GR Service Elevator 3_Drawings.pdf
PDF 10 MB Posted
- Attached to
- Elevator Modernization- Grand Rapids, MI Federal contract opportunity
- Solicitation number
- 47PF0025R0027
About this file
These are architectural and engineering drawings for an elevator modernization project at the Gerald R. Ford Federal Building in Grand Rapids, Michigan. The comprehensive set of documents includes detailed plans for renovating multiple elevators, specifically focusing on Service Elevator 3, with drawings covering architectural, electrical, and mechanical aspects of the project. The documents are prepared by Forbes Associates Architects and Peter Basso Associates Engineering, dated April 26, 2024, and marked as Final 100% Construction Documents.
The drawings provide extensive technical specifications for a complete elevator system overhaul, including detailed floor plans, electrical schematics, fire alarm systems, machine room layouts, and elevator lobby elevations. Key elements include replacing hoisting machines, control panels, electrical systems, mechanical equipment, lighting, and cab interiors. The project involves modernization of elevator infrastructure across multiple building levels, from the sub-basement to the penthouse, with particular attention to safety systems, emergency operations, and compliance with ASME A17.1 safety codes. The technical drawings demonstrate a comprehensive approach to upgrading the building's vertical transportation system while maintaining existing architectural and structural integrity.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 47PF0025R0027_Amendment 0002.pdf | ||
| 47PF0025R0027_Amendment 0001.pdf | ||
| Preproposal Conf Sign In Sheet_GR Elevator Modernization.pdf | ||
| Preproposal Conf Agenda_GR Elevator Modernization.pdf | ||
| GR Passenger Elevators 1_2_4_Drawings.pdf | ||
| GR Service Elevator Spec_REV03.pdf | ||
| GR Passenger Elevator Spec_REV03.pdf | ||
| Preproposal Mtg Registration_GR Elevator.pdf | ||
| RFP 47PF0025R0027.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
DEJ
G-001
Gerald R. Ford Federal Building MI0137ZZ
110 Michigan St. NW
Grand Rapids, Michigan 49503
Elevator Modernization - Service Elevator
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
DEJ
G-002
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
G-003
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
G-004
FLOOR PLAN
ELEVATOR PITS
A-101
ELEVATOR PIT ACCESS ROOM
ELEVATOR PIT
ELEVATOR PIT ACCESS ROOM
ELEVATOR PIT
ELEVATOR PIT ACCESS ROOM
ELEVATOR PIT
ELEVATOR PIT ACCESS ROOM
ELEVATOR PIT
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
VARIES
A-102
ELEVATOR LOBBY
CORRIDOR
CORRIDOR
ELEVATOR LOBBY
CORRIDOR
ELEVATOR LOBBY
ELEVATOR PIT ACCESS ROOM
CORRIDOR
HOISTWAY
HOISTWAY
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
FIRST FLOOR
A-103
ELEVATOR LOBBY
CORRIDOR
ELEVATOR LOBBY
VAULT
HOISTWAY
HOISTWAY
STORAGE JANITOR
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
DEJ
GUARD ROOM
A-104
ELEVATOR LOBBY
CORRIDOR
ELEVATOR LOBBY
CORRIDOR
HOISTWAY
HOISTWAY
STORAGE JANITOR
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
PENTHOUSE
A-105
CORRIDOR
CORRIDOR
MECHANICAL ROOM
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
DEJ
ELEVATOR SECONDARY
SPACE
ELEVATOR SECONDARY
SPACE
MACHINE ROOM PENTHOUSE
A-106
ELEVATOR
MACHINE ROOM
ELEVATOR
MACHINE ROOM
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
In Case Of Fire
Elevators Are Out Of Service
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
COD E B LUE
O
N
OFF
USE EXIT
USE EXIT
USE EXIT
USE EXIT
USE EXIT
USE EXIT
USE EXIT
USE EXIT
USE EXIT
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
COD E B LUE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
COD E B LUE
O
N
OFF
CODE
BLUE
In Case Of Fire
Elevators Are Out Of Service
C
ODE BL UE
O
N
OFF
USE EXIT
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
CODE BL UE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
CODE BL UE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
CODE BL UE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
CODE BL UE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
CODE BL UE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
CODE BL UE
O
N
OFF
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
CODE BL UE
O
N
OFF
ELEVATIONS
VARIES
A-201
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
ELEVATION
A-202
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
ELEVATOR
PIT ACCESS
ELEVATOR
PIT ACCESS
ELEVATOR LOBBY
ELEVATOR LOBBY
ELEVATOR LOBBY
ELEVATOR
#2
ELEVATOR
#3
ELEVATOR MACHINE ROOM
PENTHOUSE
VARIES
A-301
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
SECTION
SECTIONS
A-302
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
MACHINE ROOM PENTHOUSE
Q-106
ELEVATOR
MACHINE ROOM
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
4/26/2024
D
D
H
H
CAPACITY 3000 LBS.
OPEN CLOSE
4 3
NO
TO USE EMERGENCY
TELEPHONE, PRESS
BUTTON ABOVE.
DIALING WILL OCCUR
AUTOMATICALLY.
ELEVATOR 3
CALL HAS BEEN
RECEIVED
FIREFIGHTERS
OPERATION
NO SMOKING
YES
SBB
OFF
O
N
OPEN CLOSE
2R
4R
6R
BR
1R
3R
5R
7R
SBR
HD
OPEN CLOSE
2R
4R
6R
BR
1R
3R
5R
7R
SBR
D H
D
H
SECURITY PLANS
VARIES
Q-201
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
PIT ACCESS
ELEVATOR
PIT ACCESS
ELEVATOR LOBBY
ELEVATOR LOBBY
ELEVATOR LOBBY
ELEVATOR
#2
ELEVATOR
#3
ELEVATOR MACHINE ROOM
PENTHOUSE
1 2
3 4
ELEVATOR
EMERGENCY
POWER
DOOR
OPEN
C
O
D
E
B
L
U
E
O
N
OFF
FIREFIGHTERS' OPERATION
TO RECALL ELEVATORS
INSERT FIRE KEY AND TURN TO "ON"
C
O
D
E
B
L
U
E
O
N
OFF
C
O
D
E
B
L
U
E
O
N
OFF
C
O
D
E
B
L
U
E
O
N
OFF
ELEVATOR
EMERGENCY
POWER
DOOR
OPEN
ELEVATOR
EMERGENCY
POWER
DOOR
OPEN
ELEVATOR
EMERGENCY
POWER
DOOR
OPEN
A
U
T
O
FLOOR PLAN-EXISTING/DEMO
VARIES
Q-301
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
C
O
D
E
B
L
U
E
O
N
OFF
ELEVATOR
EMERGENCY
POWER
B
U
Z
Z
E
R
T
E
X
T
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
In Case Of Fire
Elevators Are Out Of Service
USE EXIT
C
O
D
E
B
L
U
E
O
N
OFF
EQUIPMENT DETAILS
VARIES
Q-501
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
Elevator Modernization -
Service Elevator
RMI12652
PRELIMINARY DESIGN
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
AS
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
CAPACITY 3000 LBS.
OPEN CLOSE
4 3
NO
TO USE EMERGENCY
TELEPHONE, PRESS
BUTTON ABOVE.
DIALING WILL OCCUR
AUTOMATICALLY.
ELEVATOR 3
CALL HAS BEEN
RECEIVED
FIREFIGHTERS
OPERATION
NO SMOKING
YES
SBB
OFF
O
N
OPEN CLOSE
2R
4R
6R
BR
1R
3R
5R
7R
SBR
HD
ELEV EQUIP DETAILS
VARIES
Q-502
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
FIRE ALARM PLAN
FA-101
ELEVATOR PIT ACCESS ROOM
ELEVATOR PIT
ELEVATOR PIT ACCESS ROOM
ELEVATOR PIT
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
FIRST FLOOR
RECALL LANDING (1)
BASEMENT
SECOND FLOOR
RECALL LANDING (2)
THIRD TO SEVENTH
FLOOR - TYP.
PENTHOUSE
F.A.
PANEL
SUB-BASEMENT
MACHINE ROOM
PENTHOUSE
ELEVATOR PIT
FIRST FLOOR
RECALL LANDING (1)
BASEMENT
SECOND FLOOR
RECALL LANDING (2)
MACHINE ROOM
PENTHOUSE
F.A.
PANEL
SUB-BASEMENT
THIRD TO SEVENTH
FLOOR - TYP.
PENTHOUSE
ELEVATOR PIT
FIRE ALARM DIAGRAMS
VARIES
FA-102
General Services Administration
Public Buildings Service
Great Lakes
G. R. Ford Federal Building
110 Michigan St NW
Grand Rapids, MI 49503
MI0137ZZ
ELEVATOR MODERNIZATION -
SERVICE ELEVATOR
RMI12652
Design and Construction, Project Delivery Division
John C. Kluczynski Federal Building
230 South Dearborn St.
Chicago, IL 60604
MARK DATE DESCRIPTION
ARCHITECTURAL
816 E 4th ST.
Royal Oak, MI 48067
248.542.7866/www.ghfaa.com
SWG
A S S O C I A T E S A R C H I T E C T S
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDED
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
FINAL 100% CONST. DOCS
816 E 4th ST.
Royal Oak, MI 48067 248.542.7866/www.ghfaa.com
A S S O C I A T E S A R C H I T E C T S
5145 Livernois, Suite 100
Fax: 248-879-0007 Troy, Michigan 48098-3276
Tel: 248-879-5666 www.PeterBassoAssociates.com
CONSULTING ENGINEERS
Peter Basso Associates Inc
PBA Project No.: 2023.0045
ST
AM
P O
R S
EA
L
BU
IL
D
IN
G
PR
O
JE
C T
G
RA
PH
IC
S
CA
LE
D
ES
IG
N
ER
ID
EN
TI
FI
C
AT
IO
N
C O
N
SU
LT
AN
T
ID
EN
TI
FI
C
AT
IO
N R
EV
IS
IO
N
B
LO
C K
Elevator Modernization -
SCHEMATIC DESIGN
06/26/2023
ELECTRICAL
STAGE
SUBMISSION DATE
PROJECT TITLE
DRAWN BY
CHECKED BY
FLOOR NO.
DISCIPLINE
PLAN TYPE
SHEET NUMBER
AND FILENAME
KE
Y
PL
AN
GSA PROJECT NO.RMI12652
General Services Administration Public Buildings Service
Great Lakes
G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503
MI0137ZZ
Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.
Chicago, IL 60604
SH
EE
T
47PF0021F0046
GP-05-P13-SVD-0030
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
Service Elevator
95% REVIEW DOCUMENTS09/29/2023
100% REVIEW DOCUMENTS04/16/2024
FINAL 100% CONST. DOCS04/26/2024
SYMBOLS AND INDEX
E-001
EMG
SMB
N/A
248.542.7866/www.ghfaa.com
A S S O C I A T E S A R C H I T E C T S
5145 Livernois, Suite 100
Fax: 248-879-0007 Troy, Michigan 48098-3276
Tel: 248-879-5666 www.PeterBassoAssociates.com
CONSULTING ENGINEERS
Peter Basso Associates Inc
PBA Project No.: 2023.0045
ST
AM
P O
R S
EA
L
BU
IL
D
IN
G
PR
O
JE
C T
G
RA
PH
IC
S
CA
LE
D
ES
IG
N
ER
ID
EN
TI
FI
C
AT
IO
N
C O
N
SU
LT
AN
T
ID
EN
TI
FI
C
AT
IO
N R
EV
IS
IO
N
B
LO
C K
Elevator Modernization -
SCHEMATIC DESIGN
06/26/2023
ELECTRICAL
STAGE
SUBMISSION DATE
PROJECT TITLE
DRAWN BY
CHECKED BY
FLOOR NO.
DISCIPLINE
PLAN TYPE
SHEET NUMBER
AND FILENAME
KE
Y
PL
AN
GSA PROJECT NO.RMI12652
General Services Administration Public Buildings Service
Great Lakes
G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503
MI0137ZZ
Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.
Chicago, IL 60604
SH
EE
T
47PF0021F0046
GP-05-P13-SVD-0030
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
Service Elevator
95% REVIEW DOCUMENTS09/29/2023
100% REVIEW DOCUMENTS04/16/2024
FINAL 100% CONST. DOCS04/26/2024
SCHEDULES
E-002
EMG
MACHINE ROOM
816 E 4th ST.
Royal Oak, MI 48067 248.542.7866/www.ghfaa.com
A S S O C I A T E S A R C H I T E C T S
5145 Livernois, Suite 100
Fax: 248-879-0007 Troy, Michigan 48098-3276
Tel: 248-879-5666 www.PeterBassoAssociates.com
CONSULTING ENGINEERS
Peter Basso Associates Inc
PBA Project No.: 2023.0045
ST
AM
P O
R S
EA
L
BU
IL
D
IN
G
PR
O
JE
C T
G
RA
PH
IC
S
CA
LE
D
ES
IG
N
ER
ID
EN
TI
FI
C
AT
IO
N
C O
N
SU
LT
AN
T
ID
EN
TI
FI
C
AT
IO
N R
EV
IS
IO
N
B
LO
C K
Elevator Modernization -
SCHEMATIC DESIGN
06/26/2023
ELECTRICAL
STAGE
SUBMISSION DATE
PROJECT TITLE
DRAWN BY
CHECKED BY
FLOOR NO.
DISCIPLINE
PLAN TYPE
SHEET NUMBER
AND FILENAME
KE
Y
PL
AN
GSA PROJECT NO.RMI12652
General Services Administration Public Buildings Service
Great Lakes
G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503
MI0137ZZ
Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.
Chicago, IL 60604
SH
EE
T
47PF0021F0046
GP-05-P13-SVD-0030
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
Service Elevator
95% REVIEW DOCUMENTS09/29/2023
100% REVIEW DOCUMENTS04/16/2024
FINAL 100% CONST. DOCS04/26/2024
DEMOLITION AND NEW WORK
E-307
EMG
ELEVATOR - PENTHOUSE
248.542.7866/www.ghfaa.com
A S S O C I A T E S A R C H I T E C T S
5145 Livernois, Suite 100
Fax: 248-879-0007 Troy, Michigan 48098-3276
Tel: 248-879-5666 www.PeterBassoAssociates.com
CONSULTING ENGINEERS
Peter Basso Associates Inc
PBA Project No.: 2023.0045
ST
AM
P O
R S
EA
L
BU
IL
D
IN
G
PR
O
JE
C T
G
RA
PH
IC
S
CA
LE
D
ES
IG
N
ER
ID
EN
TI
FI
C
AT
IO
N
C O
N
SU
LT
AN
T
ID
EN
TI
FI
C
AT
IO
N R
EV
IS
IO
N
B
LO
C K
Elevator Modernization -
SCHEMATIC DESIGN
06/26/2023
ELECTRICAL
STAGE
SUBMISSION DATE
PROJECT TITLE
DRAWN BY
CHECKED BY
FLOOR NO.
DISCIPLINE
PLAN TYPE
SHEET NUMBER
AND FILENAME
KE
Y
PL
AN
GSA PROJECT NO.RMI12652
General Services Administration Public Buildings Service
Great Lakes
G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503
MI0137ZZ
Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.
Chicago, IL 60604
SH
EE
T
47PF0021F0046
GP-05-P13-SVD-0030
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
Service Elevator
95% REVIEW DOCUMENTS09/29/2023
100% REVIEW DOCUMENTS04/16/2024
FINAL 100% CONST. DOCS04/26/2024
DIAGRAM
E-501
EMG
EXISTING PANELBOARD ELEV-3&4
# LOAD
TYPE DESCRIPTION CB
TYPE CB VA ØA ØB ØC VA CB CB
TYPE DESCRIPTION LOAD
TYPE #
1 NC
ELEVATOR 3
EXIST
13025 22724 9699
EXIST
ELEVATOR 4
NC 2
3 NC EXIST 13025 22724 9699 EXIST NC 4
5 NC EXIST 13025 22724 9699 EXIST NC 6
7 SPARE EXIST 20 2105 2105 15 EXIST VF-1 NC 8
9 NC ELEVATOR 3&4 CAB LIGHTING EXIST 20 100 100 20 EXIST SPARE 10
11 NC ELEVATOR 3&4 CAB CONTROLS EXIST 20 100 100 20 EXIST SPARE 12
13 SPARE EXIST 20 20 EXIST SPARE 14
15 E
EUH-1
EXIST
1690 1690 20 EXIST SPARE 16
17 E EXIST 1690 1690 20 EXIST SPARE 18
19 E EXIST 1690 1690 20 EXIST SPARE 20
21 SPARE EXIST 20 20 EXIST SPARE 22
23 SPARE EXIST 20 20 EXIST SPARE 24
25 SPARE EXIST 20 20 EXIST SPARE 26
27 SPARE EXIST 20 20 EXIST SPARE 28
29 SPARE EXIST 20 20 EXIST SPARE 30
26519 24514 24514
ØA ØB ØC
FEEDER AND
OVERCURRENT SIZING
PANELBOARD INFORMATION DEMAND
FACTOR
CALCULATED
LOADVOLTAGE: 480Y/277 BRANCH CIRCUIT CONNECTED LOAD NOTES:
BUS AMPACITY: 225A CONTINUOUS LOAD (C) 100% 125%
MAIN TYPE: 200A MCB ELECTRIC HEAT (E) 5070 100% 5070 100% 5070
MINIMUM A.I.C.: 35,000 NON-CONTINUOUS LOAD (NC) 70477 100% 70477 100% 70477
MOUNTING: SURFACE KITCHEN LOAD (K) 100% 100%
RECEPTACLE BASE LOAD (R) 100% 100%
FEED-THROUGH LUGS RECEPTACLE DEMAND LOAD (R) 50% 100%
DOUBLE LUGS LIGHTING LOAD (L) 100% 125%
INTEGRAL SPD ADDITIONAL TRACK LIGHTING LOAD 100%
MOTORS, HIGHEST LOAD (MH) 125% 100%
PANELBOARD LOCATION MOTORS, REMAINING LOAD (M) 100% 100%
NOTE: DEMAND AND SIZING INFORMATION IS CALCULATED
FROM CONNECTED LOAD
TOTAL(KVA): 75.55
TOTAL (AMPS): 91 TOTAL (AMPS): 91
© Copyright 2021 by Peter Basso Associates, Inc
EXISTING PANELBOARD ELEV-1&2
# LOAD
TYPE DESCRIPTION CB
TYPE CB VA ØA ØB ØC VA CB CB
TYPE DESCRIPTION LOAD
TYPE #
1 NC
ELEVATOR 1
EXIST
9699 19398 9699
EXIST
ELEVATOR 2
NC 2
3 NC EXIST 9699 19398 9699 EXIST NC 4
5 NC EXIST 9699 19398 9699 EXIST NC 6
7 L LTG - PENTHOUSE EXIST 20 471 7245 6774
EXIST
ELEV-A
C 8
9 NC ELEVATOR 1&2 CAB LIGHTING EXIST 20 50 7298 7248 EXIST C 10
11 NC ELEVATOR 1&2 CAB CONTROLS EXIST 20 50 5520 5470 EXIST C 12
13 L LTG - PENTHOUSE MACHINE ROOM EXIST 20 471 471 20 EXIST SPARE 14
15 E
EUH-2
EXIST
1690 1690 20 EXIST SPARE 16
17 E EXIST 1690 1690 20 EXIST SPARE 18
19 E EXIST 1690 1690 20 EXIST SPARE 20
21 SPARE EXIST 20 20 EXIST SPARE 22
23 SPARE EXIST 20 20 EXIST SPARE 24
25 SPARE EXIST 20 20 EXIST SPARE 26
27 SPARE EXIST 20 20 EXIST SPARE 28
29 SPARE EXIST 20 20 EXIST SPARE 30
28804 28386 26608
ØA ØB ØC
FEEDER AND
OVERCURRENT SIZING
PANELBOARD INFORMATION DEMAND
FACTOR
CALCULATED
LOADVOLTAGE: 480Y/277 BRANCH CIRCUIT CONNECTED LOAD NOTES:
BUS AMPACITY: 225A CONTINUOUS LOAD (C) 19492 100% 19492 125% 24365
MAIN TYPE: 200A MCB ELECTRIC HEAT (E) 5070 100% 5070 100% 5070
MINIMUM A.I.C.: 35,000 NON-CONTINUOUS LOAD (NC) 58294 100% 58294 100% 58294
MOUNTING: SURFACE KITCHEN LOAD (K) 100% 100%
RECEPTACLE BASE LOAD (R) 100% 100%
FEED-THROUGH LUGS RECEPTACLE DEMAND LOAD (R) 50% 100%
DOUBLE LUGS LIGHTING LOAD (L) 942 100% 942 125% 1178
INTEGRAL SPD ADDITIONAL TRACK LIGHTING LOAD 100%
MOTORS, HIGHEST LOAD (MH) 125% 100%
PANELBOARD LOCATION MOTORS, REMAINING LOAD (M) 100% 100%
NOTE: DEMAND AND SIZING INFORMATION IS CALCULATED
FROM CONNECTED LOAD
TOTAL(KVA): 83.80
TOTAL (AMPS): 101 TOTAL (AMPS): 107
© Copyright 2021 by Peter Basso Associates, Inc
EXISTING PANELBOARD EM
# LOAD
TYPE DESCRIPTION CB
TYPE CB VA ØA ØB ØC VA CB CB
TYPE DESCRIPTION LOAD
TYPE #
1 L S STAIRWAY EXIT LIGHTS EXIST 20 100 200 100 20 EXIST W STAIRWAY EXIT LIGHTS L 2 3 R E TELEPHONE CLOSET RCPTS EXIST 20 360 460 100 20 EXIST W STAIRWAY EXIT LIGHTS L 4 5 L S STAIRWAY BATTERY LIGHTS EXIST 20 500 680 180 20 EXIST PHONE ROOM ISO KTWIST LOCK R 6
7 L BATTERY LIGHTS EXIST 20 500 680 180 20 EXIST B62 RCPT R 8
9 R W TELEPHONE CLOSE RCPT EXIST 20 180 360 180 20 EXIST FIRE PUMP RM RCPT R 10
11 L N CENTER HALL EXIT LIGHTS EXIST 20 100 300 200 20 EXIST CLOCK SYSTEM NC 12
13 R ELEVATOR PIT - RCPT EXIST 20 1080 2080 1000
EXIST
PHONE RM RCPT
R 14
15 R B70 RCPT EXIST 20 180 1180 1000 EXIST R 16
17 L E STAIRWAY EXIT LIGHTS EXIST 20 100 300 200 20 EXIST INTERFACE UNITS SECUIRTY RM NC 18 19 R BOIELR LEAD LAG CONTROK RCPT EXIST 20 180 380 200 20 EXIST INTERFACE UNITS GARAGE NC 20 21 NC JOHNSON CONTROL PANEL CLOCK SYSTEM EXIST 20 200 250 50 20 EXIST KEY CARD SYSTEM NC 22
23 R RM B58 RCPT EXIST 20 180 380 200 20 EXIST B7FA CONTROL NC 24
25 C
LPA (FIRE ALARM PANEL)
EXIST
2000 2200 200 20 EXIST B7FA CONTROL NC 26
27 C EXIST 2000 6000 4000
EXIST
PANEL B44
C 28
29 C EXIST 2000 6000 4000 EXIST C 30
31 SPARE EXIST 20 4000 4000 EXIST C 32
33 SPARE EXIST 20 20 EXIST SPARE 34
35 R B70 RCPT EXIST 20 180 180 20 EXIST SPARE 36
SPARE
EXIST
40 40
EXIST
SPARE
39 EXIST EXIST 40
41 EXIST EXIST 42
9540 8250 7840
ØA ØB ØC
FEEDER AND
OVERCURRENT SIZING
PANELBOARD INFORMATION DEMAND
FACTOR
CALCULATED
LOADVOLTAGE: 208Y/120 BRANCH CIRCUIT CONNECTED LOAD NOTES:
BUS AMPACITY: 100A CONTINUOUS LOAD (C) 18000 100% 18000 125% 22500
MAIN TYPE: 100A MCB ELECTRIC HEAT (E) 100% 100%
MINIMUM A.I.C.: 22,000 NON-CONTINUOUS LOAD (NC) 1250 100% 1250 100% 1250
MOUNTING: SURFACE KITCHEN LOAD (K) 100% 100%
RECEPTACLE BASE LOAD (R) 4880 100% 4880 100% 4880
FEED-THROUGH LUGS RECEPTACLE DEMAND LOAD (R) 50% 100%
DOUBLE LUGS LIGHTING LOAD (L) 1500 100% 1500 125% 1875
INTEGRAL SPD ADDITIONAL TRACK LIGHTING LOAD 100%
MOTORS, HIGHEST LOAD (MH) 125% 100%
PANELBOARD LOCATION MOTORS, REMAINING LOAD (M) 100% 100%
BASEMENT SUBSTATION RM
NOTE: DEMAND AND SIZING INFORMATION IS CALCULATED
FROM CONNECTED LOAD
TOTAL(KVA): 25.63
TOTAL (AMPS): 71 TOTAL (AMPS): 85
© Copyright 2021 by Peter Basso Associates, Inc
EXISTING PANELBOARD ELEV-A
# LOAD
TYPE DESCRIPTION CB
TYPE CB VA ØA ØB ØC VA CB CB
TYPE DESCRIPTION LOAD
TYPE #
1 L ELEVATOR PIT AND SHAFT - LIGHTS EXIST 20 1100 2868 1768
EXIST
ACU-1
NC 2
3 NC
ACU-3
EXIST
1768 3536 1768 EXIST NC 4
5 NC EXIST 1768 3536 1768
EXIST
ACU-2
NC 6
7 R RCPT - ELEVATOR EXIST 20 360 2128 1768 EXIST NC 8
9 M
SP-3
EXIST
1144 1934 790
EXIST
SP-2
M 10
11 M EXIST 1144 1934 790 EXIST M 12
13 MH
SP-1
EXIST
1778 1778 20 EXIST SPARE 14
15 MH EXIST 1778 1778 20 EXIST SPARE 16
17 SPARE EXIST 20 20 EXIST SPARE 18
19 SPARE EXIST 20 20 EXIST SPARE 20
21 SPARE EXIST 20 20 EXIST SPARE 22
23 SPARE EXIST 20 20 EXIST SPARE 24
25 SPARE EXIST 20 20 EXIST SPARE 26
27 SPARE EXIST 20 20 EXIST SPARE 28
29 SPARE EXIST 20 20 EXIST SPARE 30
6774 7248 5470
ØA ØB ØC
FEEDER AND
OVERCURRENT SIZING
PANELBOARD INFORMATION DEMAND
FACTOR
CALCULATED
LOADVOLTAGE: 208Y/120 BRANCH CIRCUIT CONNECTED LOAD NOTES:
BUS AMPACITY: 100A CONTINUOUS LOAD (C) 100% 125%
MAIN TYPE: 100A MCB ELECTRIC HEAT (E) 100% 100%
MINIMUM A.I.C.: 22,000 NON-CONTINUOUS LOAD (NC) 10608 100% 10608 100% 10608
MOUNTING: SURFACE KITCHEN LOAD (K) 100% 100%
RECEPTACLE BASE LOAD (R) 360 100% 360 100% 360
FEED-THROUGH LUGS RECEPTACLE DEMAND LOAD (R) 50% 100%
DOUBLE LUGS LIGHTING LOAD (L) 1100 100% 1100 125% 1375
INTEGRAL SPD ADDITIONAL TRACK LIGHTING LOAD 100%
MOTORS, HIGHEST LOAD (MH) 3556 125% 4445 100% 4445
PANELBOARD LOCATION MOTORS, REMAINING LOAD (M) 3868 100% 3868 100% 3868
NOTE: DEMAND AND SIZING INFORMATION IS CALCULATED
FROM CONNECTED LOAD
TOTAL(KVA): 20.38
TOTAL (AMPS): 57 TOTAL (AMPS): 57
© Copyright 2021 by Peter Basso Associates, Inc
816 E 4th ST.
Royal Oak, MI 48067 248.542.7866/www.ghfaa.com
A S S O C I A T E S A R C H I T E C T S
5145 Livernois, Suite 100
Fax: 248-879-0007 Troy, Michigan 48098-3276
Tel: 248-879-5666 www.PeterBassoAssociates.com
CONSULTING ENGINEERS
Peter Basso Associates Inc
PBA Project No.: 2023.0045
ST
AM
P O
R S
EA
L
BU
IL
D
IN
G
PR
O
JE
C T
G
RA
PH
IC
S
CA
LE
D
ES
IG
N
ER
ID
EN
TI
FI
C
AT
IO
N
C O
N
SU
LT
AN
T
ID
EN
TI
FI
C
AT
IO
N R
EV
IS
IO
N
B
LO
C K
Elevator Modernization -
SCHEMATIC DESIGN
06/26/2023
ELECTRICAL
STAGE
SUBMISSION DATE
PROJECT TITLE
DRAWN BY
CHECKED BY
FLOOR NO.
DISCIPLINE
PLAN TYPE
SHEET NUMBER
AND FILENAME
KE
Y
PL
AN
GSA PROJECT NO.RMI12652
General Services Administration Public Buildings Service
Great Lakes
G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503
MI0137ZZ
Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.
Chicago, IL 60604
SH
EE
T
47PF0021F0046
GP-05-P13-SVD-0030
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
Service Elevator
95% REVIEW DOCUMENTS09/29/2023
100% REVIEW DOCUMENTS04/16/2024
FINAL 100% CONST. DOCS04/26/2024
SCHEDULES
E-502
EMG
248.542.7866/www.ghfaa.com
A S S O C I A T E S A R C H I T E C T S
5145 Livernois, Suite 100
Fax: 248-879-0007 Troy, Michigan 48098-3276
Tel: 248-879-5666 www.PeterBassoAssociates.com
CONSULTING ENGINEERS
Peter Basso Associates Inc
PBA Project No.: 2023.0045
ST
AM
P O
R S
EA
L
BU
IL
D
IN
G
PR
O
JE
C T
G
RA
PH
IC
S
CA
LE
D
ES
IG
N
ER
ID
EN
TI
FI
C
AT
IO
N
C O
N
SU
LT
AN
T
ID
EN
TI
FI
C
AT
IO
N R
EV
IS
IO
N
B
LO
C K
Elevator Modernization -
SCHEMATIC DESIGN
06/26/2023
ELECTRICAL
STAGE
SUBMISSION DATE
PROJECT TITLE
DRAWN BY
CHECKED BY
FLOOR NO.
DISCIPLINE
PLAN TYPE
SHEET NUMBER
AND FILENAME
KE
Y
PL
AN
GSA PROJECT NO.RMI12652
General Services Administration Public Buildings Service
Great Lakes
G. R. Ford Federal Building 110 Michigan St NW Grand Rapids, MI 49503
MI0137ZZ
Design and Construction, Project Delivery Division John C. Kluczynski Federal Building 230 South Dearborn St.
Chicago, IL 60604
SH
EE
T
47PF0021F0046
GP-05-P13-SVD-0030
PROPERTY OF THE UNITED STATES GOVERNMENT - THIS IS CONTROLLED UNCLASSIFIED INFORMATION - DO NOT REMOVE THE CUI MARKING - PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER NEEDEDCONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
Service Elevator
95% REVIEW DOCUMENTS09/29/2023
100% REVIEW DOCUMENTS04/16/2024
FINAL 100% CONST. DOCS04/26/2024
DETAILS
E-701
EMG
File details come from the government source that posted it. Updated .