This document appears to be an overview of the existing fuel storage and dispensing facilities at Joint Base Anacostia-Bolling. It provides detailed information on the underground storage tanks, including their capacity, contents, construction, corrosion protection, release detection, and overfill prevention features.
The related federal contract opportunity solicitation is for the replacement of four 12,000-gallon underground fiberglass reinforced plastic gasoline storage tanks, six under dispenser containment sumps, associated piping, fittings, monitoring systems, and accessories at the AAFES gas station on the base. The work also includes removing the old tanks and sumps, excavating and backfilling trenches, testing and commissioning the new system, and coordinating with AAFES personnel. The contract is a Small Business set-aside with a magnitude between $500,000 and $1,000,000. A bid bond of 20% of the proposal price is required, and the contract will be Firm-Fixed Price.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Joint Base Anacostia-Bolling SPCC
General Information
Tank No.:
Building No.:
TankType:
1311-1
UST
Tank Design Information
Capacity (gallons):
Contents:
Tank Corrosion Protection:
Tank Construction:
Tank Fabrication:
Anc/1/ary AST Information
Release Prevention Barrier:
Bunkered Tank:
Direct ground contact:
Secondary Containment
Type:
Construction Material:
xxxxxx
Gasoline
N/A
Double Walled FRP
Shop-Fabricated
N/A UST
N/A UST
N/A UST
Double Walled UST
FRP
Capacity: 100%
Drainage Controls: None
Release Detection Method; Interstitial Monitoring
Equipment and Spill/Overfill Prevention
Level Gauge:
High level Alarm:
Comm. link b/w gauger & pumper:
Level Gauge linked to Computer:
CRDM:
Spill Control:
STI Category:
Spill Prevention:
Yes(ATG)
Audible & Visual
Audible & Visual
No
No
N/AUST
N/AUST
Spill Bucket
January 2021
Tank Systems
Date Installed: xxxxxxxx
Tank Use: Product Dispenser
Activity/ Operator: AAFES Service Station
Piping Design Information Aboveground Piping:
Aboveground Piping Corrosion Protection:
Pipe Pressurization:
Underground Piping:
Underground Piping Corrosion Protection:
Automatic line Leak Detection:
None
N/A
Pressure
Double Walled Plastic
N/A
Yes
Release Detection Method: Interstitial Monitoring
Secondary Containment Type: Double walled piping
FRP
Construction Material:
Capacity:
Drainage Controls:
Overfill Prevention:
2S Gallons
Monitoring Sump
0 Communication link b/w Gauger and Pumper (Electronic)
0 Communication link b/w Gauger and Pumper (Visual)
0 Level Gauge Visible at Fill Port
� Overfill/High Level Alarm
0 Vent Whistle
0 Overfill Prevention Valve (AST}
� Automatic Restrictor/Shutoff Device (UST)
0 Not Required (UST fill event< 25 gallons/event)
0 None
)(o
Tank No.:
Building No.:
Tank Type:
1311-2
UST
Tank Design Information
Capacity ( gallons): xxxxx
Contents:
Tank Corrosion Protection:
Tank Construction:
Tank Fabrication:
Ancillary AST Information
Release Prevention Barrier:
Bunkered Tank:
Direct ground contact:
Secondary Containment
Type:
Construction Material:
Gasoline
N/A
Double Walled FRP
Shop-Fabricated
N/AUST
N/AUST
N/A UST
Double Walled UST
FRP
Capacity: 100%
Drainage Controls: None
Release Detection Method: Interstitial Monitoring
Equipment and Spill/Overfill Prevention
Level Gauge:
High level Alarm:
Comm. link b/w gauger & pumper:
Level Gauge linked 19 Computer:
CRDM:
Spill Control:
STI Category:
Spill Prevention:
Yes (ATG)
Audible & Visual
Audible & Visual
No
UST
N/A UST
N/AUST
Spill Bucket
Tank Systems
Date Installed: xxxxxxx
Tank Use: Product Dispenser
Activity/ Operator: AAFES Service Station
Piping Design Information Aboveground Piping: None
Aboveground Piping Corrosion Protection:
Pipe Pressurization:
Underground Piping:
Underground Piping Corrosion Protection:
Automatic line Leak Detection:
N/A
Pressure
Double Walled Plastic
N/A
Yes
Release Detection Method: Interstitial Monitoring
Secondary Containment
Type:
Construction Material:
Capacity:
Drainage Controls:
Overfill Prevention:
Double walled piping
FRP
25 Gallons
Monitoring Sump
January 2021
D Communication Link b/w Gauger and Pumper ( Electronic)
D Communication link b/w Gauger and Pumper (Visual)
D Level Gauge Visible at Fill Port
� Overfill/High Level Alarm
D Vent Whistle
D Overfill Prevention Valve (AST)
� Automatic Restrictor/ Shutoff Device (UST)
D Not Required (UST fill event< 25 gallons/ event)
D None
Tank No.:
Building No.:
TankType:
1311-3
UST
Tank Design Information
Capacity (gallons): xxxxxxxx
Contents:
Tank Corrosion Protection:
Tank Construction:
Tank Fabrication:
Ancillary AST Information
Release Prevention Barrier:
Bunkered Tank:
Direct ground contact:
Secondary Containment
Type:
Construction Material:
Gasoline
N/A
Double Walled FRP
Shop-Fabricated
N/A UST
N/A UST
N/A UST
Double Walled UST
FRP
Capacity: 100%
Drainage Controls: None
Release Detection Method: Interstitial Monitoring
Equipment and Spill/Overfill Prevention
Level Gauge:
High level Alarm:
Comm. link b/w gauger & pumper:
Level Gauge linked to Computer:
CROM:
Spill Control:
STI Category:
Spill Prevention:
Yes(ATG)
Audible & Visual
Audible & Visual
No
UST
N/A UST
N/A UST
Spill Bucket
Tank Systems
Date Installed: xxxxxx
Tank Use: Product Dispenser
Activity/ Operator: AAFES Service Station
Piping Design Information Aboveground Piping: None
Aboveground Piping Corrosion Protection:
Pipe Pressurization:
Underground Piping:
Underground Piping Corrosion Protection:
N/A
Pressure
Double Walled Plastic
N/A
Automatic line Leak Yes Detection:
Release Detection Method: Interstitial Monitoring
Secondarv Containment Type:
Construction Material:
Capacity:
Drainage Controls:
Overfill Prevention:
Double walled piping
FRP
25 Gallons
Monitoring Sump
January 2021
0 Communication Link b/w Gauger and Pumper (Electronic)
0 Communication Link b/w Gauger and Pumper (Visual)
0 Level Gauge Visible at Fill Port
� Overfill/High Level Alarm
0 Vent Whistle
0 Overfill Prevention Valve (AST)
� Automatic Restrictor/Shutoff Device (UST)
0 Not Required (UST fill event< 25 gallons/event)
Tank No.:
Building No.:
TankType:
1311-4
UST
Tank Design Information
Capacity (gallons):
Contents:
Tank Corrosion Protection:
Tank Construction:
Tank Fabrication:
Ancillary AST Information
Release Prevention Barrier:
Bunkered Tank:
Direct ground contact:
Secondary Containment
Type:
Construction Material:
xxxxx
Gasoline
N/A
Double Walled FRP
Shop-Fabricated
N/A UST
N/A UST
N/A UST
Double Walled UST
FRP
Capacity: 100%
Drainage Controls: None
Release Detection Method: Interstitial Monitoring
Equipment and Spill/Overfill Prevention level Gauge:
High level Alarm:
Comm. link b/w gauger & pumper:
level Gauge Linked to Computer:
CROM:
Spill Control:
STI Category:
Spill Prevention:
Yes(ATG)
Audible & Visual
Audible & Visual
No
UST
N/A UST
N/A UST
Spill Bucket
Tank Systems
Date Installed: xxxxxxx
Tank Use: Product Dispenser
Activity/ Operator: AAFES Service Station
Piping Design Information Aboveground Piping:
Aboveground Piping Corrosion Protection:
Pipe Pressurization:
Underground Piping:
Underground Piping Corrosion Protection:
None
N/A
Pressure
Double Walled Plastic
N/A
Automatic Line leak Yes Detection:
Release Detection Method: Interstitial Monitoring
Secondary Containment
Type:
Construction Material:
Capacity:
Drainage Controls:
Overfill Prevention:
Double walled piping
FRP
25 Gallons
Monitoring Sump
January 2021
0 Communication link b/w Gauger and Pumper (Electronic)
0 Communication link b/w Gauger and Pumper (Visual)
0 Level Gauge Visible at Fill Port
� Overfill/High Level Alarm
0 Vent Whistle
0 Overfill Prevention Valve (AST)
� Automatic Restrictor/Shutoff Device (UST)
0 Not Required (UST fill event< 25 gallons/event)
BLDG 1311
Firestone/
AAFES
Station
Tank Type A Aboveground Storage Tank
T Underground Storage Tank
POL Line Type
- Aboveground
- Underground
LEGEND
POL Vehicle Activity [gj Fuel Offload Site
■ Mobile Equipment Site
[gJ Mobile Refueler
POL Compliance Site Flow Direction
Flow Direction t xxxxxxxxxxxxx xxxxx
File details come from the government source that posted it. Updated .