RFI 3
General Note G page A-001 requires the contractors reconstruct an entire partition if said partition should become unstable during the renovation process. Based on what is provided in the contract documents there is no way for bidding contractors to determine the structural stability of any partition in this facility. With this, how are bidding contractors to approach pricing this item?
General Note I page A-001 directs the contractors to paint above the ceiling & below the access floor the note “THIS WALL IS ONE HOUR RATED”. Although this note refers to “bay” there are no bays indicated on the project drawings. Further clarification is required.
Response
General Note G page A-001:
The current partitions are operating without defect if the contractor’s actions impact the stability of the partition then the contractor is responsible to repair with no additional cost to the government. The drawings do indicate specific locations work is to occur therefore this is a quantifiable activity.
General Note I page A-001:
See Addendum 2 for response.