16-Sampling_Plan_Community_Water_Systems_2015_Luke_AFB.pdf

PDF 1006 KB Posted

Attached to
AFICA Perform Sampling and Analysis and Drinking Well Operations and Maintenance at Luke Air Force Base, Arizona
Solicitation number
FA8903-16-R-0009
Issued by

About this file

Sampling Plan Community Water Systems_2015_Luke AFB

View the file

Other files

File Type Posted
FA8903-16-R-0009_Amendment_1.pdf PDF
13-Luke_Well_Data.pdf PDF
7-Notification_of_Compliance_with_Contract_Insurance_Requirements.docx DOCX document
FA8903-16-R-0009.pdf PDF
SECTION_M_FA8903-16-R-0009.pdf PDF
3-SCA_Wage_Determination_FA8903-16-R-0009.pdf PDF
8-Well_7_lithologic_log.pdf PDF
2-BSL_FA8903-16-R-0009.pdf PDF
1-PWS_FA8903-16-R-0009.pdf PDF
17-Well_14_Schematic.pdf PDF
14-Luke_Well_Data_Pump_Depth.pdf PDF
Exhibit_A-FA8903-16-R-0009.PDF PDF
6-Internal_Confidentiality_Agreements_FA8903-16-R-0009.docx DOCX document
Exhibit_B-FA8903-16-R-0009.PDF PDF
10-Well_Rehab_Rpt_URS_May_2007.pdf PDF
19-Luke_AFB_New_Well_Pilot_Holes.pdf PDF
5-Tax_Liability_FA8903-16-R-0009.docx DOCX document
11-Historic_Nitrate_Arsenic_Levels.pdf PDF
15-Map_of_Luke_AFB_Well_7_Location.pdf PDF
12-Luke_Nitate_Levels.pdf PDF
SECTION_L_FA8903-16-R-0009.pdf PDF
4-Questions_and_Responses_FA8903-16-R-0009.pdf PDF
9-Well_Schematic_of_Well_No._7.pdf PDF
18-Labor_Category_Qualifications_FA8903-16-R-0009.pdf PDF
16-R-0009_SECTION_L.pdf PDF
16-R-0009_SECTION_M.pdf PDF
8-Well_7_lithologic_log.pdf PDF
16-SAP.pdf PDF
15-Map_of_Luke_AFB_Well_7_Location.pdf PDF
9-Well_Schematic_of_Well_No._7.pdf PDF
13-Luke_Well_Data.pdf PDF
2-BSL_FA8903-16-R-0009.pdf PDF
17-Well_14_Schematic.pdf PDF
4-Questions_Template_FA8903-16-R-0009.docx DOCX document
5-Tax_Liability_FA8903-16-R-0009.docx DOCX document
10-Well_Rehab_Rpt_URS_May_2007.pdf PDF
7-Notification_of_Compliance_with_Contract_Insurance_Requirements.docx DOCX document
18-Labor_Category_Qualifications_FA8903-16-R-0009.pdf PDF
3-SCA_Wage_Determination_FA8903-16-R-0009.pdf PDF
14-Luke_Well_Data_Pump_Depth.pdf PDF
6-Internal_Confidentiality_Agreements_FA8903-16-R-0009.docx DOCX document
1-PWS_FA8903-16-R-0009.pdf PDF
11-Historic_Nitrate_Arsenic_Levels.pdf PDF
12-Luke_Nitate_Levels.pdf PDF
Questionnaire_FA8903-16-R-0009.docx DOCX document
Sources_Sought_FA8903-16-R-0009.pdf PDF
Draft_PWS_FA8903-16-R-0009.pdf PDF
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sampling Plan – Community Water Systems – 2015

FOR OFFICIAL USE ONLY

Drinking Water Program

Environmental Sampling, Analysis and Monitoring Plan

Luke AFB

Public Water Systems

PWS ID#: AZ070305

FA8903-16-R-0009

Attachment 16

Table of Contents

Section Title Page #

I System Name and Identifying Information 3

II Sampling Plan - Purpose 3

III Rules Regarding Bacteriological Sampling for Medium Water System 3

IV Special Monitoring Requirements 9

V Chemical Sampling and Compliance Section 14

VI Public Notification 15

VII Rules Regarding Compliance Monitoring for Lead and Copper 17

VIII Public Education and Notification Requirements for Lead and Copper Exceedance 23

IX Sanitary Survey 24

X Aircraft Watering Point 25

XI Consumer Confidence Report 25

XII Swimming Pool Inspections 27

XIII Sample Collection QA/QC 29

XIV Contact Information 30

Attachment 1 Luke AFB Base Grid Map 31

Attachment 2 Water Main Break Bacteriological Sampling Requirements 32

Attachment 3 New Well Sampling Requirements 33

Attachment 4 Swimming Pool Inspection Checklists 35

Attachment 5 Force Protection Sampling Point Schedule and VOC Parameters 36

Attachment 6 ADEQ Drinking Water Monitoring and Protection Unit Contact Information 38

Attachment 7 LEGEND Laboratories QA/QC Program 39

Bacteriological Sampling Plan

FA8903-16-R-0009

Luke AFB Medium Community Water Systems

I. System Names and Identifying Information

i. Luke AFB Water System

ii. System City/Town: Luke AFB, Arizona.

iii. System PWS ID#: AZ07305 – This potable water distribution system is supplied by water produced by three (3) water wells:

Well 10 (ADEQ: 55‐609886) Well 11 (ADEQ: 55‐609887) Well 12 (ADEQ: 55‐609888)

iv. Population served: 9,500 personnel (Data obtained in 2012 WVA interview with CE Utilities).

v. Luke water system has two pressure zones:

a. Low zone aka North Side aka EPDS 1 (Well 10,12)

b. High zone aka South Side aka EPDS 5 (Well 11)

i. Serves: entire 900, 1000, and 1200 areas

ii. Bldgs 497, 795, 492, 482, 486, 485, 460, 454, 431, 843, 840

i. Gila Bend Water System, Geographically Separated Unit

ii. System City/Town: Gila Bend AFAF, Arizona.

iii. System PWS ID#: AZ07055 - Gila Bend AFAF is a non-transient, non-community water system.

Water is disinfected after it is pumped from the water table. This potable water distribution system is supplied by water pumped from two (2) wells:

Well 3 Well 4

iv. Population served: Approximately 130 April - October /230 November - March

II. Purpose: All Community water systems must analyze for coliform bacteria to determine compliance with

Arizona Administrative Code, Department of Environmental Quality – Safe Drinking Water. The purpose of this plan is to identify specific bacteriological sample locations for each water source (e.g. well) and locations that are representative of the water quality throughout the distribution system. This plan also addresses the timing, frequency and rotation period for the collection of water samples in compliance with Arizona Administrative Code. This plan will be available for review and possible revision during all sanitary surveys conducted by the Arizona Department of Environmental Quality (ADEQ).

III. Rules Regarding Bacteriological Sampling for Medium Water Systems

A. Routine Samples - Per ADEQ, R18-4-202, which currently requires the collection of the following number of distribution system samples each month for Total Coliform analysis:

a. Systems serving from 8,501 to 12,900 persons (e.g. AZ07305):

Ten (10) distribution system samples at sites that are representative of water throughout the distribution system.

3 of 10 compliance locations, BEF collects are requirements (Youth Center, Child

Development Center) per Air Force Instruction.

b. Non-Transient, Non-Community Water Systems:

One (1) distribution system samples at sites that are representative of water throughout the distribution system.

Routine Sampling – Type, Amount, and Frequency of Samples

System Name Type of Sample #/month

Luke AFB

AZ07305

Distribution system 10

Gila Bend Distribution system 1

AZ07055

Routine Sampling – Luke AFB Locations of Bacterial Sampling Each Week Month/Week Location 1 Location 2 Location 3 Location 4 Location 5

1st Thursday January, March, May, July, September, November

Bldg 1365 – Emergency Mgmt Men’s bathroom Sink

Bldg 545 – Amn Dining Hall Kitchen Sink

Bldg 700 –

HAWC

Kitchen Sink

Bldg 1130 – Medical Clinic Lab Sink

Bldg 1118 – CDC kitchen sink

3rd Thursday

January, March, May, July, September, November

Bldg 954 – Falcon Flightline Kitchen Sink

Bldg 942- 309th FS Breakroom Sink

Bldg 343 – CE Bldg

Supply Closet

Bldg 1113 – Amn Family Readiness kitchen sink

Bldg 13313B Jemez – Ocotillo Base Housing outside spigot

1st Thursday February, April, June, August, October, December

Bldg 993 – 944th Reserve Bldg, Family Readiness Sink Rm 13

Bldg 161 – Club 56 kitchen sink

Bldg 179- 56 SFS Supply Closet

Bldg 1119 –

CDC

break room

Bldg #1676/ physical address: 1656 Mohave – TLF Unit

3rd Thursday

February, April, June, August, October, December

Bldg 2201 – Falcon Dunes kitchen sink

Bldg 1143 – Youth Center kitchen sink

Bldg 1514 – Satellite Pharmacy bathroom Sink

Bldg 3709 - Sioux Street Base Housing outside spigot

Bldg 2221 Apache – Base Housing outside spigot

*****When Silver Wings Pool is open for the season, test the Chlorine levels at the beginning of each month********************************

Routine Sampling – Gila Bend Locations of Bacterial Sampling Each Month Month 1 Bldg 14 Logistics

FA8903-16-R-0009

Month 2 Bldg 2358A Conrad Circle Month 3 Bldg 3316 Famcamp Month 4 Bldg 4300 Billeting Month 5 Bldg 314 Fire Dept

B. Repeat Samples - Positive Total Coliform or E. coli Sample

a. Luke AFB Water System - If a sample is determined as positive for total-coliform, it must be further tested for E. Coli and a set of three repeat samples must be collected on the same day within 24 hours (This time begins from when you were notified by the lab of the positive result).

The below table identifies site locations for resampling.

Original Location

Upstream tap w/in 5 service connections

Downstream tap w/in 5 service connections

All supplying active wells

(pre-treatment)

1 1 1 multiple

Total-Coliform Rule (TCR) – The re-sampling must be performed at the site where the original sample tested positive, and also two alternate locations five points upstream and downstream of the original site. If resample results come back negative, from original sampling point no further sampling is necessary. If resample results are positive for total coliform, CE Utilities will be contacted. Notification procedures must be followed; residents of housing/building where positive occurred will be notified.

Ground Water Rule (GWR) - Triggered source water monitoring is required after a total-coliform positive sample is collected from the distribution system in compliance with the TCR. Samples must be collected within 24 hours of notification, at least one sample from each ground water source (Wells) in use at the time the total coliform-positive routine sample was collected. The triggered source water samples must be analyzed for the presence of a State-approved fecal indicator (E. Coli). A positive fecal indicator GWR results is an Acute Violation requiring Public Notice. Contact ADEQ immediately at (602) 771-4560 or 1(800) 234-5677.

Repeat Sampling Locations - If a sample is taken at the beginning or at one service connection away from the beginning of the system is total-coliform positive, a repeat sample may not be required (can be waived by ADEQ, R18-4-202, H. d.) at an upstream site. If a sample taken at the end of the distribution system is total-coliform positive, then the original site plus 2 samples within 5 service connections upstream must be taken. In addition to these repeat samples, all active supplying well locations require sampling IAW the Groundwater Rule.

b. Gila Bend Water System- If a sample is determined positive for total-coliform, it must be tested for E. Coli and a set of at least three (3) repeat samples for each total coliform positive routine sample found (R18-4-202, H. 1.). Four (4) samples will be taken if a positive for total-coliform has been identified.

A public water system that collects fewer than five (5) routine samples per month and has one or more total coliform positive routine samples shall collect five (5) routine samples during the next month (R18-4-202, I.) (Not applicable Luke AFB has 10 routine samples per month)

Original

Upstream tap w/in 5 service connections

Downstream tap w/in 5 service connections

Any other sampling site w/in system

1 1 1 1

c. Maximum Contaminant Levels (MCL) – If the MCL is exceeded, contact ADEQ at (602) 771-

4560/ 4561 immediately for further guidance concerning public notification of potential health risks. Notify 56 CES Utilities and Luke AFB Water Manager (56 CES/ CEOIU at DSN: 896- 6109). The following table presents MCL information gathered from the EPA quick reference guide for the TCR:

Samples collected MCL Non-Compliance

Less than 40 samples/month 1 sample is positive for total coliform bacteria

Any e. Coli positive repeat sample 1 positive repeat sample is an acute health risk (24 hr public notice)

Any total coliform positive sample following an E. coli positive routine sample

1 positive sample is an acute health risk (24 hr public notice)

d. Possible Health Risks – Confirmatory samples containing fecal coliforms or E. coli indicate the presence of contamination that could cause acute health problems. This may result in the ADEQ notice of violation.

*triggered source water sampling identified in EPA, Ground Water Rule, collect at least one ground water source sample from each source in use at the time the total coliform+ sample was collected.

IV. Rules R

Figure 1 - Bacteriological Repeat Sampling Guidelines – Medium Water Systems

Y

Y

Medium Water Systems o Luke AFB Water System

Positive Sample is from the distribution system*

Do all of the following:

1. Test original sample for E. coli. If a repeat sample is E. coli+, contact ADEQ ASAP.

2. Within 24 hr. of receiving + result, collect on the same day four (4) samples for each total coliform+ sample.

Additional sampling is required at every active well supplying water to the distribution system.

3. If any repeat sample is total coliform+, repeat step 2 above until total coliforms are absent in one complete set of four

(4) samples. If any resample from any well is positive for E.

Coli, 4 additional samples must be taken and public notification started (Boiling Water Notice)

Positive Sample is from a well

Sample tested positive for total-coliform bacteria

1. Test sample for E. coli. If a repeat sample is E. coli+, contact ADEQ ASAP, and:

2. If notified to do so by ADEQ, disinfect, bacteriologically survey the relevant well(s) & conduct physical characteristics monitoring

Y

N

Y

* IMPORTANT: For small water systems, in month following the total coliform+ result, 5 samples must be collected in the distribution system that yielded the positive result.

FA8903-16-R-0009

Luke AFB Bacteriological Repeat Sampling Points

Sampling Points(Bldg#) Upstream(Bldg#) Downstream(Bldg#) 1365 1370 328 545 528 617 700 637,636 750, 808 1130 1145 1140 1118 1124 1550 954 913 958 942 904 938 343 338 347 1113 1143 1119 8104 8103 8105 993 979 999, 1018 161 248 156 179 299 176 1119 1109 1111 1656 1675 1677 2201 2202 1143 1109 1104 1514 1525 1535 3709 3707 3711 2221 2219 2223

IV. Special Monitoring Requirements:

a. Routine Monitoring – ADEQ requires community water systems to conduct the following monitoring for chemical contaminants:

Group Non - TCR Sample Schedule

Facility Begin/End

Dates

Initial Monitoring

Plan Sampling Frequency

Group Code

Analytic Group Name begin Date

DS001

01-01-2008 Continuous

1/1/2008 4 RT/YR DBP

DBPS

(TTHM/HAA5)

DS001

01-01-2007 Continuous

1/1/2007 10 RT/3Y PBCU

LEAD &

COPPER

EPDS001

01-01-2004 Continuous

1/1/2004 1 RT/3Y IOCC IOCS-CWS

EPDS001

01-01-2010 Continuous

1/1/2010 1 RT/6Y RADS RADS

EPDS001

01-01-2004 Continuous

1/1/2004 2 RT/3Y SOCS SOCS

EPDS001

01-01-2010 Continuous

1/1/2010 1 RT/6Y VOCD

DATA

ENTRY-VOCS

EPDS005

01-01-2004 Continuous

1/1/2004 1 RT/3Y IOCC IOCS-CWS

EPDS005

01-01-2010 Continuous

1/1/2010 1 RT/6Y RADS RADS

EPDS005

01-01-2004 Continuous

1/1/2004 2 RT/3Y SOCS SOCS

EPDS005

07-01-2010 Continuous

7/1/2010 1 RT/QT VOCD

DATA

ENTRY-VOCS

Individual Non- TCR Sample Schedules

Facility Begin/End

Date

Initial Monitoring

Period Begin Date

Seasonal Req. Code Analytic

Name

EPDS001

01-01-

Continuous

1/1/2008 1 RT/QT 1005 ARSENIC

1/1/2004

1/1/2004 1 RT/QT 1040 NITRATE

EPDS001 Continuous

EPDS001

01/01/2004 Continuous

1/1/2004 1 RT/9Y 1041 NITRITE

EPDS001

01/01/2004 Continuous

1/1/2004 1 RT/9Y 1094 ASBESTOS

EPDS005

01/01/2008 Continuous

1/1/2008 1 RT/QT 1005 ARSENIC

EPDS005

01/01/2004 Continuous

1/1/2004 1 RT/YR 1040 NITRATE

EPDS005

01/01/2004 Continuous

1/1/2004 1 RT/9Y 1041 NITRITE

EPDS005

01/01/2004 Continuous

1/1/2004 1 RT/9Y 1094 ASBESTOS

Facility Analyte Levels (FANLS)

Site Analyte Level Type

Value Units Days/Month Samples/

Day Begin Date

End Date

MDBP

Type

DS001 999 MAX 4 mg/L 0 0 1/1/2004 Continuous MRDL DS001 2456 MAX 0.06 mg/L 0 0 1/1/2004 Continuous HAA5 DS001 2950 MAX 0.08 mg/L 0 0 1/1/2009 Continuous TTHM

Procedures for Chemical Analysis of Drinking Water

Chemical analysis of drinking water is performed by Legend Labs. The preparation and actual sampling for all of the different analytes is performed in accordance with the procedures outlined in the QA/QC section of this plan.

CHEMICAL ANALYSIS SAMPLING SCHEDULE

Chemicals (with sampling frequency)

Scheduled Sample Year J F M A M J J A S O N D

--- SOCs 2RT/3YR/EPDS1 & 5 2013-2016-2019 X X

--- VOCs 1RT/3YR/EPDS 1 2013-2016-2019 X

--- VOCs 1RT/1YR/EPDS 5 2013 (Annual) X

--- IOCs 1RT/3YR/EPDS 1 & 5 2013-2016-2019 X

--- Other Inorganic

* Asbestos 1RT/9YR/EPDS 1 &

2016-2019-2022 X

* Nitrate 1RT/YR/EPDS 5 2013 (Annual) X

* Nitrate 1RT/QR/EPDS 1 2013 (Quarterly) X X X X

--- TTHM/HAA 4RT/YR/designated sites (Once btwn Jun-Sep)

2013 (Annual)

--- Pb/Cu 20RT/3YR/designated sites (Once btwn Jun-Sep)

2013-2016-2019

--- RADs

1RT/6YR/EPDS 1 & 5

2016-2025-2031

X

C. Chemical Sampling Sites and Monitoring Schedule Changes – The following table identifies sampling locations for each contaminant and disinfect residual or by-products and triggers for increased or reduced monitoring.

FA8903-16-R-0009

Contaminant Monitoring

Trigger That

Increases Monitoring Increased

Monitoring Reduced Monitoring

Disinfectant Residual

Same locations in distribution system where monthly Bac-Ts are collected

1 sample/yr during warmest month

Disinfection Byproducts

TTHM, HAAS

Stage 1 (2013): Bldgs 1113, 1365

Stage 2 (2014): Bldg 283(TTHM) and 3618 Zuni (HAA5)

Annual average >

MCL

1 sample/qtr. If annual average of TTHM & HAAS is < 50% of MCL for 2 yrs – start triennial during warmest month of year

Asbestos Bldgs 1111 CDC, 954 Falcon Flight Kitchen, Sample > MCL

1 sample/qtr. Every 9 years

Volatile Organics

For EPDS 5: (1) 1st qrtr sample/yr EPDS 1: (1) 1st qrtr sample every 6 yrs

Any VOC >.0005 mg/L.

1 sample/qtr. No VOC detected during 3 yrs. of annual sampling – start triennial sampling

Synthetic Organics

Detection of any SOC 1 sample/qtr. No SOC is detected during initial CP, take 2 quarterly samples every 3 yrs.

Nitrate Nitrite

Every entry pt. to distribution system during normal conditions.

Sample > 50% of

MCL

1 sample/ quarter

4 quarterly samples average < 50% MCL, start annual monitoring in qtr. w/highest result.

Primary Inorganic

Every entry pt. to dist.

system during normal conditions.

Sample > MCL 1 sample/qtr. 4 quarters < MCL – go to triennial

Secondary Every entry pt. to dist.

system during normal conditions.

corrective actions may include monitoring

Triennial

Radio nuclides Gross alpha Radium 226 Radium 226 Uranium

Every entry pt. to dist.

system during normal conditions.

1. Sample is > MCL

2. Sample is > 50% MCL but <MCL, or > det. limit but < 50% MCL if sampling every 6 yrs.

3. Sample > det. limit if monitoring every 9 yrs.

1. Sample quarterly.

2. Sample every 3 yrs.

3. Sample every 6 yrs.

1. Average of 4 samples is < det. Limit. – begin sampling every 9 yrs.

2. Last reduced monitoring sample is < ½ MCL – begin sampling every 6 yrs.

Radio nuclides Gross beta & photon Radioactivity

Every entry pt. to dist.

system during normal conditions.

Sample >MCL Monthly for gross beta, tritium & strontium -90

Triennial for gross beta, tritium & strontium-90

D. Asbestos - Sampling Requirements: Figure 3 lists asbestos sampling requirements flow chart for Luke AFB Public Water System. At least one sample representative of each source after treatment (if applicable) must be taken at a tap served by asbestos-cement-pipe and under conditions where

FA8903-16-R-0009

asbestos contamination is most likely to occur. Samples must be taken at the same sampling point unless conditions make another sampling point more representative of each source.

E. Sampling Frequency and Compliance Cycles

A chemical sampling schedule is included in pages 10-11. The following table identifes sample collection frequencies:

Y

N

Y

Y

N

N

Y

Y

N

Annual average of 4 consecutive quarterly samples using initial exceedance as 1st. quarter sample is > asbestos MCL

Conduct 1 yr of quarterly monitoring

Figure 3 – Asbestos Monitoring Requirements

Y

N

Due solely to corrosion of asbestos‐cement Y

System is susceptible to asbestos contamination Take 1 sample at tap served by asbestos‐cement pipe under conditions where asbestos contamination is most likely to occur.

Y

N

Due solely to source water

Due to source water & corrosion of asbestos‐cement pipe

Take at least 1 sample at every entry point to distribution system representative of each source after treatment as directed by ADEQ.

Monitor every 9 yrs

Sample exceeds the MCL

3 yr average is > 50% of MCL

Begin annual monitoring with ADEQ written approval.

Monitor every 6 yrs with ADEQ written approval.

Out of compliance

1. Notify ADEQ w/in 24 hours of receiving results

2. Notify public as required by #1

Y

1 sample exceeds MCL.

Y

Y

FA8903-16-R-0009

Sampling Frequency

Triennial

Quarterly

Annual Medium Systems

Every Nine Years

May be taken at any time during a quarter.

Samples taken in consecutive quarters must be taken at least 30 days apart.

May be taken at any time during the year.

Samples taken in consecutive years must be at least 90 days apart.

Take during 1st. yr of each compliance period. For example, if the compliance year are 2013-2016 the 1st compliance period is 2013.

Take during the 3rd.

year of the first 3-yr compliance period of each 9-year compliance cycle.

V. Chemical Sampling & Compliance Section

A. Confirmation Samples

Confirmation samples must be taken whenever a sample exceeds the MCL for nitrate or nitrite and/or if an unregulated contaminant is detected. Confirmation samples should be taken for other inorganic contaminants, organic contaminants, radionuclides, or secondary contaminants. For regulated contaminants, average the confirmation sample result with the first sample result, and use the average to determine compliance. Confirmation samples must be collected at the same sampling point as soon as possible (no later than two weeks) after the initial sample was taken.

B. Determinating Compliance with Sampling Requirements

Compliance with Arizona Administrative Code (AAC) Title 18, Chapter 4, is based on the analytical results obtained at each sampling point. If one sampling point violates the MCL, the system is in violation of the MCL. If more than one sample is collected during the year, compliance is determined by averaging all samples taken at each sampling point. If the annual average of any sampling point is exceeds the MCL, the system is out of compliance. Any sample result below the regulatory detection limit is calculated as zero in determining the running annual average.

Except for nitrate and nitrite, if sampling is conducted annually or less frequently, a sample result exceeding the MCL will not be considered in violation of the MCL until one year of quarterly sampling has been completed. For nitrate or nitrite, the system is immediately out-of-compliance if any sample result exceeds 50% of the MCL.

If an initial or a subsequent sample would cause the annual average to exceed the MCL, then the system is immediately out of compliance. If a system that is not in compliance with an MCL or MRDL, ADEQ must be notified as soon as possible (within 24 hours) of receiving the results and the public must be notified. Also notify 56 CES Utilities and Luke AFB Water Manager (56 CES/ CEOIU at DSN: 896-6109).

Figure 4 - Determining Compliance – See Figure 5 for Nitrate/Nitrite

Y

Any sample exceeds MCL for inorganics, VOCs, SOCs, rads, secondaries

Take confirmation (2nd.) Sample ASAP at same sampling

pt. & average result with 1st. sample

FA8903-16-R-0009

VI. Public Notification

A. Public Notification Requirements

Figure 6 – Public Notification Requirements

N

N

N

Y

Y

N

N

MCL violation for nitrate, nitrite, or total nitrate & nitrite

N

N

N

Acute risk to public health:

1. Provide Tier 1 notice to radio &

TV stations within 24 hrs and notify MAJCOM BE

2. Initiate consultation with ADEQ

ASAP (no later than 24 hrs)

MCL violation for fecal coliform or E. coli in distribution system, or failure to test for E. coli when any repeat sample tests + for coliforms

Waterborne microbial disease outbreak, other waterborne emergency

Failure or significant interruption in water treatment processes

Natural disaster disrupts water supply or distribution system

Chemical spill w/potential for short‐term adverse health effects

Unexpected pathogens in source water w/potential for short‐ term adverse health effects

N

Y

Y

Y

Y

Y

Y

Other violation/situation w/potential for short‐term adverse health effects, as determined by ADEQ.

ClO2 MDRL violation in distrib. system

Turbidity MCL violation ‐ issue Tier 1 if ADEQ deems acute. If non‐ acute, issue Tier 2 if ADEQ deems necessary.

Y

YViolation of non‐acute MCL, MDRL, treatment technique requirement, & variance or exemption schedule

ASAP (< 30 days), issue

Tier 2 notice:

By mail or by hand delivery after system learns of violation, situation, or failure, to each affected customer & to other service connections to which water is delivered

By publication in a daily newspaper

Notify MAJCOM BE

Continue to give notice < every 3 months by mail or hand delivery, as long as violation, exceedance, situation, or failure exists.

N

Y

Y

FA8903-16-R-0009

B. Content of Public Notices

* IMPORTANT: For Public Notices the rule specialist should be contacted for the violation template to be completed. The template includes the below information as well as up-to-date requirements.

Each notice must be conspicuous, contain only neccessary technical language, be printed in easily readable print and contain all of the following elements:

a. Description of the violation, exceedance, situation, or failure, including the contaminant(s) of concern, and (as applicable) the contaminant level(s);

b. When the violation, exceedance, situation, or failure occurred;

c. Potential adverse health effects resulting from the violation, exceedance, situation, or failure, including the applicable language on potential adverse health effects for those contaminants and disinfectants found in Appendix B to Subpart Q of 40 CFR 141, “Standard Health Effects Language for Public Notification,”

d. The population at risk, including subpopulations particularly vulnerable if exposed to the contaminant in their drinking water;

e. Whether boiled water or alternative sources of water should be used;

f. What action consumers should take, including when they should seek medical help;

g. What the system is doing to correct the violation, exceedance, situation, or failure;

h. When the system expects to return to compliance or resolve the violation, exceedance, situation, or failure;

i. Name, business address, and phone number of the water system owner, operator, or designee of the public water system as a source of additional information concerning the notice;

j. The following standard language to encourage the distribution of the public notice to all persons served: “Please share this information with all the other people who drink this water, especially those who may not have received this notice directly (for example, people in apartments, nursing homes, schools, and businesses). You can do this by posting this notice in a public place or distributing copies by hand or mail.”

For monitoring violations, the following standard language must be used: “We are required to monitor your drinking water for specific contaminants on a regular basis. Results of regular monitoring are an indicator of whether or not your drinking water meets health standards.

During [fill in compliance period], we did not monitor or test for [fill in contaminant(s)], and therefore cannot be sure of the quality of your drinking water during that time.”

C. Recission of Public Notices

The rescission notice must be distributed in the same manner to the same target audience as the initial public notice. Rescissions must include all of the following information:

a. Description and the date of the original notice;

b. Actions taken that resulted in the lifting of the notice;

c. Effective date of the rescission;

d. Name, business address, and phone number of the water system owner, operator, or designee of the public water system as a source of additional information concerning the rescission.

VII. Rules Regarding Compliance Monitoring for Copper and Lead

A. Initial and Routine Monitoring – 40 CFR 141, sections 141.80 -141.91 requires community water systems to conduct the following initial and routine monitoring for lead and copper:

Contaminant 40 CFR Monitoring Frequency MCL

Initial Routine Lead Copper

141.8 -141.9 Establish a lead & copper tap sampling plan & collect samples according to the following schedule: 2 semi-annual sample sets, followed by 3 annual sample sets.

Tri-annually

Pb-0.015 mg/L Cu-1.3 mg/L Based on 90th percentile level* of tap water samples.

* Calculate 90th percentile by sorting all lead and copper samples in ascending order from the lowest to the highest concentration. Each sample result is assigned a number with #1 assigned to the lowest contaminant level. The number of samples multiplied by .9 is the 90th percentile.

Contaminant Monitoring Locations

Lead Copper

2923 Sioux Bldg 810 6973 B Salado Bldg 942 3616 Zuni Bldg 954 3505 Command Dr. Bldg 976 3421 Thunderbird Bldg 988 3132 Hopi Bldg 1118 CDC Kitchen Bldg 640 Rm 122 Bldg 1130 Clinic Bldg 445 Bldg 1143 Bldg 636 Rm 314 Bldg 1384 Bldg 302 Bldg 1525

a. Sample Collection Methods - First Draw Samples

All tap samples for lead and copper collected must be first-draw samples. All first-draw tap samples must be one liter in volume and have stood motionless in the plumbing system of each sampling site for at least six hours. First draw samples from residential housing must be collected from the cold water kitchen tap or a bathroom sink tap. First-draw samples from a nonresidential building must be collected at an interior tap from which water is typically drawn for consumption.

Each first draw tap sample must be taken from the same sampling site where previous samples were collected. If entry to a sampling site is prevented, the follow-up tap sample may be collected from another sampling site in its sampling pool as long as the new site meets the same targeting criteria, and is within reasonable proximity of the original site.

b. Sampling Requirements for Tap Water – Number of Samples and Monitoring Frequency

A pool of targeted sampling sites within distribution system for each water system must be identified that meets regulatory requirements, and is large enough to ensure that the correct number of samples for lead and copper tap samples are collected. The sampling sites must consist of buildings that contain copper pipes with lead solder installed after 1982 or contain lead pipes;

and/or are served by a lead service line. Sampling sites cannot include faucets that have a point of use or point of entry treatment devices that remove inorganic contaminants. Any water system whose distribution system contains lead service lines must draw 50% of the samples for each monitoring period from sites that contain lead pipes or copper pipes with lead solder and 50% of the samples from sites served by a lead service line. If the water system cannot identify enough sampling sites served by a lead service line, first draw samples must be collected from all sites being served by such lines.

A medium community water system is required to collect at least one (1) sample from 40 sampling sites for initial sampling. The number of sampling sites may be reduced to 20 after the lead and copper action levels are achieved for two consecutive six month monitoring periods.

Y

Figure 7 – Pb and Cu Sampling Requirements for Medium Systems

Reduce sampling to 20 samples once per year (w/written ADEQ approval) beginning in the year immediately following the end of the 2nd consecutive 6-mo monitoring period. Note: If system was previously on triennial monitoring, it may resume triennial monitoring at this point.

N

Y

System collects 40 tap samples per sampling period for 2 consecutive 6‐mo periods & meets Pb & Cu action levels (ALs)

Note: Systems sampling annually or less frequently must collect samples from June – Sept.

Continued operation and monitoring. All systems optimizing corrosion control must maintain optimal corrosion control treatment, including WQPs at > minimum values or within ranges designated by ADEQ. Compliance is determined every six months, as specified under §141.87(d). System is out of compliance with the requirements of this paragraph for a six-month period if it has excursions for any State-specified parameter on more than nine days during the period. An excursion occurs whenever the daily value for one or more of the water quality parameters measured at a sampling location is below minimum value or outside range designated by ADEQ.

N

Y

System exceeds Pb or Cu AL

N

1. Implement public notification requirements outlined in Section VIII.

2. Recommend optimal corrosion control (OCO) options to ADEQ w/in 6 months. ADEQ has 24 months after end of monitoring period to specify OCO.

3. Install OCO w/in 24 months after ADEQ designates such treatment.

4. Beginning on date ADEQ specifies optimal values for corrosion control, monitor for 2 Consecutive, 6‐month periods collecting samples for:

Pb & Cu (at 40 taps) Concurrently during each sampling period:

o Collect 2 WQP samples for each applicable WQP at each of 3 taps & analyze for pH, alkalinity conc. (if used for OCO) & orthophosphate or silica conc. if applicable.

o Collect 1 WQP sample every 2 weeks at each entry point to distribution system & analyze for analyze for pH, alkalinity conc. (if used for OCO) & orthophosphate or silica conc. if applicable.

If applicable, during sample collections, record dosage rate readings for corrosion control inhibitor and/or alkalinity.

5. ADEQ reviews installation of treatment & designates optimal WQP w/in 6 months of completing step #4.

Y

System meets Pb & Cu ALs OR Pb AL & WQC parameters reflecting optimal corrosion control treatment for 3 consecutive yrs.

Reduce monitoring to triennially w/written ADEQ approval.

Collect samples no later than 3rd calendar yr.

System sample results for 2 consecutive, 6 mo periods are <

.005 mg/L for Pb & < .65mg/L

Y

Y

During 2 consecutive, 6 mo periods, system meets

Pb & Cu AL

Y Y

c. Sampling Requirements for Source Water and Water Quality Parameters

A water system that fails to meet the lead or copper action level on the basis of tap water samples must also concurrently collect lead and copper source water samples and source water and distribution system samples for water quality parameters (WQP). Monitoring requirements for WQP and source water are presented in figures 8 and 9.

Monitoring Period

Location and # of Samples Medium System

Parameters Frequency

Initial monitoring after Pb or Cu exceedance

2 samples for each applicable WQP at 3 taps & 1 sample for each applicable WQP at each entry point(s) to the distribution. system pH, alkalinity, orthophosphate or silica3, calcium, conductivity, temperature

Every 6 months.

After installation of corrosion control

2 samples for each applicable WQP at 3 taps pH, alkalinity, orthophosphate or silica, calcium

Every 6 months.

pH, alkalinity, dosage rate & concentration (if alkalinity adjusted as part of OCC), inhibitor dosage rate and inhibitor residual

Every 2 weeks

After State specifies parameter values for optimal corrosion control

2 samples for each applicable WQP at 3 tap pH, alkalinity, orthophosphate or silica, calcium

Every 6 months.

pH, alkalinity dosage rate and concentration (if alkalinity adjusted as part of OCC), inhibitor dosage rate and inhibitor residual

Every 2 weeks

Figure 8 - Summary of Monitoring Requirements for Water Quality

1 sample for each applicable WQP at each entry point(s) to the distribution system

1 sample for each applicable WQP at each entry point(s) to the distribution system

FA8903-16-R-0009

Reduced monitoring

(Must maintain range of values indicative of OCC during

2, 6-mo.

monitoring periods.)

2 samples for each applicable WQP at 1 tap pH, alkalinity, orthophosphate or silica3, calcium4

Every 6 mo, annually (after 3 yrs of satisfactory results) & triennially (after 3 yrs of satisfactory results.)

pH, alkalinity dosage rate & concentration (if alkalinity adjusted as part of OCC), inhibitor dosage rate & inhibitor residual5

Every 2 weeks

OCC – Optimal Corrosion Control

1 sample for each applicable WQP at each entry point(s) to the distribution system

FA8903-16-R-0009

Y

Y

Y

Y

Figure 9 – Pb & Cu Sampling Requirements for Source Water (141.83 and 141.88)

System exceeds Pb or Cu Action Level (AL) in initial or routine tap sample

ASAP, take at least 1 source water sample at every entry point to distribution system representative of each well after treatment

Sample results exceed maximum permissible source water levels per 141.83(b)(4)

Y

Y

Y

N Y

Y

ADEQ determines that the average of the 1st & 2nd samples exceeds Pb or Cu MCL for water entering distribution system.

ASAP, take 2nd source sample at same sampling point. Average the 2 samples to determine compliance. (In calculating average, use zero for any sample below detection limit.)

System must:

1. Take source water samples from every entry point to the distribution system < 6 months after end of monitoring period that showed an exceedance. If sampling annually or triennially ‐ period ends on 9/30.

2. Recommend in writing treatment options to ADEQ < 6 months after end of monitoring period where exceedance for Pb or Cu was measured. Note: May recommend no treatment if system can demonstrate that treatment is not required to minimize Pb & Cu at user’s taps.

W/in 6 months, ADEQ determines if source water treatment is needed.

Install water treatment w/in 24 month.

Monitor for 2 consecutive, 6‐mo. periods collecting during each period:

(1) Source water sample from each entry point to the distribution system.

(2) 40 tap samples for medium systems and 10 tap samples for small water systems.

System collects source water samples (1/entry point to distribution system) in 3rd.

year of next compliance period & continues on triennial monitoring Schedule

Y

Within 6 months after completion of the

2, 6‐mo sampling periods, ADEQ specifies source water MCLs.

System exceeds Pb or Cu MCL Y

VIII. Public Education and Notification Requirements for Lead and Copper Exceedance

A. Consumer Notice - A consumer notice of lead tap water monitoring results must be provided to persons served at the sites (taps) that are tested. If the lead action level (AL) is exceeded, a public education material must be delivered to affected consumers, and that tap water must be sampled by any customer who requests it. Public education materials are not required in the event of a copper action level exceedance.

B. Content of Public Education Materials - All of the following information (in the same order as listed below) must be included in printed materials. ADEQ may require approval of the content of written public materials prior to delivery.

a. “IMPORTANT INFORMATION ABOUT LEAD IN YOUR DRINKING WATER. [INSERT

NAME OF WATER SYSTEM] found elevated levels of lead in drinking water in some homes/buildings. Lead can cause serious health problems, especially for pregnant women and young children. Please read this information closely to see what you can do to reduce lead in your drinking water.”

b. “Health effects of lead. Lead can cause serious health problems if too much enters your body from drinking water or other sources. It can cause damage to the brain and kidneys, and can interfere with the production of red blood cells that carry oxygen to all parts of your body. The greatest risk of lead exposure is to infants, young children, and pregnant women. Scientists have linked the effects of lead on the brain with lowered IQ in children. Adults with kidney problems and high blood pressure can be affected by low levels of lead more than healthy adults. Lead is stored in the bones, and it can be released later in life. During pregnancy, the child receives lead from the mother's bones, which may affect brain development.

c. Possible sources of lead in drinking water and how it enters drinking water, including information on home/building plumbing materials and service lines that may contain lead

d. Other important sources of lead exposure in addition to drinking water (e.g., paint).

e. Steps consumers can take to reduce their exposure to lead in drinking water such as running the water to flush out the lead.

f. Concerns with using hot water from the tap and a specific caution against the use of hot water for preparing baby formula.

g. A statement that boiling water does not reduce lead levels.

h. Other options consumers can take to reduce exposure to lead in drinking water, such as alternative sources or treatment of water.

i. A suggestion that parents have their child's blood tested for lead.

j. Why lead levels are elevated in the system's drinking water (if known) and what the water system is doing to reduce the lead levels in homes/buildings in this area.

k. “For more information, call us at [INSERT YOUR NUMBER] [(IF APPLICABLE), or visit our Web

FA8903-16-R-0009

site at [INSERT YOUR WEB SITE HERE]]. For more information on reducing lead exposure around your home/building and the health effects of lead, visit EPA's Web site at http://www.epa.gov/lead or contact your health care provider.”

A lead public education report for the PWS must be completed and submitted to ADEQ for systems that exceed the lead action level within ten days after the end of each period that the system is required to perform public education tasks per 141.85.

C. Delivery of Public Education Materials - Public education materials must be delivered within 60 days of a lead exceedance, continue every six months for PSAs and annually for all other forms of delivery for as long as the lead exceedance continues. Delivery can be discontinued once sampling results indicate compliance with the lead action level but must resume if there is a subsequent exceedance. Public education materials must meet all of the following delivery criteria:

a. Informational posters on lead in drinking water must be posted in a public place or common area in each of the buildings served by the system.

b. Informational pamphlets on lead in drinking water must be delivered to each person served by the water system. ADEQ may approve electronic transmission in lieu of printed materials if it achieves at least the same coverage.

These tasks must be repeated at least annually at least once during the time that the system exceeds the lead action level. A water system may discontinue delivery of public education materials if the system has met the lead action level during the most recent six-month monitoring period.

IX. Sanitary Survey

A safe and reliable drinking water supply is essential to the health and well-being of our Air Force personnel and to sustain the many mission-critical operations that depend on it. Large quantities of potable water are required on a continuous basis for drinking, firefighting, decontamination, personal hygiene, sanitation, industrial operations, and other needs. These requirements can be met only if our water systems are properly designed, operated, maintained, and monitored. A sanitary survey periodically reviews these aspects in accordance with Safe Drinking Water Act (SDWA) regulations and DoD/Air Force directives. A sanitary survey is a proactive public health measure designed to identify and correct deficiencies before they can lead to contamination or disruption of the public water supply.

A sanitary survey examines and evaluates the adequacy of eight specific critical elements associated with water systems, as identified by the EPA:

� Source (Protection, Physical Components and Condition);

� Treatment;

� Distribution;

� Finished Water Storage;

� Pumps/Pump Facilities and Controls;

� Monitoring/Reporting/Data Verification;

� Water System Management/Operations; and, FA8903-16-R-0009

� Operator Compliance with State Requirements.

A sanitary survey identifies deficiencies associated with water safety and survivability, assesses the risks they pose, identifies practical control recommendations, and enables compliance with applicable regulatory requirements. A sanitary survey does not assess security-related deficiencies associated with water systems and supplies; this is the function of a Water Vulnerability Assessment (WVA). However, due to a number of overlapping factors, efficiencies can be realized when the sanitary survey and WVA are conducted in conjunction with each other.

AFI 48-144 states that the Bioenvironmental (BE) will ensure a sanitary survey is performed to satisfy the requirements of applicable regulations and standards. The BE is also responsible for recommending measures to be taken to maintain the sanitary quality of the base drinking water system. Currently, ADEQ funds and conducts the required sanitary survey.

Deficiencies found during the sanitary survey requiring infrastructure repair, redesign, or construction will be forwarded to the Base Civil Engineer (BCE) with recommendations for corrective action.

Water Source Community System Non-Community System Ground Water 3 years** 5 years *Community systems that have outstanding performance (as determined by the state) may have sanitary surveys conducted every five years.

** Community systems that have outstanding performance (as determined by the state) or treat to 4-log (99.99%) inactivation of viruses may have sanitary surveys conducted every five years.

X. Aircraft Watering Points Sampling

Aircraft Watering Point (AWP) sanitary surveys shall be conducted IAW AFI 48-144, “Safe Drinking Water Surveillance Program” and the Drinking Water Surveillance Technical Guide, published April 2011.

An AWP includes all of the equipment used to transfer potable water for human consumption to an aircraft. It does not include any part of the base distribution system or the aircraft’s internal water storage and dispensing system. It may include water trucks; hoses and faucets not permanently plumbed to the distribution system; and jugs, cans, and other containers that deliver potable water to aircraft.

Luke AFB does not have Aircraft Water Points.

XI. Consumer Confidence Report

The Consumer Confidence Report (CCR) Rule is an effort to improve the communication between the purveyor and the consumer, or public. The CCR Rule was promulgated on 19 Aug 98 (63 FR 44511) and is codified in Subpart O of 40 CFR 141. The Public Notification Rule revises timing and distribution requirements for public notices, expands the lists of violations and situations requiring immediate notification, simplifies mandatory health effects and monitoring violations language, consolidates public notification requirements, increases primacy agency flexibility, and amends the CCR Rule to conform

FA8903-16-R-0009

with these changes. The CCR Rule applies to all Community Water Systems (CWSs) and provides material to consumers to assist in making risk based decisions pertaining to their drinking water supply. It requires purveyors to prepare and distribute an annual water quality report summarizing information on the drinking water system and providing educational information.

The CCR is due to the base general public no later than 1 Jul of each year to be in compliance with the State regulator. The CCR is based on calendar-year data from the previous year. For example, all data from Jan-Dec 2012 must be included in the 2012 CCR, which is due to customers by 1 Jul 2013. Saying that, start compiling the information needed for the CCR early in the calendar year, to avoid possibly being late. At Luke, the CCR is prepared and routed for review NLT May of each year.

All CCRs must include the following eight basic items, at a minimum:

1. Required Information about the Water System (Name/phone number of contact person;

information on public participation opportunities; information for non-English speaking populations, if applicable)

2. Source(s) of Water (Type, name, and general location of water sources; availability of source water assessment; information on significant sources of contamination, if available)

3. Definitions (specific language) (MCL; MCLG; others as needed (i.e., variances, exemptions, Treatment Technique (TT), Action Level (AL), MRDL, and MRDLG)

4. Reported Levels of Detected Contaminants (Table summarizing data on detected regulated & unregulated contaminants; known or likely source of each detected contaminant; health effects language and explanation for any violations

5. Information on Monitoring for Cryptosporidium, Radon, and Other Contaminants (Warning for vulnerable populations about Cryptosporidium, if detected; explanation of radon and its presence in the finished water, if detected; explanation of unregulated contaminants and their presence in drinking water, if detected)

6. Compliance with Other Drinking Water Regulations (Explanation of violations, potential health effects and steps taken to correct the violations; special notices for GWR)

7. Variances and Exemptions (Explanation of variance/exemption, if applicable)

8. Required Educational Information (specific language) (Explanation regarding contaminants that may reasonably be expected to be found in drinking water, including bottled water; information to customers that some people may be more vulnerable to contaminants in drinking water; explanation of contaminants and their presence in drinking water, if detected; informational statements on arsenic and nitrate, if necessary, and lead, always required)

XII. Swimming Pool Inspection

A. Pool season usually begins in May at Luke AFB. Contact Pool Manager from Services (56 FSS/SVR) around 1 May to find out projected season opening date. Pre-season inspections must be accomplished within 72 hrs of pool opening. The following are steps to accomplish a pre-season pool inspection.

1. Review AFI 48-114 for guidance regarding Bioenvironmental Engineering Flight (BEF) responsibilities.

2.11.5. Bioenvironmental Engineering (BE).

2.11.5.1. Provides water quality supervision of swimming pools, spas and hot tubs, and natural bathing areas under Air Force jurisdiction.

2.11.5.2. Participates in pre-season, post-season, and other inspections, as necessary, of all such bathing areas, and submits recommendations to MDG/CC, MSG/CC and other responsible persons for the safe and sanitary operation and maintenance of the facilities. For facilities operated continuously, conduct inspections at least twice per year. If a pool or hot tub/spa is closed for renovation or repair, it shall be inspected before re-opening.

2.11.5.3. Provides bacteriological monitoring in support of specific requests attributable to disease outbreaks.

2.11.5.4. Reviews engineering designs for new and/or modified swimming pools, spas, and hot tubs and associated equipment and facilities to ensure adequacy of sanitary processes and controls.

2.11.5.5. Identifies, analyzes and recommends controls for any occupational and environmental health (OEH) hazards due to daily operations, processes, and location of pools, spas and hot tubs, and natural bathing areas.

2. Schedule pre-season inspection with Pool Manager from FSS, Sam Harvey at ext. 9335.

Conduct inspection IAW AFI 48-114 Attachment 5 or Attachment 6 of this document.

3. Measure pH and disinfectant residual levels (FAC). Compare results to the lifeguard’s readings. Enter results into Water Log book.

4. Write MFR swimming pool inspection letter and forward to 56 FSS/SVR and 56 CE/CEOIU.

Letter should include: who conducted the inspection, date, and summary of findings, as necessary.

5. Letters are saved to Swimming Pool (click on the hyperlink for location).

B. Emergency* Swimming Pool Inspection Procedures: If you are notified of an incident, such as feces, blood, or vomit in the pool: Follow the requirements listed in AFI 48-114 Attachment 6. You

FA8903-16-R-0009

may also reference the CDC’s recommendations at their website for Healthy Swimming:

http://www.cdc.gov/healthywater/swimming/pools/vomit‐blood‐contamination.html. Below is an abbreviated version of the contact time required for proper disinfection.

1. What is recommended when there is a vomit or blood spill in a swimming pool?

- These germs do not survive long when diluted into properly chlorinated pool water. There is no public health reason to recommend closing the pool after a blood spill. However, some pool staff choose to do so temporarily to satisfy patrons.

2. What is recommended when there is a formed stool in a swimming pool?

-remove the stool with a net or a bucket ASAP and follow disinfection removal times… -E. coli (bacteria) – less than 1 minute -Hepatitis A (virus) – approximately 16 minutes

Giardia Inactivation Time for a Formed-Stool Fecal Incident

Free Chlorine Level (ppm) Disinfection Time*

1.0 45 min

2.0 25 min

3.0 19 min *…ensure pH level is 7.5 or less and temperature is 77°F or higher

3. What is recommended when there is diarrhea in a swimming pool?

-Close the pool and coordinate with CE and BE. The pool will have to be closed for 7-26 hours.

Crypto Inactivation Time for a Diarrheal Fecal Incident Free Chlorine Level (ppm) Disinfection Time* 10…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .