE

4 3

NO

TO USE EMERGENCY

TELEPHONE, PRESS

BUTTON ABOVE.

DIALING WILL OCCUR

AUTOMATICALLY.

ELEVATOR 3

CALL HAS BEEN

RECEIVED

FIREFIGHTERS

OPERATION

NO SMOKING

YES

SBB

OFF

O

N

OPEN CLOSE

2R

4R

6R

BR

1R

3R

5R

7R

SBR

HD

OPEN CLOSE

2R

4R

6R

BR

1R

3R

5R

7R

SBR

D H

D

H

SECURITY PLANS

VARIES

Q-201

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

PIT ACCESS

ELEVATOR

PIT ACCESS

ELEVATOR LOBBY

ELEVATOR LOBBY

ELEVATOR LOBBY

ELEVATOR

#2

ELEVATOR

#3

ELEVATOR MACHINE ROOM

PENTHOUSE

1 2

3 4

ELEVATOR

EMERGENCY

POWER

DOOR

OPEN

C

O

D

E

B

L

U

E

O

N

OFF

FIREFIGHTERS' OPERATION

TO RECALL ELEVATORS

INSERT FIRE KEY AND TURN TO "ON"

C

O

D

E

B

L

U

E

O

N

OFF

C

O

D

E

B

L

U

E

O

N

OFF

C

O

D

E

B

L

U

E

O

N

OFF

ELEVATOR

EMERGENCY

POWER

DOOR

OPEN

ELEVATOR

EMERGENCY

POWER

DOOR

OPEN

ELEVATOR

EMERGENCY

POWER

DOOR

OPEN

A

U

T

O

FLOOR PLAN-EXISTING/DEMO

VARIES

Q-301

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

C

O

D

E

B

L

U

E

O

N

OFF

ELEVATOR

EMERGENCY

POWER

B

U

Z

Z

E

R

T

E

X

T

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

In Case Of Fire

Elevators Are Out Of Service

USE EXIT

C

O

D

E

B

L

U

E

O

N

OFF

EQUIPMENT DETAILS

VARIES

Q-501

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

Elevator Modernization -

Service Elevator

RMI12652

PRELIMINARY DESIGN

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

AS

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

CAPACITY 3000 LBS.

OPEN CLOSE

4 3

NO

TO USE EMERGENCY

TELEPHONE, PRESS

BUTTON ABOVE.

DIALING WILL OCCUR

AUTOMATICALLY.

ELEVATOR 3

CALL HAS BEEN

RECEIVED

FIREFIGHTERS

OPERATION

NO SMOKING

YES

SBB

OFF

O

N

OPEN CLOSE

2R

4R

6R

BR

1R

3R

5R

7R

SBR

HD

ELEV EQUIP DETAILS

VARIES

Q-502

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

FIRE ALARM PLAN

FA-101

ELEVATOR PIT ACCESS ROOM

ELEVATOR PIT

ELEVATOR PIT ACCESS ROOM

ELEVATOR PIT

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

FIRST FLOOR

RECALL LANDING (1)

BASEMENT

SECOND FLOOR

RECALL LANDING (2)

THIRD TO SEVENTH

FLOOR - TYP.

PENTHOUSE

F.A.

PANEL

SUB-BASEMENT

MACHINE ROOM

PENTHOUSE

ELEVATOR PIT

FIRST FLOOR

RECALL LANDING (1)

BASEMENT

SECOND FLOOR

RECALL LANDING (2)

MACHINE ROOM

PENTHOUSE

F.A.

PANEL

SUB-BASEMENT

THIRD TO SEVENTH

FLOOR - TYP.

PENTHOUSE

ELEVATOR PIT

FIRE ALARM DIAGRAMS

VARIES

FA-102

General Services Administration

Public Buildings Service

Great Lakes

G. R. Ford Federal Building

110 Michigan St NW

Grand Rapids, MI 49503

MI0137ZZ

ELEVATOR MODERNIZATION -

SERVICE ELEVATOR

RMI12652

Design and Construction, Project Delivery Division

John C. Kluczynski Federal Building

230 South Dearborn St.

Chicago, IL 60604

MARK DATE DESCRIPTION

ARCHITECTURAL

816 E 4th ST.

Royal Oak, MI 48067

248.542.7866/www.ghfaa.com

SWG

A S S O C I A T E S A R C H I T E C T S

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED

CONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

FINAL 100% CONST. DOCS

816 E 4th ST.

Royal Oak, MI 48067 248.542.7866/www.ghfaa.com

A S S O C I A T E S A R C H I T E C T S

5145 Livernois, Suite 100

Fax: 248-879-0007 Troy, Michigan 48098-3276

Tel: 248-879-5666 www.PeterBassoAssociates.com

CONSULTING ENGINEERS

Peter Basso Associates Inc

PBA Project No.: 2023.0045

ST

AM

P O

R S

EA

L

BU

IL

D

IN

G

PR

O

JE

C T

G

RA

PH

IC

S

CA

LE

D

ES

IG

N

ER

ID

EN

TI

FI

C

AT

IO

N

C O

N

SU

LT

AN

T

ID

EN

TI

FI

C

AT

IO

N R

EV

IS

IO

N

B

LO

C K

Elevator Modernization -

SCHEMATIC DESIGN

06/26/2023

ELECTRICAL

STAGE

SUBMISSION DATE

PROJECT TITLE

DRAWN BY

CHECKED BY

FLOOR NO.

DISCIPLINE

PLAN TYPE

SHEET NUMBER

AND FILENAME

KE

Y

PL

AN

GSA PROJECT NO.RMI12652

General Services Administration Public Buildings Service

Great Lakes

G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503

MI0137ZZ

Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.

Chicago, IL 60604

SH

EE

T

47PF0021F0046

GP-05-P13-SVD-0030

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

Service Elevator

95% REVIEW DOCUMENTS09/29/2023

100% REVIEW DOCUMENTS04/16/2024

FINAL 100% CONST. DOCS04/26/2024

SYMBOLS AND INDEX

E-001

EMG

SMB

N/A

248.542.7866/www.ghfaa.com

A S S O C I A T E S A R C H I T E C T S

5145 Livernois, Suite 100

Fax: 248-879-0007 Troy, Michigan 48098-3276

Tel: 248-879-5666 www.PeterBassoAssociates.com

CONSULTING ENGINEERS

Peter Basso Associates Inc

PBA Project No.: 2023.0045

ST

AM

P O

R S

EA

L

BU

IL

D

IN

G

PR

O

JE

C T

G

RA

PH

IC

S

CA

LE

D

ES

IG

N

ER

ID

EN

TI

FI

C

AT

IO

N

C O

N

SU

LT

AN

T

ID

EN

TI

FI

C

AT

IO

N R

EV

IS

IO

N

B

LO

C K

Elevator Modernization -

SCHEMATIC DESIGN

06/26/2023

ELECTRICAL

STAGE

SUBMISSION DATE

PROJECT TITLE

DRAWN BY

CHECKED BY

FLOOR NO.

DISCIPLINE

PLAN TYPE

SHEET NUMBER

AND FILENAME

KE

Y

PL

AN

GSA PROJECT NO.RMI12652

General Services Administration Public Buildings Service

Great Lakes

G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503

MI0137ZZ

Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.

Chicago, IL 60604

SH

EE

T

47PF0021F0046

GP-05-P13-SVD-0030

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

Service Elevator

95% REVIEW DOCUMENTS09/29/2023

100% REVIEW DOCUMENTS04/16/2024

FINAL 100% CONST. DOCS04/26/2024

SCHEDULES

E-002

EMG

MACHINE ROOM

816 E 4th ST.

Royal Oak, MI 48067 248.542.7866/www.ghfaa.com

A S S O C I A T E S A R C H I T E C T S

5145 Livernois, Suite 100

Fax: 248-879-0007 Troy, Michigan 48098-3276

Tel: 248-879-5666 www.PeterBassoAssociates.com

CONSULTING ENGINEERS

Peter Basso Associates Inc

PBA Project No.: 2023.0045

ST

AM

P O

R S

EA

L

BU

IL

D

IN

G

PR

O

JE

C T

G

RA

PH

IC

S

CA

LE

D

ES

IG

N

ER

ID

EN

TI

FI

C

AT

IO

N

C O

N

SU

LT

AN

T

ID

EN

TI

FI

C

AT

IO

N R

EV

IS

IO

N

B

LO

C K

Elevator Modernization -

SCHEMATIC DESIGN

06/26/2023

ELECTRICAL

STAGE

SUBMISSION DATE

PROJECT TITLE

DRAWN BY

CHECKED BY

FLOOR NO.

DISCIPLINE

PLAN TYPE

SHEET NUMBER

AND FILENAME

KE

Y

PL

AN

GSA PROJECT NO.RMI12652

General Services Administration Public Buildings Service

Great Lakes

G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503

MI0137ZZ

Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.

Chicago, IL 60604

SH

EE

T

47PF0021F0046

GP-05-P13-SVD-0030

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

Service Elevator

95% REVIEW DOCUMENTS09/29/2023

100% REVIEW DOCUMENTS04/16/2024

FINAL 100% CONST. DOCS04/26/2024

DEMOLITION AND NEW WORK

E-307

EMG

ELEVATOR - PENTHOUSE

248.542.7866/www.ghfaa.com

A S S O C I A T E S A R C H I T E C T S

5145 Livernois, Suite 100

Fax: 248-879-0007 Troy, Michigan 48098-3276

Tel: 248-879-5666 www.PeterBassoAssociates.com

CONSULTING ENGINEERS

Peter Basso Associates Inc

PBA Project No.: 2023.0045

ST

AM

P O

R S

EA

L

BU

IL

D

IN

G

PR

O

JE

C T

G

RA

PH

IC

S

CA

LE

D

ES

IG

N

ER

ID

EN

TI

FI

C

AT

IO

N

C O

N

SU

LT

AN

T

ID

EN

TI

FI

C

AT

IO

N R

EV

IS

IO

N

B

LO

C K

Elevator Modernization -

SCHEMATIC DESIGN

06/26/2023

ELECTRICAL

STAGE

SUBMISSION DATE

PROJECT TITLE

DRAWN BY

CHECKED BY

FLOOR NO.

DISCIPLINE

PLAN TYPE

SHEET NUMBER

AND FILENAME

KE

Y

PL

AN

GSA PROJECT NO.RMI12652

General Services Administration Public Buildings Service

Great Lakes

G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503

MI0137ZZ

Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.

Chicago, IL 60604

SH

EE

T

47PF0021F0046

GP-05-P13-SVD-0030

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

Service Elevator

95% REVIEW DOCUMENTS09/29/2023

100% REVIEW DOCUMENTS04/16/2024

FINAL 100% CONST. DOCS04/26/2024

DIAGRAM

E-501

EMG

EXISTING PANELBOARD ELEV-3&4

# LOAD

TYPE DESCRIPTION CB

TYPE CB VA ØA ØB ØC VA CB CB

TYPE DESCRIPTION LOAD

TYPE #

1 NC

ELEVATOR 3

EXIST

13025 22724 9699

EXIST

ELEVATOR 4

NC 2

3 NC EXIST 13025 22724 9699 EXIST NC 4

5 NC EXIST 13025 22724 9699 EXIST NC 6

7 SPARE EXIST 20 2105 2105 15 EXIST VF-1 NC 8

9 NC ELEVATOR 3&4 CAB LIGHTING EXIST 20 100 100 20 EXIST SPARE 10

11 NC ELEVATOR 3&4 CAB CONTROLS EXIST 20 100 100 20 EXIST SPARE 12

13 SPARE EXIST 20 20 EXIST SPARE 14

15 E

EUH-1

EXIST

1690 1690 20 EXIST SPARE 16

17 E EXIST 1690 1690 20 EXIST SPARE 18

19 E EXIST 1690 1690 20 EXIST SPARE 20

21 SPARE EXIST 20 20 EXIST SPARE 22

23 SPARE EXIST 20 20 EXIST SPARE 24

25 SPARE EXIST 20 20 EXIST SPARE 26

27 SPARE EXIST 20 20 EXIST SPARE 28

29 SPARE EXIST 20 20 EXIST SPARE 30

26519 24514 24514

ØA ØB ØC

FEEDER AND

OVERCURRENT SIZING

PANELBOARD INFORMATION DEMAND

FACTOR

CALCULATED

LOADVOLTAGE: 480Y/277 BRANCH CIRCUIT CONNECTED LOAD NOTES:

BUS AMPACITY: 225A CONTINUOUS LOAD (C) 100% 125%

MAIN TYPE: 200A MCB ELECTRIC HEAT (E) 5070 100% 5070 100% 5070

MINIMUM A.I.C.: 35,000 NON-CONTINUOUS LOAD (NC) 70477 100% 70477 100% 70477

MOUNTING: SURFACE KITCHEN LOAD (K) 100% 100%

RECEPTACLE BASE LOAD (R) 100% 100%

FEED-THROUGH LUGS RECEPTACLE DEMAND LOAD (R) 50% 100%

DOUBLE LUGS LIGHTING LOAD (L) 100% 125%

INTEGRAL SPD ADDITIONAL TRACK LIGHTING LOAD 100%

MOTORS, HIGHEST LOAD (MH) 125% 100%

PANELBOARD LOCATION MOTORS, REMAINING LOAD (M) 100% 100%

NOTE: DEMAND AND SIZING INFORMATION IS CALCULATED

FROM CONNECTED LOAD

TOTAL(KVA): 75.55

TOTAL (AMPS): 91 TOTAL (AMPS): 91

© Copyright 2021 by Peter Basso Associates, Inc

EXISTING PANELBOARD ELEV-1&2

# LOAD

TYPE DESCRIPTION CB

TYPE CB VA ØA ØB ØC VA CB CB

TYPE DESCRIPTION LOAD

TYPE #

1 NC

ELEVATOR 1

EXIST

9699 19398 9699

EXIST

ELEVATOR 2

NC 2

3 NC EXIST 9699 19398 9699 EXIST NC 4

5 NC EXIST 9699 19398 9699 EXIST NC 6

7 L LTG - PENTHOUSE EXIST 20 471 7245 6774

EXIST

ELEV-A

C 8

9 NC ELEVATOR 1&2 CAB LIGHTING EXIST 20 50 7298 7248 EXIST C 10

11 NC ELEVATOR 1&2 CAB CONTROLS EXIST 20 50 5520 5470 EXIST C 12

13 L LTG - PENTHOUSE MACHINE ROOM EXIST 20 471 471 20 EXIST SPARE 14

15 E

EUH-2

EXIST

1690 1690 20 EXIST SPARE 16

17 E EXIST 1690 1690 20 EXIST SPARE 18

19 E EXIST 1690 1690 20 EXIST SPARE 20

21 SPARE EXIST 20 20 EXIST SPARE 22

23 SPARE EXIST 20 20 EXIST SPARE 24

25 SPARE EXIST 20 20 EXIST SPARE 26

27 SPARE EXIST 20 20 EXIST SPARE 28

29 SPARE EXIST 20 20 EXIST SPARE 30

28804 28386 26608

ØA ØB ØC

FEEDER AND

OVERCURRENT SIZING

PANELBOARD INFORMATION DEMAND

FACTOR

CALCULATED

LOADVOLTAGE: 480Y/277 BRANCH CIRCUIT CONNECTED LOAD NOTES:

BUS AMPACITY: 225A CONTINUOUS LOAD (C) 19492 100% 19492 125% 24365

MAIN TYPE: 200A MCB ELECTRIC HEAT (E) 5070 100% 5070 100% 5070

MINIMUM A.I.C.: 35,000 NON-CONTINUOUS LOAD (NC) 58294 100% 58294 100% 58294

MOUNTING: SURFACE KITCHEN LOAD (K) 100% 100%

RECEPTACLE BASE LOAD (R) 100% 100%

FEED-THROUGH LUGS RECEPTACLE DEMAND LOAD (R) 50% 100%

DOUBLE LUGS LIGHTING LOAD (L) 942 100% 942 125% 1178

INTEGRAL SPD ADDITIONAL TRACK LIGHTING LOAD 100%

MOTORS, HIGHEST LOAD (MH) 125% 100%

PANELBOARD LOCATION MOTORS, REMAINING LOAD (M) 100% 100%

NOTE: DEMAND AND SIZING INFORMATION IS CALCULATED

FROM CONNECTED LOAD

TOTAL(KVA): 83.80

TOTAL (AMPS): 101 TOTAL (AMPS): 107

© Copyright 2021 by Peter Basso Associates, Inc

EXISTING PANELBOARD EM

# LOAD

TYPE DESCRIPTION CB

TYPE CB VA ØA ØB ØC VA CB CB

TYPE DESCRIPTION LOAD

TYPE #

1 L S STAIRWAY EXIT LIGHTS EXIST 20 100 200 100 20 EXIST W STAIRWAY EXIT LIGHTS L 2 3 R E TELEPHONE CLOSET RCPTS EXIST 20 360 460 100 20 EXIST W STAIRWAY EXIT LIGHTS L 4 5 L S STAIRWAY BATTERY LIGHTS EXIST 20 500 680 180 20 EXIST PHONE ROOM ISO KTWIST LOCK R 6

7 L BATTERY LIGHTS EXIST 20 500 680 180 20 EXIST B62 RCPT R 8

9 R W TELEPHONE CLOSE RCPT EXIST 20 180 360 180 20 EXIST FIRE PUMP RM RCPT R 10

11 L N CENTER HALL EXIT LIGHTS EXIST 20 100 300 200 20 EXIST CLOCK SYSTEM NC 12

13 R ELEVATOR PIT - RCPT EXIST 20 1080 2080 1000

EXIST

PHONE RM RCPT

R 14

15 R B70 RCPT EXIST 20 180 1180 1000 EXIST R 16

17 L E STAIRWAY EXIT LIGHTS EXIST 20 100 300 200 20 EXIST INTERFACE UNITS SECUIRTY RM NC 18 19 R BOIELR LEAD LAG CONTROK RCPT EXIST 20 180 380 200 20 EXIST INTERFACE UNITS GARAGE NC 20 21 NC JOHNSON CONTROL PANEL CLOCK SYSTEM EXIST 20 200 250 50 20 EXIST KEY CARD SYSTEM NC 22

23 R RM B58 RCPT EXIST 20 180 380 200 20 EXIST B7FA CONTROL NC 24

25 C

LPA (FIRE ALARM PANEL)

EXIST

2000 2200 200 20 EXIST B7FA CONTROL NC 26

27 C EXIST 2000 6000 4000

EXIST

PANEL B44

C 28

29 C EXIST 2000 6000 4000 EXIST C 30

31 SPARE EXIST 20 4000 4000 EXIST C 32

33 SPARE EXIST 20 20 EXIST SPARE 34

35 R B70 RCPT EXIST 20 180 180 20 EXIST SPARE 36

SPARE

EXIST

40 40

EXIST

SPARE

39 EXIST EXIST 40

41 EXIST EXIST 42

9540 8250 7840

ØA ØB ØC

FEEDER AND

OVERCURRENT SIZING

PANELBOARD INFORMATION DEMAND

FACTOR

CALCULATED

LOADVOLTAGE: 208Y/120 BRANCH CIRCUIT CONNECTED LOAD NOTES:

BUS AMPACITY: 100A CONTINUOUS LOAD (C) 18000 100% 18000 125% 22500

MAIN TYPE: 100A MCB ELECTRIC HEAT (E) 100% 100%

MINIMUM A.I.C.: 22,000 NON-CONTINUOUS LOAD (NC) 1250 100% 1250 100% 1250

MOUNTING: SURFACE KITCHEN LOAD (K) 100% 100%

RECEPTACLE BASE LOAD (R) 4880 100% 4880 100% 4880

FEED-THROUGH LUGS RECEPTACLE DEMAND LOAD (R) 50% 100%

DOUBLE LUGS LIGHTING LOAD (L) 1500 100% 1500 125% 1875

INTEGRAL SPD ADDITIONAL TRACK LIGHTING LOAD 100%

MOTORS, HIGHEST LOAD (MH) 125% 100%

PANELBOARD LOCATION MOTORS, REMAINING LOAD (M) 100% 100%

BASEMENT SUBSTATION RM

NOTE: DEMAND AND SIZING INFORMATION IS CALCULATED

FROM CONNECTED LOAD

TOTAL(KVA): 25.63

TOTAL (AMPS): 71 TOTAL (AMPS): 85

© Copyright 2021 by Peter Basso Associates, Inc

EXISTING PANELBOARD ELEV-A

# LOAD

TYPE DESCRIPTION CB

TYPE CB VA ØA ØB ØC VA CB CB

TYPE DESCRIPTION LOAD

TYPE #

1 L ELEVATOR PIT AND SHAFT - LIGHTS EXIST 20 1100 2868 1768

EXIST

ACU-1

NC 2

3 NC

ACU-3

EXIST

1768 3536 1768 EXIST NC 4

5 NC EXIST 1768 3536 1768

EXIST

ACU-2

NC 6

7 R RCPT - ELEVATOR EXIST 20 360 2128 1768 EXIST NC 8

9 M

SP-3

EXIST

1144 1934 790

EXIST

SP-2

M 10

11 M EXIST 1144 1934 790 EXIST M 12

13 MH

SP-1

EXIST

1778 1778 20 EXIST SPARE 14

15 MH EXIST 1778 1778 20 EXIST SPARE 16

17 SPARE EXIST 20 20 EXIST SPARE 18

19 SPARE EXIST 20 20 EXIST SPARE 20

21 SPARE EXIST 20 20 EXIST SPARE 22

23 SPARE EXIST 20 20 EXIST SPARE 24

25 SPARE EXIST 20 20 EXIST SPARE 26

27 SPARE EXIST 20 20 EXIST SPARE 28

29 SPARE EXIST 20 20 EXIST SPARE 30

6774 7248 5470

ØA ØB ØC

FEEDER AND

OVERCURRENT SIZING

PANELBOARD INFORMATION DEMAND

FACTOR

CALCULATED

LOADVOLTAGE: 208Y/120 BRANCH CIRCUIT CONNECTED LOAD NOTES:

BUS AMPACITY: 100A CONTINUOUS LOAD (C) 100% 125%

MAIN TYPE: 100A MCB ELECTRIC HEAT (E) 100% 100%

MINIMUM A.I.C.: 22,000 NON-CONTINUOUS LOAD (NC) 10608 100% 10608 100% 10608

MOUNTING: SURFACE KITCHEN LOAD (K) 100% 100%

RECEPTACLE BASE LOAD (R) 360 100% 360 100% 360

FEED-THROUGH LUGS RECEPTACLE DEMAND LOAD (R) 50% 100%

DOUBLE LUGS LIGHTING LOAD (L) 1100 100% 1100 125% 1375

INTEGRAL SPD ADDITIONAL TRACK LIGHTING LOAD 100%

MOTORS, HIGHEST LOAD (MH) 3556 125% 4445 100% 4445

PANELBOARD LOCATION MOTORS, REMAINING LOAD (M) 3868 100% 3868 100% 3868

NOTE: DEMAND AND SIZING INFORMATION IS CALCULATED

FROM CONNECTED LOAD

TOTAL(KVA): 20.38

TOTAL (AMPS): 57 TOTAL (AMPS): 57

© Copyright 2021 by Peter Basso Associates, Inc

816 E 4th ST.

Royal Oak, MI 48067 248.542.7866/www.ghfaa.com

A S S O C I A T E S A R C H I T E C T S

5145 Livernois, Suite 100

Fax: 248-879-0007 Troy, Michigan 48098-3276

Tel: 248-879-5666 www.PeterBassoAssociates.com

CONSULTING ENGINEERS

Peter Basso Associates Inc

PBA Project No.: 2023.0045

ST

AM

P O

R S

EA

L

BU

IL

D

IN

G

PR

O

JE

C T

G

RA

PH

IC

S

CA

LE

D

ES

IG

N

ER

ID

EN

TI

FI

C

AT

IO

N

C O

N

SU

LT

AN

T

ID

EN

TI

FI

C

AT

IO

N R

EV

IS

IO

N

B

LO

C K

Elevator Modernization -

SCHEMATIC DESIGN

06/26/2023

ELECTRICAL

STAGE

SUBMISSION DATE

PROJECT TITLE

DRAWN BY

CHECKED BY

FLOOR NO.

DISCIPLINE

PLAN TYPE

SHEET NUMBER

AND FILENAME

KE

Y

PL

AN

GSA PROJECT NO.RMI12652

General Services Administration Public Buildings Service

Great Lakes

G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503

MI0137ZZ

Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.

Chicago, IL 60604

SH

EE

T

47PF0021F0046

GP-05-P13-SVD-0030

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

Service Elevator

95% REVIEW DOCUMENTS09/29/2023

100% REVIEW DOCUMENTS04/16/2024

FINAL 100% CONST. DOCS04/26/2024

SCHEDULES

E-502

EMG

248.542.7866/www.ghfaa.com

A S S O C I A T E S A R C H I T E C T S

5145 Livernois, Suite 100

Fax: 248-879-0007 Troy, Michigan 48098-3276

Tel: 248-879-5666 www.PeterBassoAssociates.com

CONSULTING ENGINEERS

Peter Basso Associates Inc

PBA Project No.: 2023.0045

ST

AM

P O

R S

EA

L

BU

IL

D

IN

G

PR

O

JE

C T

G

RA

PH

IC

S

CA

LE

D

ES

IG

N

ER

ID

EN

TI

FI

C

AT

IO

N

C O

N

SU

LT

AN

T

ID

EN

TI

FI

C

AT

IO

N R

EV

IS

IO

N

B

LO

C K

Elevator Modernization -

SCHEMATIC DESIGN

06/26/2023

ELECTRICAL

STAGE

SUBMISSION DATE

PROJECT TITLE

DRAWN BY

CHECKED BY

FLOOR NO.

DISCIPLINE

PLAN TYPE

SHEET NUMBER

AND FILENAME

KE

Y

PL

AN

GSA PROJECT NO.RMI12652

General Services Administration Public Buildings Service

Great Lakes

G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503

MI0137ZZ

Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.

Chicago, IL 60604

SH

EE

T

47PF0021F0046

GP-05-P13-SVD-0030

PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION

CONTROLLED UNCLASSIFIED INFORMATION

Service Elevator

95% REVIEW DOCUMENTS09/29/2023

100% REVIEW DOCUMENTS04/16/2024

FINAL 100% CONST. DOCS04/26/2024

DETAILS

E-701

EMG

File details come from the government source that posted it. Updated .