About this file

This is an electrical security plan showing floor plans and detailed diagrams for an Access Control System (ACS) installation at Tinker AFB, OK. The drawings include both an overall electrical security plan and detailed rough-in diagrams for single and double door installations.

The floor plan shows multiple administrative areas (Admin 1-6) with varying numbers of workstations, totaling approximately 87 workstations across all areas. The security infrastructure includes door contacts, card readers, electric strikes, and request-to-exit (REX) sensors. The detailed diagrams specify 3/4" conduit requirements, junction box placements, and wiring paths for both access control and intrusion detection systems. The plans indicate integration requirements with fire alarm systems for door release and specify that rough-in work must comply with DoD 5200.01 Vol 3 standards for secure open storage spaces. The contractor is responsible for providing junction boxes and conduit while the owner will install wiring and components.

View the file

Other files for this federal contract opportunity

Other files attached to Access Control System Equipment, newest first.
File Type Posted
Questions and Answers_23 Dec 2024.pdf PDF
Tab 3. ACS ET401.pdf PDF
Tab 2. ACS A601.pdf PDF
Tab 4. Door Hardware_Lines 284, 286-290.pdf PDF
Questions and Answers.pdf PDF
Brand Name Justification_Redacted.pdf PDF
12467 CDRL A002 Training Certificate.pdf PDF
FA813925Q0002.pdf PDF
12467 CDRL A004 72hr Failure Plan.pdf PDF
Performance Work Statement w. App C.pdf PDF
12467 CDRL A001 Design Drawings.pdf PDF
12467 CDRL A003 Installation Items.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

ADMIN 3A

Workstations 8 177A

ADMIN 2

Workstations 30

FACILITY

Workstations 4

Office 1

Workstations 1

Office 2

181A

181B

ADMIN 5

Workstations 16

ADMIN 1

Workstations 3

MECHANICAL ROOM

Security Office

Workstations 1

VAULTSTORAGE

STORAGE

185A185B

LAB

MECHANICAL & ELECTRICAL ROOM

178A

178B

ADMIN 4

Workstations 16

76 SWEG

COMM. RM

BREAK AREA

ADMIN 3

Workstations 15

ELEC. RM

MEN

175A

175B

WOMEN

72 ABW

COMM. RM

176A

JAN.

Workstations 1

ADMIN 6

Workstations 13

V

V

HGFEDB1A CB J

EL

EC

TR

IC

AL

SE

C U

R

IT

Y

PL

AN

- N

EW

W

O R

K

EY101

KL

JS

JM

OF

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

W W

YK

R

EN

O

VA

TE

N

W A

R

EA

O F

IN

TE

G R

AT

IO

N S

U

PP

O R

T, B

M

AY

H D

R

KEYPLAN

ELECTRICAL SECURITY PLAN - NEW WORK

SCALE: 3/32" = 1'-0"

EY101

GENERAL NOTES:

1. INSTALLATION TO BE IN ACCORDANCE WITH DoD 5200.01 VOLUME 3

AS IT APPLIES TO SECURE OPEN STORAGE.

2. COORDINATE ROUTING OF CONDUITS WITH EXISTING CONDITIONS,

BASE COMM SQUADRON, AND BASE SECURITY.

3. ACCESS CONTROL SYSTEM (ACS) COMPONENTS AND HARDWARE

WILL BE OWNER FURNISHED OWNER INSTALLED. CONTRACTOR

RESPONSIBLE TO PROVIDE ALL ROUGH-INS AND RACEWAYS TO

SUPPORT THE COMPLETE INSTALLATION. CONFIRM REQUIREMENTS

WITH BASE SECURITY AND USER PRIOR TO ROUGH-IN.

4. INTRUSION DETECTION SYSTEM (IDS) COMPONENTS AND

HARDWARE WILL BE OWNER FURNISHED OWNER INSTALLED.

CONTRACTOR RESPONSIBLE TO PROVIDE ALL WALL AND DOOR

ROUGH-INS AND RACEWAYS, OWNER WILL BE RESPONSIBLE FOR

MOTION DETECTOR ROUGH-IN, TO SUPPORT THE COMPLETE

INSTALLATION. CONFIRM REQUIREMENTS WITH BASE SECURITY AND

USER PRIOR TO ROUGH-IN.

5. ALL RECESSED ROUGH-INS WILL BE PROVIDED WITH ACOUSTICAL

PADS, STI SSP OR EQUAL. ROUGH-INS ON OPPOSITE SIDES OF

WALL REQUIRE MINIMUM 16" HORIZONTAL SEPARATION.

6. COORDINATE ROUGH-INS WITH DOOR HARDWARE SUPPLIER AND

BASE SECURITY OFFICER. PROVIDE ROUGH-IN AS REQUIRED FOR

DOOR CONTACTS, ELECTRIC STRIKES, CARD READERS, AND

REQUEST-TO-EXIT DEVICES.

SECURE DOOR WITH ACCESS CONTROLS. SEE DETAIL 1/EY501.

SECURE DOOR WITH INTRUSION DETECTION. SEE DETAIL 2/EY501.

SECURE DOOR WITH ACCESS CONTROLS AND INTRUSION DETECTION.

SEE DETAIL 4/EY501.

MOTION DETECTOR. ROUGH-IN AND DEVICES WILL BE OWNER

FURNISHED OWNER INSTALLED. LOCATIONS NOT SHOWN.

VINDICATOR SECURE/ACCESS SITE COMMANDER - 42" AFF. PROVIDE

3/4" CONDUIT HOMERUNNED TO THE ACS OR IDS SYSTEM PANEL AS

INDICATED.

CARD READER - 42" AFF

DURESS BUTTON - 42" AFF

TAMPER SWITCH

DOOR CONTACT

ELECTRIFIED LOCKSET

REQUEST TO EXIT MOTION DEVICE

LEGEND:

M

V

C

T

D

D

E

KEYED NOTES:

PERIMETER BOUNDARY OF SECURE OPEN STORAGE AREA.

CONSTRUCT PER DoD 5200.01 VOL 3. COORDINATE WITH BASE

SECURITY TO ENSURE THAT ALL PERIMETER OPENINGS ARE

SEALED AND ALL PERIMETERS WALLS ARE INSPECTIBLE.

3/4" CONDUIT TO PULLBOX 'ESS' IN COMM ROOM 176 FOR FUTURE

ACCESS CONTROL SYSTEM WIRING.

3/4" CONDUIT TO PULLBOX 'ESS' IN COMM ROOM 176 FOR FUTURE

INTRUSION DETECTION SYSTEM WIRING.

PULLBOX 'ESS'. REFER TO ELECTRONIC SECURITY SYSTEM RISER

6/EY501.

EXISTING DOOR. ROUGH-IN FOR IDS WILL BE SURFACE MOUNT.

ROUGH-IN FOR ELECTRONIC SECURITY SITE COMMANDER.

PROVIDE RECESSED 4-SQUARE BOX AT 48". PROVIDE 1" CONDUIT

TO PULLBOX 'ESS'. CONFIRM LOCATION WITH CONTRACTING

OFFICER PRIOR TO ROUGH-IN.

DOOR WILL BE PROVIDED WITH CDX10 LOCK. REFER TO

ARCHITECTURAL SHEETS AND HARDWARE SCHEDULE.

2 2

REX

05/24/21205/2

EL

EC

TR

IC

AL

SE

C U

R

IT

Y D

ET

AI

LS

EY501

KL

JS

JM

OF

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET

SHEET NUMBER

SH

EE

T

TI

TL

E

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

W W

YK

R

EN

O

VA

TE

N

W A

R

EA

O F

IN

TE

G R

AT

IO

N S

U

PP

O R

T, B

M

AY

H D

R

DOOR POWER SUPPLY

PROVIDED BY DIV 08

AND INSTALLED BY

DIVISION 26.

3/4" CONDUIT. FOR SURFACE

MOUNT APPLICATIONS PROVIDE

WIREMOLD 700 SERIES SURFACE

MOUNTED WIREMOLD. PROVIDE

BOXES AS REQUIRED FOR

DEVICES. COORDINATE WIRING

FOR ELECTRIC STRIKE AND

DOOR CONTACT WITH DOOR

AND HARDWARE VENDOR.

NOTES THIS DIAGRAM:

1. CONTRACTOR SHALL PROVIDE ALL NECESSARY JUNCTION BOXES AND

CONDUIT TO PROVIDE A COMPLETE AND OPERABLE ACS ROUGH-IN.

OWNER TO INSTALL ALL WIRING AND COMPONENTS. COORDINATE FINAL

ROUGH-IN REQUIREMENTS WITH OWNER AND ESS INSTALLER.

2. PROVIDE JUNCTION BOX ABOVE SECURITY PULL BOX WITH A 120V

CIRCUIT AND A 3/4" NIPPLE BETWEEN THE TWO BOXES.

3. DOOR CONTACT ROUGH-IN SHOWN IS DEDICATED TO ACCESS CONTROL.

4. ROUGH-IN TO BE IN ACCORDANCE WITH DOD 5200.01 VOL 3 FOR

SECURE OPEN STORAGE SPACES.

J

120V

D

3/4" CONDUIT. FOR

SURFACE MOUNT

APPLICATIONS PROVIDE

WIREMOLD 700 SERIES

SURFACE MOUNTED

WIREMOLD. COORDINATE

WIRING FOR DOOR

CONTACT WITH DOOR AND

HARDWARE VENDOR.

NOTES THIS DIAGRAM:

1. CONTRACTOR SHALL PROVIDE ALL NECESSARY JUNCTION BOXES AND

CONDUIT TO PROVIDE A COMPLETE AND OPERABLE IDS ROUGH-IN.

OWNER TO INSTALL ALL WIRING AND COMPONENTS. COORDINATE FINAL

ROUGH-IN REQUIREMENTS WITH OWNER AND ESS INSTALLER.

2. DOOR CONTACT ROUGH-IN SHOWN IS DEDICATED TO INTRUSION

DETECTION.

3. ROUGH-IN TO BE IN ACCORDANCE WITH DOD 5200.01 VOL 3 FOR

SECURE OPEN STORAGE SPACES.

ON EXTERIOR

SIDE OF DOOR

CEILING CEILING

D

T

C

ACCESS CONTROL

SINGLE DOOR ROUGH-IN DETAIL

N.T.S.

EY501

INTRUSION DETECTION

SINGLE DOOR ROUGH-IN DETAIL

N.T.S.

EY501

E

IN DOOR FRAME

8" x 8" x 4" PULL BOX

T

3/4" CONDUIT

3/4" CONDUIT TO PULL

BOX 'ESS'

4" x 4" x 4" PULL BOX

T

3/4" CONDUIT TO PULL

BOX 'ESS'

3/4" CONDUIT TO

INTEGRATE WITH FIRE

ALARM SYSTEM FOR

LOCK RELEASE WIRING.

PULL BOX 'ESS' IN COMM ROOM 176

72" x 8" x 6"

MOUNT 10' AFF

ELECTRONIC

SECURITY SYSTEM RISER

SCALE: NTS

EY501

IDS CONTROLLER AND IDS

WIRING TO BE INSTALLED IN A

SEPARATE CONTRACT.

3/4"CONDUITS, QUANTITY AS

REQUIRED, FOR ACS AND IDS

ROUGH-INS. REFER TO FLOOR

PLAN FOR LOCATIONS. PROVIDE

PULL STRINGS IN ALL CONDUITS.

ACS CONTROLLER AND ACS

WIRING TO BE INSTALLED IN A

SEPARATE CONTRACT.

REX

3/4" CONDUIT. FOR SURFACE

MOUNT APPLICATIONS PROVIDE

WIREMOLD 700 SERIES SURFACE

MOUNTED WIREMOLD. PROVIDE

BOXES AS REQUIRED FOR

DEVICES. COORDINATE WIRING

FOR ELECTRIC STRIKE AND

DOOR CONTACT WITH DOOR

AND HARDWARE VENDOR.

NOTES THIS DIAGRAM:

1. CONTRACTOR SHALL PROVIDE ALL NECESSARY JUNCTION BOXES AND

CONDUIT TO PROVIDE A COMPLETE AND OPERABLE ACS ROUGH-IN.

OWNER TO INSTALL ALL WIRING AND COMPONENTS. COORDINATE FINAL

ROUGH-IN REQUIREMENTS WITH OWNER AND ESS INSTALLER.

2. PROVIDE JUNCTION BOX ABOVE SECURITY PULL BOX WITH A 120V

CIRCUIT AND A 3/4" NIPPLE BETWEEN THE TWO BOXES.

3. DOOR CONTACT WILL HAVE TWO INDEPENDENT OUTPUTS.

4. ROUGH-IN TO BE IN ACCORDANCE WITH DOD 5200.01 VOL 3 FOR

SECURE OPEN STORAGE SPACES.

J 120V

ON EXTERIOR

SIDE OF DOOR

CEILING

D

T

C

ACCESS CONTROL AND INTRUSION

DETECTION SINGLE DOOR ROUGH-IN DETAIL

N.T.S.

EY501

E

IN DOOR FRAME

8" x 8" x 4" PULL BOX

T

3/4" CONDUIT

3/4" CONDUIT TO PULL BOX 'ESS'

3/4" CONDUIT TO INTEGRATE WITH FIRE

ALARM SYSTEM FOR LOCK RELEASE WIRING.

REX

T

3/4" CONDUIT TO PULL

BOX 'ESS'

4" x 4" x 4" PULL BOX

DOOR POWER SUPPLY

PROVIDED BY DIV 08

AND INSTALLED BY

DIVISION 26.

AS

R

EQ

U

IR

ED

6" 48

AS

R

EQ

U

IR

ED

6" 48

D

3/4" CONDUIT. FOR SURFACE MOUNT

APPLICATIONS PROVIDE WIREMOLD

700 SERIES SURFACE MOUNTED

WIREMOLD. COORDINATE WIRING

FOR DOOR CONTACT WITH DOOR

AND HARDWARE VENDOR.

NOTES THIS DIAGRAM:

1. CONTRACTOR SHALL PROVIDE ALL NECESSARY JUNCTION BOXES AND

CONDUIT TO PROVIDE A COMPLETE AND OPERABLE IDS ROUGH-IN.

OWNER TO INSTALL ALL WIRING AND COMPONENTS. COORDINATE FINAL

ROUGH-IN REQUIREMENTS WITH OWNER AND ESS INSTALLER.

2. DOOR CONTACT ROUGH-IN SHOWN IS DEDICATED TO INTRUSION

DETECTION.

3. ROUGH-IN TO BE IN ACCORDANCE WITH DOD 5200.01 VOL 3 FOR

SECURE OPEN STORAGE SPACES.

CEILING

INTRUSION DETECTION

DOUBLE DOOR ROUGH-IN DETAIL

N.T.S.

EY501

4" x 4" x 4" PULL BOX

T

3/4" CONDUIT TO PULL

BOX 'ESS'

D

3/4" CONDUIT. FOR SURFACE

MOUNT APPLICATIONS PROVIDE

WIREMOLD 700 SERIES SURFACE

MOUNTED WIREMOLD. PROVIDE

BOXES AS REQUIRED FOR

DEVICES. COORDINATE WIRING

FOR ELECTRIC STRIKE AND

DOOR CONTACT WITH DOOR

AND HARDWARE VENDOR.

NOTES THIS DIAGRAM:

1. CONTRACTOR SHALL PROVIDE ALL NECESSARY JUNCTION BOXES AND

CONDUIT TO PROVIDE A COMPLETE AND OPERABLE ACS ROUGH-IN.

OWNER TO INSTALL ALL WIRING AND COMPONENTS. COORDINATE FINAL

ROUGH-IN REQUIREMENTS WITH OWNER AND ESS INSTALLER.

2. PROVIDE JUNCTION BOX ABOVE SECURITY PULL BOX WITH A 120V

CIRCUIT AND A 3/4" NIPPLE BETWEEN THE TWO BOXES.

3. DOOR CONTACT WILL HAVE TWO INDEPENDENT OUTPUTS.

4. ROUGH-IN TO BE IN ACCORDANCE WITH DOD 5200.01 VOL 3 FOR

SECURE OPEN STORAGE SPACES.

J 120V

ON EXTERIOR

SIDE OF DOOR

CEILING

D

T

C

ACCESS CONTROL AND INTRUSION

DETECTION DOUBLE DOOR ROUGH-IN DETAIL

N.T.S.

EY501

E

IN DOOR FRAME

8" x 8" x 4" PULL BOX

T

3/4" CONDUIT

3/4" CONDUIT TO PULL BOX 'ESS'

3/4" CONDUIT TO INTEGRATE WITH FIRE

ALARM SYSTEM FOR LOCK RELEASE WIRING.

REX

T

3/4" CONDUIT TO PULL

BOX 'ESS'

4" x 4" x 4" PULL BOX

DOOR POWER SUPPLY

PROVIDED BY DIV 08

AND INSTALLED BY

DIVISION 26.

AS

R

EQ

U

IR

ED

6" 48

05/24/21205/2

File details come from the government source that posted it. Updated .