Summary: TAFB Technical Specifications 2019 - Section 23 57 10

This document is a technical specification for forced hot water heating systems using water and steam heat exchangers at Tinker Air Force Base, Oklahoma, dated April 2019. The specification covers low temperature forced hot water heating systems operating at 210 degrees F and less at 30 psig working pressure, as well as high and medium temperature water systems and steam systems. It applies to steam heat exchangers with approximately 100 psig supply pressure and high temperature water at 350-450 degrees F. The specification incorporates numerous ASME, ASTM, AWS, and MSS standards for piping, fittings, valves, and equipment. Key materials include carbon steel pipe (ASTM A53/A106), copper tubing (ASTM B88), and various fitting standards based on temperature and pressure classes (150-600 pound ratings). Equipment specifications include circulating pumps, condensate pumping units, heat exchangers (shell and U-tube or plate and frame types), steam traps, air separation tanks, expansion tanks, strainers, and thermometers. Valves required include check valves, globe valves, gate valves, angle valves, balancing valves, air vents, and gravity flow control valves, with material and pressure ratings dependent on system type.

The execution section mandates installation conformity with ASME B31.1 piping code, welding qualifications per ASME BPVC Section IX, and comprehensive testing including hydrostatic pressure testing at 45 psig for four hours. System cleaning requirements involve filling with caustic soda or trisodium phosphate solution heated to 150 degrees F and circulating for 48 hours before flushing. Submittals required include shop drawings, product data, welding qualifications, framed operating instructions, test reports, operation and maintenance manuals (six copies each), and bolt certificates. Water treatment systems must include chemical shot feeders or automatic feed systems with monthly water analysis for one year per ASTM D596. A 16-hour field training course must be provided to operating and maintenance staff prior to final acceptance. The specification requires manufacturer's representatives to supervise installation and adjustment, with all testing performed in the presence of the Contracting Officer.

View the file

Other files

File Type Posted
03 39 00.00 10.pdf PDF
03 62 16.pdf PDF
04 20 00.pdf PDF
05 21 00.pdf PDF
06 20 00.pdf PDF
06 61 16.pdf PDF
07 60 00.pdf PDF
07 61 14.00 20.pdf PDF
07 84 00.pdf PDF
07 92 00.pdf PDF
08 11 16.pdf PDF
08 36 13.pdf PDF
08 71 00.pdf PDF
09 68 00.pdf PDF
10 28 13.pdf PDF
13 48 00.pdf PDF
21 13 17.pdf PDF
22 00 00.pdf PDF
23 00 00.pdf PDF
23 08 00.pdf PDF
23 11 25.pdf PDF
23 35 00.pdf PDF
23 64 26.pdf PDF
23 82 16.00 40.pdf PDF
23 82 43.00 40.pdf PDF
26 56 00.pdf PDF
31 23 06.pdf PDF
32 01 14.pdf PDF
32 13 74.pdf PDF
03 11 13.00 10.pdf PDF
03 20 00.00 10.pdf PDF
03 30 00.pdf PDF
07 14 00.pdf PDF
190023 Renovate Restrooms B117 RFIs_FINAL_COR_Signed.pdf PDF
TAFB_Tech_Reqs (Div 02-48).zip ZIP file
Model.zip ZIP file
00 71 00.pdf PDF
01 78 23.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 32 16.00 20.pdf PDF
01 33 16.00 10.pdf PDF
01 42 00.pdf PDF
01 78 00.pdf PDF
Tinker General Requirements Specifications_Nov 2022_Change Log.pdf PDF
Initial Site Visit WWYK190023.pdf PDF
Solicitation - FA813726R0030.pdf PDF
Att10_190023_SOW.pdf PDF
EAL List - BLANK to Contractors WWYK190023.xlsx XLSX spreadsheet
Att12_190023_Drawings_Final.pdf PDF
Section L - Instructions to Offerors.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Tinker AFB, OK TAFB Technical Specifications 2019

April 2019 Page 1 Section 23 57 10

SECTION 23 57 10

FORCED HOT WATER HEATING SYSTEMS USING WATER AND STEAM HEAT EXCHANGERS

This guide specification covers the requirements for forced hot water heating system using a steam or high temperature water heat exchanger.

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only. Current editions of references at time of delivery order shall be used.

AMERICAN WATER WORKS ASSOCIATION (AWWA)

AWWA C606 Grooved and Shouldered Joints

AMERICAN WELDING SOCIETY (AWS)

AWS A5.8/A5.8M Specification for Filler Metals for Brazing and Braze Welding

ASME INTERNATIONAL (ASME)

ASME B1.20.1 Pipe Threads, General Purpose (Inch)

ASME B16.1 Gray Iron Pipe Flanges and Flanged Fittings

Classes 25, 125, and 250

ASME B16.11 Forged Fittings, Socket-Welding and Threaded

ASME B16.15 Cast Bronze Alloy Threaded Fittings Classes

125 and 250

ASME B16.18 Cast Copper Alloy Solder Joint Pressure

Fittings

ASME B16.21 Nonmetallic Flat Gaskets for Pipe Flanges

ASME B16.22 Standard for Wrought Copper and Copper Alloy

Solder Joint Pressure Fittings

ASME B16.26 Standard for Cast Copper Alloy Fittings for

Flared Copper Tubes

ASME B16.3 Malleable Iron Threaded Fittings, Classes 150 and 300

ASME B16.34 Valves - Flanged, Threaded and Welding End

ASME B16.39 Standard for Malleable Iron Threaded Pipe

Unions; Classes 150, 250, and 300

April 2019 Page 2 Section 23 57 10

ASME B16.4 Standard for Gray Iron Threaded Fittings;

Classes 125 and 250

ASME B16.5 Pipe Flanges and Flanged Fittings: NPS 1/2

Through NPS 24 Metric/Inch Standard

ASME B16.9 Standard for Factory-Made Wrought Steel

Buttwelding Fittings

ASME B31.1 Power Piping

ASME B40.100 Pressure Gauges and Gauge Attachments

ASME BPVC SEC IX BPVC Section IX-Welding and Brazing

Qualifications

ASME BPVC SEC VIII D1 BPVC Section VIII-Rules for Construction of

Pressure Vessels Division 1

ASTM INTERNATIONAL (ASTM)

ASTM A105/A105M Standard Specification for Carbon Steel

Forgings for Piping Applications

ASTM A106/A106M Standard Specification for Seamless Carbon

Steel Pipe for High-Temperature Service

ASTM A183 Standard Specification for Carbon Steel Track

Bolts and Nuts

ASTM A193/A193M Standard Specification for Alloy-Steel and

Stainless Steel Bolting Materials for High- Temperature Service and Other Special Purpose Applications

ASTM A234/A234M Standard Specification for Piping Fittings of

Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature Service

ASTM A47/A47M Standard Specification for Ferritic Malleable

Iron Castings

ASTM A515/A515M Standard Specification for Pressure Vessel

Plates, Carbon Steel, for Intermediate- and Higher-Temperature Service

ASTM A516/A516M Standard Specification for Pressure Vessel

Plates, Carbon Steel, for Moderate- and Lower-Temperature Service

ASTM A53/A53M Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless

April 2019 Page 3 Section 23 57 10

ASTM A536 Standard Specification for Ductile Iron Castings

ASTM A653/A653M Standard Specification for Steel Sheet, Zinc-

Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM A733 Standard Specification for Welded and

Seamless Carbon Steel and Austenitic Stainless Steel Pipe Nipples

ASTM B251 General Requirements for Wrought Seamless

Copper and Copper-Alloy Tube

ASTM B265 Standard Specification for Titanium and

Titanium Alloy Strip, Sheet, and Plate

ASTM B32 Standard Specification for Solder Metal

ASTM B333 Standard Specification for Nickel-Molybdenum

Alloy Plate, Sheet, and Strip

ASTM B395/B395M Standard Specification for U-Bend Seamless

Copper and Copper Alloy Heat Exchanger and Condenser Tubes

ASTM B424 Standard Specification for Ni-Fe-Cr-Mo-Cu

Alloy (UNS N08825 and UNS N08221)* Plate, Sheet, and Strip

ASTM B62 Standard Specification for Composition Bronze or Ounce Metal Castings

ASTM B650 Standard Specification for Electrodeposited

Engineering Chromium Coatings on Ferrous Substrates

ASTM B687 Standard Specification for Brass, Copper, and

Chromium-Plated Pipe Nipples

ASTM B75 Standard Specification for Seamless Copper

Tube

ASTM B813 Standard Specification for Liquid and Paste

Fluxes for Soldering of Copper and Copper Alloy Tube

ASTM B828 Standard Practice for Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings

ASTM B88 Standard Specification for Seamless Copper

Water Tube

ASTM B88M Standard Specification for Seamless Copper

Water Tube (Metric)

April 2019 Page 4 Section 23 57 10

ASTM D1248 Standard Specification for Polyethylene

Plastics Extrusion Materials for Wire and Cable

ASTM D1384 Corrosion Test for Engine Coolants in

Glassware

ASTM D2000 Standard Classification System for Rubber

Products in Automotive Applications

ASTM D3308 PTFE Resin Skived Tape

ASTM D596 Reporting Results of Analysis of Water

EXPANSION JOINT MANUFACTURERS ASSOCIATION (EJMA)

EJMA Stds EJMA Standards

HYDRONICS INSTITUTE DIVISION OF GAMA (HYI)

HYI-005 I=B=R Ratings for Boilers, Baseboard

Radiation and Finned Tube (Commercial)

MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS

INDUSTRY (MSS)

MSS SP-25 Standard Marking System for Valves, Fittings, Flanges and Unions

MSS SP-58 Pipe Hangers and Supports - Materials, Design and Manufacture, Selection, Application, and Installation

MSS SP-69 Pipe Hangers and Supports - Selection and

Application (ANSI Approved American National Standard)

MSS SP-70 Gray Iron Gate Valves, Flanged and Threaded

Ends

MSS SP-71 Gray Iron Swing Check Valves, Flanged and

Threaded Ends

MSS SP-80 Bronze Gate, Globe, Angle and Check Valves

MSS SP-85 Gray Iron Globe & Angle Valves Flanged and

Threaded Ends

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA 250 Enclosures for Electrical Equipment (1000

Volts Maximum)

NEMA MG 1 Motors and Generators

April 2019 Page 5 Section 23 57 10

PLUMBING-HEATING-COOLING CONTRACTORS NATIONAL ASSOCIATION (PHCC)

NAPHCC NSPC National Standard Plumbing Code

U.S. DEPARTMENT OF DEFENSE (DOD)

UFC 3-310-04 Seismic Design for Buildings

1.2 SUBMITTALS

Government approval is required for submittals. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Heating System

Detail drawings consisting of a complete list of equipment and material, including manufacturer's descriptive and technical literature, performance charts and curves, catalog cuts, and installation instructions. Drawings shall also contain complete wiring and schematic diagrams and any other details required to demonstrate that the system has been coordinated and will properly function as a unit. Drawings shall show proposed layout and anchorage of equipment and appurtenances and equipment relationship to other parts of the work including clearances for maintenance and operation.

SD-03 Product Data

Spare Parts Welding

Six copies of qualified procedures and list of names and the identification symbols of qualified welders and welding operators, prior to welding operations.

Framed Instructions

Proposed diagrams, instructions, and other sheets, submit prior to posting. The instructions shall show wiring and control diagrams and complete layout of the entire system. The instructions shall include, in typed form, condensed operating instructions explaining preventive maintenance procedures, methods of checking the system for normal safe operation and procedures for safely starting and stopping the system.

SD-06 Test Reports

Testing and Cleaning Water Treatment Testing

Performance Tests

Performance test reports in booklet form showing all field tests performed to adjust each component and all field tests performed to

April 2019 Page 6 Section 23 57 10 prove compliance with the specified performance criteria, upon completion and testing of the installed system. Each test report shall indicate the final position of controls.

SD-07 Certificates

Bolts

SD-10 Operation and Maintenance Data

Operation and Maintenance Manuals

Heating System

Six copies of operation and six copies of maintenance manuals for the equipment furnished. One complete set, prior to performance testing, and the remainder upon acceptance. Operating manuals shall detail the step-by-step procedures required for system startup, operation, and shutdown. Operating manuals shall include the manufacturer's name, model number, parts list, and brief description of all equipment and their basic operating features.

Maintenance manuals shall list routine maintenance procedures, water treatment procedures, possible breakdowns and repairs, and troubleshooting guides. Maintenance manuals shall include piping and equipment layout and simplified wiring and control diagrams of the system as installed. Manuals shall be provided prior to the field training course.

1.3 QUALITY ASSURANCE

Procedures and welders shall be qualified in accordance with the code under which the welding is specified to be accomplished.

1.4 DELIVERY, STORAGE, AND HANDLING

Protect all equipment delivered and placed in storage from the weather, excessive humidity and excessive temperature variation; and dirt, dust, or other contaminants.

1.5 EXTRA MATERIALS

Submit spare parts data for each different item of material and equipment specified, after approval of the related submittals and not later than the date of beneficial occupancy. Include in the data a complete list of parts and supplies, with current unit prices and source of supply.

PART 2 PRODUCTS

This guide specification covers low temperature forced hot water heating systems using water temperatures of 210 degrees F and less, at a working pressure of 30 psig using a steam or high temperature water heat exchanger.

A steam supply pressure of approximately 100 psig and a high water temperature of 350 to 450 degrees F were used in preparation of this specification. The high temperature water portion of this specification

April 2019 Page 7 Section 23 57 10 may be used for medium water temperature system of 250 to 350 degrees F if the tests and class of valves, fittings, and piping are adjusted for the temperature and pressure required, but not less than 150 pound class system

The designer should consider all pressure reductions such as pump suction and system cool-down effects and should not consider any pressure increases such as pump discharge heads and system heat-up effects when determining the high or medium temperature water system pressurization required to prevent flash steaming and water hammer

Where ENERGY STAR or FEMP products are not applicable, energy consuming products and systems shall meet or exceed the requirements of ASHRAE 90.1.

2.1 MATERIALS AND EQUIPMENT

2.1.1 Standard Products

Provide materials and equipment which are the standard products of a manufacturer regularly engaged in the manufacture of such products and that essentially duplicate items that have been in satisfactory use for at least 2 years prior to bid opening. Equipment shall be supported by a service organization that is, in the opinion of the Contracting Officer, reasonably convenient to the site.

2.1.2 Nameplates

Place a plate on each major item of equipment having the manufacturer's name, address, type or style, model or serial number, and catalog number secured to the item of equipment.

2.1.3 Equipment Guards and Access

Fully enclose or guard belts, pulleys, chains, gears, couplings, projecting setscrews, keys, and other rotating parts exposed to personnel contact in accordance with OSHA requirements. High temperature equipment and piping exposed to contact by personnel or where it creates a potential fire hazard shall be properly guarded or covered with insulation of a type specified.

Catwalks, operating platforms, ladders, and guardrails shall be provided where shown and shall be constructed in accordance with Section 05 50 13

MISCELLANEOUS METAL FABRICATIONS.

2.1.4 Asbestos Prohibition

Asbestos and asbestos-containing products will not be accepted.

2.1.5 Electrical Work

Electrical motor driven equipment specified shall be provided complete with motors, motor starters, and controls. Electric equipment (including motor efficiencies), and wiring shall be in accordance with Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Integral size motors shall be the premium efficiency type in accordance with NEMA MG 1. Electrical characteristics shall be as specified or indicated. Motor starters shall be provided complete with thermal overload protection and other appurtenances necessary for the motor control specified. Each motor shall be of sufficient size to file://tss-414srv-1/tss_dfs1/Spec_LIB/Saber_2012/05%2050%2013.doc

April 2019 Page 8 Section 23 57 10 drive the equipment at the specified capacity without exceeding the nameplate rating of the motor. Manual or automatic control and protective or signal devices required for the operation specified, and any control wiring, conduit, and connection to power required for controls and devices but not shown shall be provided.

2.2 PIPING, TUBING, AND FITTINGS

Copper tubing and steel pipe will be considered as competitive unless one is not applicable for service.

2.2.1 General

Piping, tubing, and fittings shall be as follows:

a. Low temperature water piping shall be black steel or copper tubing with cast iron, malleable iron or steel, solder-joint, flared-tube or grooved mechanical joint fittings.

b. Steam pipe shall be black steel with malleable iron or steel fittings.

c. Condensate return piping shall be black steel Schedule 80 with cast iron or malleable iron, Class 250 minimum.

d. High temperature water piping shall be black steel, Schedule 40.

e. Vent piping shall be black steel, Schedule 40, with black malleable iron fittings.

2.2.2 Steel Pipe

Pipe shall conform to ASTM A53/A53M or ASTM A106/A106M, Grade A or B, black steel, Schedule 40, unless otherwise specified. Steel pipe to be bent shall be ASTM A53/A53M, Grade A, standard, or Grade B, extra strong weight. Steam pipe shall be ASTM A53/A53M Grade A.

2.2.3 High Temperature Water Piping

Piping shall be Type S for 1-1/2 inches and smaller, Type S or Type E for pipe 2 inches and larger, schedule 40 steel conforming to ASTM A53/A53M, Grade B; or to ASTM A106/A106M, Grade B.

2.2.4 Gauge Piping

Piping shall be copper tubing for steam and low temperature water. Black steel, ASTM A106/A106M, seamless, Grade A pipe shall be used for high temperature.

2.2.5 Copper Tubing

Tubing shall conform to ASTM B88, ASTM B88M, Type K or L. Tubing for compressed air tubing shall conform to ASTM B251.

April 2019 Page 9 Section 23 57 10

2.2.6 High Temperature Water Fittings

Fittings shall be steel welding fittings conforming in physical and chemical properties to ASTM A234/A234M. Buttwelding fittings shall conform to ASME B16.9. Socket welded fittings shall conform to ASME B16.1. Screwed fittings, when required, shall be black forged steel, 2000-pound class, conforming to ASME B16.11. Flanges shall be serrated or raised-faced type.

2.2.7 Malleable Iron Pipe Fittings

Fittings shall conform to ASME B16.3, type required to match adjacent piping.

2.2.8 Cast Iron Pipe Fittings

Fittings shall conform to ASME B16.1 or ASME B16.4 type required to match adjacent piping.

2.2.9 Steel Pipe Fittings

Fittings shall have the manufacturer's trademark affixed in accordance with MSS SP-25 so as to permanently identify the manufacturer.

2.2.9.1 Welded Fittings

Welded fittings shall conform to ASTM A234/A234M with WPA marking. Butt welded fittings shall conform to ASME B16.9, and socket welded fittings shall conform to ASME B16.11.

2.2.9.2 Grooved Mechanical Fittings

Standard fittings shall be of malleable iron conforming to ASTM A47/A47M, Grade 32510, or ductile iron conforming to ASTM A536, Grade 65-45-12.

Fittings may also be constructed of steel, conforming to ASTM A106/A106M, Grade B or ASTM A53/A53M.

2.2.9.3 Grooved Mechanical Pipe Joints

Pipe joints shall conform to AWWA C606. Grooved mechanical joint fittings shall be full flow factory manufactured forged steel fittings. Fittings, couplings, gaskets, and pipe grooving tool or grooved end pipe shall be products of the same manufacturer. Mechanical pipe couplings shall be of the bolted type and shall consist of a housing fabricated in two or more parts, a synthetic rubber gasket, and nuts and bolts to secure unit together. Housings shall be of malleable iron conforming to ASTM A47/A47M, Grade 32510 or ductile iron conforming to ASTM A536, Grade 65-45-12.

Coupling nuts and bolts shall be of steel and conform to ASTM A183. Submit written certification that the bolts furnished comply with the requirements of this specification, provided by the bolt manufacturer. The certification shall include illustrations of product-required markings, the date of manufacture, and the number of each type of bolt to be furnished based on this certification. Gaskets shall be of molded synthetic rubber, Type EPDM or Buna-N with central cavity, pressure responsive configuration and shall conform to ASTM D2000. Gasket material must be appropriate for service conditions: Typically EPDM is used for temperatures to 230 degrees F;

Typically Buna-N is used for temperatures to 180 degrees F. Review

April 2019 Page 10 Section 23 57 10 manufacturer's data for other requirements and limits. Do not use molded synthetic rubber for steam.

2.2.10 Joints and Fittings for Copper Tubing

Wrought copper and bronze fittings shall conform to ASME B16.22 and ASTM B75. Cast copper alloy fittings shall conform to ASME B16.18 and ASTM B828.

Flared fittings shall conform to ASME B16.26 and ASTM B62. Adaptors may be used for connecting tubing to flanges and threaded ends of valves and equipment. Extracted brazed tee joints produced with an acceptable tool and installed as recommended by the manufacturer may be used. Cast bronze threaded fittings shall conform to ASME B16.15. Grooved mechanical joints and fittings shall be designed for not less than 125 psig service and shall be the product of the same manufacturer. Grooved fitting and mechanical coupling housing shall be ductile iron conforming to ASTM A536. Gaskets for use in grooved joints shall be molded synthetic polymer of pressure responsive design and shall conform to ASTM D2000 for circulating medium up to 230 degrees F. Grooved joints shall conform to AWWA C606. Coupling nuts and bolts for use in grooved joints shall be steel and shall conform to ASTM A183.

2.2.11 Steel Flanges

Flanged fittings including flanges, bolts, nuts, bolt patterns. etc. shall be in accordance with ASME B16.5 class 150 and shall have the manufacturers trademark affixed in accordance with MSS SP-25. Flange material shall conform to ASTM A105/A105M. Flanges for high temperature water systems shall be serrated or raised-face type. Blind flange material shall conform to ASTM A516/A516M cold service and ASTM A515/A515M for hot service. Bolts shall be high strength or intermediate strength with material conforming to

ASTM A193/A193M.

2.2.12 Pipe Threads

Pipe threads shall conform to ASME B1.20.1.

2.2.13 Nipples

Nipples shall conform to ASTM A733 or ASTM B687, standard weight.

2.2.14 Unions

Unions shall conform to ASME B16.39, type to match adjacent piping.

2.2.15 Adapters

Adapters for copper tubing shall be brass or bronze for soldered fittings.

2.2.16 Dielectric Waterways or Unions

Dielectric waterways or unions shall conform to the tensile strength and dimensional requirements specified in ASME B16.39. Waterways or unions shall have metal connections on both ends to match adjacent piping. Metal parts of dielectric waterways or unions shall be separated so that the electrical current is below 1 percent of the galvanic current which would exist upon metal-to-metal contact. Dielectric waterways or unions shall

April 2019 Page 11 Section 23 57 10 have temperature and pressure rating equal to or greater than that specified for the connecting piping. Dielectric waterways or unions shall be internally lined with an insulator specifically designed to prevent current flow between dissimilar metals. Dielectric flanges shall meet the performance requirements described herein for dielectric waterways.

2.2.17 Grooved Mechanical Joints

Rigid grooved pipe joints may be provided in lieu of unions, welded, flanges or screwed piping connections at chilled water pumps and allied equipment, and on aboveground pipelines in serviceable locations, if the temperature of the circulating medium does not exceed 230 degrees F. Flexible grooved joints will not be permitted, except as vibration isolators adjacent to mechanical equipment. Rigid grooved joints shall incorporate an angle bolt pad design which maintains metal-to-metal contact with equal amount of pad offset of housings upon installation to insure positive rigid clamping of the pipe. Designs which can only clamp on the bottom of the groove or which utilize gripping teeth or jaws, or which use misaligned housing bolt holes, or which require a torque wrench or torque specifications, will not be permitted. Rigid grooved pipe couplings shall be used with grooved end pipes, fittings, valves and strainers. Rigid couplings shall be designed for not less than 125 psi service and appropriate for static head plus the pumping head, and shall provide a water-tight joint. Grooved fittings and couplings, and grooving tools shall be provided from the same manufacturer.

Segmentally welded elbows shall not be used. Grooves shall be prepared in accordance with the coupling manufacturer's latest published standards.

Grooving shall be performed by qualified grooving operators having demonstrated proper grooving procedures in accordance with the tool manufacturer's recommendations. The Contracting Officer shall be notified 24 hours in advance of test to demonstrate operator's capability, and the test shall be performed at the work site, if practical, or at a site agreed upon. The operator shall demonstrate the ability to properly adjust the grooving tool, groove the pipe, and verify the groove dimensions in accordance with the coupling manufacturer's specifications.

2.2.18 Flexible Pipe Connectors

Flexible pipe connectors shall be designed for 125 psi or 150 psi service as appropriate for the static head plus the system head, and 250 degrees F.

Connectors shall be installed where indicated. The flexible section shall be constructed of rubber, tetrafluoroethylene resin, or corrosion-resisting steel, bronze, monel, or galvanized steel. Materials used and the configuration shall be suitable for the pressure, vacuum, temperature, and circulating medium. The flexible section may have threaded, welded, soldered, flanged, grooved, or socket ends. Flanged assemblies shall be equipped with limit bolts to restrict maximum travel to the manufacturer's standard limits. Unless otherwise indicated, the length of the flexible connectors shall be as recommended by the manufacturer for the service intended. Internal sleeves or liners, compatible with circulating medium, shall be provided when recommended by the manufacturer. Covers to protect the bellows shall be provided where indicated.

April 2019 Page 12 Section 23 57 10

2.3 MATERIALS AND ACCESSORIES

2.3.1 Iron and Steel Sheets

2.3.1.1 Galvanized Iron and Steel

Galvanized iron and steel shall conform to ASTM A653/A653M, with general requirements conforming to ASTM A653/A653M. Gauge numbers specified are Manufacturer's Standard Gauge.

2.3.1.2 Uncoated (Black) Steel

Uncoated (black) steel shall conform to ASTM A 366/A 366M or ASTM A 569/A 569M, composition, condition, and finish best suited to the intended use.

Gauge numbers specified refer to Manufacturer's Standard Gauge.

2.3.2 Solder

Solder shall conform to ASTM B32. Solder and flux shall be lead free.

Solder flux shall be liquid or paste form, non-corrosive and conform to ASTM B813.

2.3.3 Solder, Silver

Silver solder shall conform to AWS A5.8/A5.8M.

2.3.4 Thermometers

Mercury shall not be used in thermometers. Thermometers shall have brass, malleable iron, or aluminum alloy case and frame, clear protective face, permanently stabilized glass tube with indicating-fluid column, white face, black numbers, and a 9 inch scale, and thermometers shall have rigid stems with straight, angular, or inclined pattern.

2.3.5 Gauges

Gauges shall conform to ASME B40.100.

2.3.6 Gaskets for Flanges

Composition gaskets shall conform to ASME B16.21. Gaskets shall be nonasbestos compressed material in accordance with ASME B16.21, 1/16 inch thickness, full face or self-centering flat ring type. Gaskets shall contain aramid fibers bonded with styrene butadiene rubber (SBR) or nitrile butadiene rubber (NBR). NBR binder shall be used for hydrocarbon service.

Gaskets shall be suitable for pressure and temperatures of piping system.

2.3.7 Polyethylene Tubing

Low-density virgin polyethylene shall conform to ASTM D1248, Type I, Category 5, Class B or C.

2.3.8 Bellows-Type Joints

Select bellows-type or slip-type to satisfy specific design conditions.

April 2019 Page 13 Section 23 57 10

Joints shall be flexible, guided expansion joints. Expansion element shall be of stainless steel. Bellows-type expansion joints shall be in accordance with the applicable requirements of EJMA Stds and ASME B31.1 with internal liners.

2.3.9 Expansion Joints

Expansion joints shall provide for either single or double slip of connected pipes, as required or indicated, and for not less than the traverse indicated. Joints shall be designed for hot water working pressure and shall be in accordance with applicable requirements of EJMA Stds and ASME B31.1. Joints shall be designed for packing injection under full line pressure. End connections shall be flanged or beveled for welding as indicated. Joints shall be provided with anchor base where required or indicated. Where adjoining pipe is carbon steel, the sliding slip shall be seamless steel plated with a minimum of 2 mils of hard chrome conforming to ASTM B650. Joint components shall be fabricated from material equivalent to that of the pipeline. Initial settings shall be made in accordance with manufacturer's recommendations to compensate for ambient temperature at time of installation. Pipe alignment guides shall be installed as recommended by joint manufacturer, but in any case shall not be more than 5 feet from expansion joint except for lines 4 inches or smaller, guides shall be installed not more than 2 feet from the joint. Service outlets shall be provided where indicated.

2.3.10 Flexible Ball Joints

Flexible ball joints shall be constructed of alloys as appropriate for the service intended. Where so indicated, the ball joint shall be designed for packing injection under full line pressure to contain leakage. Joint ends shall be threaded (to 2 inches only), grooved, flanged or beveled for welding as indicated or required and shall be capable of absorbing a minimum of 15-degree angular flex and 360-degree rotation. Balls and sockets shall be of equivalent material as the adjoining pipeline. Exterior spherical surface of carbon steel balls shall be plated with 2 mils of hard chrome conforming to ASTM B650. Ball type joints shall be designed and constructed in accordance with ASME B31.1 and ASME BPVC SEC VIII D1, where applicable.

Flanges where required shall conform to ASME B16.5. Gaskets and compression seals shall be compatible with the service intended.

2.3.11 Pipe Hangers, Inserts, and Supports

Pipe hangers, inserts, and supports shall conform to MSS SP-58 and MSS SP- 69.

2.4 VALVES FOR LOW TEMPERATURE WATER HEATING AND STEAM SYSTEMS

Valves in this section apply to low temperature water heating or low pressure steam systems. Delete for high or medium temperature water systems.

2.4.1 Check Valves

Sizes 2-1/2 inches and less, bronze shall conform to MSS SP-80, Type 3 or 4, Class 125. Sizes 3 inches through 24 inches, cast iron shall conform to MSS SP-71, Type III or IV, Class 125.

April 2019 Page 14 Section 23 57 10

2.4.2 Globe Valves

Sizes 2-1/2 inches and less, bronze shall conform to MSS SP-80, Type 1, 2 or 3, Class 125. Sizes 3 inches through 12 inches, cast iron shall conform to MSS SP-85, Type III, Class 125.

2.4.3 Angle Valves

3, Class 125. Sizes 3 inches through 12 inches, cast iron shall conform to MSS SP-85, Type III, Class 125.

2.4.4 Gate Valves

Sizes 2-1/2 inches and less, bronze shall conform to MSS SP-80, Type 1 or 2, Class 125. Sizes 3 inches through 48 inches, cast iron shall conform to MSS SP-70, Type I, Class 125, Design OT or OF (OS&Y), bronze trim.

2.4.5 Air Vents

Air vents shall be provided at all piping high points in water systems, with block valve in inlet and internal check valve to allow air vent to be isolated for cleaning and inspection. Outlet connection shall be piped to nearest open site or suitable drain, or terminated 12 inches above finished grade. Pressure rating of air vent shall match pressure rating of piping system. Body and cover shall be cast iron or semi-steel with stainless steel or copper float and stainless steel or bronze internal parts. Air vents installed in piping in chase walls or other inaccessible places shall be provided with an access panel.

2.4.6 Balancing Valves

Balancing valves shall have meter connections with positive shutoff valves.

An integral pointer shall register degree of valve opening. Valves shall be calibrated so that flow in gpm can be determined when valve opening in degrees and pressure differential across valve is known. Each balancing valve shall be constructed with internal seals to prevent leakage and shall be supplied with preformed insulation. Valves shall be suitable for 250 degrees F temperature and working pressure of the pipe in which installed.

Valve bodies shall be provided with tapped openings and pipe extensions with shutoff valves outside of pipe insulation. The pipe extensions shall be provided with quick connecting hose fittings for a portable meter to measure the pressure differential. One portable differential meter shall be furnished. The meter suitable for the operating pressure specified shall be complete with hoses, vent, and shutoff valves and carrying case. In lieu of the balancing valve with integral metering connections, a ball valve or plug valve with a separately installed orifice plate or venturi tube may be used for balancing. Plug valves and ball valves 8 inches or larger shall be provided with manual gear operators with position indicators.

2.4.7 Automatic Flow Control Valves

In any facility where technological and occupancy requirements indicate that load imbalances cannot be tolerated and there is a need for automatic control ensuring constant hydronic flow, the design shall incorporate

April 2019 Page 15 Section 23 57 10 automatic flow control valves and indicate their location and capacity on the as built drawings.

The valves shall be designed to be sensitive to pressure differential across the valve to provide the required opening. The valves shall be selected for the flow required and provided with a permanent nameplate or tag carrying a record of the factory-determined flow rate and flow control pressure levels.

Valves shall control the flow within 5 percent of the tag rating. Valves shall be suitable for the maximum operating pressure of 125 psi or 150 percent of the system operating pressure, whichever is greater. Where the available system pressure is not adequate to provide the minimum pressure differential that still allows flow control, the system pump head shall be increased. Valves shall be suitable for the maximum system operating temperature and pressure. Valve materials shall be same as specified for low temperature heating system check, globe, angle and gate valves. Valve operator shall be the electric motor type or pneumatic type as applicable.

Valve operator shall be capable of positive shutoff against the system pump head.

2.4.8 Gravity Flow Control Valves

Ends shall be soldered, threaded, or flanged type as applicable, and designed for easy cleaning without disconnecting piping. Valves for copper tubing shall be bronze. Valves shall prevent flow due to gravity when circulators are off.

2.4.9 Radiator Valves

Automatic thermostatic radiator valves shall be self-contained direct sensor, remote sensor, or wall thermostat controlled nonelectric temperature control valves. Valve bodies shall be constructed of chrome plated brass and shall be angle or straight pattern as indicated, with threaded or brazed end connections. Valve disc shall be of ethylene propylene or composition material. Thermostatic operators shall be a modulating type consisting of a sensing unit counter balanced by a spring setting.

2.5 VALVES FOR HIGH AND MEDIUM TEMPERATURE WATER SYSTEMS

Valves in this section apply to high and medium temperature water systems and high pressure steam systems. Delete for low temperature water heating systems or low pressure steam systems.

2.5.1 Check Valves

Sizes 2-1/2 inches and less, bronze shall conform to MSS SP-80, Class 300 Sizes 2-1/2 inches and less, bronze shall conform to MSS SP-80, Class 300 minimum. Sizes 3 inches through 24 inches, steel shall conform to ASME B16.34, Class 300 minimum, flanged ends, swing disc; water, oil gas or steam service to 850 degrees F.

2.5.2 Globe Valves

3, Class 300 minimum. Sizes 3 inches through 24 inches, steel shall conform

April 2019 Page 16 Section 23 57 10 to ASME B16.34, Class 300 minimum, flanged ends; water, oil, gas, or steam

2.5.3 Angle Valves

3, Class 300 minimum. Sizes 3 inches through 24 inches, steel shall conform to ASME B16.34, Class 300 minimum, flanged ends; water, oil, gas, or steam

2.5.4 Gate Valves

Sizes 2-1/2 inches and less, bronze shall conform to MSS SP-80, Type 1, or 2, Class 300 minimum. Sizes 3 inches through 24 inches, steel shall conform to ASME B16.34, Class 300 minimum, flanged ends; water, oil, gas or steam service to 850 degrees F. Gate shall be split wedge (double disc) type.

2.6 COLD WATER CONNECTIONS

Connections shall be provided which include consecutively in line a strainer, backflow prevention device, and water pressure regulator. The backflow prevention device shall be provided as indicated and in compliance with Section 22 00 00 PLUMBING, GENERAL PURPOSE.

2.6.1 Strainers

Basket or Y-type strainers shall be the same size as the pipelines in which they are installed. Strainer bodies shall be rated for 250 pound service, with bottoms drilled and plugged. Bodies shall have arrows cast on the sides to indicate the direction of flow. Each strainer shall be equipped with a removable cover and sediment basket. Basket shall not be less than 22 gauge and shall have perforations to provide a net free area through the basket of at least four times that of the entering pipe.

2.6.2 Pressure Regulating Valve

Valve shall be a type that will not stick nor allow pressure to build up on the low side. Valve shall be set to maintain a terminal pressure approximately 5 psi in excess of the static head on the system and shall operate within a 20 psi variation regardless of initial pressure and without objectionable noise under any condition of operation.

2.7 FLASH TANK

Tank shall be sized and installed as indicated, and shall be of welded construction utilizing black steel sheets not less than 11 gauge. Tank shall be provided with a handhole and with tapping for the condensate returns, drip lines, vent line, and condensate discharge line to the condensate receiver. Discharge line shall be equipped with a float trap.

Tank shall be ASME rated in accordance with ASME BPVC SEC VIII D1.

2.8 EXPANSION TANK

Pressurization system shall include a replaceable diaphragm-type captive air expansion tank which will accommodate the expanded water of the system generated within the normal operating temperature range, limiting this

April 2019 Page 17 Section 23 57 10 pressure increase at all components in the system to the maximum allowable pressure at those components. The only air in the system shall be the permanent sealed-in air cushion contained in the diaphragm-type tank. Sizes shall be as indicated. Expansion tank shall be welded steel, constructed, tested and stamped in accordance with ASME BPVC SEC VIII D1 for a working pressure suitable for the specific system and precharged to the minimum operating pressure. Tank air chamber shall be fitted with an air charging valve. Tank shall be supported by steel legs or bases for vertical installation or steel saddles for horizontal installations.

2.9 AIR SEPARATOR TANK

External air separation tank shall be steel, constructed, tested, and stamped in accordance with ASME BPVC SEC VIII D1 for a working pressure of suitable for the specific system. The capacity of the air separation tank indicated is minimum.

2.10 STEAM TRAPS

This section applicable to steam systems only.

A schedule of steam trap selection shall be shown and located on as built drawings showing trap orifice size, capacity ( #/hr), and pressure drop (psi), for each trap required.

2.10.1 Float Traps

Capacity, working pressure, and differential pressure of the traps shall be as indicated.

2.10.2 Float-and-Thermostatic Traps

Traps shall be designed for a steam working pressure of approximately 15 psig, but shall operate with a supply pressure of approximately 5 psig. The capacity of the traps shall be as indicated. Trap capacity shall be based on a pressure differential of 1/4 psi. Each float-and-thermostatic trap shall be provided with a hard bronze, monel, or stainless steel valve seat and mechanism and brass float, all of which can be removed easily for inspection or replacement without disturbing the piping connections. Inlet to each trap shall have a cast iron strainer, either an integral part of the trap or a separate item of equipment.

2.10.3 Bucket Traps

Traps shall be inverted or vertical bucket type with automatic air discharge. Traps shall be designed for a working pressure of 150 psig, but shall operate under a steam supply pressure of approximately 40 to 100 psig as required. Each trap shall have a heavy body and cap of fine-grained, gray cast iron. The bucket shall be made of brass; the mechanism of hard bronze; the valve and seat of stainless or monel; or each of equivalent material. Traps shall be tested hydrostatically under a pressure of 200 psig. Traps shall have capacities as indicated when operating under the specified working conditions. A strainer shall be installed in the suction connection of each trap. Impact operated traps, impulse-operated traps, or thermodynamic traps with continuous discharge may be installed in lieu of bucket traps, subject to approval. Thermostatic traps designed for a steam

April 2019 Page 18 Section 23 57 10 working pressure suitable for the application may be furnished in lieu of the traps specified above. Thermostatic traps shall be equipped with valves and seats of stainless steel or monel metal, and shall have capacities based on a pressure differential not in excess of the following:

Steam Working Pressure, psi Differential, psi

25-50 20

90-100 80

2.11 HEAT EXCHANGERS

Heat exchangers shall be multiple pass shell and U-tube type or plate and frame type as indicated, to provide low temperature hot water for the heating system when supplied with steam or high temperature hot water or medium temperature hot water at the temperatures and pressures indicated.

Temperature and pressure for plate and frame exchangers shall not exceed 280 degrees F and 280 psig for medium temperature hot water, or 280 degrees F and 35 psig for steam. Temperature and pressure for shell and U-tube exchangers shall not exceed 338 degrees F and 100 psig for steam or 430 degrees F and 400 psig for high temperature hot water. Exchangers shall be constructed in accordance with ASME BPVC SEC VIII D1 and certified with ASME stamp secured to unit. U-tube bundles shall be completely removable for cleaning and tube replacement and shall be free to expand with shell.

Shells shall be of seamless steel pipe or welded steel construction and tubes shall be seamless tubing as specified below unless otherwise indicated. Tube connections to plates shall be leakproof. Saddles or cradles shall be provided to mount shell and U-tube exchangers. Frames of plate and frame type exchangers shall be fabricated of carbon steel and finished with baked epoxy enamel. Design fouling factor shall be as indicated.

Note: Fouling allowances for steam or high temperature water and for low temperature water shall be determined by the system designer. Recommended allowances are listed in the Tubular Exchanger Manufacturers Association (TEMA) Standards as a general reference and guide.

2.11.1 Steam Heat Exchangers, Shell and U-Tube Type

Exchangers shall operate with steam in shell and low temperature water in tubes. Shell and tube sides shall be designed for 150 psig working pressure and factory tested at 300 psig. Steam, water, condensate, and vacuum and pressure relief valve connections shall be located in accordance with the manufacturer's standard practice. Connections larger than 3 inches shall be ASME 150 pound flanged. Water pressure loss through clean tubes shall not exceed 6 psi and water velocity shall not exceed 6 fps unless otherwise indicated. Minimum water velocity in tubes shall be not less than 1 fps and assure turbulent flow. Tubes shall be seamless copper or copper alloy, constructed in accordance with ASTM B75 or ASTM B395/B395M, suitable for the temperatures and pressures specified. Tubes shall be not less than 3/4 inch unless otherwise indicated. Maximum steam inlet nozzle velocity shall not exceed 6000 fpm.

April 2019 Page 19 Section 23 57 10

2.11.2 High Temperature Water Heat Exchangers, Shell and U-tube Type

Exchangers shall operate with low temperature water in shell and high temperature water in tubes. Shell side shall be designed for 150 psig working pressure and factory tested at 300 psig. Tubes shall be designed for 400 psig working pressure and an operating temperature of 450 degrees F.

High and low temperature water and pressure relief connections shall be located in accordance with the manufacturer's standard practice. Water connections larger than 3 inches shall be ASME 600 pound flanged for high temperature water, and ASME 150 pound flanged for low temperature water.

Water pressure loss through clean tubes shall not exceed 6 psig unless otherwise indicated. Minimum water velocity in tubes shall be 1 fps and assure turbulent flow. Tubes shall be cupronickel or inhibited admiralty, constructed in accordance with ASTM B395/B395M, suitable for the temperatures and pressures specified. Tubes shall be not less than 3/4 inch unless otherwise indicated.

2.11.3 Steam Heat Exchangers, Plate and Frame Type

Plates, frames and gaskets shall be designed for a working pressure of 300 psig and factory tested at 450 psig. Steam, low temperature water, condensate, and vacuum and pressure relief valve connections shall be located in accordance with the manufacturer's standard practice.

Connections larger than 3 inches shall be ASME 150 pound flanged. Water pressure drop through clean plates and headers shall not exceed the designated psig at the flow rates and temperatures indicated. Plates shall be designed to assure turbulent flow at a minimum rate of indicated gpm through any 2 plate segment. Plates shall be corrugated Type 304 stainless steel, Type 316 stainless steel, nickel-iron-chromium alloy conforming to ASTM B424, nickel-molybdenum alloy conforming to ASTM B333, or titanium alloy conforming to ASTM B265. Plate thickness shall be not less than the design indicated or manufacturer recommended amount.

2.11.4 Medium Temperature Water Heat Exchangers, Plate and Frame Type

Plates, frames and gaskets shall be designed for a working pressure of 300 psig and factory tested at 450 psig. Medium temperature water, low temperature water, and pressure relief valve connections shall be located in accordance with the manufacturer's standard practice. Connections larger than 3 inches shall be ASME 300 pound flanged. Water pressure drop through clean plates and headers shall not exceed the design specified psi at the flow rates and temperatures indicated. Plates shall be designed to assure turbulent flow at a minimum rate of design specified gpm through any 2 plate segment. Plates shall be corrugated Type 304 stainless steel, Type 316 stainless steel, nickel-iron-chromium alloy conforming to ASTM B424, nickel-molybdenum alloy conforming to ASTM B333, or titanium alloy conforming to ASTM B265. Plate thickness shall be not less than design indicated or manufacturer recommended amount.

2.12 SYSTEM EQUIPMENT AND ACCESSORIES

2.12.1 Circulating Pumps

Pumps for hot water shall be of the single-stage centrifugal type, electrically driven. Pumps shall be supported on a concrete foundation as indicated. Pumps shall be either integrally mounted with the motor or

April 2019 Page 20 Section 23 57 10 direct-connected by means of a flexible-shaft coupling on a cast iron, or steel sub-base. Pump housing shall be of close grained cast iron. Shaft shall be carbon or alloy steel, turned and ground. Shaft seal shall be mechanical-seal or stuffing-box type. Impeller, impeller wearing rings, glands, casing wear rings, and shaft sleeve shall be bronze. Bearings shall be ball-, roller-, or oil-lubricated, bronze-sleeve type, and shall be sealed or isolated to prevent loss of oil or entrance of dirt or water.

Motor shall be of a type approved by the manufacturer of the pump.

2.12.2 Condensate Pumping Unit

Size condensate pumping rate for three times the expected condensate flow.

Size receiver for five times the expected condensate flow for expected condensate flow up to 8 GPM.

Size receiver two times the expected condensate flow for expected condensate flow over 8 GPM.

Pump shall have a minimum capacity, as indicated, when discharging against the specified pressure. The minimum capacity of the tank shall be as indicated above. Condensate pumping unit shall be of the single or duplex, horizontal-shaft or vertical-shaft type, as indicated. Unit shall consist of one or two pumps, one electric motor or two electric motors and a single receiver. Pumps shall be centrifugal or turbine type, bronze-fitted throughout with impellers of bronze or other corrosion-resistant metal.

Pumps shall be free from air-binding when handling condensate with temperatures up to 200 degrees F. Pumps shall be connected directly to dripproof enclosed motors. Receiver shall be cast iron and shall be provided with condensate return, vent, overflow, and pump suction connections, and water level indicator and automatic air vent. Inlet strainer shall be provided in the inlet line to the tank. Vent pipe shall be galvanized steel, and fittings shall be galvanized malleable iron. Vent pipe shall be installed as indicated or directed. Vent piping shall be flashed as specified. Pump, motor, and receiving tank may be mounted on a single base with the receiver piped to the pumps suctions. A gate valve and check valve shall be provided in the discharge connection from each pump.

2.12.2.1 Controls

Enclosed float switches complete with float mechanisms shall be installed in the head of the receiver. The condensate pump shall be controlled automatically by means of the [respective] float switch that will automatically start the motor when the water in the receiving tank reaches the high level and stop the motor when the water reaches the low level.

Motors shall be provided with magnetic across-the-line starters equipped with general purpose enclosure and Automatic-Manual-Off selector switch in the cover.

2.12.2.2 Factory Testing

Submit a certificate of compliance from the pump manufacturer covering the actual test of the unit and certifying that the equipment complies with the indicated requirements.

April 2019 Page 21 Section 23 57 10

2.12.3 Pressure Gauges and Thermometers

Gauges shall be provided for each heat exchanger and piping as indicated. A thermometer and pressure gauge shall be provided on the high temperature water supply and return mains. Thermometers shall be separable socket type.

2.12.4 Vacuum Relief Valve

Vacuum relief valve shall be installed on the shell of each shell and U-tube steam heat exchanger and on the factory supplied steam inlet nozzle of each plate and frame heat exchanger. On shutoff of steam supply and condensing of steam, the vacuum relief valve shall automatically admit air to the heat exchanger.

2.12.5 Pressure Relief Valves

One or more pressure relief valves shall be provided for each heat exchanger in accordance with ASME BPVC SEC VIII D1. The aggregate relieving capacity of the relief valves shall be not less than that required by the above code.

Discharge from the valves shall be installed as indicated. Pressure relief valves for steam heat exchangers shall be located on the low temperature water supply coming from near the heat exchanger as indicated. Relief valves for high temperature water heat exchanger shall be installed on the heat exchanger shell.

2.12.6 Drains

A drain connection with 3/4 inch hose bib shall be installed at the lowest point in the low temperature water return main near the heat exchanger. In addition, threaded drain connections with threaded cap or plug shall be installed wherever required for thorough draining of the low temperature water system. Submitted and as built drawings shall clearly indicate low-point drains.

2.12.7 Strainers

Basket or Y-type strainer-body connections shall be the same size as the pipe lines in which the connections are installed. The bodies shall have arrows clearly cast on the sides to indicate the direction of flow. Each strainer shall be equipped with an easily removable cover and sediment basket. The body or bottom opening shall be equipped with nipple and gate valve for blowdown. The basket for steam systems shall be of not less than

0.025 inch thick stainless steel, or monel with small perforations of sufficient number to provide a net free area through the basket of at least

2.5 times that of the entering pipe. The flow shall be into the basket and out through the perforations. For high temperature water systems, only cast steel bodies shall be used.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .