S-105
REPAIR LOCATION PLAN
5th STREET TUNNEL
S-105 SCALE: N.T.S.
REPAIR LOCATION PLAN
5th STREET STEAM TUNNEL
NORTH
EXISTING STANCHION ASSESSMENT
LOCATION
STANCHION
(EXISTING)
REPAIR
CLEAN
(w/ NEW)
REPLACEMENT
(STANCHION)
LOCATIONS
75, 76, 77, 79, 67, 68, 69, 74, 62, 63, 64, 65, 58, 59, 60, 61, 43, 53, 56, 57, 26, 29, 31, 34, 8, 9, 41, 70, 78
84, 85, 86, 87
66, 71, 72, 73, 83, 50, 51, 52, 54, 55, 45, 46, 47, 48, 49, 38, 39, 40, 42, 44, 32, 33, 35, 36, 37, 24, 25, 27, 28, 30, 19, 20, 21, 22, 23, 14, 15, 16, 17, 18, 7, 10, 11, 12, 13, 1, 2, 3, 4, 5, 6, TUNNEL CONCRETE REPLACEMENT
(STANCHION)
LOCATION
SURFACE
TUNNEL
(APPROXIMATE)
LENGTH
BETWEEN 8 & 9 CEILING 10’-0"
CEILING 9’-0"BETWEEN 14 & 15
CEILINGBETWEEN 18 & 20 15’-0"
BETWEEN 40 & 41 CEILING 11’-0"
BETWEEN 44 & 50 CEILING 50’-0"
CEILINGBETWEEN 54 & 56 20’-0"
20’-0"CEILING
CEILING 7’-0"NEAR 65
CEILING 35’-0"BETWEEN 78 & 82
BETWEEN 82 & 83 15’-0"CEILING/WALL
APPLICATION LOCATIONS
EXTERNAL/INTERNAL WATERPROOFING
WATERPROOFING
EXTERNAL
WATERPROOFING
INTERNAL
-NEAR 82
-BETWEEN 29 & 30
-NEAR 23
-BETWEEN 21 & 22
-NEAR 4
BETWEEN 60 & 63
-BETWEEN 82 & 83
-BETWEEN 78 & 82
-NEAR 65
-BETWEEN 60 & 63
-BETWEEN 54 & 56
-BETWEEN 44 & 50
-BETWEEN 40 & 41
-BETWEEN 18 & 20
-BETWEEN 14 & 15
-BETWEEN 8 & 9
APPLICATION.
2. SEE DETAIL 1/S-301 FOR EXTERNAL WATERPROOFING
WATERPROOFING APPLICATION.
REQUIRED. SEE DETAIL 2/S-301 FOR INTERNAL
ADDITIONAL INTERNAL WATERPROOFING APPLICATIONS ARE
1. LOCATIONS DEPICTED IN CHART ARE LOCATIONS WHERE
NOTES:
(STANCHION)
LOCATIONS
(ALONG TUNNEL LENGTH)
UTILITIES AFFECTED BY EXCAVATIONS
BETWEEN 8 & 9 WATER, STORM WATER
UTILITY TYPE (LINES)
BETWEEN 14 & 15
BETWEEN 18 & 20
COMM, COMM MANHOLE, STORM WATER, WATER
COMM, STORM WATER, WATER
BETWEEN 40 & 41
UTILITY, ELECTRIC MANHOLES
COMM, WATER VALVE, WATER MAINS, ELECTRIC
BETWEEN 46 & 50
MAINS, WATER VALVES, WATER SERVICE
COMM, COMM MANHOLE, WATER LINE
BETWEEN 54 & 56
ELECTRIC MANHOLE, WATER MAINS
COMM, COMM MANHOLE, ELECTRIC,
BETWEEN 60 & 62
WASTEWATER
COMM, WATER MAIN, STORM WATER,
NEAR 65 COMM
BETWEEN 78 & 83
MANHOLE, STORM WATER, WASTEWATER
COMM, COMM MANHOLE, ELECTRIC, ELECTRIC
1/S-301 EXTERNAL WATERPROOFING APPLICATION DETAIL.
ON S-105 FOR APPLICATION LOCATIONS AND DETAIL
2. FOR EXTERNAL WATERPROOFING APPLICATION, SEE CHART
ALONG TUNNEL CEILING & WALLS.
1. SEE DETAIL 2/S-303 FOR REPLACEMENT OF CONCRETE
NOTES:
DWGS.
5. UTILITIES HAVE BEEN IDENTIFITED PER WPFAB EXISTING UTILITY
ELECTRICAL AND COMMUNICATION (COMM) UTILITIES.
EXTRA PRECAUTION MUST BE TAKEN TO AVOID DAMAGE TO
(PARTICULARLY ELECTRIC AND COMM UTILITIES) IS CRITICAL.
SHORING OF UTILITIES, IF EXCAVATING AROUND UTILITIES
01 01 01, BEFORE EXCAVATION AROUND UTILITIES. PROPER
4. REFERENCE WPAFB SPEC 01 01 50, SECTION 1.4, AND SPEC
EXCAVATION AND REPAIR MEANS AND METHODS.
CONTRACTING OFFICER’S REPRESENTATIVE TO REVIEW PLANNED
C. A "PRE-DIG" CONFERENCE SHALL BE CONDUCTED WITH THE
WITH FORM AF103.
B. THE GOVT. WILL CONDUCT A SURVEY OF UTILITIES COMPLETE
AREAS OF EXCAVATION AND SUBMIT FINDINGS TO THE GOVT.
A. THE CONTRACTOR SHALL CONDUCT A UTILITY SURVEY IN ALL
COMMENCEMENT OF EXCAVATION:
3. THE FOLLOWING ITEMS SHALL BE COMPLETED PRIOR TO
UTILITIES TO PREVENT DAMAGE AND DISRUPTION TO SERVICE
2. WHERE NECESSARY, THE CONTRACTOR SHALL HAND DIG AROUND
AS WELL.
NOTED, HOWEVER UTILITIES MAY BE PRESENT IN OTHER AREAS
FOR TUNNEL REPAIRS. AREAS OF SIGNIFICANT CONGESTION ARE
1. EXISTING UTILITIES MAY BE PRESENT IN AREAS OF EXCAVATION
NOTES:
CONTAINING MATERIALS PRESENT.
ADJOINING HALF ROUND TUNNELS THAT MAY HAVE ASBESTOS
IN FEW AREAS OF THE TUNNELS, THERE ARE CERTAIN
SURVEY/REMEDIATION HAS BEEN ACCOMPLISHED. HOWEVER,
IN MAIN TUNNELS IDENTIFIED IN PROJECT, ASBESTOS
NOTE TO CONTRACTOR:
WPAFB PROCEDURES/SPECIFICATIONS.
REMOVED. ANY SEEDING RESTORATION REQUIRED SHALL BE PER
CONCRETE (SIDEWALK, CURBS) TO MATCH THE EXISTING PROFILES
G. CONCTRACTOR SHALL REPLACE ANY DEMOLISHED ASPHALT AND
NOTES SECTION, "EARTHWORK", FOR ADDITIONAL REQUIREMENTS.
ROCK PRESENCE FOR ALL AREAS OF EXCAVATION. SEE GENERAL
F. CONTRACTOR SHALL INCLUDE EXCAVATION COSTS FOR 20% SHALE
ADDITIONAL REQUIREMENTS PER WPAFB.
E. CONTRACTOR SHALL REFER TO GENERAL NOTES SHEET, S-001, FOR
c. REPAIR METHODS
b. REPAIR MATERIALS
a. CONCRETE REMOVAL METHODS
SHALL FOLLOW INFORMATION IN TABLES:
DURING TUNNEL REPAIR. THE SEQUENCE AND SCHEDULE OF WORK
THE SEQUENCING AND SCHEDULING OF WORK TO BE PERFORMED
MATERIALS (PROPERTIES) TO BE USED FOR TUNNEL REPAIR WORK,
FOR CIVIL WORKS", SECTION 1.4 "SYSTEM DESCRIPTION", FOR ALL
D. REFER TO SPECIFICATION 03 01 32 "CONCRETE REHABILITATION
ANY DEMOLITION/NEW WORK THROUGHOUT THE TUNNEL.
C. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO
B. INDICATES EVERY 5th STANCHION ALONG LENGTH OF TUNNEL.
A. EXTENTS OF 5th STREET TUNNEL REPAIR ASSESSMENT.
SHEET GENERAL NOTES:
LOCATION.
3. RE-SECURE THE CONDUIT AND FIXTURES IN ORIGINAL
REQUIRED FOR WORK.
2. REMOVE CONDUIT CLAMPS AND LIGHTING FIXTURES AS
MAINTAIN CIRCUITRY.
1. TEMPORARILY SUPPORT THE CONDUIT AND FIXTURES TO
(NOTE TO CONTRACTOR):
EXISTING ELECTRICAL CONDUIT INTERFERENCE
REPLACEMENT DETAIL.
FOR NEW LADDER INFORMATION AND 5/S-302 FOR LADDER
LADDER. AS APPLICABLE. SEE SPECIFICATION SECTION 05 51 33
LADDERS/RUNGS ALONG VERTICAL FACE OF WALL w/ NEW
REQUIRED. REPAIRS SHALL INCLUDE REPLACING EXISTING
C. LADDER (AT MANHOLE/ACCESS POINTS INTO TUNNEL) REPAIR
OF CONCRETE TUNNEL REPLACEMENT.
EXTERNAL WATERPROOFING APPLICATIONS AND LOCATIONS
INTERNAL (BEYOND TYPICAL 1’-0" BASE APPLICATION) AND
SEE CHARTS ON S-105 FOR LOCATIONS OF REQUIRED
PORTIONS OF CONCRETE TUNNEL (SEE DETAIL 1/S-301).
REPAIR METHOD), AND EXCAVATION AND REPLACEMENT OF
CORROSION (SEE DETAILS 3B & 3C/S-301 FOR APPLICABLE
CLEANING/REPLACING EXISTING REINFORCING BARS WITH
3A/S-301), PATCH FOR SPALLING CONCRETE AND
ALONG CONCRETE FOR WATER INTRUSION (SEE DETAIL
IS TO OCCUR (SEE DETAIL 1/S-301), INJECTION OF CRACKS
2/S-301), EXTERNAL WATERPROOFING WHERE EXCAVATION
WATERPROOFING THE FACE OF THE TUNNEL (SEE DETAIL
AND SLAB REQUIRED. REPAIRS SHALL INCLUDE INTERNAL
B. CONCRETE REPAIR ALONG THE TUNNEL WALLS, CEILING,
INFORMATION.
SEE SPECIFICATION 23 05 15 FOR APPLICABLE PIPE ROLLER
PIPE ROLLER SUPPORT AT THE NECESSARY PIPE LOCATIONS.
STANCHIONS. NEW STANCHIONS SHALL REQUIRE NEW
REQUIRED ACTION BASED ON ASSESSMENT OF EXISTING
ON S-105 INDICATING STANCHIONS WITHIN TUNNEL AND
REQUIRED. SEE "EXISTING STANCHON ASSESSMENT" CHART
A. EXISTING PIPE STANCHION REPAIR OR FULL REPLACEMENT
DRAWING NOTES:
REMAIN.
EXISTING PIPE ROLLER SUPPORTS AT THESE STANCHIONS SHALL
REPAIR ONLY, SHALL NOT NEED NEW PIPE ROLLER SUPPORTS.
3. EXISTING STANCHIONS (WITHIN 5TH STREET TUNNEL) REQUIRING
EXISTING STANCHIONS THAT SHALL REMAIN.
2. SEE SHEET S-302 FOR REPAIRS METHOD REQUIREMENTS TO
EXISTING STANCHION) DETAIL.
1. SEE DETAIL 1/S-303 FOR NEW STANCHION (REPLACEMENT OF
NOTES:
COORDINATOR ENGINEERING CHIEF
DATE REVISION BYNO. DATE NO. REVISION BY
C I
V
IL
ENGI
N
E E
R
US AF
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
OF
DESIGN CHIEF
DATEDRAWNDESIGNED CHECKED
RPR/RPL STEAM STANCHIONS
PROJECT NUMBER ZHTV 090018
SUBMITTAL - 100% GOVT. SUBMITTAL
SPR SPR MSS JUNE 2015
B
1 8075706560555045403530252015105
A
B
A
B
A
B
A A A AA
B B
A
B BB B
C
A
E
BB
A
C
B B
AAA A A A
5TH STREET)
SIDEWALK (PARALLEL TO
TUNNEL DIRECTLY BELOW
ROADWAY
BUILDING
SIDEWALK TO
ROADWAY
ROADWAYROADWAY
PARKING LOT
ROADWAY &
S-105A 5th STREET TUNNEL PHOTOS/DESCRIPTIONS
EXISTING CONDITION REPAIR PROCEDURE EXISTING CONDITION REPAIR PROCEDURE EXISTING CONDITION REPAIR PROCEDURE
EXISTING CONDITION REPAIR PROCEDUREEXISTING CONDITION REPAIR PROCEDUREEXISTING CONDITION REPAIR PROCEDURE
EXISTING CONDITION REPAIR PROCEDURE EXISTING CONDITION REPAIR PROCEDURE
105A-c105A-b
105A-d 105A-e 105A-f
105A-h105A-g
105A-a
AT TOP OF WALL AT STANCHION 19.
CRACKING & WATER INTRUSION PRESENT
PIECES FROM CEILING SITTING ON PIPING.
EXPOSED THROUGHOUT CEILING. CONCRETE
CONCRETE SPALL & CORRODED REBAR
STANCHION 40.
THROUGHOUT CEILING NEAR
w/ CORRODED REBAR EXPOSED
CONCRETE SPALL & CRACKING
CEILING NEAR STANCHION 41.
INTRUSION PRESENT WITHIN
THROUGHOUT CEILING. WATER
CONCRETE SPALL & CRACKING
BETWEEN STANCHIONS 44 & 46.
PRESENT ALONG TOP OF WALL
EXPOSED WITHIN CEILING. CRACKING
CONCRETE SPALL & CORRODED REBAR
ALONG TOP OF WALL AT STANCHION 19.
CEILING. CRACKING & WATER INTRUSION PRESENT
HAVE CORROSION & NOT CONNECTED INTO
EXPOSED. TOP OF VERTICAL SUPPORT LEGS
CONCRETE SPALL & CORRODED REBAR
STANCHION 23 & 24.
& LOSS OF STEEL SECTION BETWEEN
VERTICAL SUPPORT LEGS HAVE CORROSION
EXPOSED WITHIN CEILING. TOP OF
CONCRETE SPALL & CORRODED REBAR
CORROSION & LOSS OF STEEL SECTION.
TOP OF VERTICAL SUPPORT LEGS HAVE
WALL & CEILING BETWEEN STANCHIONS 44 & 46.
BUILDUP & WATER INTRUSION PRESENT WITHIN
AROUND CRACK LOCATION IN CEILING. CALCIUM
CONCRETE SPALL & CORRODED REBAR EXPOSED
STEEL SECTION NEAR STANCHION 45.
SUPPORT LEGS HAVE CORROSION LOSS OF
ALONG WIDTH OF CEILING. TOP OF VERTICAL
EXPOSED WITHIN CEILING. CRACKING PRESENT
CONCRETE SPALL & CORRODED REBAR
OF CONCRETE TUNNEL DETAIL.
APPLICATION, & 2/S-303 FOR REPLACEMENT
DETAIL, 1/S-301 FOR EXTERNAL WATERPROOFING
SEE 1/S-303 FOR REPLACEMENT OF STANCHION
CLEAN AREA ADJACENT TO EXISTING STANCHION.
OF CONCRETE TUNNEL DETAIL.
APPLICATION, & 2/S-303 FOR REPLACEMENT
DETAIL, 1/S-301 FOR EXTERNAL WATERPROOFING
SEE 1/S-303 FOR REPLACEMENT OF STANCHION
CLEAN AREA ADJACENT TO EXISTING STANCHION.
WATERPROOFING APPLICATION.
SPALL REPAIR DETAIL, AND 2/S-301 FOR INTERNAL
DETAIL, 3B & 3C/S-301 FOR CONCRETE SURFACE
SEE 1/S-303 FOR REPLACEMENT OF STANCHION
CLEAN AREA ADJACENT TO EXISTING STANCHION.
OF CONCRETE TUNNEL DETAIL.
APPLICATION AND 2/S-303 FOR REPLACEMENT
SEE 1/S-301 FOR EXTERNAL WATERPROOFING
OF CONCRETE TUNNEL DETAIL.
APPLICATION AND 2/S-303 FOR REPLACEMENT
SEE 1/S-301 FOR EXTERNAL WATERPROOFING
OF CONCRETE TUNNEL DETAIL.
APPLICATION, & 2/S-303 FOR REPLACEMENT
DETAIL, 1/S-301 FOR EXTERNAL WATERPROOFING
SEE 1/S-303 FOR REPLACEMENT OF STANCHION
CLEAN AREA ADJACENT TO EXISTING STANCHION.
OF CONCRETE TUNNEL DETAIL.
APPLICATION, & 2/S-303 FOR REPLACEMENT
DETAIL, 1/S-301 FOR EXTERNAL WATERPROOFING
SEE 1/S-303 FOR REPLACEMENT OF STANCHION
CLEAN AREA ADJACENT TO EXISTING STANCHION.
OF CONCRETE TUNNEL DETAIL.
APPLICATION AND 2/S-303 FOR REPLACEMENT
SEE 1/S-301 FOR EXTERNAL WATERPROOFING
OF THE STANCHION.
THE BASE OF THE WALL & AROUND THE BASE
2. CLEAN ALL LOOSE PIECES OF DEBRIS FROM
COATING.
APPLICATION OF A CORROSION RESISTANT
STEEL SHALL BE CLEANED TO ALLOW FOR
STANCHIONS (TO REMAIN) SHALL BE REMOVED.
1. ALL CORROSION PRESENT ON EXISTING STEEL
NOTES: COORDINATOR ENGINEERING CHIEF
DATE REVISION BYNO. DATE NO. REVISION BY
C I
V
IL
ENGI
N
E E
R
US AF
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
OF
DESIGN CHIEF
DATEDRAWNDESIGNED CHECKED
RPR/RPL STEAM STANCHIONS
PROJECT NUMBER ZHTV 090018
SUBMITTAL - 100% GOVT. SUBMITTAL
SPR SPR MSS JUNE 2015