Attachment 5 - QAs (v20May25).pdf
PDF 161 KB Posted
- Attached to
- Uninterrupped Power Supply (UPS) Battery Replacement Service Federal contract opportunity
- Solicitation number
- FA812525Q0060
About this file
This document is a Questions and Answers (Q&A) file for the Uninterruptible Power Supply (UPS) Battery Replacement Services solicitation FA8125-25-Q-0060, issued by the Department of the Air Force Sustainment Center at Tinker Air Force Base in Oklahoma. The Q&A provides detailed specifications for battery replacements across multiple buildings, including specific battery model numbers such as 12-490MR (3708), 12-300MR (3907), and HRL 12540 (3707), with multiple equipment IDs requiring battery replacements ranging from 80 to 120 Valve Regulated Lead Acid batteries.
The document addresses key logistical considerations for battery replacement, including access limitations, transportation challenges, and site-specific requirements. Notably, there are no loading docks for semi-trailers, with Buildings 3707 and 3708 having forklift availability and Building 3907 requiring manual unloading. The battery replacement schedule indicates batteries in "Item 0002" will be replaced during the Base Year and potentially again in Option Year 3. There is no incumbent service provider, and special considerations include floor protection requirements in Building 3907, where rubber or poly wheels are recommended for transporting batteries.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 4 - WD 2015-5315 Rev26.pdf | ||
| Amendment 2 - FA812525Q00600002.pdf | ||
| Attachment 5 - QAs (v28May25).pdf | ||
| Solicitation Amendment FA812525Q00600001.pdf | ||
| Attachment 3 - Appendix C.pdf | ||
| Attachment 4 - WD 2015-5315 Rev25.pdf | ||
| Solicitation - FA812525Q0060.pdf | ||
| Attachment 1 - PWS (Redacted).pdf | ||
| Attachment 2 - Appendix A.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Q&As: FA8125-25-Q-0060 UPS Battery Replacement Services
DEPARTMENT OF THE AIR FORCE
AIR FORCE SUSTAINMENT CENTER (AFSC)
TINKER AIR FORCE BASE OKLAHOMA
QUESTIONS & ANSWERS FOR
FA8125-25-Q-0060, UPS BATTERY REPLACEMENT SERVICES
20 May 2025
Q1. Can we get the model numbers so we can offer the correct batteries?
A1. 12-490MR (3708), 12-300MR (3907), HRL 12540 (3707)
PWP-165 500KVA (2), 9395-550/500 (2), 9395-550/500
Equipment ID OC15695 – 80 batt. Valve Regulated Lead Acid 12-500 Equipment ID OC15696 – 80 batt. Valve Regulated Lead Acid 12-500 Equipment ID OC19140 – 120 batt. Valve Regulated Lead Acid 12-500 Equipment ID OC19141 – 120 batt. Valve Regulated Lead Acid 12-500 Equipment ID OC20201 – 80 batt. Valve Regulated Lead Acid 12-300
Q2. The 120 batteries listed in “Item 0002” seem to be the same as “option item 3002” so will those batteries be replaced during the based year or does this leave to option to wait until the optional 3rd year?
A2. Batteries replacement schedule is listed on Appendix A. 120 batteries listed in “Item 0002” will need replacement at the Base Year, then again at Option Year 3 (assuming the option year will be exercised).
Q3. Please confirm that there are no physical restrictions such as stairs, inproper access/egress, etc for battery installation. If there are special considerations that must be taken/addressed for installation of new batteries, please list them by location & description.
A3. No stairs but single doors to all locations
Q4. Please confirm new batteries can be delivered to site via dock.
A4. No docks for semi-trailers
Q5. Battery make/models are not listed. Please provide make/model of batteries for each UPS. Typically the batteries for these units are 390W or 540W.
A5. 12-490MR (3708), 12-300MR (3907), HRL 12540 (3707)
Q&As: FA8125-25-Q-0060 UPS Battery Replacement Services
Q6. Is there an incumbent on the PM service? Please provide incumbent company.
A6. No
Q7. If you have service reports that can be redacted that will provide the UPS performance & battery information, please provide those.
A7. Battery information is listed in A1 and A5.
Q8. Can you confirm the specific battery model numbers for the type of batteries required for each UPS unit listed in Appendix A?
A8. See response for Q1.
Q9. Are there loading docks available at Buildings 3707, 3708, and 3907 for unloading pallets of batteries?
A9. Buildings 3707 and 3708 have forklift availability but no dock, 3907 does not have any support. Last battery change was completed by panel truck and manual unload by cart. No stairs.
Q10. What is the approximate distance from the outside access point or loading dock to each UPS room? Are there any stairs or elevators that must be accounted for when transporting batteries?
A10. Building 3707 has exterior access, and UPS rooms are on opposite side of building.
Building 3907 is 150 feet to UPS room front door access.
Q11. Is floor protection required when transporting batteries through the facility?
A11. Building 3907 tile floor protection, rubber or poly wheels would be best.