RFI 3 Response.pdf

PDF 62 KB Posted

Attached to
Replace Fire Alarm System Federal contract opportunity
Solicitation number
FA8601-12-B-0011
Issued by
Department of the Air Force Materiel Command Lifecycle Management Center Wright Patterson Air Force Base

About this file

RFI 3 Response

View the file

Other files for this federal contract opportunity

Other files attached to Replace Fire Alarm System, newest first.
File Type Posted
FA8601-12-B-0011 - Amendment 5.pdf PDF
General Decision Number - OH29 - 3 AUG 12.pdf PDF
FA8601-12-B-0011 - Amendment 4.pdf PDF
General Decision Number - OH29 - 27 JUL 12.pdf PDF
RFI 4 Response.pdf PDF
RFI 1 Response.pdf PDF
RFI 5 Response.pdf PDF
RFI 2 Response.pdf PDF
RFI 6 Response.pdf PDF
Addendum 2 Drawing A-001.pdf PDF
Addendum 2 Drawing E-221A.pdf PDF
FA8601-12-B-0011 - Amendment 3.pdf PDF
Addendum 2 Drawing T-000.pdf PDF
Site Visit Sign-in Sheet.pdf PDF
Addendum 2 Drawing E-222A.pdf PDF
Addendum 2 Drawing E-223A.pdf PDF
Addendum 2.pdf PDF
Addendum 2 Drawing A-102.pdf PDF
FA8601-12-B-0011 - Addendum 1 Specification.pdf PDF
FA8601-12-B-0011 - Amendment 2.pdf PDF
FA8601-12-B-0011 - Addendum 1.pdf PDF
FA8601-12-B-0011 - Amendment 1 Site Visit Date.pdf PDF
DBA Wage Decision - Bldg Mod 23 6 Jul 12.pdf PDF
Final_FA_20676_Drawings 1 .pdf PDF
FA8601-12-B-0011 Replace Fire Alarm Sys.pdf PDF
Final_FA_20676_Specifications.pdf PDF
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI 3

General Note G page A-001 requires the contractors reconstruct an entire partition if said partition should become unstable during the renovation process. Based on what is provided in the contract documents there is no way for bidding contractors to determine the structural stability of any partition in this facility. With this, how are bidding contractors to approach pricing this item?

General Note I page A-001 directs the contractors to paint above the ceiling & below the access floor the note “THIS WALL IS ONE HOUR RATED”. Although this note refers to “bay” there are no bays indicated on the project drawings. Further clarification is required.

Response

General Note G page A-001:

The current partitions are operating without defect if the contractor’s actions impact the stability of the partition then the contractor is responsible to repair with no additional cost to the government. The drawings do indicate specific locations work is to occur therefore this is a quantifiable activity.

General Note I page A-001:

See Addendum 2 for response.