FA667522R0004 QA from RFI 4May22.pdf

PDF 142 KB Posted

Attached to
(FY22) B1648 Armament Shop, F-35 Infrastructure Improvements
Solicitation number
FA667522R0004
Issued by

About this file

This document package includes a question and answer file and a federal contract opportunity solicitation. The solicitation is for repairs and renovations to Building 1648 at Naval Air Station Fort Worth Joint Reserve Base in Fort Worth, Texas. Work includes floor plan changes, additional fixtures, restroom modifications, separate locker rooms, fire sprinkler installation, mechanical and electrical upgrades, and refinishing of degraded spaces and exterior elements. The single award, firm fixed price contract has a magnitude between $1,000,000 and $5,000,000. A site visit was held on March 30th and requests for information were due by April 7th. Proposals are due by April 10th for construction scheduled to be determined at award. The contracting office is located at NAS Fort Worth JRB and inquiries shall be made via email only regarding this Department of the Air Force Reserve Command solicitation.

View the file

Other files

File Type Posted
FA667522R0004 QA from RFI 18May22.pdf PDF
FA667522R00040007 Solicitation Amendment 7 B1648 Armament Shop.pdf PDF
Attachment 12 AMEND 7 1648 Mechanical.pdf PDF
FA667522R00040006 Solicitation Amendment 6 B1648 Armament Shop.pdf PDF
FA667522R00040005 Solicitation Amendment 5 B1648 Armament Shop.pdf PDF
Pump House Dataplates Pictures.pdf PDF
Attachment 2 Updated B1648 Drawing Combined.pdf PDF
FA667522R00040004 Solicitation Amendment 4 B1648 Armament Shop.pdf PDF
Fire Pump Report-from RFI012 Question.pdf PDF
FA667522R0004 QA from RFI-12Apr22.pdf PDF
RFI010-Contour Lines B1648.pdf PDF
FA667522R00040003 Amendment 3 B1648 Armament Shop.pdf PDF
FA667522R00040001 Solicitation Amendment 1 B1648 Armament Shop.pdf PDF
FA667522R00040002 Solicitation Amendment 2 B1648 Armament Shop.pdf PDF
Site Walk Sign-in Sheet-30 Mar 22.pdf PDF
FA667522R0004 QA from RFI-30Mar22.pdf PDF
Attachment 11 Narrative Amendment Date 28Mar22.pdf PDF
FA667522R0004-Solicitation B1648 Armament Shop.pdf PDF
Attachment 2 - B1648 Drawings Combined.pdf PDF
Attachment 3 - B1648 Specs Combined.pdf PDF
Attachment 6- Phasing Work.pdf PDF
Attachment 10 - DB Wage Rates 17 Dec 2021-Tarrant County.pdf PDF
Attachment 8 - RFI Form.pdf PDF
Attachment 5 - B1648 Hardware Schedule.pdf PDF
Attachment 1 -B1648 Design Analysis Combined.pdf PDF
Attachment 9 - Past Perf Questionnaire.pdf PDF
Attachment 7 - AF 3000.pdf PDF
Attachment 4 -B1648 SID Package.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA6675-22-R-00004 Q&A from RFI’s (Dated: 4 May 2022)

RFI#015

Question4: Please provide Hazardous material survey for site including possibility of LBP, Mold, Asbestos. Will the contractor be required to provide this survey?

Government Answer (BCE): Remove and dispose all asbestos duct joint mastic and asbestos containing insulation wrap on piping per drawings, including P-001, PD101, PL101 and MD101.

See Attachment 2 – Updated B1648 Drawing Combined

RFI#016

Question: New Work Keynotes are not shown on plans. See sheet A-101.

Government Answer: See revised A-101 and A-102 for keynotes. See Attachment 2 – Updated B1648 Drawing Combined

RFI#020

Question: SPECIFY MALE BETHROOM (RM 108) PARTITION TYPES SHOWN AT:

BETWEEN TOILETS AND SHOWER ROOM

BETWEEN URINALS AND SHOWER ROOM

SPECIFY FEMALE BATHROOM (RM 106) PARTITION TYPES SHOWN AT:

BETWEEN TOILETS AND SHOWER ROOM

BETWEEN TOILETS AND SINK AREA

Government Answer: See revised A-401 for missing partition types. See Attachment 2 – Updated B1648 Drawing Combined

RFI#025

Question: The document titled Attachment 1 B1648 Design Analysis Combined contradicts itself regarding asbestos material. At first on page 81 it says prior surveys indicate no asbestos or lead have been found. I believe we were told that at the site visit as well. Then later on pages 327 to 330, the below materials are identified. Can you confirm if the below items do need to be removed for this project?

• Duct Joint Mastic in Rooms 3 and 4 attic - 160 LF

• Insulation Wrap on Piping in Rooms 10 and 11, and attic throughout building - 78 fittings plus 350 LF Government Answer: Remove and dispose all asbestos duct joint mastic and asbestos containing insulation wrap on piping per drawings, including P-001, PD101, PL101, and MD101. See Attachment 2 – Updated B1648 Drawing Combined

RFI#026

Question: Could you please provide photos of the manufacture plates on the fire pump, relief valves and Jockey Pump? On FS500 items 1-3 requires as part of the fire sprinkler proposal to repack the fire pump, replace check valves and jockey pump.

Government Answer: Pictures are in attachment named – Pump House Dataplates Pictures.

The jockey pump is in rough shape, and the jockey pump data plate is difficult to read but the jockey pump schedule (model information) is on sheet FS500 below the legend.