TINKER AFB MAC BOA WWYK190023 Renovate Restrooms B117
Solicitation number
FA813726R0030
Issued by

About this file

This is a technical specification document for a LonWorks Direct Digital Control (DDC) system for HVAC and building control systems at Tinker Air Force Base, Oklahoma, dated April 2019.

The specification establishes requirements for a complete DDC system using CEA-709.1-D protocol and LonMark Standard Network Variable Types for communications. All DDC hardware must be locally powered and incorporate service pins, power indicator lights, and TP/FT-10 transceivers. Hardware must support configurable input/output functions including analog inputs/outputs (minimum 8-bit resolution), binary inputs/outputs, and pulse accumulators with specified noise rejection and isolation requirements. All DDC hardware must meet FCC Part 15 and UL 916 standards. The specification mandates use of LonMark External Interface Files (XIF files) for each hardware type and requires application programs and configuration settings be retained through power loss indefinitely for programs and minimum 2,500 hours for settings.

The system architecture requires a Building Control Network (BCN) consisting of an IP network and non-IP control channels using TP/FT-10 (doubly terminated bus topology) or TP/XF-1250 configurations per CEA-709.3 and LonMark standards. Installation must limit each channel to 2/3 maximum permitted devices and maintain peak bandwidth usage below 70 percent. The specification requires Application Specific Controllers where suitable, with alternatives including General Purpose Programmable Controllers and Application Generic Controllers. Installation requirements include Hand-Off-Auto switches, Local Display Panels with password protection, network interface jacks within 10 feet of all nodes, and gateways only for connecting pre-existing non-CEA-709.1-D equipment. Scheduling must map occupancy modes to specific SNVT enumeration values, with separate schedules per AHU and terminal unit groupings.

View the file

Other files

File Type Posted
03 39 00.00 10.pdf PDF
03 62 16.pdf PDF
04 20 00.pdf PDF
05 21 00.pdf PDF
06 20 00.pdf PDF
06 61 16.pdf PDF
07 60 00.pdf PDF
07 61 14.00 20.pdf PDF
07 84 00.pdf PDF
07 92 00.pdf PDF
08 11 16.pdf PDF
08 36 13.pdf PDF
08 71 00.pdf PDF
09 68 00.pdf PDF
10 28 13.pdf PDF
13 48 00.pdf PDF
21 13 17.pdf PDF
22 00 00.pdf PDF
23 00 00.pdf PDF
23 08 00.pdf PDF
23 11 25.pdf PDF
23 35 00.pdf PDF
23 64 26.pdf PDF
23 82 16.00 40.pdf PDF
23 82 43.00 40.pdf PDF
26 56 00.pdf PDF
31 23 06.pdf PDF
32 01 14.pdf PDF
32 13 74.pdf PDF
03 11 13.00 10.pdf PDF
03 20 00.00 10.pdf PDF
03 30 00.pdf PDF
07 14 00.pdf PDF
190023 Renovate Restrooms B117 RFIs_FINAL_COR_Signed.pdf PDF
TAFB_Tech_Reqs (Div 02-48).zip ZIP file
Model.zip ZIP file
00 71 00.pdf PDF
01 78 23.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 32 16.00 20.pdf PDF
01 33 16.00 10.pdf PDF
01 42 00.pdf PDF
01 78 00.pdf PDF
Tinker General Requirements Specifications_Nov 2022_Change Log.pdf PDF
Initial Site Visit WWYK190023.pdf PDF
Solicitation - FA813726R0030.pdf PDF
Att10_190023_SOW.pdf PDF
EAL List - BLANK to Contractors WWYK190023.xlsx XLSX spreadsheet
Att12_190023_Drawings_Final.pdf PDF
Section L - Instructions to Offerors.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 23 09 23. 01

LONWORKS DI RECT DI GI TAL CONTROL FOR HVAC AND OTHER BUI LDI NG CONTROL SYSTEMS

PART 1 GENERAL

1. 1 SUMMARY

Pr ovi de a compl et e Di r ect Di gi t al Cont r ol ( DDC) syst em, except f or t he Fr ont End whi ch i s speci f i ed i n Sect i on 25 10 10 UTI LI TY MONI TORI NG AND CONROL ( UMCS) FRONT END AND I NTEGRATI ON, sui t abl e f or t he cont r ol of t he heat i ng, vent i l at i ng and ai r condi t i oni ng ( HVAC) and ot her bui l di ng- l evel syst ems as speci f i ed and shown and i n accor dance wi t h Sect i on 23 09 00

I NTRUMENTATI ON AND CONTROL FOR HVAC.

1. 1. 1 Syst em Requi r ement s

Pr ovi de a syst em meet i ng t he r equi r ement s of bot h Sect i on 23 09 00 I NTRUMENTATI ON AND CONTROL FOR HVAC and t hi s Sect i on and wi t h t he f ol l owi ng char act er i st i cs:

a. The cont r ol syst em must be an open i mpl ement at i on of LonWor ks t echnol ogy usi ng CEA-709.1-D as t he communi cat i ons pr ot ocol . syst em must use LonMar k St andar d Net wor k Var i abl e Types as def i ned i n LonMar k SNVT Li st excl usi vel y f or communi cat i on over t he net wor k.

c. I nst al l and conf i gur e conr ol har dwar e t o pr ovi de al l i nput and out put St andar d Net wor k Var i abl es ( SNVTs) as i ndi cat ed and as needed t o meet t he r equi r ement s of t hi s speci f i cat i on.

d. Al l DDC har dwar e i nst al l ed under t hi s speci f i cat i on must communi cat e via CEA-709.1-D . I nst al l t he cont r ol syst em such t hat a SNVT out put f r om any node on t he net wor k can be bound t o any ot her node i n t he same domai n.

1. 1. 2 Ver i f i cat i on of Speci f i cat i on Requi r ement s

Revi ew al l speci f i cat i ons r el at ed t o t he cont r ol syst em i nst al l at i on and advi se t he Cont r act i ng Of f i cer of any di scr epanci es bef or e per f or mi ng any wor k. I f Sect i on 23 09 00 I NTRUMENTATI ON AND CONTROL FOR HVAC or any ot her Sect i on r ef er enced i n t hi s speci f i cat i on i s not i ncl uded i n t he pr oj ect speci f i cat i ons advi se t he Cont r act i ng Of f i cer and ei t her obt ai n t he mi ssi ng Sect i on or obt ai n Cont r act i ng Of f i cer appr oval bef or e per f or mi ng any wor k.

1. 2 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by

Apr i l 2019 Page 1 SECTI ON 23 09 23. 01 t he basi c desi gnat i on onl y.

CONSUMER ELECTRONI CS ASSOCI ATI ON ( CEA)

CEA-709.1-D ( 2014) Cont r ol Net wor k Pr ot ocol Specification

CEA-709.3 ( 1999; R 2004) Fr ee- Topol ogy Twi st ed- Pai r Channel Speci f i cat i on

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE 802. 3 ( 2012; ERTA 2013; BK 2013; BJ 2014; BM

2015) St andar d I nf or mat i on Technol ogy- - Tel ecommuni cat i ons and I nf or mat i on Exchange Bet ween Syst ems- - Speci f i c Requi r ement s Par t 3:

CSMA/ CD Access Met hod and Physi cal Layer Specifications

LONMARK I NTERNATI ONAL ( LonMar k)

LonMar k I nt er oper abi l i t y Gui de ( 2005) LonMar k Appl i cat i on- Layer I nt er oper abi l i t y Gui de and LonMar k Layer 1- 6 I nt er oper abi l i t y Gui de; Ver si on 3. 4

LonMar k SCPT Li st ( 2003) LonMar k SCPT Mast er Li st ; Ver si on 12

LonMar k SNVT Li st ( 2003) LonMar k SNVT Mast er Li st ; Ver si on

LonMar k XI F Gui de ( 2001) LonMar k Ext er nal I nt er f ace Fi l e Ref er ence Gui de; Revi s i on 4. 402

U. S. FEDERAL COMMUNI CATI ONS COMMI SSI ON ( FCC)

FCC Par t 15 Radi o Fr equency Devi ces ( 47 CFR 15)

UNDERWRI TERS LABORATORI ES ( UL)

UL 916 ( 2007; Repr i nt Aug 2014) St andar d f or Ener gy Management Equi pment

1. 3 DEFINITIONS

For def i ni t i ons r el at ed t o t hi s sect i on, see Sect i on 23 09 00

I NTRUMENTATI ON AND CONTROL FOR HVAC.

1. 4 SUBMITTALS

Submi t t al s r el at ed t o t hi s Sect i on ar e speci f i ed i n Sect i on 23 09 00

I NTRUMENTATI ON AND CONTROL FOR HVAC.

PART 2 PRODUCTS

Al l pr oduct s used t o meet t hi s speci f i cat i on must meet t he speci f i ed r equi r ement s, but not al l pr oduct s speci f i ed her e wi l l be r equi r ed by ever y pr oj ect . Pr ovi de pr oduct s whi ch meet t he r equi r ement s of bot h Sect i on 23 09 00 I NTRUMENTATI ON AND CONTROL FOR HVAC and t hi s Sect i on.

Apr i l 2019 Page 2 SECTI ON 23 09 23. 01

2. 1 NETWORK HARDWARE

2. 1. 1 CEA- 709. 1- D Rout er s

CEA-709.1-D Rout er s must meet t he r equi r ement s of CEA-709.1-D and must pr ovi de connect i on bet ween t wo or mor e CEA-709.3 TP/ FT- 10 channel s, or bet ween one or mor e CEA-709.3 TP/ FT- 10 channel s and a LonMar k I nt er oper abi l i t y Gui de TP/ XF- 1250 channel .

2. 1. 2 CEA- 709. 1- D Repeat er s

CEA-709.1-D Repeat er s must be CEA-709.1-D Rout er s conf i gur ed as r epeat er s.

Physi cal l ayer r epeat er s ar e pr ohi bi t ed.

2. 1. 3 CEA- 709. 1- D Gat eways

I n addi t i on t o t he r equi r ement s f or DDC Har dwar e, CEA-709.1-D gat eways must

a. Aal l ow bi - di r ect i onal mappi ng of dat a bet ween t he non- CEA-709.1-D pr ot ocol and SNVTs

b. I ncor por at e a net wor k connect i on t o a TP/ FT- 10 net wor k i n accor dance with CEA-709.3 and a separ at e connect i on appr opr i at e f or t he a non- CEA-709.1-D net wor k

Al t hough Gat eways must meet DDC Har dwar e r equi r ement s t hey ar e not DDC Har dwar e and must not be used when DDC Har dwar e i s r equi r ed.

2. 1. 4 Et her net Swi t ch

Et her net Swi t ches [ must be managed swi t ches and ] must aut oconf i gur e bet ween 10, 100 and 1000 megabi t s per second ( MBPS) .

2. 2 CONTROL NETWORK WI RI NG

a. Pr ovi de TP/ FT- 10 cont r ol wi r i ng i n accor dance wi t h CEA-709.3 .

b. Pr ovi de TP/ XF- 1250 cont r ol wi r i ng i n accor dance wi t h t he LonMar k I nt er oper abi l i t y Gui de.

c. For t he Bui l di ng Cont r ol Net wor k I P Net wor k pr ovi de medi a t hat i s CAT- 5e Et her net medi a at a mi ni mum and meet s al l r equi r ement s of I EEE 802. 3 [ and [ _____] ] .

2. 3 DI RECT DI GI TAL CONTROL ( DDC) HARDWARE

Al l DDC Har dwar e must meet t he f ol l owi ng gener al r equi r ement s:

a. must i ncor por at e a " ser vi ce pi n" whi ch, when pr essed wi l l cause t he DDC Har dwar e t o br oadcast i t s 48- bi t NodeI D and i t s Pr ogr amI D over t he net wor k. The ser vi ce pi n must be di st i ngui shabl e and accessi bl e.

b. I t must i ncor por at e a l i ght t o i ndi cat e t he devi ce i s r ecei v i ng power .

c. i ncor por at e a TP/ FT- 10 t r anscei ver i n accor dance wi t h CEA-709.3 and connect i ons f or TP/ FT- 10 cont r ol net wor k wi r i ng.

Apr i l 2019 Page 3 SECTI ON 23 09 23. 01

d. I t must communi cat e on t he net wor k usi ng onl y t he CEA-709.1-D pr ot ocol .

e. I t must be capabl e of havi ng net wor k communi cat i ons conf i gur ed vi a.

f . I t must be l ocal l y power ed; l i nk power ed devi ces ar e not accept abl e.

g. LonMar k ext er nal i nt er f ace f i l es ( XI F f i l es) , as def i ned i n t he LonMar k XI F Gui de, must be submi t t ed f or each t ype of DDC Har dwar e .

h. Appl i cat i on pr ogr ams and conf i gur at i on set t i ngs must be st or ed i n a manner such t hat a l oss of power does not r esul t i n a l oss of t he appl i cat i on pr ogr am or conf i gur at i on set t i ngs:

( 1) Loss of power must never r esul t i n t he l oss of appl i cat i on pr ogr ams, r egar dl ess of t he l engt h of t i me power i s l ost .

( 2) Loss of power f or l ess t han 2, 500 hour s must not r esul t i n t he l oss of conf i gur ed set t i ngs.

i . I t must have al l f unct i onal i t y speci f i ed and r equi r ed t o suppor t t he appl i cat i on ( Sequence of Oper at i on or por t i on t her eof ) i n whi ch i t i s used, i ncl udi ng but not l i mi t ed t o:

( 1) I t must pr ovi de i nput and out put SNVTs as speci f i ed, as i ndi cat ed on t he Poi nt s Schedul e, and as ot her wi se r equi r ed t o suppor t t he sequence and appl i cat i on i n whi ch i t i s used. Al l SNVTs must have meani ngf ul names i dent i f y i ng t he val ue r epr esent ed by t he SNVT .

Unl ess a st andar d net wor k var i abl e t ype of an appr opr i at e engi neer i ng t ype i s not avai l abl e, al l net wor k var i abl es must be of a st andar d net wor k var i abl e t ype wi t h engi neer i ng uni t s appr opr i at e t o t he val ue t he var i abl e r epr esent s.

( 2) Al l set t i ngs and par amet er s used by t he appl i cat i on i n whi ch t he DDC har dwar e i s used must be conf i gur abl e v i a one of t he f ol l owi ng: st andar d conf i gur at i on pr oper t i es ( SCPTs) as def i ned i n the LonMar k SCPT Li st , user - def i ned conf i gur at i on pr oper t i es ( UCPTs) , net wor k conf i gur at i on i nput s ( ncis) of a SNVT t ype as def i ned i n t he LonMar k SNVT Li st , net wor k conf i gur at i on i nput s ( nci

s) of a user def i ned net wor k var i abl e t ype, or har dwar e set t i ngs on t he cont r ol l er i t sel f .

j . I t must meet FCC Par t 15 r equi r ement s and have UL 916 or equi val ent saf et y l i s t i ng.

k. I n addi t i on t o t hese gener al r equi r ement s and t he DDC Har dwar e I nput - Out put ( I / O) Funct i on r equi r ement s, al l DDC Har dwar e must al so meet t he r equi r ement s of a Local Di spl ay Panel ( LDP) , Appl i cat i on Speci f i c Cont r ol l er ( ASC) , Gener al Pur pose Pr ogr ammabl e Cont r ol l er ( GPPC) , or an Appl i cat i on Gener i c Cont r ol l er ( AGC) . Al l pi eces of DDC Har dwar e must have t hei r DDC Har dwar e Type i dent i f i ed as par t of t he Manuf act ur er ' s Pr oduct Dat a submi t t al as speci f i ed i n Sect i on 23 09 00 I NTRUMENTATI ON AND CONTROL FOR HVAC. Except f or Local Di spl ay Panel s pr ovi ded as par t of anot her cont r ol l er , wher e a s i ngl e devi ce meet s t he r equi r ement s of mul t i pl e t ypes, sel ect a s i ngl e t ype f or t hat speci f i c devi ce based on i t ' s use. Wher e a Local Di spl ay Panel i s pr ovi ded as par t of anot her devi ce, i ndi cat e bot h t he cont r ol l er t ype and l ocal di spl ay panel . One model of DDC har dwar e may be submi t t ed as di f f er ent DDC Har dwar e t ypes when used i n mul t i pl e applications.

Apr i l 2019 Page 4 SECTI ON 23 09 23. 01 l . The user i nt er f ace on al l DDC Har dwar e wi t h a user i nt er f ace whi ch al l ows f or modi f i cat i on of a val ue must be passwor d pr ot ect ed.

m. Cl ocks i n DDC Har dwar e i ncor por at i ng a Cl ock must cont i nue t o f unct i on f or 120 hour s upon l oss of power t o t he DDC Har dwar e.

2. 3. 1 Har dwar e I nput - Out put ( I / O) Funct i ons

DDC Har dwar e i ncor por at i ng har dwar e i nput - out put ( I / O) f unct i ons must meet t he f ol l owi ng r equi r ement s:

2. 3. 1. 1 Anal og I nput s

DDC Har dwar e anal og i nput s ( AI s) must per f or m anal og t o di gi t al ( A- t o- D) conver si on wi t h a mi ni mum r esol ut i on of 8 bi t s pl us s i gn or bet t er as needed t o meet t he accur acy r equi r ement s speci f i ed i n Sect i on 23 09 00 I NTRUMENTATI ON AND CONTROL FOR HVAC. Si gnal condi t i oni ng i ncl udi ng t r ansi ent r ej ect i on must be pr ovi ded f or each anal og i nput . Anal og i nput s must be capabl e of bei ng i ndi v i dual l y cal i br at ed f or zer o and span.

Cal i br at i on v i a sof t war e scal i ng per f or med as par t of poi nt conf i gur at i on i s accept abl e. The AI must i ncor por at e common mode noi se r ej ect i on of at l east 50 dB f r om 0 t o 100 Hz f or di f f er ent i al i nput s, and nor mal mode noi se r ej ect i on of at l east 20 dB at 60 Hz f r om a sour ce i mpedance of 10, 000 ohms.

2. 3. 1. 2 Anal og Out put s

DDC Har dwar e anal og out put s ( AOs) must per f or m di gi t al t o anal og ( D- t o- A) conver si on wi t h a mi ni mum r esol ut i on of 8 bi t s pl us s i gn, and out put a s i gnal wi t h a r ange of 4- 20 mAdc or 0- 10 Vdc. Anal og out put s must be capabl e of bei ng i ndi v i dual l y cal i br at ed f or zer o and span. Cal i br at i on v i a sof t war e scal i ng per f or med as par t of poi nt conf i gur at i on i s accept abl e. DDC Har dwar e wi t h Hand- Of f - Aut o ( H- O- A) swi t ches f or anal og out put s must pr ovi de f or over r i di ng t he out put [ t o 0 per cent and t o 100 per cent ] [ t hr ough t he r ange of 0 per cent t o 100 per cent ]

2. 3. 1. 3 Bi nar y I nput s

DDC Har dwar e bi nar y i nput s ( BI s) must accept cont act c l osur es and must i gnor e t r ansi ent s of l ess t han 5 mi l l i - second dur at i on. Pr ot ect i on agai nst a t r ansi ent of 50 Vac must be pr ovi ded.

2. 3. 1. 4 Bi nar y Out put s

DDC Har dwar e bi nar y out put s ( BOs) must pr ovi de r el ay cont act c l osur es or t r i ac out put s f or moment ar y and mai nt ai ned oper at i on of out put devi ces.

DDC Har dwar e wi t h H- O- A swi t ches f or bi nar y out put s must pr ovi de f or over r i di ng t he out put open or c l osed.

2. 3. 1. 4. 1 Rel ay Cont act Cl osur es

Cl osur es must have a mi ni mum dur at i on of 0. 1 second. Rel ays must pr ovi de at l east 180V of i sol at i on. El ect r omagnet i c i nt er f er ence suppr essi on must be pr ovi ded on al l out put l i nes t o l i mi t t r ansi ent s t o 50 Vac. Mi ni mum cont act r at i ng must be 0. 5 amper es at 24 Vac.

Apr i l 2019 Page 5 SECTI ON 23 09 23. 01

2. 3. 1. 4. 2 Tr i ac Out put s

Tr i ac out put s must pr ovi de at l east 180 V of i sol at i on. Mi ni mum cont act r at i ng must be 0. 5 amper es at 24 Vac.

2. 3. 1. 5 Pul se Accumul at or

DDC Har dwar e pul se accumul at or s must have t he same char act er i st i cs as t he BI . I n addi t i on, a buf f er must be pr ovi ded t o t ot al i ze pul ses. The pul se accumul at or must accept r at es of at l east 20 pul ses per second. The t ot al i zed val ue must be r eset t abl e v i a a conf i gur abl e par amet er .

[ 2. 3. 1. 6 I nt egr at ed H- O- A Swi t ches

Wher e i nt egr at ed H- O- A swi t ches ar e pr ovi ded on har dwar e out put s, cont r ol l er must pr ovi de means of moni t or i ng posi t i on or st at us of H- O- A swi t ch. Thi s f eedback may be pr ovi ded vi a net wor k var i abl e.

] 2. 3. 2 Local Di spl ay Panel ( LDP)

The Local Di spl ay Panel s ( LDPs) must be DDC Har dwar e wi t h a di spl ay and navi gat i on but t ons or a t ouch scr een di spl ay, and must pr ovi de di spl ay and adj ust ment of net wor k var i abl es as i ndi cat ed on t he Poi nt s Schedul e and as speci f i ed. LDPs must be pr ovi ded as st and- al one DDC Har dwar e or as an i nt egr al par t of anot her pi ece of DDC Har dwar e. LDPs must come f act or y i nst al l ed wi t h al l appl i cat i ons necessar y f or t he devi ce t o f unct i on as an

LDP.

The adj ust ment of val ues usi ng di spl ay and navi gat i on but t ons must be passwor d pr ot ect ed.

2. 3. 3 Appl i cat i on Speci f i c Cont r ol l er ( ASC)

Appl i cat i on Speci f i c Cont r ol l er s ( ASCs) have a f i xed f act or y- i nst al l ed appl i cat i on pr ogr am ( i . e. Pr ogr amI D) wi t h conf i gur abl e set t i ngs and do not have t he abi l i t y t o be pr ogr ammed f or cust om appl i cat i ons. ASCs must meet t he f ol l owi ng r equi r ement s i n addi t i on t o t he Gener al DDC Har dwar e and DDC Har dwar e I nput - Out put ( I / O) Funct i on r equi r ement s:

a. ASCs must be LonMar k Cer t i f i ed.

b. Unl ess ot her wi se appr oved, al l necessar y Conf i gur at i on Pr oper t i es and net wor k conf i gur at i on i nput s ( ncis) f or t he sequence and appl i cat i on i n whi ch t he ASC i s used must be f ul l y conf i gur abl e t hr ough ( Not e:

conf i gur at i on accompl i shed vi a har dwar e set t i ngs does not r equi r e conf i gur at i on v i a. )

c. ASCs may i ncl ude an i nt egr al or t et her ed Local Di spl ay Panel

2. 3. 4 Gener al Pur pose Pr ogr ammabl e Cont r ol l er ( GPPC)

A Gener al Pur pose Pr ogr ammabl e Cont r ol l er ( GPPC) must be pr ogr ammed f or t he appl i cat i on. GPPCs must meet t he f ol l owi ng r equi r ement s i n addi t i on t o t he gener al DDC Har dwar e r equi r ement s and Har dwar e I nput - Out put ( I / O) Functions:

a. The pr ogr ammed GPPC must conf or m t o t he LonMar k I nt er oper abi l i t y Gui de.

b. Al l pr ogr ammi ng sof t war e r equi r ed t o pr ogr am t he GPPC must be

Apr i l 2019 Page 6 SECTI ON 23 09 23. 01 del i ver ed t o and l i censed t o t he pr oj ect s i t e i n accor dance wi t h Sect i on 23 09 00 I NTRUMENTATI ON AND CONTROL FOR HVAC. Submi t t he most r ecent ver si on of t he Pr ogr ammi ng sof t war e f or each t ype ( manuf act ur er and model ) of Gener al Pur pose Pr ogr ammabl e Cont r ol l er ( GPPC) .

c. Submi t copi es of t he i nst al l ed GPPC appl i cat i on pr ogr ams ( al l sof t war e t hat i s not common t o ever y cont r ol l er of t he same manuf act ur er and model ) as sour ce code compat i bl e wi t h t he suppl i ed pr ogr ammi ng sof t war e i n accor dance wi t h Sect i on 23 09 00 I NTRUMENTATI ON AND CONTROL FOR HVAC. The submi t t ed GPPC appl i cat i on pr ogr am must be t he compl et e appl i cat i on necessar y f or t he GPPC t o f unct i on as i nst al l ed and be suf f i c i ent t o al l ow r epl acement of t he i nst al l ed cont r ol l er wi t h a GPPC of t he same t ype.

d. GPPCs may be i ncl ude an i nt egr al or t et her ed Local Di spl ay Panel

2. 3. 5 Appl i cat i on Gener i c Cont r ol l er ( AGC)

An Appl i cat i on Gener i c Cont r ol l er ( AGC) has a f i xed appl i cat i on pr ogr am whi ch i ncl udes t he abi l i t y t o be pr ogr ammed f or cust om appl i cat i ons. AGCs must meet t he f ol l owi ng r equi r ement s i n addi t i on t o t he gener al DDC Har dwar e r equi r ement s and Har dwar e I nput - Out put ( I / O) Funct i ons:

a. The pr ogr ammed AGC must conf or m t o t he LonMar k I nt er oper abi l i t y Gui de.

b. The AGC must have a f i xed Pr ogr amI D and f i xed XI F f i l e.

c. Unl ess ot her wi se appr oved, t he ACG must be f ul l y conf i gur abl e and pr ogr ammabl e f or t he appl i cat i on usi ng one or mor e , al l of whi ch must be submi t t ed as speci f i ed f or each t ype of AGC ( manuf act ur er and model).

d. Submi t copi es of t he i nst al l ed AGC appl i cat i on pr ogr ams as sour ce code compat i bl e wi t h t he suppl i ed used f or pr ogr ammi ng t he devi ce i n accor dance wi t h Sect i on 23 09 00 I NTRUMENTATI ON AND CONTROL FOR HVAC.

The submi t t ed AGC appl i cat i on pr ogr am must be t he compl et e appl i cat i on pr ogr am necessar y f or t he AGC t o f unct i on as i nst al l ed and be suf f i c i ent t o al l ow r epl acement of t he i nst al l ed cont r ol l er wi t h an AGC of t he same t ype.

e. AGCs may be i ncl ude an i nt egr al or t et her ed Local Di spl ay Panel

PART 3 EXECUTI ON

3. 1 CONTROL SYSTEM I NSTALLATI ON

3. 1. 1 Bui l di ng Cont r ol Net wor k ( BCN)

Pr ovi de a Bui l di ng Cont r ol Net wor k ( BCN) connect i ng al l DDC har dwar e as speci f i ed. The Bui l di ng Cont r ol Net wor k ( BCN) must consi st of an I P Net wor k, one or mor e , and one or mor e Non- I P Bui l di ng Cont r ol Net wor k Channels:

3. 1. 1. 1 Bui l di ng Cont r ol Net wor k ( BCN) I nst al l at i on

Pr ovi de bui l di ng cont r ol net wor ks meet i ng t he f ol l owi ng r equi r ement s:

a. Pr ovi de a Bui l di ng Cont r ol Net wor k I P Net wor k, Non- I P Bui l di ng Cont r ol Net wor k Channel s and t o a cr eat e a s i ngl e bui l di ng cont r ol net wor k

Apr i l 2019 Page 7 SECTI ON 23 09 23. 01 connect i ng al l DDC Har dwar e.

b. I n addi t i on t o t he connect i on t o t he, each Non- I P Bui l di ng Cont r ol Net wor k ( BCN) Channel di r ect l y connect ed t o a must be di r ect l y connect ed t o ei t her DDC Har dwar e or t o CEA- 709. 1- D Rout er s, but not t o bot h. A channel cont ai ni ng onl y CEA- 709. 1- D Rout er s i s a backbone channel and a channel cont ai ni ng DDC Har dwar e i s a non- backbone channel.

c. When onl y a s i ngl e i s r equi r ed, t he I P net wor k consi st s of onl y t he .

When mul t i pl e ar e r equi r ed, pr ovi de an I P Net wor k connect i ng al l .

d. Connect al l DDC Har dwar e t o a non- backbone BCN Channel .

e. I nst al l component s such t hat t her e i s no mor e t han t han one CEA- 709. 1- D Rout er bet ween any DDC Har dwar e and a f . I nst al l t he net wor k such t hat t he peak expect ed bandwi dt h usage f or each and ever y channel i s l ess t han 70 per cent , i ncl udi ng devi ce- t o- devi ce t r af f i c and t r af f i c t o t he Ut i l i t y Moni t or i ng and Cont r ol Syst em ( UMCS) as i ndi cat ed on t he Poi nt s Schedul e.

g. Wher e mul t i pl e pi eces of DDC Har dwar e ar e used i n t he execut i on of a s i ngl e sequence of oper at i on, di r ect l y connect al l DDC Har dwar e used t o execut e t he sequence t o t he same channel and do not i snt al l ot her DDC Har dwar e t o t hat channel .

3. 1. 1. 2 Non- I P Bui l di ng Cont r ol Net wor k ( BCN) Channel

Pr ovi de Non- I P Bui l di ng Cont r ol Net wor k ( BCN) Channel s meet i ng t he f ol l owi ng r equi r ement s:

a. For each non- backbone channel , pr ovi de a TP/ FT- 10 channel i n doubl y t er mi nat ed bus t opol ogy i n accor dance wi t h CEA-709.3 . For each backbone channel , pr ovi de ei t her a TP/ FT- 10 channel i n doubl y t er mi nat ed bus t opol ogy i n accor dance wi t h CEA-709.3 or a TP/ XF- 1250 channel i n accor dance wi t h t he LonMar k I nt er oper abi l i t y Gui de.

b. Connect no mor e t han 2/ 3 t he maxi mum number of devi ces per mi t t ed by CEA-709.3 t o each TP/ FT- 10 channel . Connect no mor e t han 2/ 3 t he maxi mum number of devi ces per mi t t ed by LonMar k I nt er oper abi l i t y Gui de t o TP/ XF- 1250 channel .

c. Connect no mor e t han 2/ 3 t he maxi mum number of devi ces per mi t t ed by t he manuf act ur er of t he devi ce t r anscei ver s t o each channel . When mor e t han one t ype of t r anscei ver i s used on t he same channel , use t he t r anscei ver wi t h t he l owest maxi mum number of devi ces t o cal cul at e t he 2/ 3 l i mi t .

3. 1. 1. 3 Bui l di ng Cont r ol Net wor k ( BCN) I P Net wor k

I nst al l I P Net wor k Cabl i ng i n condui t . I nst al l Et her net Swi t ches i n l ockabl e encl osur es. I nst al l t he Bui l di ng Cont r ol Net wor k ( BCN) I P Net wor k so t hat i t i s avai l abl e at t he Faci l i t y Poi nt of Connect i on ( FPOC) l ocat i on [ as speci f i ed] [ _____] . When t he FPOC l ocat i on i s a r oom number , pr ovi de suf f i c i ent addi t i onal medi a t o ensur e t hat t he Bui l di ng Cont r ol Net wor k ( BCN) I P Net wor k can be ext ended t o any l ocat i on i n t he r oom.

Apr i l 2019 Page 8 SECTI ON 23 09 23. 01

3. 1. 2 DDC Har dwar e

I nst al l i n l ockabl e encl osur es. I nst al l ot her DDC Har dwar e whi ch i s not i s suspended cei l i ngs i n [ l ockabl e ] encl osur es.

Conf i gur e and commi ssi on al l DDC Har dwar e on t he Bui l di ng Cont r ol Net wor k .

Use Appl i cat i on Speci f i c Cont r ol l er s whenever an Appl i cat i on Speci f i c Cont r ol l er sui t abl e f or t he appl i cat i on exi st s. When an Appl i cat i on Speci f i c Cont r ol l er sui t abl e f or t he appl i cat i on does not exi st use [ Appl i cat i on Gener i c Cont r ol l er s, Gener al Pur pose Pr ogr ammabl e Cont r ol l er s or mul t i pl e Appl i cat i on Speci f i c Cont r ol l er s] [ Appl i cat i on Gener i c Cont r ol l er s or Gener al Pur pose Pr ogr ammabl e Cont r ol l er s] [ mul t i pl e Appl i cat i on Speci f i c Cont r ol l er s] .

3. 1. 2. 1 Hand- Of f - Aut o ( H- O- A) Swi t ches

Pr ovi de Hand- Of f - Aut o ( H- O- A) swi t ches [ f or al l DDC Har dwar e anal og out put s and bi nar y out put s used f or cont r ol of syst ems ot her t han t er mi nal uni t s, ] as speci f i ed and as i ndi cat ed on t he Poi nt s Schedul e. H- O- A swi t ches must be i nt egr al t o t he cont r ol l er har dwar e, an ext er nal devi ce co- l ocat ed wi t h ( i n t he same encl osur e as) t he cont r ol l er , i nt egr al t o t he cont r ol l ed equi pment , or an ext er nal devi ce co- l ocat ed wi t h ( i n t he same encl osur e as) t he cont r ol l ed equi pment .

a. For H- O- A swi t ches i nt egr al t o DDC Har dwar e, meet t he r equi r ement s speci f i ed i n par agr aph DI RECT DI GI TAL CONTROL ( DDC) HARDWARE.

b. For ext er nal H- O- A swi t ches f or bi nar y out put s, pr ovi de swi t ches capabl e of over r i di ng t he out put open or c l osed.

c. For ext er nal H- O- A swi t ches f or anal og out put s, pr ovi de swi t ches capabl e of over r i di ng [ t o 0 per cent or 100 per cent ] [ t hr ough t he r ange of 0 per cent t o 100 per cent ] .

3. 1. 2. 2 Local Di spl ay Panel s

Pr ovi de LDPs t o di spl ay and over r i de val ues of Net wor k Var i abl es as i ndi cat ed on t he Poi nt s Schedul e. I nst al l LDPs di spl ayi ng poi nt s f or anyt hi ng ot her t han a t er mi nal uni t i n t he same r oom as t he equi pment .

I nst al l LDPs di spl ayi ng poi nt s f or onl y t er mi nal uni t s [ i n a mechani cal r oom cent r al t o t he gr oup of t er mi nal uni t s i t ser ves] [ _____] .

3. 1. 2. 3 Over r i des f or GPPCs and AGCs

Pr ovi de t he capabi l i t y t o over r i de poi nt s f or al l Gener al Pur pose Pr ogr ammabl e Cont r ol l er s and Appl i cat i on Gener i c Cont r ol l er s as speci f i ed and as i ndi cat ed on t he Poi nt s Schedul e usi ng one of t he f ol l owi ng met hods:

a. Over r i de SNVT of Same SNVT Type met hod:

( 1) Use t hi s met hod f or al l set poi nt over r i des and f or over r i des of i nput s and out put s whenever pr act i cal .

( 2) Pr ovi de a SNVT i nput t o t he DDC har dwar e cont ai ni ng t he poi nt t o be over r i dden of t he same SNVT t ype as t he poi nt t o be over r i dden.

( 3) Pr ogr am and conf i gur e t he DDC har dwar e such t hat :

Apr i l 2019 Page 9 SECTI ON 23 09 23. 01

( a) I f t he val ue of t he SNVT on t he over r i de i nput i s t he Invalid Value def i ned f or t hat SNVT by t he LonMar k SNVT Li st , t hen t he poi nt i s not over r i dden ( i t s val ue i s det er mi ned f r om t he sequence).

( b) I f t he val ue of t he SNVT on t he over r i de i nput i s not t he Invalid Value def i ned f or t hat SNVT by t he LonMar k SNVT Li st t hen set t he val ue of t he poi nt t o be over r i dden t o t he val ue of t he SNVT on t he over r i de i nput .

b. HVAC Over r i de SNVT met hod:

( 1) Use t hi s met hod f or over r i de of i nput s and out put s when t he " Over r i de SNVT Shar es SNVT Type" met hod i s i mpr act i cal .

( 2) Pr ovi de a SNVT i nput t o t he DDC har dwar e cont ai ni ng t he poi nt t o be over r i dden of SNVT t ype SNVT_hvac_overid. Show on t he Poi nt s Schedul e how t o per f or m t he speci f i ed over r i de usi ng t hi s SNVT.

3. 1. 2. 4 Over r i des f or ASCs

Whenever possi bl e use t he met hods speci f i ed f or Gener al Pur pose Pr ogr ammabl e Cont r ol l er s and Appl i cat i on Gener i c Cont r ol l er s t o per f or m over r i des f or al l Appl i cat i on Speci f i c Cont r ol l er s. I f nei t her t he " Over r i de SNVT of Same SNVT Type" met hod or " HVAC Over r i de SNVT" met hod ar e suppor t ed by t he Appl i cat i on Speci f i c Cont r ol l er show t hi s on t he Poi nt s Schedul e and per f or m over r i des as f ol l ows:

a. Pr ovi de one or mor e SNVT i nput ( s) t o t he DDC har dwar e cont ai ni ng t he poi nt t o be over r i dden. Document t he number and t ype of each SNVT pr ovi ded on t he Poi nt s Schedul e.

b. Conf i gur e t he Appl i cat i on Speci f i c Cont r ol l er such t hat :

( 1) For some speci f i c combi nat i on or combi nat i ons of val ues at t he SNVT over r i de i nput ( s) t he poi nt i s not over r i dden, and i t s val ue i s det er mi ned f r om t he sequence as usual . Show on t he Poi nt s Schedul e t he val ues r equi r ed at t he SNVT over r i de i nput ( s) t o not over r i de t he poi nt .

( 2) For ot her speci f i c combi nat i ons of SNVT over r i de i nput ( s) , t he val ue of t he poi nt t o be over r i dden i s det er mi ned f r om t he val ue of t he over r i de i nput ( s) . Show on t he Poi nt s Schedul e t he cor r el at i on bet ween t he SNVT over r i de i nput ( s) and t he r esul t i ng val ue of t he over r i dden poi nt .

3. 1. 3 Schedul i ng, Al ar mi ng, Tr endi ng and Over r i des

3. 1. 3. 1 Scheduling

3. 1. 3. 1. 1 Schedul e Gr oupi ngs

Pr ovi de a separ at e schedul e f or each AHU i ncl udi ng i t ' s associ at ed Ter mi nal Uni t s and f or each st and- al one Ter mi nal Uni t ( t hose not dependent upon AHU ser vi ce) [ or gr oup of st and- al one Ter mi nal Uni t s act i ng accor di ng t o a common schedul e[ as i ndi cat ed] ] .

Apr i l 2019 Page 10 SECTI ON 23 09 23. 01

3. 1. 3. 1. 2 Occupancy Mode Mappi ng t o SNVT Val ues

Use t he f ol l owi ng mappi ng bet ween SNVT_Occupancy enumer at i ons and occupancy modes:

a. OCCUPI ED mode: Enumer at i on val ue of OC_OCCUPI ED

b. UNOCCUPI ED mode: Enumer at i on val ue of OC_UNOCCUPI ED

c. WARM- UP/ COOL- DOWN ( PRE- OCCUPANCY) mode: Enumer at i on val ue of OC_STANDBY

3. 1. 3. 2 Alarming

For each poi nt whi ch i s shown on t he Poi nt s Schedul e wi t h an al ar m condi t i on, pr ovi de a SNVT out put f or t he poi nt t o be used f or al ar m generation.

3. 1. 3. 3 Trending

For each poi nt whi ch i s shown on t he Poi nt s Schedul e as r equi r i ng a t r end, pr ovi de a SNVT out put f or t he poi nt t o be used f or t r endi ng.

3. 1. 3. 4 Overrides

3. 1. 4 Gateways

The r equi r ement s i n t hi s par agr aph do not per mi t t he i nst al l at i on of har dwar e not meet i ng t he ot her r equi r ement s of t hi s sect i on. Al l cont r ol har dwar e i nst al l ed under t hi s pr oj ect must meet t he r equi r ement s of t hi s speci f i cat i on, i ncl udi ng cont r ol har dwar e pr ovi ded as par t of a package uni t or as par t of equi pment speci f i ed under anot her sect i on. Onl y use gat eways t o connect t o pr e- exi st i ng cont r ol devi ces.

Pr ovi de Gat eways t o non- CEA-709.1-D cont r ol har dwar e as r equi r ed t o connect exi st i ng non- CEA-709.1-D packaged uni t s and i n accor dance wi t h t he following:

a. Each gat eway must communi cat e wi t h and per f or m pr ot ocol t r ansl at i on f or non- CEA-709.1-D cont r ol har dwar e cont r ol l i ng one and onl y one package uni t .

b. Connect one net wor k por t on t he gat eway t o t he Bui l di ng Cont r ol Net wor k and t he ot her por t t o t he s i ngl e pi ece of cont r ol l ed equi pment .

c. Conf i gur e gat eway t o map wr i t eabl e dat a poi nt s i n t he cont r ol l ed equi pment t o Net wor k Var i abl e I nput s of St andar d Net wor k Var i abl e Types as def i ned by t he LonMar k SNVT Li st as i ndi cat ed i n t he Poi nt s Schedul e and as speci f i ed.

d. Conf i gur e gat eway t o map r eadabl e dat a poi nt s i n t he cont r ol l ed equi pment t o Net wor k Var i abl e Out put s of St andar d Net wor k Var i abl e Types as def i ned by t he LonMar k SNVT Li st as i ndi cat ed i n t he Poi nt s Schedul e and as speci f i ed.

Apr i l 2019 Page 11 SECTI ON 23 09 23. 01 f . Do not use non- CEA-709.1-D cont r ol har dwar e f or cont r ol l i ng bui l t - up uni t s or any ot her equi pment t hat was not f ur ni shed wi t h f act or y- i nst al l ed cont r ol s.

g. Do not use non- CEA-709.1-D cont r ol har dwar e f or syst em schedul i ng functions.

h. Non- CEA-709.1-D net wor k wi r i ng connect i ng t he gat eway t o t he package uni t must not exceed 10 f eet i n l engt h and must connect t o exact l y t wo devi ces: t he cont r ol l ed equi pment ( packaged uni t ) and t he gat eway.

3. 1. 5 Net wor k I nt er f ace Jack

Pr ovi de st andar d net wor k i nt er f ace j acks such t hat each node on t he cont r ol net wor k i s wi t hi n 10 f t of an i nt er f ace j ack. For t er mi nal uni t cont r ol l er s wi t h har dwi r ed t her most at s t hi s net wor k i nt er f ace j ack may i nst ead be l ocat ed at t he t her most at . Locat i ng t he i nt er f ace j ack [ at t he t her most at ] [ near t he cont r ol l er ] i s pr ef er r ed. I f t he net wor k i nt er f ace j ack i s ot her t han a 1/ 8 i nch phone j ack, pr ovi de an i nt er f ace cabl e wi t h a st andar d 1/ 8 i nch phone j ack on one end and a connect or sui t abl e f or mat i ng wi t h i nst al l ed net wor k i nt er f ace j ack on t he ot her . No mor e t han one t ype of i nt er f ace cabl e must be r equi r ed t o access al l net wor k i nt er f ace j acks. Fur ni sh [ one] [ _____] i nt er f ace cabl e( s) .

- - End of Sect i on - -

Apr i l 2019 Page 12 SECTI ON 23 09 23. 01