Attachment B - Bldg_27497- E6 marked up.pdf

PDF 3 MB Posted

Attached to
Replace Two 12, 470V to 480V Transformers
Solicitation number
FA940124B0003
Issued by

About this file

This document appears to be an attachment detailing the electrical equipment layout and requirements for a project to replace two 12,470V to 480V transformers and install a new 200A panelboard in Building 27497 at Kirtland Air Force Base.

The key details are: The project requires replacing a 750 kVA and a 1500 kVA transformer, including their associated switchgear and instrumentation, with new copper-wound dry-type transformers. It also requires installing a new 200A, 480Y/277V, 3-phase, 42-space panelboard. The transformers provide power to several nearby buildings. The project is part of the broader federal contract opportunity FA940124B0003 issued by the Department of the Air Force Materiel Command Nuclear Weapons Center to complete this work at the specified location.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SCALE: 1/4" = 1'-0"

NEW ELECTRICAL EQUIPMENT LAYOUT

K

IR

T L A N

D A

F B

N

M

Existing 750kVA Transformer switchgear and instrumentation

Existing 1500 kVA Transformer switchgear and instrumentation

1522246871E Rectangle

1522246871E Rectangle

1522246871E Rectangle

1522246871E Callout Provide a new 200A, 480Y/277V, 3Φ, 42-space panelboard.

1522246871E Callout Replace a 750 kVA, 12,470 V-480Y/277V, 3Φ dry-type transformer (Z = 5.9%) and its primary/associated switchgear and instrumentation (as recommended by the transformer manufacturer). New transformer shall have copper/copper (CU/CU) for windings.

1522246871E Callout Replace a 1500 kVA, 12,470 V-480Y/277V, 3Φ dry-type transformer (Z = 5.55%) and its primary/associated switchgear and instrumentation (as recommended by the transformer manufacturer). New transformer shall have copper/copper (CU/CU) for windings.