This is a technical specification document for diesel-generator sets in the 15-300 kW range for standby applications at Tinker Air Force Base, Oklahoma, dated April 2019.

The specification establishes comprehensive requirements for complete engine-generator sets including engines, generators, fuel systems, cooling systems, lubrication systems, exhaust systems, starting systems, governors, voltage regulators, protective devices, control panels, instrumentation, and ancillary equipment. Engine-generator sets must be stationary, diesel-powered units rated for standby service with water/ethylene glycol cooling, isochronous or droop governors, and maximum speed of 1800 rpm. Key performance parameters include 0.8 lagging power factor, frequency regulation of ±0.4 percent steady state, voltage regulation of ±2 percent, 60 Hz frequency, 3-phase delta configuration, and capability to accept 100 percent step load changes without shutdown. The specification requires 24-hour fuel tank capacity at 100 percent rated load, comprehensive safety systems with audible and visual alarms for high temperature, low oil pressure, overspeed, and fuel level conditions, and automated shutdown capabilities. Sound limitations are specified by frequency band, with maximum acceptable levels ranging from 87 decibels at 31-63 Hz to 60-62 decibels at 1000-8000 Hz measured at 22.9 feet. Extensive onsite testing, inspections, and commissioning activities are required, including construction tests, safety run tests, performance tests, continuous load run testing, and final acceptance testing with documentation. The contractor must provide four-hour operator training, operation and maintenance manuals, spare parts, special tools, and qualified field engineering supervision during installation and testing.

View the file

Other files

File Type Posted
03 39 00.00 10.pdf PDF
03 62 16.pdf PDF
04 20 00.pdf PDF
05 21 00.pdf PDF
06 20 00.pdf PDF
06 61 16.pdf PDF
07 60 00.pdf PDF
07 61 14.00 20.pdf PDF
07 84 00.pdf PDF
07 92 00.pdf PDF
08 11 16.pdf PDF
08 36 13.pdf PDF
08 71 00.pdf PDF
09 68 00.pdf PDF
10 28 13.pdf PDF
13 48 00.pdf PDF
21 13 17.pdf PDF
22 00 00.pdf PDF
23 00 00.pdf PDF
23 08 00.pdf PDF
23 11 25.pdf PDF
23 35 00.pdf PDF
23 64 26.pdf PDF
23 82 16.00 40.pdf PDF
23 82 43.00 40.pdf PDF
26 56 00.pdf PDF
31 23 06.pdf PDF
32 01 14.pdf PDF
32 13 74.pdf PDF
03 11 13.00 10.pdf PDF
03 20 00.00 10.pdf PDF
03 30 00.pdf PDF
07 14 00.pdf PDF
190023 Renovate Restrooms B117 RFIs_FINAL_COR_Signed.pdf PDF
TAFB_Tech_Reqs (Div 02-48).zip ZIP file
Model.zip ZIP file
00 71 00.pdf PDF
01 78 23.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 32 16.00 20.pdf PDF
01 33 16.00 10.pdf PDF
01 42 00.pdf PDF
01 78 00.pdf PDF
Tinker General Requirements Specifications_Nov 2022_Change Log.pdf PDF
Initial Site Visit WWYK190023.pdf PDF
Solicitation - FA813726R0030.pdf PDF
Att10_190023_SOW.pdf PDF
EAL List - BLANK to Contractors WWYK190023.xlsx XLSX spreadsheet
Att12_190023_Drawings_Final.pdf PDF
Section L - Instructions to Offerors.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 26 32 14. 00 10

DI ESEL- GENERATOR SET, STATI ONARY 15- 300 KW, STANDBY APPLI CATI ONS

04/17

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )

ANSI C39. 1 ( 1981; R 1992) Requi r ement s f or El ect r i cal Anal og I ndi cat i ng I nst r ument s

ASME I NTERNATI ONAL ( ASME)

ASME B16. 11 ( 2011) For ged Fi t t i ngs, Socket - Wel di ng and Threaded

ASME B16. 3 ( 2011) Mal l eabl e I r on Thr eaded Fi t t i ngs, Cl asses 150 and 300

ASME B16. 5 ( 2013) Pi pe Fl anges and Fl anged Fi t t i ngs:

NPS 1/ 2 Thr ough NPS 24 Met r i c/ I nch St andar d

ASME B31. 1 ( 2014; I NT 1- 47) Power Pi pi ng

ASME BPVC SEC I X ( 2010) BPVC Sect i on I X- Wel di ng and Br azi ng Qualifications

ASME BPVC SEC VI I I D1 ( 2010) BPVC Sect i on VI I I - Rul es f or Const r uct i on of Pr essur e Vessel s Di v i s i on 1

ASSOCI ATI ON OF EDI SON I LLUMI NATI NG COMPANI ES ( AEI C)

AEI C CS8 ( 2013) Speci f i cat i on f or Ext r uded Di el ect r i c Shi el ded Power Cabl es Rat ed 5 Thr ough 46 kV

ASTM I NTERNATI ONAL ( ASTM)

ASTM A106/ A106M ( 2014) St andar d Speci f i cat i on f or Seaml ess Car bon St eel Pi pe f or Hi gh- Temper at ur e Service

ASTM A135/ A135M ( 2009; R2014) St andar d Speci f i cat i on f or El ect r i c- Resi st ance- Wel ded St eel Pi pe

ASTM A181/ A181M ( 2014) St andar d Speci f i cat i on f or Car bon St eel For gi ngs, f or Gener al - Pur pose Pi pi ng

ASTM A234/ A234M ( 2013; E 2014) St andar d Speci f i cat i on f or Pi pi ng Fi t t i ngs of Wr ought Car bon St eel

Apr i l 2019 Page 1 SECTI ON 26 32 14. 00 10 and Al l oy St eel f or Moder at e and Hi gh Temper at ur e Ser vi ce

ASTM A53/ A53M ( 2012) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess

ASTM B395/ B395M ( 2013) St andar d Speci f i cat i on f or U- Bend Seaml ess Copper and Copper Al l oy Heat Exchanger and Condenser Tubes

ASTM D975 ( 2015b) St andar d Speci f i cat i on f or Di esel Fuel Oi l s

ELECTRI CAL GENERATI NG SYSTEMS ASSOCI ATI ON ( EGSA)

EGSA 101P ( 1995) Per f or mance St andar d f or Engi ne Dr i ven Gener at or Set s

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE 1 ( 2000; R 2011) Gener al Pr i nci pl es f or Temper at ur e Li mi t s i n t he Rat i ng of El ect r i c Equi pment and f or t he Eval uat i on of El ect r i cal I nsul at i on

I EEE 120 ( 1989; R 2007) Mast er Test Gui de f or El ect r i cal Measur ement s i n Power Ci r cui t s

I EEE 404 ( 2012) St andar d f or Ext r uded and Lami nat ed Di el ect r i c Shi el ded Cabl e Joi nt s Rat ed 2500 V t o 500, 000 V

I EEE 48 ( 2009) St andar d f or Test Pr ocedur es and Requi r ement s f or Al t er nat i ng- Cur r ent Cabl e Ter mi nat i ons Used on Shi el ded Cabl es Havi ng Lami nat ed I nsul at i on Rat ed 2. 5 kV t hr ough 765 kV or Ext r uded I nsul at i on Rat ed 2. 5 kV t hr ough 500 kV

I EEE 519 ( 2014) Recommended Pr act i ces and Requi r ement s f or Har moni c Cont r ol i n El ect r i cal Power Syst ems

I EEE 81 ( 2012) Gui de f or Measur i ng Ear t h Resi st i v i t y, Gr ound I mpedance, and Ear t h Sur f ace Pot ent i al s of a Gr ound Syst em

I EEE C2 ( 2012; Er r at a 1 2012; I NT 1- 4 2012; Er r at a

2 2013; I NT 5- 7 2013; I NT 8- 10 2014; I NT

11 2015; I NT 12 2016) Nat i onal El ect r i cal Saf et y Code

I EEE St ds Di ct i onar y ( 2009) I EEE St andar ds Di ct i onar y: Gl ossar y of Ter ms & Def i ni t i ons

Apr i l 2019 Page 2 SECTI ON 26 32 14. 00 10

MANUFACTURERS STANDARDI ZATI ON SOCI ETY OF THE VALVE AND FI TTI NGS

I NDUSTRY ( MSS)

MSS SP- 58 ( 1993; Reaf f i r med 2010) Pi pe Hanger s and Suppor t s - Mat er i al s, Desi gn and Manuf act ur e, Sel ect i on, Appl i cat i on, and Installation

MSS SP- 80 ( 2013) Br onze Gat e, Gl obe, Angl e and Check Valves

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

NEMA I CS 2 ( 2000; R 2005; Er r at a 2008) St andar d f or Cont r ol l er s, Cont act or s, and Over l oad Rel ays Rat ed 600 V

NEMA I CS 6 ( 1993; R 2011) Encl osur es

NEMA MG 1 ( 2014) Mot or s and Gener at or s

NEMA PB 1 ( 2011) Panel boar ds

NEMA WC 74/ I CEA S- 93- 639 ( 2012) 5- 46 kV Shi el ded Power Cabl e f or Use i n t he Tr ansmi ssi on and Di st r i but i on of El ect r i c Ener gy

NEMA/ ANSI C12. 11 ( 2007) I nst r ument Tr ansf or mer s f or Revenue Met er i ng, 10 kV BI L t hr ough 350 kV BI L ( 0. 6 kV NSV t hr ough 69 kV NSV)

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 110 ( 2016) St andar d f or Emer gency and St andby Power Syst ems

NFPA 30 ( 2015) Fl ammabl e and Combust i bl e Li qui ds Code

NFPA 37 ( 2015) St andar d f or t he I nst al l at i on and Use of St at i onar y Combust i on Engi nes and Gas Tur bi nes

NFPA 70 ( 2014; AMD 1 2013; Er r at a 1 2013; AMD 2 2013; Er r at a 2 2013; AMD 3 2014; Er r at a 3- 4 2014; AMD 4- 6 2014) Nat i onal El ect r i cal Code

NFPA 99 ( 2015) Heal t h Car e Faci l i t i es Code

SOCI ETY OF AUTOMOTI VE ENGI NEERS I NTERNATI ONAL ( SAE)

SAE ARP892 ( 1965; R 1994) DC St ar t er - Gener at or , Engi ne

SAE J537 ( 2016) St or age Bat t er i es

U. S. DEPARTMENT OF DEFENSE ( DOD)

UFC 3- 310- 04 ( 2013) Sei smi c Desi gn f or Bui l di ngs

Apr i l 2019 Page 3 SECTI ON 26 32 14. 00 10

UNDERWRI TERS LABORATORI ES ( UL)

UL 1236 ( 2015) St andar d f or Bat t er y Char ger s f or Char gi ng Engi ne- St ar t er Bat t er i es

UL 489 ( 2013; Repr i nt Mar 2014) Mol ded- Case Ci r cui t Br eaker s, Mol ded- Case Swi t ches, and Ci r cui t - Br eaker Encl osur es

UL 891 ( 2005; Repr i nt Oct 2012) Swi t chboar ds

1. 2 SYSTEM DESCRI PTI ON

a. Pr ovi de and i nst al l each engi ne- gener at or set compl et e and t ot al l y f unct i onal , wi t h al l necessar y anci l l ar y equi pment t o i ncl ude ai r f i l t r at i on; st ar t i ng syst em; gener at or cont r ol s, pr ot ect i on, and i sol at i on; i nst r ument at i on; l ubr i cat i on; f uel syst em; cool i ng syst em;

and engi ne exhaust syst em. Each engi ne gener at or set shal l sat i sf y t he r equi r ement s speci f i ed i n t he Engi ne Gener at or Par amet er Schedul e. Submi t cer t i f i cat i on t hat t he engi ne- gener at or set and cool i ng syst em f unct i on pr oper l y i n t he ambi ent t emper at ur es speci f i ed.

b. Pr ovi de each engi ne- gener at or set consi st i ng of one engi ne, one gener at or , and one exci t er , mount ed, assembl ed, and al i gned on one base; and al l ot her necessar y anci l l ar y equi pment whi ch may be mount ed separ at el y. Set s shal l be assembl ed and at t ached t o t he base pr i or t o shi ppi ng. Set component s shal l be envi r onment al l y sui t abl e f or t he l ocat i ons shown and shal l be t he manuf act ur er ' s st andar d pr oduct of f er ed i n cat al ogs f or commer ci al or i ndust r i al use. Pr ovi de a gener at or st r i p heat er f or moi st ur e cont r ol when t he gener at or i s not operating.

1. 2. 1 Engi ne- Gener at or Par amet er Schedul e

ENGI NE GENERATOR PARAMETER SCHEDULE

Ser vi ce Load As Speci f i ed kW

Power Fact or 0. 8 l aggi ng

Mot or St ar t i ng kVA ( maxi mum) As Speci f i ed kVA

Maxi mum Speed 1800 r pm

Engi ne- Gener at or Appl i cat i on stand-alone

Engi ne Cool i ng Type wat er / et hyl ene gl ycol

Heat Exchanger Type f i n- t ube or shel l - t ube As Speci f i ed

Gover nor Type Isochronous

Fr equency Bandwi dt h per cent st eady st at e + 0. 4

Apr i l 2019 Page 4 SECTI ON 26 32 14. 00 10

ENGI NE GENERATOR PARAMETER SCHEDULE

Gover nor Type Droop

Fr equency Regul at i on ( dr oop) ( No l oad t o f ul l l oad)

3 per cent max. )

Fr equency Bandwi dt h per cent ( st eady state)

+ 0. 4

Vol t age Regul at i on ( No l oad t o f ul l l oad) + 2 per cent ( max. )

Vol t age Bandwi dt h ( st eady st at e) + 0. 5 per cent

Frequency 60 Hz

Voltage as speci f i ed vol t s

Phases 3 Phase, Del t a

Mi ni mum Gener at or React ance as speci f i ed per cent Subt r ansi ent

Nonl i near Loads as speci f i ed kVA

Max St ep Load I ncr ease 100 per cent of Ser vi ce Load at 0. 8 PF

Max St ep Load Decr ease ( w/ o shut down) 100 per cent of Ser vi ce Load at 0. 8 PF

Max Ti me t o St ar t and be Ready t o Assume Load

10 seconds

Max Summer I ndoor Temp ( Pr i or t o Genset Operation)

80 degr ees F

Mi n Wi nt er I ndoor Temp ( Pr i or t o Genset Operation)

40 degr ees F

Mi n Wi nt er I ndoor Temp 40 degr ees F

Max Al l owabl e Heat Tr ansf er r ed To Engi ne Gener at or Space at Rat ed Out put Capaci t y as speci f i ed MBTUH/ hr

Max Summer Out door Temp ( Ambi ent ) 110 degr ees F

Mi n Wi nt er Out door Temp ( Ambi ent ) 10 degr ees F

I nst al l at i on El evat i on 1253 f eet above sea l evel

Apr i l 2019 Page 5 SECTI ON 26 32 14. 00 10

1. 2. 2 Out put Capaci t y

Pr ovi de each gener at or set wi t h power equal t o t he sum of ser vi ce l oad pl us t he machi ne' s ef f i c i ency l oss and associ at ed anci l l ar y equi pment l oads. Rat ed out put capaci t y shal l al so consi der engi ne and/ or gener at or over si z i ng r equi r ed t o meet r equi r ement s i n par agr aph Engi ne- Gener at or Par amet er Schedul e.

1. 2. 3 Power Rat i ng

St andby r at i ngs shal l be i n accor dance wi t h EGSA 101P.

1. 2. 4 Engi ne Gener at or Set Encl osur e

The engi ne gener at or set encl osur e shal l be cor r osi on r esi st ant , f ul l y weat her r esi st ant , cont ai n al l set component s, and pr ovi de vent i l at i on t o per mi t oper at i on at r at ed l oad under secur ed condi t i ons. Pr ovi de door s f or access t o al l cont r ol s and equi pment r equi r i ng per i odi c mai nt enance or adj ust ment . Pr ovi de r emovabl e panel s f or access t o component s r equi r i ng per i odi c r epl acement . The encl osur e shal l be capabl e of bei ng r emoved wi t hout di sassembl y of t he engi ne- gener at or set or r emoval of component s ot her t han exhaust syst em. The encl osur e shal l r educe t he noi se of t he gener at or set t o wi t hi n t he l i mi t s speci f i ed i n t he par agr aph SOUND

LIMITATIONS.

1. 2. 5 Vi br at i on I sol at i on

1. 2. 5. 1 Vi br at i on Li mi t at i ons

The maxi mum engi ne- gener at or set v i br at i on i n t he hor i zont al , ver t i cal and axi al di r ect i ons shal l be l i mi t ed t o 6 mi l s ( peak- peak RMS) , wi t h an over al l vel oci t y l i mi t of 0. 95 i nches/ seconds RMS, f or al l speeds t hr ough 110 per cent of r at ed speed. The engi ne- gener at or set shal l be pr ovi ded wi t h v i br at i on- i sol at i on i n accor dance wi t h t he manuf act ur er ' s st andar d r ecommendat i on. Wher e t he vi br at i on- i sol at i on syst em does not secur e t he base t o t he st r uct ur e f l oor or uni t f oundat i on, pr ovi de sei smi c r est r ai nt s i n accor dance wi t h t he sei smi c par amet er s speci f i ed.

1. 2. 5. 2 Tor si onal Anal ysi s

Submi t t or s i onal anal ysi s i ncl udi ng pr ot ot ype t est i ng or cal cul at i ons whi ch cer t i f y and demonst r at e t hat no damagi ng or danger ous t or si onal v i br at i ons wi l l occur when t he pr i me mover i s connect ed t o t he gener at or , at synchr onous speeds, pl us/ mi nus 10 per cent .

1. 2. 5. 3 Per f or mance Dat a

Submi t v i br at i on i sol at i on syst em per f or mance dat a f or t he r ange of f r equenci es gener at ed by t he engi ne- gener at or set dur i ng oper at i on f r om no l oad t o f ul l l oad and t he maxi mum vi br at i on t r ansmi t t ed t o t he f l oor .

Al so submi t a descr i pt i on of sei smi c qual i f i cat i on of t he engi ne- gener at or mount i ng, base, and vi br at i on i sol at i on.

1. 2. 6 Rel i abi l i t y and Dur abi l i t y

Submi t document at i on whi ch ci t es engi nes and gener at or s i n s i mi l ar ser vi ce t o demonst r at e compl i ance wi t h t he r equi r ement s of t hi s speci f i cat i on.

Cer t i f i cat i on does not excl ude annual t echnol ogi cal i mpr ovement s made by a manuf act ur er i n t he basi c st andar d model set on whi ch exper i ence was

Apr i l 2019 Page 6 SECTI ON 26 32 14. 00 10 obt ai ned, pr ovi ded par t s i nt er changeabi l i t y has not been subst ant i al l y af f ect ed and t he cur r ent st andar d model meet s al l t he per f or mance r equi r ement s of t hi s speci f i cat i on. For each di f f er ent set , 2 l i ke set s shal l have per f or med sat i sf act or i l y i n a st at i onar y power appl i cat i on, i ndependent and separ at e f r om t he physi cal l ocat i on of t he manuf act ur er ' s and assembl er ' s f aci l i t i es, f or a mi ni mum of 2 consecut i ve year s wi t hout any f ai l ur e t o st ar t , i ncl udi ng per i odi c exer ci se. The cer t i f i cat i on shal l st at e t hat f or t he set pr oposed t o meet t hi s speci f i cat i on, t her e wer e no f ai l ur es r esul t i ng i n downt i me f or r epai r s i n excess of 72 hour s or any f ai l ur e due t o over heat i ng dur i ng 2 consecut i ve year s of ser vi ce.

Li ke set s ar e of t he same model , speed, bor e, st r oke, number and conf i gur at i on of cyl i nder s, and out put power r at i ng. Li ke gener at or s ar e of t he same model , speed, pi t ch, cool i ng, exci t er , vol t age r egul at or and out put power r at i ng. A l i s t shal l be pr ovi ded wi t h t he name of t he i nst al l at i ons, compl et i on dat es, and name and t el ephone number of a poi nt of cont act .

1. 3 SUBMITTALS

Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL

PROCEDURES:

SD- 02 Shop Dr awi ngs

Det ai l ed Dr awi ngs;

Acceptance;

SD- 03 Pr oduct Dat a

Manuf act ur er ' s Cat al og Instructions;

Experience Fi el d Engi neer Si t e Wel di ng Gener al I nst al l at i on Si t e Vi s i t

SD- 05 Desi gn Dat a

Sound Li mi t at i ons;

Generator I nt egr al Mai n Fuel St or age Tank Day Tank Power Fact or Heat Exchanger Ti me- Del ay on Al ar ms Cool i ng Syst em Vi br at i on I sol at i on

SD- 06 Test Repor t s

Per f or mance Test s Onsi t e I nspect i on and Test s;

SD- 07 Cer t i f i cat es

Vi br at i on I sol at i on Pr ot ot ype Test s Rel i abi l i t y and Dur abi l i t y

Apr i l 2019 Page 7 SECTI ON 26 32 14. 00 10

Emissions Sound l i mi t at i ons Cur r ent Bal ance Mat er i al s and Equi pment Fact or y I nspect i on and Test s Inspections Cool i ng Syst em

SD- 10 Oper at i on and Mai nt enance Dat a

Oper at i on Manual ;

Mai nt enance Manual ;

Ext r a Mat er i al s

1. 4 QUALI TY ASSURANCE

1. 4. 1 Conf or mance t o Codes and St andar ds

Wher e equi pment i s speci f i ed t o conf or m t o r equi r ement s of any code or st andar d such as UL, t he desi gn, f abr i cat i on and i nst al l at i on shal l conf or m t o t he code.

1. 4. 2 Si t e Wel di ng

Wel d st r uct ur al member s i n accor dance wi t h Sect i on 05 05 23. 16 STRUCTURAL WELDI NG. For al l ot her wel di ng, qual i f y pr ocedur es and wel der s i n accor dance wi t h ASME BPVC SEC I X.

a. Wel di ng pr ocedur es qual i f i ed by ot her s, and wel der s and wel di ng oper at or s qual i f i ed by a pr evi ousl y qual i f i ed empl oyer may be accept ed as per mi t t ed by ASME B31. 1.

b. Wel der qual i f i cat i on t est s shal l be per f or med f or each wel der whose qual i f i cat i ons ar e not i n compl i ance wi t h t he r ef er enced st andar ds.

Not i f y t he Cont r act i ng Of f i cer 24 hour s i n advance of qual i f i cat i on t est s. The qual i f i cat i on t est s shal l be per f or med at t he wor k s i t e i f practical.

c. The wel der or wel di ng oper at or shal l appl y t he assi gned per sonal symbol near each wel d made as a per manent r ecor d

d. Submi t a l et t er l i s t i ng t he wel der qual i f y i ng pr ocedur es f or each wel der , compl et e wi t h suppor t i ng dat a such as t est pr ocedur es used, what was t est ed t o, and a l i s t of t he names of al l wel der s and t hei r qual i f i cat i ons symbol s.

1. 4. 3 Experience

Each component manuf act ur er shal l have a mi ni mum of 3 year s exper i ence i n t he manuf act ur e, assembl y and sal e of component s used wi t h st at i onar y di esel engi ne- gener at or set s f or commer ci al and i ndust r i al use. The engi ne- gener at or set manuf act ur e/ assembl er shal l have a mi ni mum of 3 year s exper i ence i n t he manuf act ur e, assembl y and sal e of st at i onar y di esel engi ne- gener at or set s f or commer ci al and i ndust r i al use. Submi t a st at ement showi ng and ver i f y i ng t hese r equi r ement s.

1. 4. 4 Fi el d Engi neer

The engi ne- gener at or set manuf act ur er or assembl er shal l f ur ni sh a

Apr i l 2019 Page 8 SECTI ON 26 32 14. 00 10 qual i f i ed f i el d engi neer t o super vi se t he compl et e i nst al l at i on of t he engi ne- gener at or set , assi st i n t he per f or mance of t he onsi t e t est s, and i nst r uct per sonnel as t o t he oper at i onal and mai nt enance f eat ur es of t he equi pment . The f i el d engi neer shal l have at t ended t he engi ne- gener at or manuf act ur er ' s t r ai ni ng cour ses on i nst al l at i on and oper at i on and mai nt enance f or engi ne gener at or set s. Submi t a l et t er l i s t i ng t he qual i f i cat i ons, school s, f or mal t r ai ni ng, and exper i ence of t he f i el d engineer.

1. 4. 5 Sei smi c Requi r ement s

Sei smi c r equi r ement s shal l be i n accor dance wi t h UFC 3- 310- 04 and Sect i ons 13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT and 26 05 48. 00 10

SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT.

1. 4. 6 Det ai l ed Dr awi ngs

Submi t det ai l ed dr awi ngs showi ng t he f ol l owi ng:

a. Base- mount ed equi pment , compl et e wi t h base and at t achment s i ncl udi ng anchor bol t t empl at e and r ecommended cl ear ances f or mai nt enance and operation.

b. St ar t i ng syst em.

c. Fuel syst em.

d. Cool i ng syst em.

e. Exhaust syst em.

f . El ect r i c wi r i ng of r el ays, br eaker s, pr ogr ammabl e cont r ol l er s, and swi t ches i ncl udi ng si ngl e l i ne and wi r i ng di agr ams.

g. Lubr i cat i on syst em, i ncl udi ng pi pi ng, pumps, st r ai ner s, f i l t er s, heat exchanger s f or l ube oi l and t ur bochar ger cool i ng, el ect r i c heat er , cont r ol s and wi r i ng, as speci f i ed.

h. Locat i on, t ype, and descr i pt i on of v i br at i on i sol at i on devi ces.

i . The saf et y syst em, i ncl udi ng wi r i ng schemat i cs.

j . One- l i ne schemat i c and wi r i ng di agr ams of t he gener at or , exci t er , r egul at or , gover nor , and al l i nst r ument at i on.

k. Panel l ayout s.

l . Mount i ng and suppor t f or each panel and maj or pi ece of el ect r i cal equipment.

m. Engi ne- gener at or set r i ggi ng poi nt s and l i f t i ng i nst r uct i ons.

1. 5 DELI VERY, STORAGE AND HANDLI NG

Pr oper l y pr ot ect mat er i al s and equi pment i n accor dance wi t h t he manuf act ur er s r ecommended st or age pr ocedur es, bef or e, dur i ng, and af t er i nst al l at i on. Pr ot ect st or ed i t ems f r om t he weat her and cont ami nat i on.

Dur i ng i nst al l at i on, pi pi ng and si mi l ar openi ngs shal l be capped t o keep out di r t and ot her f or ei gn mat t er .

Apr i l 2019 Page 9 SECTI ON 26 32 14. 00 10

1. 6 MAI NTENANCE SERVI CE

Submi t t he oper at i on and mai nt enance manual s and have t hem appr oved pr i or t o commenci ng onsi t e t est s.

1. 6. 1 Oper at i on Manual

Pr ovi de f our copi es of t he oper at i on manual i n 8- 1/ 2 by 11 i nch t hr ee- r i ng bi nder s. Sect i ons shal l be separ at ed by heavy pl ast i c di v i der s wi t h t abs whi ch i dent i f y t he mat er i al i n t he sect i on. Dr awi ngs shal l be f ol ded bl ue l i nes, wi t h t he t i t l e bl ock v i s i bl e, and pl aced i n 8- 1/ 2 by 11 i nch pl ast i c pocket s wi t h r ei nf or ced hol es. The manual shal l i ncl ude:

a. St ep- by- st ep pr ocedur es f or syst em st ar t up, oper at i on, and shut down;

b. Dr awi ngs, di agr ams, and si ngl e- l i ne schemat i cs t o i l l ust r at e and def i ne t he el ect r i cal , mechani cal , and hydr aul i c syst ems wi t h t hei r cont r ol s, al ar ms, and saf et y syst ems;

c. Pr ocedur es f or i nt er f ace and i nt er act i on wi t h r el at ed syst ems t o i ncl ude aut omat i c t r ansf er swi t ches.

1. 6. 2 Mai nt enance Manual

Pr ovi de f our copi es of t he mai nt enance manual cont ai ni ng t he i nf or mat i on descr i bed bel ow i n 8- 1/ 2 x 11 i nch t hr ee- r i ng bi nder s. Each sect i on shal l be separ at ed by a heavy pl ast i c di v i der wi t h t abs. Dr awi ngs shal l be f ol ded, wi t h t he t i t l e bl ock v i s i bl e, and pl aced i n pl ast i c pocket s wi t h r ei nf or ced hol es. The manual shal l i ncl ude:

a. Pr ocedur es f or each r out i ne mai nt enance i t em. Pr ocedur es f or t r oubl eshoot i ng. Fact or y- ser vi ce, t ake- down over haul , and r epai r ser vi ce manual s, wi t h par t s l i s t s.

b. The manuf act ur er ' s r ecommended mai nt enance schedul e.

c. A component l i s t whi ch i ncl udes t he manuf act ur er ' s name, addr ess, t ype or st y l e, model or ser i al number , r at i ng, and cat al og number f or t he maj or component s l i s t ed i n par agr aph GENERAL REQUI REMENTS.

d. A l i s t of spar e par t s f or each pi ece of equi pment and a compl et e l i s t of mat er i al s and suppl i es needed f or oper at i on.

1. 6. 3 Ext r a Mat er i al s

Pr ovi de t wo set s of speci al t ool s and t wo set s of f i l t er s r equi r ed f or mai nt enance. Speci al t ool s ar e t hose t hat onl y t he manuf act ur er pr ovi des, f or speci al pur poses, or t o r each ot her wi se i naccessi bl e par t s. One handset shal l be pr ovi ded f or each el ect r oni c gover nor when r equi r ed t o i ndi cat e and/ or change gover nor r esponse set t i ngs. Suppl y t wo compl et e set s of f i l t er s i n a sui t abl e st or age box i n addi t i on t o f i l t er s r epl aced af t er t est i ng.

PART 2 PRODUCTS

2. 1 NAMEPLATES

Each maj or component of t hi s speci f i cat i on shal l have t he manuf act ur er ' s

Apr i l 2019 Page 10 SECTI ON 26 32 14. 00 10 name, t ype or st y l e, model or ser i al number , and r at i ng number on a pl at e secur ed t o t he equi pment . As a mi ni mum, namepl at es shal l be pr ovi ded f or : Engi nes; Rel ays; Gener at or s; Day t anks; Tr ansf or mer s ( CT & PT) ;

Regul at or s; Pumps and pump mot or s; Gover nor s; Gener at or Br eaker ;

Economi zer s; Heat exchanger s ( ot her t han base- mount ed) .

Wher e t he f ol l owi ng equi pment i s pr ovi ded as a st andar d component by t he di esel - engi ne gener at or set manuf act ur er , t he namepl at e i nf or mat i on may be pr ovi ded i n t he mai nt enance manual i n l i eu of namepl at es.

Bat t er y char ger Heat er s Exhaust muf f l er s Exci t er s Swi t chgear Si l encer s Battery

2. 2 SAFETY DEVI CES

Exposed movi ng par t s, par t s t hat pr oduce hi gh oper at i ng t emper at ur es, par t s whi ch may be el ect r i cal l y ener gi zed, and par t s t hat may be a hazar d t o oper at i ng per sonnel dur i ng nor mal oper at i on shal l be i nsul at ed, f ul l y encl osed, guar ded, or f i t t ed wi t h ot her t ypes of saf et y devi ces. The saf et y devi ces shal l be i nst al l ed so t hat pr oper oper at i on of t he equi pment i s not i mpai r ed.

2. 3 MATERI ALS AND EQUI PMENT

Mat er i al s and equi pment shal l be as speci f i ed. Submi t a l et t er cer t i f y i ng t hat wher e mat er i al s or equi pment ar e speci f i ed t o compl y wi t h r equi r ement s of UL, or ot her st andar ds, wr i t t en pr oof of such compl i ance has been obt ai ned. The l abel or l i s t i ng of t he speci f i ed agency, or a wr i t t en cer t i f i cat e f r om an appr oved, nat i onal l y r ecogni zed t est i ng or gani zat i on equi pped t o per f or m such ser vi ces, st at i ng t hat t he i t ems have been t est ed and conf or m t o t he r equi r ement s and t est i ng met hods of t he speci f i ed agency ar e accept abl e as pr oof .

2. 3. 1 Ci r cui t Br eaker s, Low Vol t age

UL 489 and UL 489.

2. 3. 2 Fi l t er El ement s ( Fuel - oi l , Lubr i cat i ng- oi l , and Combust i on- ai r )

Manuf act ur er ' s st andar d.

2. 3. 3 I nst r ument Tr ansf or mer s

NEMA/ ANSI C12. 11.

2. 3. 4 Pi pe ( Fuel / Lube- oi l , Compr essed- Ai r , Cool ant and Exhaust )

ASTM A53/ A53M, ASTM A106/ A106M or ASTM A135/ A135M, st eel pi pe. Pi pe smal l er t han 2 i nches shal l be Schedul e 80. Pi pe 2 i nches and l ar ger shal l be Schedul e 40.

2. 3. 5 Pi pe Fl anges and Fi t t i ngs

2. 3. 5. 1 Pi pe Fl anges and Fl anged Fi t t i ngs

ASTM A181/ A181M, Cl ass 60, or ASME B16. 5, Gr ade 1, Cl ass 150.

Apr i l 2019 Page 11 SECTI ON 26 32 14. 00 10

2. 3. 5. 2 Pi pe Wel di ng Fi t t i ngs

ASTM A234/ A234M, Gr ade WPB or WPC, Cl ass 150, or ASME B16. 11, 3000 l b.

2. 3. 5. 3 Thr eaded Fi t t i ngs

ASME B16. 3, Cl ass 150.

2. 3. 5. 4 Valves

MSS SP- 80, Cl ass 150.

2. 3. 5. 5 Gaskets

Manuf act ur er s St andar d.

2. 3. 6 Pi pe Hanger s

MSS SP- 58.

2. 3. 7 El ect r i cal Encl osur es

2. 3. 7. 1 General

NEMA I CS 6.

2. 3. 7. 2 Panelboards

NEMA PB 1.

2. 3. 8 El ect r i c Mot or s

El ect r i c mot or s shal l conf or m t o t he r equi r ement s of NEMA MG 1. Mot or s shal l have seal ed bal l bear i ngs, a maxi mum speed of 1800 r pm and i nt egr al aut omat i c or manual r eset t her mal over l oad pr ot ect or s. Mot or s used i ndoor s shal l have dr i p pr oof f r ames; t hose used out si de shal l be t ot al l y encl osed. AC mot or s l ar ger t han 1/ 2 Hp shal l be of t he squi r r el cage i nduct i on t ype f or st andar d vol t age of 230 and 460 vol t s, 60 Hz 240 vol t s, t hr ee phase power . AC mot or s 1/ 2 Hp or smal l er , shal l be f or st andar d vol t age 115 and 230 vol t s, 60 Hz, s i ngl e phase power .

2. 3. 9 Mot or Cont r ol l er s

Mot or cont r ol l er s and st ar t er s shal l conf or m t o t he r equi r ement s of NFPA 70 and NEMA I CS 2.

2. 4 ENGINE

Each engi ne shal l oper at e on No. 2- D di esel conf or mi ng t o ASTM D975, shal l be desi gned f or st at i onar y appl i cat i ons and shal l be compl et e wi t h anci l l ar i es. The engi ne shal l be a st andar d pr oduct i on model descr i bed i n t he manuf act ur er ' s cat al og dat a, whi ch descr i bes and depi ct s each engi ne- gener at or set and al l anci l l ar y equi pment i n suf f i c i ent det ai l t o demonst r at e speci f i cat i on compl i ance. The engi ne shal l be nat ur al l y aspi r at ed, scavenged, super char ged or t ur bochar ged. The engi ne shal l be t wo- or f our - st r oke- cycl e and compr essi on- i gni t i on t ype. The engi ne shal l be ver t i cal i nl i ne, V- , or opposed- pi st on t ype, wi t h a sol i d cast bl ock or i ndi v i dual l y cast cyl i nder s. The engi ne shal l have a mi ni mum of t wo cyl i nder s. Opposed- pi st on t ype engi nes shal l have no l ess t han f our

Apr i l 2019 Page 12 SECTI ON 26 32 14. 00 10 cyl i nder s. Each bl ock shal l have a cool ant dr ai n por t . Each engi ne shal l be equi pped wi t h an over speed sensor .

2. 5 FUEL SYSTEM

The f uel syst em f or each engi ne gener at or set shal l conf or m t o t he r equi r ement s of NFPA 30 and NFPA 37 and cont ai n t he f ol l owi ng el ement s.

2. 5. 1 Pumps

2. 5. 1. 1 Mai n Pump

Each engi ne shal l be pr ovi ded wi t h an engi ne dr i ven pump. The pump shal l suppl y f uel at a mi ni mum r at e suf f i c i ent t o pr ovi de t he amount of f uel r equi r ed t o meet t he per f or mance i ndi cat ed wi t hi n t he par amet er schedul e.

The f uel f l ow r at e shal l be based on meet i ng t he l oad r equi r ement s and al l necessar y r eci r cul at i on.

2. 5. 1. 2 Auxi l i ar y Fuel Pump

Auxi l i ar y f uel pumps shal l be pr ovi ded t o mai nt ai n t he r equi r ed engi ne f uel pr essur e, ei t her r equi r ed by t he i nst al l at i on or i ndi cat ed on t he dr awi ngs. The auxi l i ar y pump shal l be dr i ven by a dc el ect r i c mot or power ed by t he st ar t i ng/ st at i on bat t er i es. The auxi l i ar y pump shal l be aut omat i cal l y act uat ed by a pr essur e det ect i ng devi ce.

2. 5. 2 Filter

A mi ni mum of one f ul l f l ow f uel f i l t er shal l be pr ovi ded f or each engi ne.

The f i l t er shal l be r eadi l y accessi bl e and capabl e of bei ng changed wi t hout di sconnect i ng t he pi pi ng or di st ur bi ng ot her component s. The f i l t er shal l have i nl et and out l et connect i ons pl ai nl y mar ked.

2. 5. 3 Rel i ef / Bypass Val ve

A r el i ef / bypass val ve shal l be pr ovi ded t o r egul at e pr essur e i n t he f uel suppl y l i ne, r et ur n excess f uel t o a r et ur n l i ne, and pr event t he bui l d- up of excessi ve pr essur e i n t he f uel syst em.

2. 5. 4 I nt egr al Mai n Fuel St or age Tank

Each engi ne shal l be pr ovi ded wi t h an i nt egr al mai n f uel t ank. Each t ank shal l be f act or y i nst al l ed and pr ovi ded as an i nt egr al par t of t he di esel gener at or manuf act ur er ' s pr oduct . Each t ank shal l be pr ovi ded wi t h connect i ons f or f uel suppl y l i ne, f uel r et ur n l i ne, l ocal f uel f i l l por t , gauge, vent l i ne, and f l oat swi t ch assembl y. A f uel r et ur n l i ne cool er shal l be pr ovi ded as r ecommended by t he manuf act ur er and assembl er . The t emper at ur e of t he f uel r et ur ni ng t o t he t ank shal l be bel ow t he f l ash poi nt of t he f uel . Each engi ne- gener at or set pr ovi ded wi t h weat her pr oof encl osur es shal l have i t s t ank mount ed wi t hi n t he encl osur e. The f uel f i l l l i ne shal l be accessi bl e wi t hout openi ng t he encl osur e.

2. 5. 4. 1 Capacity

Each t ank shal l have capaci t y t o suppl y f uel t o t he engi ne f or an uni nt er r upt ed 24 hour per i od at 100 per cent r at ed l oad wi t hout bei ng refilled.

Apr i l 2019 Page 13 SECTI ON 26 32 14. 00 10

2. 5. 4. 2 Local Fuel Fi l l

Each l ocal f uel f i l l por t on t he day t ank shal l be pr ovi ded wi t h a scr ew- on cap.

2. 5. 4. 3 Fuel Level Cont r ol s

Each t ank shal l have a f l oat - swi t ch assembl y t o per f or m t he f ol l owi ng functions:

a. Act i vat e t he " Low Fuel Level " al ar m at 70 per cent of t he r at ed t ank capacity.

b. Act i vat e t he " Over f i l l Fuel Level " al ar m at 95 per cent of t he r at ed t ank capaci t y.

2. 5. 4. 4 Arrangement

I nt egr al t anks may al l ow gr avi t y f l ow i nt o t he engi ne. Gr avi t y f l ow t anks and any t ank t hat al l ows a f uel l evel above t he f uel i nj ect or s shal l be pr ovi ded wi t h an i nt er nal or ext er nal f act or y i nst al l ed val ve l ocat ed as near as possi bl e t o t he shel l of t he t ank. The val ve shal l c l ose when t he engi ne i s not oper at i ng. I nt egr al day t anks shal l be pr ovi ded wi t h any necessar y pumps t o suppl y f uel t o t he engi ne as r ecommended by t he gener at or set manuf act ur er . The f uel suppl y l i ne f r om t he t ank t o t he manuf act ur er ' s st andar d engi ne connect i on shal l be wel ded pi pe.

2. 5. 5 Day Tank

Pr ovi de each engi ne wi t h i nt egr al day t ank. Pr ovi de each day t ank wi t h connect i ons f or f uel suppl y l i ne, f uel r et ur n l i ne, f uel over f l ow l i ne, l ocal f uel f i l l por t , gauge, vent l i ne, dr ai n l i ne, and f l oat swi t ch assembl y f or cont r ol . Pr ovi de a f uel r et ur n l i ne cool er as r ecommended by t he manuf act ur er and assembl er . The t emper at ur e of t he f uel r et ur ni ng t o t he day t ank shal l be bel ow t he f l ash poi nt of t he f uel . I nst al l a t emper at ur e sensi ng devi ce i n t he f uel suppl y l i ne. Each engi ne- gener at or set pr ovi ded wi t h weat her pr oof encl osur es shal l have i t s day t ank mount ed wi t hi n t he encl osur e. The f uel f i l l l i ne shal l be accessi bl e wi t hout openi ng t he encl osur e.

2. 5. 5. 1 Capaci t y, St andby

Each day t ank shal l have capaci t y t o suppl y f uel t o t he engi ne f or an uni nt er r upt ed 24 hour per i od at 100 per cent r at ed l oad wi t hout bei ng r ef i l l ed, pl us any f uel whi ch may be r et ur ned t o t he mai n f uel st or age t ank. Submi t cal cul at i ons f or t he capaci t y of each day t ank, i ncl udi ng al l owances f or r eci r cul at ed f uel , usabl e t ank capaci t y, and dur at i on of f uel suppl y. The cal cul at i on of t he capaci t y of each day t ank shal l i ncor por at e t he r equi r ement t o st op t he suppl y of f uel i nt o t he day t ank at 90 per cent of t he ul t i mat e vol ume of t he t ank.

2. 5. 5. 2 Dr ai n Li ne

Each day t ank dr ai n l i ne shal l be accessi bl e and equi pped wi t h a shut of f val ve. Sel f suppor t i ng day t anks shal l be ar r anged t o al l ow dr ai nage i nt o a 12 i nch t al l bucket .

Apr i l 2019 Page 14 SECTI ON 26 32 14. 00 10

2. 5. 5. 3 Local Fuel Fi l l

Pr ovi de each l ocal f uel f i l l por t on t he day t ank wi t h a scr ew- on cap.

2. 5. 5. 4 Fuel Level Cont r ol s

Each day t ank shal l have a f l oat - swi t ch- assembl y t o per f or m t he f ol l owi ng functions:

a. When t he mai n st or age t ank i s l ocat ed hi gher t han t he day t ank, St ar t t he suppl y of f uel i nt o t he day t ank when t he f uel l evel i s at t he " Low" l evel mar k, 75 per cent of t he r at ed t ank capaci t y.

b. When t he mai n st or age t ank i s l ocat ed hi gher t han t he day t ank, St op t he suppl y of f uel i nt o t he day t ank when t he f uel l evel i s at 90 per cent of t he r at ed t ank capaci t y.

c. Act i vat e t he " Over f i l l Fuel Level " al ar m at 95 per cent of t he r at ed t ank vol ume.

d. Act i vat e t he " Low Fuel Level " al ar m at 70 per cent of t he r at ed t ank Capaci t y.

e. Act i vat e t he aut omat i c f uel suppl y shut - of f val ve l ocat ed on t he f i l l l i ne of t he day t ank and shut down t he f uel pump whi ch suppl i es f uel t o t he day t ank at 95 per cent of t he r at ed t ank vol ume. The f l ow of f uel shal l be st opped bef or e any f uel can be f or ced i nt o t he f uel over f l ow l i ne.

2. 5. 5. 5 Arrangement

I nt egr al day t anks may al l ow gr avi t y f l ow i nt o t he engi ne. Gr avi t y f l ow t anks shal l be pr ovi ded wi t h an i nt er nal or ext er nal val ve l ocat ed as near as possi bl e t o t he shel l of t he t ank. The val ve shal l c l ose when t he engi ne i s not oper at i ng. I nt egr al day t anks shal l be pr ovi ded wi t h any necessar y pumps t o suppl y f uel t o t he engi ne as r ecommended by t he gener at or set manuf act ur er . The over f l ow connect i on and t he f uel suppl y l i ne f or i nt egr al day t anks whi ch do not r el y upon gr avi t y f l ow shal l be ar r anged so t hat t he hi ghest possi bl e f uel l evel i s bel ow t he f uel i nj ect or s. Sel f - suppor t i ng day t ank shal l ei t her be ar r anged so t hat t he f uel l evel i n t he day t ank r emai ns above t he suct i on por t of t he engi ne dr i ven f uel pump or be pr ovi ded wi t h a t r ansf er pump t o pr ovi de f uel t o t he engi ne dr i ven pump. The over f l ow connect i on and f uel suppl y l i ne shal l be ar r anged so t hat t he hi ghest possi bl e f uel l evel i s bel ow t he f uel i nj ect or s. When t he mai n f uel st or age t anks ar e l ocat ed bel ow t he day t ank, a check val ve shal l be pr ovi ded i n t he f uel suppl y l i ne ent er i ng t he day t ank. When t he mai n f uel st or age t anks ar e l ocat ed above t he day t ank, a sol enoi d val ve shal l be i nst al l ed i n t he f uel suppl y l i ne ent er i ng t he day t ank. The sol enoi d val ve shal l be i n addi t i on t o t he aut omat i c f uel shut of f val ve. The f uel suppl y l i ne f r om t he day t ank t o t he manuf act ur er ' s st andar d engi ne connect i on shal l be wel ded pi pe.

2. 5. 6 Fuel Suppl y Syst em

The f uel suppl y f r om t he mai n st or age of f uel t o t he day t ank shal l be as speci f i ed i n t he Scope of Wor k.

Apr i l 2019 Page 15 SECTI ON 26 32 14. 00 10

2. 6 LUBRICATION

Each engi ne shal l have a separ at e l ube- oi l syst em conf or mi ng t o NFPA 30 and NFPA 37. Each syst em shal l be pr essur i zed by engi ne- dr i ven oi l pumps. Each syst em shal l be f ur ni shed wi t h a r el i ef val ve f or oi l pr essur e r egul at i on ( f or c l osed syst ems) and a di p- st i ck f or oi l l evel i ndi cat i ons. The cr ankcase shal l be vent ed i n accor dance wi t h t he manuf act ur er ' s r ecommendat i on except t hat i t shal l not be vent ed t o t he engi ne exhaust syst em. Cr ankcase br eat her s, i f pr ovi ded on engi nes i nst al l ed i n bui l di ngs or encl osur es, shal l be pi ped t o vent t o t he out si de. The syst em shal l be r eadi l y accessi bl e f or ser vi ce such as dr ai ni ng, r ef i l l i ng, et c. Each syst em shal l per mi t addi t i on of oi l and have oi l - l evel i ndi cat i on wi t h t he set oper at i ng. The syst em shal l ut i l i ze an oi l cool er as r ecommended by t he engi ne manuf act ur er .

2. 6. 1 Filter

One f ul l - f l ow f i l t er shal l be pr ovi ded f or each pump. The f i l t er shal l be r eadi l y accessi bl e and capabl e of bei ng changed wi t hout di sconnect i ng t he pi pi ng or di st ur bi ng ot her component s. The f i l t er shal l have i nl et and out l et connect i ons pl ai nl y mar ked.

2. 6. 2 Lube- Oi l Sensor s

Each engi ne shal l be equi pped wi t h l ube- oi l pr essur e sensor s. Pr essur e sensor s shal l be l ocat ed downst r eam of t he f i l t er s and pr ovi de si gnal s f or r equi r ed i ndi cat i on and al ar ms.

2. 7 COOLI NG SYSTEM

Each engi ne cool i ng syst em shal l oper at e aut omat i cal l y whi l e t he engi ne i s r unni ng. Each cool i ng syst em shal l be s i zed f or t he maxi mum summer out door or i ndoor desi gn t emper at ur e and si t e el evat i on, as speci f i ed.

Wat er - cool ed syst em cool ant shal l use a combi nat i on of wat er and et hyl ene- gl ycol suf f i c i ent f or f r eeze pr ot ect i on at t he mi ni mum wi nt er out door t emper at ur e speci f i ed. The maxi mum t emper at ur e r i se of t he cool ant acr oss t he engi ne shal l be no mor e t han t hat r ecommended and submitted.

a. The maxi mum and mi ni mum al l owabl e i nl et t emper at ur es of t he cool ant fluid.

b. The maxi mum al l owabl e t emper at ur e r i se i n t he cool ant f l ui d t hr ough t he engi ne.

c. The mi ni mum al l owabl e i nl et f uel t emper at ur e.

2. 7. 1 Cool ant Pumps

Cool ant pumps shal l be t he cent r i f ugal t ype. Each engi ne shal l have an engi ne- dr i ven pr i mar y pump. Secondar y pumps shal l be el ect r i c mot or dr i ven and have aut omat i c cont r ol l er s.

2. 7. 2 Heat Exchanger

Each heat exchanger shal l be of a s i ze and capaci t y t o l i mi t t he maxi mum al l owabl e t emper at ur e r i se i n t he cool ant acr oss t he engi ne t o t hat r ecommended and submi t t ed i n accor dance wi t h par agr aph SUBMI TTALS f or t he maxi mum summer out door desi gn t emper at ur e and si t e el evat i on. Each heat

Apr i l 2019 Page 16 SECTI ON 26 32 14. 00 10 exchanger shal l be cor r osi on r esi st ant , sui t abl e f or ser vi ce i n ambi ent condi t i ons of appl i cat i on. Submi t manuf act ur er s dat a t o quant i f y heat r ej ect ed t o t he space wi t h t he engi ne gener at or set at r at ed capaci t y.

2. 7. 2. 1 Fi n- Tube- Type Heat Exchanger ( Radi at or )

Heat exchanger may be f act or y coat ed wi t h cor r osi ve r esi st ant f i l m pr ovi di ng t hat cor r osi on measur es ar e t aken t o r est or e t he heat r ej ect i on capabi l i t y of t he r adi at or t o t he i ni t i al desi gn r equi r ement v i a over si z i ng, or ot her compensat i ng met hods. I nt er nal sur f aces shal l be compat i bl e wi t h l i qui d f l ui d cool ant used. Mat er i al s and cool ant ar e subj ect t o appr oval by t he Cont r act i ng Of f i cer . Heat exchanger s shal l be pr essur e t ype i ncor por at i ng a pr essur e val ve, vacuum val ve and a cap.

Caps shal l be desi gned f or pr essur e r el i ef pr i or t o r emoval . Each heat exchanger and t he ent i r e cool i ng syst em shal l be capabl e of wi t hst andi ng a mi ni mum pr essur e of 7 psi . Each heat exchanger shal l be pr ot ect ed wi t h a st r ong gr i l l e or scr een guar d. Each heat exchanger shal l have at l east t wo t apped hol es. One t apped hol e i n t he heat exchanger shal l be equi pped wi t h a dr ai n cock, t he r est shal l be pl ugged.

2. 7. 2. 2 Shel l and U- Tube Type Heat Exchanger

Heat exchanger shal l be mul t i pl e pass shel l and U- t ube t ype. Exchanger shal l oper at e wi t h l ow t emper at ur e wat er i n t he shel l and hi gh t emper at ur e wat er i n t he t ubes. Exchanger s shal l be const r uct ed i n accor dance wi t h ASME BPVC SEC VI I I D1 and cer t i f i ed ASME st amp secur ed t o t he uni t .

U- t ube bundl es shal l be compl et el y r emovabl e f or c l eani ng and t ube r epl acement and shal l be f r ee t o expand wi t h t he shel l . Shel l s shal l be const r uct ed of seaml ess st eel pi pe or wel ded st eel . Tubes shal l be cupr oni ckel or i nhi bi t ed admi r al t y, const r uct ed i n accor dance wi t h ASTM B395/ B395M, sui t abl e f or t he t emper at ur e and pr essur e speci f i ed.

Tubes shal l be not l ess t han 3/ 4 i nch unl ess ot her wi se i ndi cat ed. Shel l s i de and t ube si de shal l be desi gned f or 150 psi wor ki ng pr essur e and f act or y t est ed at 300 psi . Hi gh and l ow t emper at ur e wat er and pr essur e r el i ef connect i ons shal l be l ocat ed i n accor dance wi t h t he manuf act ur er s st andar d pr act i ce. Wat er connect i ons l ar ger t han 3 i nches shal l be ASME Cl ass 150 f l anged. Wat er pr essur e l oss t hr ough cl ean t ubes shal l be as r ecommended by t he engi ne manuf act ur er . Mi ni mum wat er vel oci t y t hr ough t ubes shal l be 1 f oot per second and assur e t ur bul ent f l ow. One or mor e pr essur e r el i ef val ves shal l be pr ovi ded f or each heat exchanger i n accor dance wi t h ASME BPVC SEC VI I I D1. The aggr egat e r el i evi ng capaci t y of t he r el i ef val ves shal l be not l ess t han t hat r equi r ed by t he above code. Di schar ge f r om t he val ves shal l be i nst al l ed as i ndi cat ed. The r el i ef val ves shal l be i nst al l ed on t he heat exchanger shel l . A dr ai n connect i on wi t h 3/ 4 i nch hose bi b shal l be i nst al l ed at t he l owest poi nt i n t he syst em near t he heat exchanger . Addi t i onal dr ai n connect i on wi t h t hr eaded cap or pl ug shal l be i nst al l ed wher ever r equi r ed f or t hor ough dr ai ni ng of t he syst em.

2. 7. 3 Expansi on Tank

The cool i ng syst em shal l i ncl ude an ai r expansi on t ank whi ch wi l l accommodat e t he expanded wat er of t he syst em gener at ed wi t hi n t he nor mal oper at i ng t emper at ur e r ange, l i mi t i ng t he pr essur e i ncr ease at al l component s i n t he syst em t o t he maxi mum al l owabl e pr essur e at t hose component s. The t ank shal l be sui t abl e f or an oper at i ng t emper at ur e of 250 degr ees F and a wor ki ng pr essur e of 125 psi . The t ank shal l be const r uct ed of wel ded st eel , t est ed and st amped i n accor dance wi t h ASME BPVC SEC VI I I D1 f or t he st at ed wor ki ng pr essur e. A bl adder t ype

Apr i l 2019 Page 17 SECTI ON 26 32 14. 00 10 t ank shal l not be used. The t ank shal l be suppor t ed by st eel l egs or bases f or ver t i cal i nst al l at i on or st eel saddl es f or hor i zont al installation.

2. 7. 4 Ductwork

Duct wor k shal l be as speci f i ed i n Sect i on 23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS except t hat a f l exi bl e connect i on shal l be used t o connect t he duct t o t he di esel engi ne r adi at or . Mat er i al f or t he connect i on shal l be wi r e- r ei nf or ced gl ass.

The connect i on shal l be r ender ed pr act i cal l y ai r t i ght .

2. 7. 5 Temper at ur e Sensor s

Each engi ne shal l be equi pped wi t h cool ant t emper at ur e sensor s.

Temper at ur e sensor s shal l pr ovi de si gnal s f or pr e- hi gh and hi gh i ndi cat i on and al ar ms.

2. 8 SOUND LI MI TATI ONS

The noi se gener at ed by t he di esel gener at or set oper at i ng at 100 per cent l oad shal l not exceed t he f ol l owi ng sound pr essur e l evel s i n any of t he i ndi cat ed f r equenci es when measur ed i n a f r ee f i el d at a r adi al di st ance of

22. 9 f eet at 45 degr ees apar t i n al l di r ect i ons. Submi t dat a t o demonst r at e compl i ance wi t h t hese sound l i mi t at i on r equi r ement s. Al so submi t cer t i f i cat i on f r om t he manuf act ur er st at i ng t hat t he sound emi ssi ons meet t he speci f i cat i on.

Fr equency Band ( Hz) Maxi mum Accept abl e Pr essur e Level ( Deci bel s)

31 87

63 87

125 77

250 70

500 65

1000 61

2000 60

4000 60

8000 62

2. 9 AI R I NTAKE EQUI PMENT

Fi l t er s and si l encer s shal l be pr ovi ded i n l ocat i ons t hat ar e conveni ent f or ser vi c i ng. The si l encer shal l be of t he hi gh- f r equency f i l t er t ype, l ocat ed i n t he ai r i nt ake syst em as r ecommended by t he engi ne manuf act ur er . Si l encer shal l be capabl e of r educi ng t he noi se l evel at

Apr i l 2019 Page 18 SECTI ON 26 32 14. 00 10 t he ai r i nt ake t o a poi nt bel ow t he maxi mum accept abl e l evel s speci f i ed i n par agr aph SOUND LI MI TATI ONS. A combi ned f i l t er - s i l encer uni t meet i ng r equi r ement s f or t he separ at e f i l t er and si l encer i t ems may be pr ovi ded.

Expansi on el ement s i n ai r - i nt ake l i nes shal l be r ubber .

2. 10 EXHAUST SYSTEM

The syst em shal l be separ at e and compl et e f or each engi ne. Pi pi ng shal l be suppor t ed so as t o mi ni mi ze vi br at i on. Wher e a V- t ype engi ne i s pr ovi ded, a V- t ype connect or wi t h necessar y f l exi bl e sect i ons and har dwar e shal l connect t he engi ne exhaust out l et s.

2. 10. 1 Fl exi bl e Sect i ons and Expansi on Joi nt s

A f l exi bl e sect i on at each engi ne and an expansi on j oi nt at each muf f l er shal l be pr ovi ded. Fl exi bl e sect i ons and expansi on j oi nt s shal l have f l anged connect i ons. Fl exi bl e sect i ons shal l be made of convol ut ed seaml ess t ube wi t hout j oi nt s or packi ng. Expansi on j oi nt s shal l be t he bel l ows t ype. Expansi on and f l exi bl e el ement s shal l be st ai nl ess st eel sui t abl e f or di esel - engi ne exhaust gas at t he maxi mum exhaust t emper at ur e t hat i s speci f i ed by t he engi ne manuf act ur er . Expansi on and f l exi bl e el ement s shal l be capabl e of absor bi ng vi br at i on f r om t he engi ne and compensat i on f or t her mal expansi on and cont r act i on.

2. 10. 2 Exhaust Muf f l er

A chamber t ype exhaust muf f l er shal l be pr ovi ded. The muf f l er shal l be const r uct ed of wel ded st eel and desi gned f or out si de or i nsi de, and ver t i cal or hor i zont al mount i ng, as speci f i ed. Eyebol t s, l ugs, f l anges, or ot her i t ems shal l be pr ovi ded as necessar y f or suppor t i n t he l ocat i on and posi t i on i ndi cat ed. Pr essur e dr op t hr ough t he muf f l er shal l not exceed t he r ecommendat i ons of t he engi ne manuf act ur er . Out si de muf f l er s shal l be z i nc coat ed or pai nt ed wi t h hi gh t emper at ur e 400 degr ees F r esi st i ng pai nt . The muf f l er and exhaust pi pi ng t oget her shal l r educe t he noi se l evel t o l ess t han t he maxi mum accept abl e l evel l i s t ed f or sound l i mi t at i ons i n par agr aph SOUND LI MI TATI ONS. The muf f l er shal l have a dr ai n val ve, ni ppl e, and cap at t he l ow- poi nt of t he muf f l er .

2. 10. 3 Exhaust Pi pi ng

Hor i zont al sect i ons of exhaust pi pi ng shal l be s l oped downwar d away f r om t he engi ne t o a condensat e t r ap and dr ai n val ve. Changes i n di r ect i on shal l be l ong- r adi us. Exhaust pi pi ng, muf f l er s and si l encer s i nst al l ed i nsi de any bui l di ng shal l be i nsul at ed i n accor dance wi t h par agr aph THERMAL I NSULATI ON and cover ed t o pr ot ect per sonnel . Ver t i cal exhaust pi pi ng shal l be pr ovi ded wi t h a hi nged, gr avi t y oper at ed, sel f - c l osi ng, r ai n cover .

2. 11 EMISSIONS

The f i ni shed i nst al l at i on shal l compl y wi t h Feder al , st at e, and l ocal r egul at i ons and r est r i ct i ons r egar di ng t he l i mi t s of emi ssi ons, as specified

Submi t a cer t i f i cat i on f r om t he engi ne manuf act ur er st at i ng t hat t he engi ne exhaust emi ssi ons meet f eder al , st at e, and l ocal r egul at i ons and r est r i ct i ons speci f i ed. At a mi ni mum, t hi s cer t i f i cat i on shal l i ncl ude emi ssi on f act or s f or cr i t er i a pol l ut ant s i ncl udi ng ni t r ogen oxi des, car bon monoxi de, par t i cul at e mat t er , sul f ur di oxi de, non- met hane hydr ocar bon, and

Apr i l 2019 Page 19 SECTI ON 26 32 14. 00 10 f or hazar dous ai r pol l ut ant s ( HAPs) .

2. 12 STARTI NG SYSTEM

The st ar t i ng syst em f or st andby engi ne gener at or set s used i n emer gency appl i cat i ons shal l be i n accor dance wi t h NFPA 99 and NFPA 110 and as f ol l ows. The st ar t i ng syst em f or engi ne gener at or set s used i n non- emer gency appl i cat i ons shal l be as f ol l ows.

2. 12. 1 Controls

An engi ne cont r ol swi t ch shal l be pr ovi ded wi t h f unct i ons i ncl udi ng:

r un/ st ar t ( manual ) , of f / r eset , and aut omat i c mode. St ar t - st op l ogi c shal l be pr ovi ded f or adj ust abl e cycl e cr anki ng and cool down oper at i on. The l ogi c shal l be ar r anged f or f ul l y aut omat i c st ar t i ng i n accor dance wi t h par agr aph AUTOMATI C ENGI NE- GENERATOR SET SYSTEM OPERATI ON. El ect r i cal st ar t i ng syst ems shal l be pr ovi ded wi t h an adj ust abl e cr anki ng l i mi t devi ce t o l i mi t cr anki ng per i ods f r om 1 second up t o t he maxi mum dur at i on.

2. 12. 2 Capacity

The st ar t i ng syst em shal l be of suf f i c i ent capaci t y, at t he maxi mum out door or i ndoor summer t emper at ur e speci f i ed, t o cr ank t he engi ne wi t hout damage or over…