Fire Pump Report-from RFI012 Question.pdf

PDF 168 KB Posted

Attached to
(FY22) B1648 Armament Shop, F-35 Infrastructure Improvements
Solicitation number
FA667522R0004
Issued by

About this file

This document contains details for two federal contract opportunities. The first is a fire pump test report for two fire pumps located at Naval Air Station Joint Reserve Base Building 1657 in Fort Worth, Texas. The report provides test results for both pumps, including nameplate information, system configuration, controller test results, NFPA performance review, and notes. It also includes a letter noting the fire pump and jockey pump pressure settings may not comply with NFPA Pamphlet 20 recommendations and suggests adjusting pressure switches or transducers to achieve closer compliance.

The second opportunity is a solicitation for repairs and renovations to Building 1648 Armament Shop at NAS Fort Worth JRB to prepare for an incoming F-35 flying mission. The single award firm fixed price contract has a magnitude between $1,000,000 to $5,000,000. A pre-bid site visit will be held on March 30 and RFIs are due by April 7. Proposals are due April 18 with an estimated construction schedule to be determined at award. The work includes floor plan changes, additional fixtures, locker room modifications, adding a fire sprinkler system and FA/MNS, ductwork modifications, and refinishing spaces. Funds are presently unavailable and the solicitation will be issued on SAM.gov.

View the file

Other files

File Type Posted
FA667522R0004 QA from RFI 18May22.pdf PDF
FA667522R00040007 Solicitation Amendment 7 B1648 Armament Shop.pdf PDF
Attachment 12 AMEND 7 1648 Mechanical.pdf PDF
FA667522R00040006 Solicitation Amendment 6 B1648 Armament Shop.pdf PDF
FA667522R00040005 Solicitation Amendment 5 B1648 Armament Shop.pdf PDF
FA667522R0004 QA from RFI 4May22.pdf PDF
Pump House Dataplates Pictures.pdf PDF
Attachment 2 Updated B1648 Drawing Combined.pdf PDF
FA667522R00040004 Solicitation Amendment 4 B1648 Armament Shop.pdf PDF
FA667522R0004 QA from RFI-12Apr22.pdf PDF
RFI010-Contour Lines B1648.pdf PDF
FA667522R00040003 Amendment 3 B1648 Armament Shop.pdf PDF
FA667522R00040001 Solicitation Amendment 1 B1648 Armament Shop.pdf PDF
FA667522R00040002 Solicitation Amendment 2 B1648 Armament Shop.pdf PDF
Site Walk Sign-in Sheet-30 Mar 22.pdf PDF
FA667522R0004 QA from RFI-30Mar22.pdf PDF
Attachment 11 Narrative Amendment Date 28Mar22.pdf PDF
FA667522R0004-Solicitation B1648 Armament Shop.pdf PDF
Attachment 2 - B1648 Drawings Combined.pdf PDF
Attachment 3 - B1648 Specs Combined.pdf PDF
Attachment 6- Phasing Work.pdf PDF
Attachment 10 - DB Wage Rates 17 Dec 2021-Tarrant County.pdf PDF
Attachment 8 - RFI Form.pdf PDF
Attachment 5 - B1648 Hardware Schedule.pdf PDF
Attachment 1 -B1648 Design Analysis Combined.pdf PDF
Attachment 9 - Past Perf Questionnaire.pdf PDF
Attachment 7 - AF 3000.pdf PDF
Attachment 4 -B1648 SID Package.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

www.bigredpumps.com

2445 Gateway Ave. Suite 140, Irving, TX 75063

(817) 430-2400

2500 Central Pkwy, Suite B, Houston, TX 77092

(713) 936-2334

NFPA 20/25

FIRE PUMP TEST REPORT

Report No. 2250-3 Pump No. P02250

Project/Job Name:

Street:

City/State/Zip:

Naval Air Station Joint Reserve Base, Building 1657 FP-1 1219 Depot Avenue Fort Worth, TX 76127

Test Date:

Pump Tech:

Performed For:

1-14-2022 Test Kit No.: 8 Harvey De Paula Texas Fire & Sound

FIRE PUMP NAMEPLATE INFO DRIVER NAMEPLATE INFO CONTROLLER NAMEPLATE INFO

Type Horizontal Split Case Type Electric Type Full Svc - ATL Pump Mfr. Fairbanks Morse/Nijhuis Manufacturer Marathon Manufacturer Metron Model 6" 2824CF Model/Frame 445TS Model Rated GPM 2000 Horse Power 200 Horse Power 200 Rated PSI 121 RPM 1,780 Voltage 460 Rated RPM 1,785 Voltage 460 Phases 3 Maximum PSI 142.4 Amps 231 Interrupt Cap. 100,000 PSI @ 150% 99.8 Phases 3 ATS S/N Impeller Size 17.10 in. Frequency (Hz) 60 Hz Diesel Ground Stages/Max BHP 1 / BHP Svc. Factor 1.15 Serial No. 23622405 Serial No. K3W1021665-1 Serial No. 0910440-7

SYSTEM CONFIGURATION CONTROLLER TEST RESULTS

Pump Suct. Flange: 10 in. Fire Pump Jockey Pump Auto Transfer Switch

Pump Disch. Flange: 8 in. Start PSI: 90 Start PSI: 100 Installed: No Pump Rotation: LH (CCW) Stop PSI: Stop PSI: 140 Tested: No

Water Source: Tank Manual Starts: 1 RPT Setting: Transfer Time Settings

Flowmeter: No Test Header: Yes

Auto Starts: 1 JP HP: 3 To Emerg. (secs):

Emergency Starts: 1 JP Model: To Normal (mins):

TEST TYPES: R-Roof H-Ground Header M-Flowmeter TEST RESULTS

Speed

RPM

Pressure Readings PSI Test Type

Streams GPM % Rated MRV

Volts / Amps Roof PSIDisch. Suct. Net Size No. Pitot

PSI A B C

1782 150 6 144 0 Churn 485 V 481 V 480 V 123 A 135 A 123 A

1776 129 4 125 H 1.75 5 20 1,981 99% 482 V 479 V 478 V 210 A 222 A 203 A

1772 100 0 100 H 1.75 5 46 3,005 150% 479 V 476 V 475 V 247 A 239 A 247 A

--- --- --- 0 0% V V V A A A

--- --- --- 0 0% V V V A A A

NFPA PERFORMANCE REVIEW

Min. Flow Rated Flow Peak Flow Min. flow head did not exceed 140% of rated flow head: Yes0% 100% 150%

Actual PSI 144 Actual PSI 125 Actual PSI 100 Peak flow head is not less than 65% of rated flow head: Yes

Adjusted PSI 144 Adjusted PSI 126 Adjusted PSI 101 Electric motor performance within allowable limits: Yes

Nameplate PSI 142.4 Nameplate PSI 121 Nameplate PSI 99.8

Difference* 101% Difference* 104% Difference* 102% Power supply voltage within allowable limits: Yes

* NFPA requires that the fire pump perform at no less than 95% of the nameplate PSI values.

NOTES: Alignment of pump/motor shafts checked, currently no alignment needed. SRC:

© 2020 Mechantek Corporation. All rights reserved.

MP300-200-480C

www.bigredpumps.com

2445 Gateway Ave. Suite 140, Irving, TX 75063

(817) 430-2400

2500 Central Pkwy, Suite B, Houston, TX 77092

(713) 936-2334

NFPA 20/25

FIRE PUMP TEST REPORT

Report No. 2251-3 Pump No. P02251

Project/Job Name:

Street:

City/State/Zip:

Naval Air Station Joint Reserve Base, Building 1657 FP-2 1219 Depot Avenue Fort Worth, TX

Test Date:

Pump Tech:

Performed For:

1-14-2022 Test Kit No.: 8 Harvey De Paula Texas Fire & Sound

FIRE PUMP NAMEPLATE INFO DRIVER NAMEPLATE INFO CONTROLLER NAMEPLATE INFO

Type Horizontal Split Case Type Electric Type Full Svc - ATL Pump Mfr. Fairbanks Morse/Nijhuis Manufacturer Marathon Manufacturer Metron Model 6" 2824CF Model/Frame 445TS Model MP300-200-480C Rated GPM 2000 Horse Power 200 Horse Power 200 Rated PSI 121 RPM 1,780 Voltage 460 Rated RPM 1,785 Voltage 460 Phases 3 Maximum PSI 142.2 Amps 231 Interrupt Cap. 100,000 PSI @ 150% 99 Phases 3 ATS S/N Impeller Size 17.10 in. Frequency (Hz) 60 Hz Diesel Ground Stages/Max BHP 1 / BHP Svc. Factor 1.15 Serial No. 23622406 Serial No. K3W1021665-0 Serial No. 09-09688-3

SYSTEM CONFIGURATION CONTROLLER TEST RESULTS

Pump Suct. Flange: 10 in. Fire Pump Jockey Pump Auto Transfer Switch

Pump Disch. Flange: 6 in. Start PSI: 85 Start PSI: 100 Installed: No Pump Rotation: LH (CCW) Stop PSI: Stop PSI: 140 Tested: No

Water Source: Municipal Manual Starts: 1 RPT Setting: Transfer Time Settings

Flowmeter: No Test Header: Yes

Auto Starts: 1 JP HP: 3 To Emerg. (secs):

Emergency Starts: 1 JP Model: To Normal (mins):

TEST TYPES: R-Roof H-Ground Header M-Flowmeter TEST RESULTS

Speed

RPM

Pressure Readings PSI Test Type

Streams GPM % Rated MRV

Volts / Amps Roof PSIDisch. Suct. Net Size No. Pitot

PSI A B C

1790 145 4 141 0 Churn 478 V 481 V 478 V 143 A 152 A 146 A

1787 128 3 125 H 1.75 5 20 1,981 99% 476 V 479 V 475 V 209 A 218 A 218 A

1781 100 0 100 H 1.75 5 46 3,005 150% 474 V 476 V 474 V 246 A 255 A 249 A

--- --- --- 0 0% V V V A A A

--- --- --- 0 0% V V V A A A

NFPA PERFORMANCE REVIEW

Min. Flow Rated Flow Peak Flow Min. flow head did not exceed 140% of rated flow head: Yes0% 100% 150%

Actual PSI 141 Actual PSI 125 Actual PSI 100 Peak flow head is not less than 65% of rated flow head: Yes

Adjusted PSI 140 Adjusted PSI 125 Adjusted PSI 100 Electric motor performance within allowable limits: Yes

Nameplate PSI 142.2 Nameplate PSI 121 Nameplate PSI 99

Difference* 99% Difference* 103% Difference* 101% Power supply voltage within allowable limits: Yes

* NFPA requires that the fire pump perform at no less than 95% of the nameplate PSI values.

NOTES: Alignment of pump/motor shafts recommended.

Replacement of coupling or coupling insert recommended. Current coupling insert has some deterioration.

Fire pump repack recommended, currently packing has no more room for adjustment.

Replacement of jockey pump recommended. Current jockey pump is leaking excessively.

SRC:

© 2020 Mechantek Corporation. All rights reserved.

106 Decker Court ■ Suite 225 ■ Irving Texas 75062

817.430.2400 ■ www.mechantek.com

Subject: Fire Pump/Jockey Pump Controller Settings

Dear Fire Protection Partner:

We recently conducted a test of a fire pump on your behalf (see attached Pump Test Report). We discovered that the start and stop pressure settings for the fire pump and/or jockey pump at this facility may not be set in accordance with the 2016 NFPA Pamphlet 20 recommendations (Annex A.14.2.6):

(4) Fire Pump Settings. The fire pump system, when started by pressure drop, should be arranged as follows:

(a) The jockey pump stop point should equal the pump churn pressure plus the minimum static supply pressure.

(b) The jockey pump start point should be at least 10 psi (0.68 bar) less than the jockey pump stop point.

(c) The fire pump start point should be 5 psi (0.34 bar) less than the jockey pump start point. Use 10 psi (0.68 bar) increments for each additional pump.

(d) Where minimum run times are provided, the pump will continue to operate after attaining these pressures. The final pressures should not exceed the pressure rating of the system.

(e) Where the operating differential of pressure switches does not permit these settings, the settings should be as close as equipment will permit. The settings should be established by pressures observed on test gauges.

Potential Problems:

Using high differentials between the fire pump start pressure and the fire pump churn pressure creates the potential for pressure surges, known as water hammering, which could damage pipes and/or fittings when the fire pump is called to service by the controller. This could potentially result in the reduced efficacy of the fire suppression system in the event of a fire and significant water damage when just performing periodic tests of the fire pump.

Possible Solutions:

The pressure settings in the jockey pump controller and fire pump controller are regulated by pressure switches and/or transducers, depending on the age of the controllers. These switches/transducers can be adjusted to achieve pressure setting differentials closer to those recommended by NFPA 20.

Over time, the sensitivity of these switches and transducers can deteriorate. If the desired settings cannot be achieved, the pressure switch or transducer may need to be replaced.

For further assistance, please contact us at 817-430-2400.

Rev.04 9/4/21

B-1657_Test Report_2250-3_Naval Air Station FP-1